THERMON . . . The Heat Tracing Specialists®

www.thermon.com

BSX

TM

Self-Regulating Heating Cable

Product Specifications

Application . . .

Freeze Protection or Process Temperature Maintenance

BSX self-regulating heating cables are designed to provide freeze protection or process temperature maintenance to metallic and nonmetallic piping, tanks and equipment. The heat output of BSX cable varies in response to the surrounding conditions along the entire length of a circuit. Whenever the heat loss of the insulated pipe, tank or equipment increases (as ambient temperature drops), the heat output of the cable increases. Conversely, when the heat loss decreases (as the ambient temperature rises or product flows), the cable reacts by reducing its heat output. This self-regulating feature allows BSX to be overlapped without temperature upset damage to the cable.

BSX cables are approved for use in ordinary (nonclassified) areas and are certified to the ATEX directive for use in Category 2 and 3 (Zone 1 and 2) classified areas.

Ratings . . .

Available Watt densities ... 9, 15, 25, 32 W/m at 10°C Nominal supply voltage1... 230 Vac Maximum maintenance temperature ... 65°C Maximum continuous exposure temperature

Power-off ... 85°C Minimum installation temperature .... -40°C (OJ); -51°C (FOJ) Minimum bend radius ... 32 mm T-rating 2

9, 15, 25 W/m ... T6 85°C 32 W/m ... T5 100°C Based on stabilised design 3... T6 85°C Basic Accessories 4 . . .

Power Connection: All BSX cables require a TBX-3L power

boot for terminating the circuit before connecting to power...

End-of-Circuit Termination: All BSX cables require the use of the ET-6 end cap and ET-60 overcap for terminating at the end of the circuit.

Corporate Headquarters 100 Thermon Dr.

PO Box 609 San Marcos, TX 78667-0609

U.S.A.

Phone: +1 512-396-5801

Facsimile: +1 512-396-3627 European Headquarters

Boezemweg 25

2641 KG Pijnacker

PO Box 205

2640 AE Pijnacker

The Netherlands

Phone: +31 (0) 15-36 15 370

Facsimile: +31 (0) 15-36 15 379

Construction . . .

1 Nickel-Plated Copper Bus Wires (1.3 mm2)

2 Radiation Cross-Linked Semiconductive Heating Matrix

3 Radiation Cross-Linked Dielectric Insulation

4 Tinned Copper Braid

5 Polyolefin overjacket provides additional protection where exposure to aqueous inorganic chemicals is expected.

Options . . .

6 FOJ Fluoropolymer overjacket provides additional protection where exposure to organic chemicals or corrosives is expected. 2 3 1 5, 6 4 Notes . . .

1. Cable may be energised at other voltages; contact Thermon for design assistance. 2. T-rating per internationally recognised testing agency guidelines.

3. Thermon heating cables are approved for the listed T-ratings using the stabilised design method. This enables the cable to operate in hazardous areas without limit-ing thermostats. The T-ratlimit-ing may be determined uslimit-ing CompuTrace® Electric Heat Tracing Design Software or contact Thermon for design assistance.

4. Information on additional accessories to complete a heater circuit installation and to comply with approval requirements can be found in the “Self-Regulating Cables Systems Accessories” product specification sheet (Form TEP0010U).

(2)

Power Output Curves . . .

The power outputs shown apply to overjacketed cable installed on insulated metallic pipe at the service voltage stated below.

BSX

TM

Self-Regulating Heating Cable

Product Specifications

Circuit Breaker Sizing and Type1 . . .

Maximum circuit lengths for various circuit breaker amperages are shown below. Circuit breaker sizing and earth-fault protection should be based on applicable local codes. For information on design and performance on other voltages, contact Thermon.

Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment. e p y T t c u d o r P l a n i m o N c a V 0 3 2 C ° 0 1 t a t u p t u O r e w o P m / W 2 -3 X S B 9 2 -5 X S B 15 2 -8 X S B 25 2 -0 1 X S B 32

BSX has additional hazardous area approvals including: • DNV • Lloyd’s • SAA • JIS • CCE/CMRS

Contact Thermon for additional approvals and specific information.

Factory Mutual Research Hazardous (Classified) Locations

European Organisation for Electrotechnical Standardisation

Hazardous (Classified) Locations Certifications/Approvals . . .

Underwriters Laboratories Inc. Hazardous (Classified) Locations

II 2 G/D EEx e II T5 or T6 02 ATEX 0132424

Note . . .

1. Maximum circuit lengths shown are based on an instantaneous trip current charac-teristic per IEC 60898 at the referenced start-up temperature and a 10°C mainte-nance temperature. For maximum circuit lengths with other trip current characteristics contact Thermon.

