Database Conversion Tool

In document Centum VP Installation Gneral Guide (Page 168-174)

If HIS is included in CS 3000 project, “HIS Database Conversion Tool” appears to convert the HIS to CENTUM VP HIS. Select the checkbox of stations to convert to CENTUM VP HIS. For the station you do not want to convert, clear the checkbox.

The graphic grouping features of CS 3000 and CENTUM VP are different according to

specifications. The main difference between CS 3000 and CENTUM VP is the displaying order of the grouped objects.

To keep the same displaying order, you need to check the option of [Ungroup group objects (for runtime compatibility when groups have overlapping Z-order)]. If this option is not checked, the displaying order of the grouped objects will be different between CS 3000 and CENTUM VP.

TIP • When HIS is converted to CENTUM VP HIS, all CS 3000 graphic files of the station are automatically

converted to CENTUM VP graphic formats.

• You also can start “HIS Database Conversion Tool” from the Tool menu of System View by selecting “HIS Database Conversion Tool”.

<6.2 Version Up Installation (from CS 3000 to CENTUM VP)>

6-16

IM 33M01A20-40E 060204E.ai Figure HIS Database Conversion Tool

n Procedure 5-2: Steps to convert Project database using “Graphic File

Converter”

You can use “Graphic File Converter” to convert a CS 3000 graphic file to a CENTUM VP graphic file, file by file. TIP You can use “Graphic File Converter” to convert a CS 3000 graphic file to a CENTUM VP graphic file. You can then import the graphic file converted to CENTUM VP formats in the CENTUM VP Graphic Builder and edit.

1. From the Start menu, select [YOKOGAWA CENTUM] - [Graphic File Converter]. “Graphic File Converter” starts.

060205E.ai

Figure Graphic File Converter -1

<6.2 Version Up Installation (from CS 3000 to CENTUM VP)>

6-17

2. Add a CS 3000 graphic file or folder you want to convert.

The graphic grouping features of CS 3000 and CENTUM VP are different according to specifications. The main difference between CS 3000 and CENTUM VP is the displaying order of the grouped objects.

To keep the same displaying order, you need to check the option of [Ungroup group objects (for runtime compatibility when groups have overlapping Z-order)]. If this option is not checked, the displaying order of the grouped objects will be different between CS 3000 and CENTUM VP.

3. Specify the Target Folder and click the [Convert] button. The following dialog box appears.

060206E.ai

Figure Graphic File Converter -2

If the file conversion is successful, “Successful” appears in the [Status] column, “Failed” if unsuccessful, at the completion of the conversion.

060207E.ai

Figure Graphic File Converter (showing conversion results)

<6.2 Version Up Installation (from CS 3000 to CENTUM VP)>

6-18

IM 33M01A20-40E

n Procedure 6: Restoration of the backed up Package Data

Restore the data for each package you backed up in procedure 1.

SEE

ALSO For details of restoring package data, see:

6.2.2, “Backup and Restoration of Package Data”

<6.2 Version Up Installation (from CS 3000 to CENTUM VP)>

6-19

6.2.2

Backup and Restoration of Package Data

The following table shows the data that needs “Backup/Restoration” in each Package. You backup data in CS 3000 and restore them in CENTUM VP. Table Backup and Restoration of Package Data (1/2) Package LHS1100 LHM1101 LHS1120 LHS1130 LHS1150 LHS2411 LHS2412 LHS4000 LHS4100 LHS4150 LHS4190 LHS4200 LHS4410 LHM4410 LHS4420 LHM4420 LHS4450 LHS4600 LHS4700 LHS4800 LHS6510 LHS6530 LHS6600 LHM6600 LHS6710 LHM6710 LHS5100 LHM5100 LHS5110

Data back up/restore

Standard Operation and Monitoring Function It keeps the HIS setup information. Optionally, back up or restore the following setup data.

Trend data

Long-term, Closed data, Scheduler, etc. HIS database

Recipe and control recipe data Tokuchu

Console HIS Support Package for Enclosed Display Style

Console HIS Support Package for Open Display Style

Server for Remote Operation and Monitoring Function

Exaopc OPC Interface Package (for HIS) CENTUM Data Access Library

Million Tag Handling Package

Configured Information Reference Package Output to External Recorder Package Line Printer Support Package

Historical Message Integration Package (meeting FDA Regulations)

Control Drawing Status Display Package Logic Chart Status Display Package Multiple Project Connection Package Multiple-Monitor Support Package Advanced Alarm Filter Package

Consolidated Alarm Management Software CAMS for HIS

Long-term Data Archive Package Report Package

CS Batch 3000 Process Management Package

FCS Data Setting/Acquisition Package (PICOT)

Standard Builder Function Access Control Package

No obvious reference No obvious reference The same as LHS1100 No obvious reference No obvious reference No obvious reference No obvious reference No obvious reference No obvious reference

The Data stored in the Historical integrated server can be inherited. It requires to re- configure the storage location in each HIS. No obvious reference

No obvious reference No obvious reference No obvious reference

Export and Import of Alarm Filter definition are required.

Optionally, back up/restore the following file. CAMS configuration information

Inheritable by the Backup/Restore the long- term Data.

Inheritable by the Backup/Restore of Report definition file.

No obvious reference

The control recipe is not inherited. Back up List of the definition Data is required.

Back up/Restore the project database. Re-configuration in the Access Control utility is required.

(The definition is SVA so that the user can store/restore.) Name • • • • • • 060208E.ai

<6.2 Version Up Installation (from CS 3000 to CENTUM VP)>

6-20

IM 33M01A20-40E

Table Backup and Restoration of Package Data (2/2)

LHS5150 Graphic Builder LHS5160 CS Batch 3000 Builder

LHS5161 CS Batch 3000 Recipe Management Package

LHS5170 Administrator Package (FDA:21 CFR Part 11 compliant)

LHS5420

LHM5150 Test Function

LHS5425 Expanded Test Functions LHS5426 FCS Simulator Package LHS5427 HIS Simulator Package

LHS5450 Multiple Project Connection Builder LHS5490

LHM5490 Self-documentation Package LFSxxxx Basic Control Functions

Subsystem Communication package LFS1250 GSGW Generic Subsystem Gateway

Package

LBCxxxx Standard Bus Converter Function LBC2100 System Integration OPC Client Package LGWxxxx Communication Gateway Unit Function LPC6900 SOE Server Package

LPC6910 SOE Server Configurator Package LPC6920 SOE Viewer Package

LPC6930 SEM OPC Interface Package LHS5495 Electronic Instruction Manual

The project database is inherited. (Back up the SVA file by the User) Back up/Restore the project database. Back up/Restore the recipe database. Back up/Restore the database that was saved by FDA support.

No obvious reference No obvious reference No obvious reference No obvious reference No obvious reference No obvious reference No obvious reference

Back up/Restore the OPC server definition information and the Item definition information file.

No obvious reference No obvious reference No obvious reference

Backup/Restore the database of SOE server.

No obvious reference Backup the configuration files. No obvious reference No obvious reference

060209E.ai

Package Name Data back up/restore

<6.2 Version Up Installation (from CS 3000 to CENTUM VP)>

6-21