2. While a heat tracing system is generally designed to keep the contents of a pipe at

BSX at 230 Vac

Pipe Temperature °C

Watts per Metre

25 30 0 20 40 50 0 20 30 65 35 10 40 60 BSX 3-2 BSX 5-2 BSX 8-2 15 10 5 BSX 10-2 s r e k a e r B t i u c r i C B e p y T e g a t l o V e c i v r e S c a V 0 3 2 Max.CircuitLength3vs.BreakerSize s e r t e M t c u d o r P e p y T p U -t r a t S e r u t a r e p m e T 2 C ° 16A 25A 32A 2 -3 X S B 0 1 191 226 226 0 191 226 226 0 2 - 156 226 226 0 4 - 127 199 226 2 -5 X S B 0 1 117 184 184 0 117 184 184 0 2 - 98 153 184 0 4 - 80 125 160 2 -8 X S B 0 1 93 146 146 0 93 146 146 0 2 - 74 116 146 0 4 - 61 95 122 2 -0 1 X S B 0 1 67 105 120 0 58 91 117 0 2 - 45 71 91 0 4 - 37 58 75 s r e k a e r B t i u c r i C C e p y T e g a t l o V e c i v r e S c a V 0 3 2 Max.CircuitLength3vs.BreakerSize s e r t e M t c u d o r P e p y T p U -t r a t S e r u t a r e p m e T 2 C ° 16A 25A 32A 2 -3 X S B 0 1 191 226 226 0 191 226 226 0 2 - 156 226 226 0 4 - 127 199 226 2 -5 X S B 0 1 117 184 184 0 117 184 184 0 2 - 98 153 184 0 4 - 80 125 160 2 -8 X S B 0 1 93 146 146 0 93 146 146 0 2 - 78 122 146 0 4 - 64 100 128 2 -0 1 X S B 0 1 77 120 120 0 75 117 120 0 2 - 59 92 118 0 4 - 48 75 96

(3)

THERMON . . . The Heat Tracing Specialists®

www.thermon.com

RSX

TM

15-2

Self-Regulating Heating Cable

Product Specifications

Application . . .

Freeze Protection or Process Temperature Maintenance

RSX 15-2 self-regulating heating cable is designed for applications where the Watt density requirements preclude the use of the standard range of winterization cables. The cable is ideally suited for freeze protection or process temperature maintenance applications that have higher heat losses but are not exposed to high temperatures (such as steam cleaning).

The ends of RSX 15-2 must be properly terminated prior to connecting the cable to power. Refer to the “Self-Regulating Cables Systems Accessories” product specification sheet (Form TEP0010U).

RSX 15-2 is approved for use in ordinary (nonclassified) areas and Zone 1 and 2 classified areas.

Ratings . . .

Available Watt density ... 48 W/m at 10°C Nominal supply voltage1... 230 Vac

Maximum maintenance temperature ... 65°C Maximum continuous exposure temperature

Power-off ... 85°C Minimum installation temperature .... -40°C (OJ); -51°C (FOJ) Minimum bend radius ... 32 mm T-rating2... T5 100°C

Power Output Curve . . .

Corporate Headquarters 100 Thermon Dr.

PO Box 609 San Marcos, TX 78667-0609

U.S.A.

Phone: +1 512-396-5801

Facsimile: +1 512-396-3627 European Headquarters

Boezemweg 25

2641 KG Pijnacker

PO Box 205

2640 AE Pijnacker

The Netherlands

Phone: +31 (0) 15-36 15 370

Facsimile: +31 (0) 15-36 15 379

Construction . . .

1 Nickel-Plated Copper Bus Wires (2.1 mm2)

2 Radiation Cross-Linked Semiconductive Heating Matrix

3 Radiation Cross-Linked Dielectric Insulation

4 Tinned Copper Braid (BC) Options . . .

5 OJ Polyolefin Overjacket

6 FOJ Fluoropolymer Overjacket Circuit Breaker Sizing . . .

4 2

Factory Mutual Research

Hazardous (Classified) Locations

European Organisation for Electrotechnical Standardisation

Hazardous (Classified) Locations

3 1

5, 6

RSX 15-2 has additional hazardous area approvals including:

• DNV • Lloyd’s • SAA

• JIS • CCE/CMRS

Contact Thermon for additional approvals and specific information.

Pipe Temperature °C

Watts per Metre

35 40 10 30 40 50 0 20 30 65 45 10 50 60 25 20 15 RSX 15-2 Certifications/Approvals . . .

Form TEP0048U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.

Notes . . .

1. Cable may be energised at other voltages; contact Thermon for design assistance. 2. T-rating per internationally recognised testing agency guidelines.

55 60 e g a t l o V e c i v r e S c a V 0 3 2 Max.CircuitLength e z i S r e k a e r B . s v ) s r e k a e r B e p y T -C ( s e r t e M t c u d o r P e p y T p U -t r a t S e r u t a r e p m e T C ° 16A 25A 32A 40A 2 -5 1 X S R 0 1 35 56 74 98 0 33 53 71 93 0 2 - 30 48 63 82

(4)

KSX

TM

Self-Regulating Heating Cable

Product Specifications

Application . . .

Process Temperature Maintenance or Freeze Protection

High performance KSX self-regulating heating cables are designed specifically for high heat loss freeze protection applications or process temperature maintenance where steam cleaning is not required.

The heat output of KSX cable varies in response to the surrounding temperature by reducing its thermal output with increasing temperature.

KSX cables are approved for use in ordinary (nonclassified) areas and are certified to the ATEX directive for use in Category 2 and 3 (Zone 1 and 2) classified areas.

Ratings . . .

Available watt densities ... 48, 64 W/m @ 10°C Nominal supply voltages1... 230 Vac

Max. maintenance or exposure temperature

Continuous power-on ... 121°C Minimum installation temperature ... -60°C Minimum bend radius ... 32 mm T-rating2 ... T3 200°C

Based on stabilised design3... T4 to T6

Basic Accessories4 . . .

Power Connection: All KSX cables require a TBX-4L power

connection boot for terminating the circuit before connect-ing to power.

End-of-Circuit Termination: KSX cables require the ET-8

end cap and ET-80 overcap for terminating at the end of the circuit.

Notes . . .

1. Cable may be energised at other voltages; contact Thermon for design assistance. 2. T-rating per internationally recognised testing agency guidelines.

3. Thermon heating cables are approved for the listed T-ratings using the stabilised design method. This enables the cable to operate in hazardous areas without limiting thermostats. The T-rating may be determined using CompuTrace® Electric

Heat Tracing Design Software or contact Thermon for design assistance. 4. Information on additional accessories to complete a heater circuit installation and to

comply with approval requirements can be found in the “Self-Regulating Cables Systems Accessories” product specification sheet (Form TEP0010U).

Construction . . .

1 Nickel-Plated Copper Bus Wires (1.3 mm2)

2 Semiconductive Heating Matrix and Fluoropolymer Dielectric Insulation 3 Tinned Copper Braid

4 Fluoropolymer overjacket provides additional protection to cable and braid where exposure to chemicals or corrosives is expected. 4 3 2 1 Product Features . . .

• Withstands continuous flamibility testing according to IEC 60332-1: 1993

• Allows cable to be installed at temperatures to -60°C

• Termination for system tested for ozone stability, UV stability and flammability testing according to ISO/IEC requirements

(5)

Form TEP0072U-0104 © Thermon Manufacturing Co. Printed in U.S.A. Power Output Curves . . .

The power outputs shown apply to overjacketed cable installed on insulated metallic pipe at the service voltage stated below.

Circuit Breaker Sizing and Type1 . . .

Maximum circuit lengths for various circuit breaker

amperages are shown below. Circuit breaker sizing and earth-fault protection should be based on applicable local codes. For information on design and performance on other voltages, contact Thermon.

Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment.

KSX

TM

Self-Regulating Heating Cable

Product Specifications

Watts per Meter

20 40 Pipe Temperature °C 0 30 60 90 120 0 10 60 e p y T t c u d o r P c a V 0 3 2 l a n i m o N t u p t u O r e w o P C ° 0 1 t a m / W 2 -5 1 X S K 48 2 -0 2 X S K 64 KSX 15-2 KSX at 230 Vac

KSX has additional hazardous area approvals including: • DNV • Lloyd’s • SAA • JIS • CCE/CMRS • GGTN Contact Thermon for additional approvals and specific information.

Factory Mutual Research

Hazardous (Classified) Locations

European Organisation for Electrotechnical Standardisation

Hazardous (Classified) Locations Certifications/Approvals . . .

Underwriters Laboratories Inc.

Hazardous (Classified) Locations II 2 G/D EEx e II T3 02 ATEX 0148864 KSX 20-2 50 30 70 Note . . .

1. Maximum circuit lengths shown are based on an instantaneous trip current characteristic per IEC 60898 at the referenced start-up temperature and a 10°C maintenance temperature. For maximum circuit lengths with other trip current characteristics contact Thermon.

2. While a heat tracing system is generally designed to keep the contents of a pipe at the desired maintain temperature, the cable may be energized at lower temperatures. For design data with lower start-up temperatures than represented above contact Thermon for design assistance.

3. The maximum circuit length is for one continuous length of cable, not the sum of segments of cable. Refer to CompuTrace® design software or contact Thermon for

current loading of segments.

s r e k a e r B t i u c r i C B e p y T e g a t l o V e c i v r e S c a V 0 3 2 Max.CircuitLength3vs.BreakerSize s e r t e M t c u d o r P e p y T p U -t r a t S e r u t a r e p m e T 2 C ° 16A 25A 32A 2 -5 1 X S K 0 1 46 76 94 0 44 72 94 0 2 - 39 63 83 0 4 - 35 56 73 2 -0 2 X S K 0 1 27 43 56 0 25 40 53 0 2 - 23 36 47 0 4 - 21 33 42 s r e k a e r B t i u c r i C C e p y T e g a t l o V e c i v r e S c a V 0 3 2 Max.CircuitLength3vs.BreakerSize s e r t e M t c u d o r P e p y T p U -t r a t S e r u t a r e p m e T 2 C ° 16A 25A 32A 2 -5 1 X S K 0 1 46 76 94 0 46 76 94 0 2 - 46 76 94 0 4 - 43 71 94 2 -0 2 X S K 0 1 36 59 78 0 36 59 78 0 2 - 36 59 78 0 4 - 35 56 74

(6)

TSX

TM

Self-Regulating Heating Cable

Product Specifications

Application . . .

Process Temperature Maintenance or Freeze Protection

TSX self-regulating heating cables are designed specifically for process temperature maintenance or freeze protection where elevated cold-start currents are unacceptable. TSX withstands the temperature exposures associated with steam purging.

The heat output of TSX cable varies in response to the surrounding temperature. Variations in the ambient tem-perature or heat lost through the thermal insulation are compensated for automatically along the entire length of a heat-traced pipe. This self-regulating feature allows TSX to be overlapped without temperature upset damage to the cable.

TSX cables are approved for use in ordinary (nonclassified) areas and Zone 1 and 2 classified areas.

Ratings . . .

Available Watt densities ... 9, 18, 27, 37 W/m at 10°C Nominal supply voltage1... 230 Vac

Maximum maintenance temperature ... 121°C Maximum continuous exposure temperature

Power-off ... 190°C Minimum installation temperature ... -51°C Minimum bend radius ... 32 mm T-rating2... T3 200°C

Basic Accessories3 . . .

Power Connection: All TSX cables require a TBX-3L power

boot for terminating the circuit before connecting to power...

End-of-Circuit Termination: TSX cables with the metallic

braid require the use of the ET-8 end cap for terminating at the end of the circuit.

TSX cables with the overjacket option require the ET-6 end cap for terminating at the end of the circuit.

Notes . . .

1. Cable may be energised at other voltages; contact Thermon for design assistance. 2. T-rating per internationally recognised testing agency guidelines.

3. Information on additional accessories to complete a heater circuit installation and to comply with approval requirements can be found in the “Self-Regulating Cables Systems Accessories” product specification sheet (Form TEP0010U).

Construction . . .

1 Nickel-Plated Copper Bus Wires (1.3 mm2)

2 Semiconductive Heating Matrix

3 Fluoropolymer Dielectric Insulation

4 Nickel-Plated Copper Braid (BN) Options . . .

5 OJ Fluoropolymer overjacket over nickel-plated copper braid provides additional protection to cable and braid where exposure to chemicals or corrosives is expected. Certifications/Approvals . . . 5 4 3 2 1

Factory Mutual Research

Hazardous (Classified) Locations

European Organisation for Electrotechnical Standardisation

Hazardous (Classified) Locations

TSX has additional hazardous area approvals including:

• DNV • Lloyd’s • SAA

• JIS • CCE/CMRS

Contact Thermon for additional approvals and specific information.

(7)

Power Output Curves . . .

The power outputs shown apply to overjacketed cable installed on insulated metallic pipe at the service voltage stated below.

TSX

TM

Self-Regulating Heating Cable

Form TEP0006U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.

Product Specifications

Circuit Breaker Sizing and Type . . .

Maximum circuit lengths for various circuit breaker amperages are shown below. Circuit breaker sizing and earth-fault protection should be based on applicable local codes. TSX heating cables do not exhibit significant elevated cold-start currents; therefore, it is not necessary to adjust the circuit length based on expected minimum ambient start-up temperatures to -40° C. For information on design and performance on other voltages, contact Thermon. Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment.

e p y T t c u d o r P l a n i m o N c a V 0 3 2 C ° 0 1 t a t u p t u O r e w o P m / W 2 -3 X S T 9 2 -6 X S T 18 2 -9 X S T 27 2 -2 1 X S T 37 TSX at 230 Vac Pipe Temperature °C TSX 12-2 TSX 6-2 TSX 3-2

Watts per Metre

TSX 9-2 20 30 0 10 50 75 100 -25 25 50 125 40 0 e g a t l o V e c i v r e S c a V 0 3 2 Max.CircuitLengthvs.BreakerSize ) s r e k a e r B e p y T -C ( s e r t e M e p y T t c u d o r P 16A 25A 2 -3 X S T 171 2 71 2 -6 X S T 111 153 2 -9 X S T 82 125 2 -2 1 X S T 64 107

(8)

HTSX

TM

15 and 20

Self-Regulating Heating Cable

Product Specifications

Application . . .

Process Temperature Maintenance or Freeze Protection

HTSX self-regulating heating cables are designed specifically for process temperature maintenance or freeze protection where high temperature exposure capability is required. HTSX withstands the temperature exposures associated with steam purging.

The heat output of HTSX cable varies in response to the surrounding temperature. Variations in the ambient tempera-ture or heat lost through the thermal insulation are compen-sated for automatically along the entire length of a heat-traced pipe.

HTSX cables are approved for use in ordinary (nonclassified) areas and are certified to the ATEX directive for use in Category 2 and 3 (Zone 1 and 2) classified areas.

Ratings . . .

Available watt densities ... 48, 64 W/m @ 10°C Nominal supply voltages1... 230 Vac

Max. maintenance temperature ... 121°C Max. exposure temperature

Intermittent power-on ... 191°C Continuous power-off ... 191°C Minimum installation temperature ... -60°C Minimum bend radius ... 32 mm T-rating2 ... T3 200°C

Based on stabilised design3... T4 to T6

Basic Accessories4 . . .

Power Connection: All HTSX cables require a TBX-4L power

connection boot for terminating the circuit before connect-ing to power.

End-of-Circuit Termination: HTSX cables require the ET-8

end cap and ET-80 overcap for terminating at the end of the circuit.

Notes . . .

1. Cable may be energised at other voltages; contact Thermon for design assistance. 2. T-rating per internationally recognised testing agency guidelines.

3. Thermon heating cables are approved for the listed T-ratings using the stabilised design method. This enables the cable to operate in hazardous areas without limit-ing thermostats. The T-ratlimit-ing may be determined uslimit-ing CompuTrace® Electric Heat

Tracing Design Software or contact Thermon for design assistance.

4. Information on additional accessories to complete a heater circuit installation and to comply with approval requirements can be found in the “Self-Regulating Cables Systems Accessories” product specification sheet (Form TEP0010U).

Construction . . .

1 Nickel-Plated Copper Bus Wires (1.3 mm2)

2 Semiconductive Heating Matrix and Fluoropolymer Dielectric Insulation 3 Tinned Copper Braid

4 Fluoropolymer overjacket provides additional protection to cable and braid where exposure to chemicals or corrosives is expected. 4 3 2 1 Product Features . . .

• Withstands continuous flamibility testing according to IEC 60332-1: 1993

• Allows cable to be installed at temperatures to -60°C

• Termination for system tested for ozone stability, UV stability and flammability testing according to ISO/IEC requirements

(9)

Form TEP0074U-0104 © Thermon Manufacturing Co. Printed in U.S.A. Power Output Curves . . .

The power outputs shown apply to overjacketed cable installed on insulated metallic pipe at the service voltage stated below.

Circuit Breaker Sizing and Type1 . . .

Maximum circuit lengths for various circuit breaker

amperages are shown below. Circuit breaker sizing and earth-fault protection should be based on applicable local codes. For information on design and performance on other voltages, contact Thermon.

Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment.

HTSX

TM

15 and 20

Self-Regulating Heating Cable

Product Specifications

e p y T t c u d o r P c a V 0 3 2 l a n i m o N t u p t u O r e w o P C ° 0 1 t a m / W 2 -5 1 X S T H 48 2 -0 2 X S T H 64 HTSX 15-2 HTSX at 230 Vac

HTSX 15 and 20 has additional hazardous area approvals including:

• DNV • Lloyd’s • SAA • JIS • CCE/CMRS • GGTN Contact Thermon for additional approvals and specific information.

Factory Mutual Research

Hazardous (Classified) Locations

European Organisation for Electrotechnical Standardisation

Hazardous (Classified) Locations Certifications/Approvals . . .

Underwriters Laboratories Inc.

Hazardous (Classified) Locations II 2 G/D EEx e II T3 02 ATEX 0120790

HTSX 20-2

Watts per Meter

20 40 Pipe Temperature °C 0 30 60 90 120 0 10 60 50 30 70 Note . . .

1. Maximum circuit lengths shown are based on an instantaneous trip current characteristic per IEC 60898 at the referenced start-up temperature and a 10°C maintenance temperature. For maximum circuit lengths with other trip current characteristics contact Thermon.

2. While a heat tracing system is generally designed to keep the contents of a pipe at the desired maintain temperature, the cable may be energized at lower temperatures. For design data with lower start-up temperatures than represented above contact Thermon for design assistance.

3. The maximum circuit length is for one continuous length of cable, not the sum of segments of cable. Refer to CompuTrace® design software or contact Thermon for

current loading of segments.

s r e k a e r B t i u c r i C B e p y T e g a t l o V e c i v r e S c a V 0 3 2 Max.CircuitLength3vs.BreakerSize s e r t e M t c u d o r P e p y T p U -t r a t S e r u t a r e p m e T 2 C ° 16A 25A 32A 2 -5 1 X S T H 0 1 46 76 94 0 44 72 94 0 2 - 39 63 83 0 4 - 35 56 73 2 -0 2 X S T H 0 1 27 43 56 0 25 40 53 0 2 - 23 36 47 0 4 - 21 33 42 s r e k a e r B t i u c r i C C e p y T e g a t l o V e c i v r e S c a V 0 3 2 Max.CircuitLength3vs.BreakerSize s e r t e M t c u d o r P e p y T p U -t r a t S e r u t a r e p m e T 2 C ° 16A 25A 32A 2 -5 1 X S T H 0 1 46 76 94 0 46 76 94 0 2 - 46 76 94 0 4 - 43 71 94 2 -0 2 X S T H 0 1 36 59 78 0 36 59 78 0 2 - 36 59 78 0 4 - 35 56 74

(10)

VSX

TM

Self-Regulating Heating Cable

Product Specifications

Application . . .

Process Temperature Maintenance or Freeze Protection

High performance VSX self-regulating heating cables are designed specifically for process temperature maintenance or freeze protection where high maintain temperatures or high temperature exposure is required. VSX withstands the temperature exposures associated with steam purging. The heat output of VSX cable varies in response to the surrounding temperature by reducing its thermal output with increasing temperature and can be overlapped without temperature upset damage to the cable. With its high self-regulating characteristic, VSX can be installed in hazardous areas requiring a T3 temperature class rating.

VSX cables are approved for use in ordinary (nonclassified) areas and Zone 1 and 2 classified areas.

Ratings . . .

Available Watt densities ... 15, 32, 48, 64 W/m at 10°C Nominal supply voltage1... 230 Vac

Maximum maintenance temperature ... 149°C Maximum continuous exposure temperature

Continuous power-off ... 204°C Intermittent power-on ... 232°C Minimum installation temperature ... -51°C Minimum bend radius ... 32 mm T-rating2... T3 200°C

Basic Accessories3 . . .

Power Connection: All VSX cables require a TBX-3L power

boot for terminating the circuit before connecting to power...

End-of-Circuit Termination: All VSX cables require the use

of the ET-6 end cap for terminating at the end of the circuit.

Notes . . .

1. Cable may be energised at other voltages; contact Thermon for design assistance. 2. T-rating per internationally recognised testing agency guidelines. VSX 20 has a T2

(300°C) temperature rating per CENELEC.

3. Information on additional accessories to complete a heater circuit installation and to comply with approval requirements can be found in the “Self-Regulating Cables Systems Accessories” product specification sheet (Form TEP0010U).

Construction . . .

1 Nickel-Plated Copper Bus Wires (2.1 mm2)

2 Semiconductive Heating Matrix and Fluoropolymer Dielectric Insulation

3 Nickel-Plated Copper Braid

4 Fluoropolymer Overjacket Certifications/Approvals . . .

4 2 1

Factory Mutual Research

Hazardous (Classified) Locations

European Organisation for Electrotechnical Standardisation

Hazardous (Classified) Locations

3

VSX has additional hazardous area approvals including:

• DNV • Lloyd’s • SAA

• JIS • CCE/CMRS

Contact Thermon for additional approvals and specific information.

(11)

Power Output Curves . . .

The power outputs shown apply to overjacketed cable installed on insulated metallic pipe at the service voltage stated below.

VSX

TM

Self-Regulating Heating Cable

Form TEP0008U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.

Product Specifications

Circuit Breaker Sizing and Type . . .

Maximum circuit lengths for various circuit breaker amperages are shown below. Circuit breaker sizing and earth-fault protection should be based on applicable local codes. For information on design and performance on other voltages, contact Thermon.

Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment.

VSX at 230 Vac

Pipe Temperature °C

Watts per Metre

20 30 0 10 70 90 110 10 50 70 150 40 30 60 50 130 VSX 20-2 VSX 15-2 VSX 5-2 VSX 10-2 e p y T t c u d o r P l a n i m o N c a V 0 3 2 C ° 0 1 t a t u p t u O r e w o P m / W 2 -5 X S V 15 2 -0 1 X S V 32 2 -5 1 X S V 48 2 -0 2 X S V 64 230VacServiceVoltage Max.CircuitLengthvs.BreakerSize ) s r e k a e r B e p y T -C ( s e r t e M t c u d o r P e p y T p U -t r a t S e r u t a r e p m e T C ° 16A 25A 32A 40A 2 -5 X S V 0 1 98 168 201 201 0 98 168 201 201 0 2 - 98 168 201 201 2 -0 1 X S V 0 1 64 105 145 163 0 64 105 145 163 0 2 - 59 99 137 163 2 -5 1 X S V 0 1 47 77 104 142 0 47 76 103 141 0 2 - 41 67 89 121 2 -0 2 X S V 0 1 35 56 74 98 0 33 53 71 93 0 2 - 30 48 63 82

(12)

HPT

TM

Power-Limiting Heating Cable

Product Specifications

Application . . .

Process Temperature Maintenance or Freeze Protection

High performance HPT power-limiting heating cables are designed specifically for process temperature maintenance or freeze protection where high maintain temperatures or high temperature exposure is required. HPT withstands the temperature exposures associated with steam purging. A coiled resistor alloy heating element (patent pending) provides the power-limiting feature of HPT. This PTC (Positive Temperature Coefficient) characteristic decreases the cable’s power output as the heat-traced product temperature increases and allows the cable to be over-lapped during installation. The composite construction of the heating element and fibre substrate, plus an additional fibre cushion layer, provides an exceptionally durable high performance heating cable.

HPT cables are approved for use in ordinary (nonclassified) areas and Zone 1 and 2 classified areas.

Ratings . . .

Available Watt densities ... 14, 28, 42, 57 W/m at 10°C Nominal supply voltage1... 230 Vac

Maximum maintenance temperature ... 149°C Maximum continuous exposure temperature

Power-off ... 260°C Minimum installation temperature ... -51°C Minimum bend radius ... 32 mm Basic Accessories2 . . .

Power Connection: All HPT cables require a TBX-4L power

boot for terminating the circuit before connecting to power...

End-of-Circuit Termination: HPT cables with exposure

temperatures below 200°C require the use of the ET-8 end cap and TT-6 fluoropolymer tape strip for terminating at the end of the circuit.

HPT cables with exposure temperatures between 200°C and 260°C require the HPEK-OJ end cap for terminating at the end of the circuit.

Notes . . .

1. Higher maintenance temperatures and operating voltages may be possible; contact Thermon for design assistance.

2. Information on additional accessories to complete a heater circuit installation and to comply with approval requirements can be found in the “Power-Limiting Cables Systems Accessories” product specification sheet (Form TEP0018U).

Construction . . .

1 Nickel-Plated Copper Bus Wires (3.3 mm2)

2 Composite Metal Alloy/Fibre

3 Heater Bus Connection (not shown)

4 Fibreglass Braid (not shown)

5 Fluoropolymer Dielectric Insulation

6 Nickel-Plated Copper Braid

7 Fluoropolymer Overjacket Certifications/Approvals . . .

2

Factory Mutual Research

Hazardous (Classified) Locations

European Organisation for Electrotechnical Standardisation

Hazardous (Classified) Locations

5 1

6

7

HPT has additional hazardous area approvals including:

• DNV • Lloyd’s • SAA

• JIS • CCE/CMRS

Contact Thermon for additional approvals and specific information.

(13)

Power Output Curves . . .

The power outputs shown apply to overjacketed cable installed on insulated metallic pipe at the service voltage stated below.

HPT

TM

Power-Limiting Heating Cable

Form TEP0011U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.

Product Specifications

Circuit Breaker Sizing and Type . . .

Maximum circuit lengths for various circuit breaker amperages are shown below. Circuit breaker sizing and earth-fault protection should be based on applicable local codes. For information on design and performance on other voltages, contact Thermon.

Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment.

HPT at 230 Vac

Watts per Metre 20 30 0 10 90 110 10 50 70 150 40 30 60 50 130 Pipe Temperature °C HPT 20-2 HPT 15-2 HPT 10-2 HPT 5-2 e g a t l o V e c i v r e S c a V 0 3 2 Max.CircuitLengthvs.BreakerSize ) s r e k a e r B e p y T -C ( s e r t e M t c u d o r P e p y T p U -t r a t S e r u t a r e p m e T C ° 16A 25A 32A 40A 2 -5 T P H 0 1 257 281 281 281 0 248 281 281 281 0 2 - 230 281 281 281 2 -0 1 T P H 0 1 124 199 199 199 0 120 199 199 199 0 2 - 112 182 199 199 2 -5 1 T P H 0 1 82 132 162 162 0 79 127 162 162 0 2 - 74 118 156 161 2 -0 2 T P H 0 1 61 98 128 133 0 59 94 124 128 0 2 - 55 88 114 118 e p y T t c u d o r P l a n i m o N c a V 0 3 2 h t g n e L e n o Z m c C º 0 1 t a t u p t u O r e w o P m / W 2 -5 T P H 76 14 2 -0 1 T P H 61 28 2 -5 1 T P H 61 42 2 -0 2 T P H 61 57

(14)

MIK

TM

Mineral Insulated Heating Cable

Product Specifications

Application . . .

Process Temperature Maintenance or Freeze Protection

MIK high performance mineral insulated heating cables are used extensively for high temperature maintenance, high temperature exposure and/or high Watt density applications which exceed the limitations of thermoplastic insulated cables.

Thermon’s MIK mineral insulated cables are available in three outer sheath materials to meet the temperature and exposure requirements of the application.

MIK cables are approved for use in ordinary (nonclassified) areas and are certified to the ATEX directive for use in Category 2 and 3 (Zone 1 and 2) classified areas.

Ratings . . .

Rated voltages1... 300 and 500 Vac

Maximum maintenance temperature2... 600°C

Maximum continuous exposure temperature

Power-off ... 650°C Maximum Watt density2... 200 W/m

Minimum installation temperature ... -20°C Minimum bend radius ... 6 x cable O.D. T-Rating5...T1 to T6

(Using the principles of stabilized design or limiters)6

Construction . . .

1 Solid Alloy or Copper Conductor 2 Compacted Magnesium Oxide Insulation 3 Metallic Sheath

Certification/Approval . . .

2

European Organisation for Electrotechnical Standardisation

Hazardous (Classified) Locations

3 1

MIK Heater Sets . . .

Thermon MIK cable sets are available in various factory-fabricated configurations designed for the cable type and number of conductors. Information regarding cable terminations is available from Thermon as part of a system design.

Notes . . .

1. Specific voltage depends on circuit length and design conditions. 2. Watt density limitations are correlated to maintain temperatures. 3. Optional overjackets are available on MIC cables; contact Thermon. 4. When using cable terminations under the insulation the maximum allowable

temperature is lower; contact Thermon.

5. T-rating per internationally recognised testing agency guidelines.

6. Thermon heating cables are approved for the listed T-ratings using the stabilised design method. This enables the cable to operate in hazardous areas without

e p y T t c u d o r P MetalSheathMaterial MaximumExposure e r u t a r e p m e T 4 C I M 3 Copper 280°C N I M CuproNickel 350°C S I M StainlessSteel 650°C

Available MIK Sheaths . . .

MIK has additional hazardous area approvals including:

• GGTN • Kazakhstan

II 2 G EEx e II T1 to T6 II 2 G EEx ed IIB or IIC T1 to T6 LCIE 01 ATEX 6025

(15)

Available Cables . . .

300 and 500 Vac—One Conductor

MIK

TM

Mineral Insulated Heating Cable

Form TEP0020U-0104 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.

Product Specifications

Circuit Breaker Sizing and Type . . .

Maximum circuit lengths for MIK heating cables will be a function of cable resistance, circuit length and operating voltage. Circuit length, breaker sizing and earth-fault protection should be based on applicable local codes. Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment.

Product Reference Legend . . .

Example: MIC-M1-800 Sheath Material C ... Copper2 N ... Cupro Nickel S ... Stainless Steel Rated Voltage L ... 300 Vac M ... 500 Vac Number of Conductors Conductor Resistance Ω/km Note . . .

1. All resistances shown are per length of cable at 20°C and are subject to a ±10% manufacturing tolerance.

2. Copper sheath available on request; contact Thermon.

t c u d o r P e p y T e l b a C r e t e m a i D m m e c n a t s i s e R 1 m / m h O C ° 0 2 t a d a e L d l o C e z i S e l b a C m m 2 0 0 6 1 -1 M -N I M 3.2 1.600 2.5 0 0 0 1 -1 M -N I M 3.4 1.000 2.5 0 3 6 -1 M -N I M 3.7 0.630 2.5 0 0 4 -1 M -N I M 4.0 0.400 2.5 0 5 2 -1 M -N I M 4.4 0.250 6.0 0 6 1 -1 M -N I M 4.9 0.160 6.0 3 6 -1 M -N I M 3.2 0.063 2.5 0 4 -1 M -N I M 3.4 0.040 2.5 5 2 -1 M -N I M 3.7 0.025 6.0 7 1 -1 M -N I M 4.6 0.017 6.0 1 1 -1 M -N I M 4.9 0.011 6.0 7 -1 M -N I M 5.3 0.007 10.0 4 -1 M -N I M 5.9 0.004 16.0 K 0 1 -1 M -S I M 3.2 10.000 2.5 0 0 3 6 -1 M -S I M 3.2 6.300 2.5 0 0 0 4 -1 M -S I M 3.2 4.000 2.5 0 0 5 2 -1 M -S I M 3.4 2.500 2.5 0 0 6 1 -1 M -S I M 3.6 1.600 2.5 0 0 0 1 -1 M -S I M 3.9 1.000 2.5 0 3 6 -1 M -S I M 4.3 0.630 2.5 0 0 4 -1 M -S I M 4.7 0.400 2.5 0 5 2 -1 M -S I M 5.3 0.250 6.0 0 6 1 -1 M -S I M 6.5 0.160 6.0

(16)

TESH

TM

Series Constant Watt Heating Cable

Product Specifications

Application . . .

Long Line Temperature Maintenance or Freeze Protection

TESH series resistance constant Watt heating cables are used where circuit lengths exceed the limitations of parallel resistance heating cables. TESH withstands the temperature exposures associated with steam purging.

The series circuitry of TESH provides consistent Watt-per-metre power output along the entire length of the cable with no voltage drop. A glassceramic tape layer adds additional protection to the heating cable and a fluoropolymer overjacket provides chemical resistance while maintaining maximum flexibility. The construction of the cable meets the 7 Joule impact test per EN50019.

TESH cables are approved for use in ordinary (nonclassi-fied) areas and Catagories 2 and 3 ATEX classified areas.

Ratings . . .

Maximum Watt density ... 25 W/m Maximum supply voltage ... 750 Vac Maximum continuous exposure temperature

Power-off ... 260°C Minimum installation temperature ... -60°C Minimum bend radius ... 5 x cable O.D. T-rating1... T2 to T6

(using the principles of stabilized design or limiters)2

Stabilised Design . . .

The Watt density limitation for TESH cables is directly related to the desired maintain temperature. Thermon is able to ensure the T-rating based on a stabilised design that enables series constant Watt heating cables to operate in hazardous areas without limiting thermostats. TESH cable output and T-rating are dependent upon supply voltage, cable resistance, temperature conditions as well as addi-tional variables. Contact Thermon for design assistance.

Basic Accessories3 . . .

Power Connection: TESH cables typically require

nonheat-ing terminations at each end of the circuit before connect-ing to power. Contact Thermon for complete information.

Notes . . .

1. T-rating per internationally recognised testing agency guidelines.

2. Thermon heating cables are approved for the listed T-ratings using the stabilised design method. This enables the cable to operate in hazardous areas without limiting thermostats. The T-rating may be determined using CompuTrace® Electric

Heat Tracing Design Software or contact Thermon for design assistance.

Construction . . .

1 Heating Conductor

2 Fluoropolymer Dielectric Insulation 3 Glassceramic Tape

4 Nickel-Plated Copper Braid (BN) 5 Fluoropolymer Overjacket

Certification/Approval . . .

2

European Organisation for Electrotechnical Standardisation

Hazardous (Classified) Locations

3 1

4

5

II 2 G/D EEx e IIC T2 to T6 LCIE 00 ATEX 6014 X

TESH has additional hazardous area approvals including:

• GGTN • Kazakhstan

Product Features . . .

• Withstands continuous flamibility testing according to IEC 60332-1: 1993

• Allows cable to be installed at temperatures to -60°C

(17)

Available Cables . . .

TESH

TM

Series Constant Watt Heating Cable

Form TEP0070U-0104 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.

Product Specifications

Circuit Breaker Sizing and Type . . .

Maximum circuit lengths for TESH heating cables will be a function of cable resistance, circuit length and operating voltage. Circuit length, breaker sizing and earth-fault protection should be based on applicable local codes. Earth-fault protection of equipment should be provided for each branch circuit supplying electric heating equipment.

Note . . .

1. Longer circuit lengths are possible based on fault protection with higher earth-fault ratings; contact Thermon.

e p y T t c u d o r P e c n a t s i s e R m / m h O C ° 0 2 t a r o t c u d n o C e z i S m m 2 h t g n e L e l b a C . x a M 1 -h t r a e A m 0 3 h ti w ( m ) n o it c e t o r p tl u a f e l b a C r e t e m a i D m m 9 . 2 H S E T 0.0029 6.00 1435 7.0 4 . 4 H S E T 0.0044 4.00 1525 6.3 7 H S E T 0.0072 2.50 185 5.5 0 1 H S E T 0.010 1.79 1775 5.1 7 . 1 1 H S E T 0.0117 1.50 2025 4.9 5 1 H S E T 0.015 1.20 2090 4.7 8 . 7 1 H S E T 0.0178 1.00 2275 4.6 5 2 H S E T 0.025 1.11 2525 4.6 5 . 1 3 H S E T 0.0315 1.60 2400 4.9 0 5 H S E T 0.050 1.02 2335 4.7 5 6 H S E T 0.065 0.75 1890 4.4 0 8 H S E T 0.080 1.21 2190 4.3 0 0 1 H S E T 0.100 1.50 2025 4.9 0 5 1 H S E T 0.150 1.02 2335 4.6 0 0 2 H S E T 0.200 0.75 2605 4.4 0 2 3 H S E T 0.320 0.92 2420 4.5 0 8 3 H S E T 0.380 0.79 2555 4.4 0 8 4 H S E T 0.480 0.64 2765 4.3 0 0 6 H S E T 0.600 0.49 3010 4.2 0 0 7 H S E T 0.700 0.43 3155 4.1 0 1 8 H S E T 0.810 0.62 2780 4.3 0 0 0 1 H S E T 1.000 0.49 3010 4.2 0 4 4 1 H S E T 1.440 0.34 3395 4.1 0 5 7 1 H S E T 1.750 0.29 3615 4.1 0 0 0 2 H S E T 2.000 0.55 2900 4.2 0 0 0 3 H S E T 3.000 0.34 3395 4.1 0 0 0 8 H S E T 8.000 0.14 4455 3.8

References

Related documents

[r]

There are three key factors in manufacturing a self-regulating heating cable for long-term performance and stability: heating core homogeneity, contact resistance between heating

Specific manifestations of this principle for personnel selection involve examining validity or adverse impact of applicants from initial application through simulated selection

The proposed scheme uses power electronic converters to control the net power output from wind generation and storage systems in order to provide both energy balancing and

Introduction: Triple anticoagulation therapy (TT), comprising dual antiplatelet therapy (DAPT) and oral anticoagulation (OAC), is essential in atrial fibrillation (AF) patients

Heating Cable mineral insula ted MI Mineral Insulated High Temperature • Constant Wattage Series Resistance Heating Cable Sets • Process Temperature Maintenance to

Chromalox heating cable line includes cables suitable for most process maintenance, pipe and vessel freeze protection and roof and gut- ter de-icing applications.. Industrial

Self-Regulating & Constant Wattage Cable Grommets Pipe Sandoff Junction Box O-Ring RTD RTV 9VDC Battery Connector Protective Sleeve... Explanation of