Fire Alarm Control Panel
N-6000
Manual
REV :B
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building.
Particles of combustion or “smoke” from a developing
fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. • Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
• The amount of “smoke” present may be insufficient to alarm smoke detectors.
Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion
and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
Smoke detectors must be installed in
the same room as the control panel. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and
understood.
System Reaccepting Test after Software
Changes. To ensure proper system operation, this product
must be tested after any programming operation or change in site-specific software.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When possible,
make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Table of Content
Section 1:About This Manual ... 6
1.1Notes, Cautions & Warnings... 6
1.2Font Definition ... 6
Section 2:System Overview... 7
2.1Introduction ... 7
2.2Characteristics of the Product... 7
Section 3:System Configuration & Installation ... 9
3.1Features Main Performances ... 9
3.2Electrical Specifications ... 9
3.3System Configuration... 9
3.4System Block Diagram... 10
3.5Installation & Connection ... 11
3.5.1Enclosures... 11
3.5.2Connection Requirements... 12
3.5.3Connection of Circuit Board Terminals... 12
3.5.3.1CPU Diagram ... 12
3.5.3.2Power Supply Connection ... 15
3.5.3.3NIC-EC... 17
3.5.3.4Loop Control Module Connection... 19
3.5.3.5MCU-16B Annunciator Control Module Connection ... 21
3.6Equipment Debugging ... 23
3.6.1Connection Inspection... 23
3.6.2Power-on Inspection... 24
3.6.3External Connection... 24
3.6.4Important Points ... 24
3.6.5Inspection Methods for Addressable Device Connections... 25
Section 4:Operation ... 26
4.1LED Indicators and Keys ... 26
4.1.1Control Panel Display LED Indicators and Keys ... 26
4.1.2Annunciator Control Module LED Indicators and Keys ... 29
4.2Power-on ... 30
4.3System Self-test... 30
4.4Event Display ... 32
4.4.1Trouble Screen... 32
4.4.2Fire Alarm Screen... 33
4.4.3Supervisory Screen ... 34
4.4.4Point Disabled Screen... 35
4.4.5CBE Screen... 36
4.4.6Pre-alarm Screen... 36
4.4.7Horn / strobe Screen ... 37
Section 5:Programming ... 38 5.1Menu ... 38 5.2System Management... 40 5.2.1System setting ... 41 5.2.2Password modification ... 42 5.2.3Main Reset... 43 5.3Device Configuration... 44 5.3.1Loop card... 45 5.3.1.1Parameter setting ... 45 5.3.1.2Auto Programming ... 47 5.3.1.3Point Programming... 49
5.3.2Annunciator Control Module ... 50
5.3.2.1Parameter setting ... 51 5.3.2.2Point Programming... 51 5.3.3Remote Display ... 52 5.3.3.1Parameter setting ... 53 5.3.3.2Label Download ... 53 5.3.3.3Point Programming... 54 5.3.4CBE Programming... 54 5.3.4.1General Zone ... 55 5.3.4.2Logic Zone ... 55 5.3.5Device Control... 56 5.3.5.1Manual Output... 57 5.3.5.2Status Tracking... 58 5.3.5.3Walk Test ... 58 5.3.5.4Loop Drill... 60
5.3.5.5Power Supply Management... 60
5.3.6History Events ... 61
Section 6:Miscellaneous ... 62
6.1Safety Protection Device ... 62
6.2Usage and Maintenance... 62
6.3Common Troubles... 62
6.4Transportation & Storage ... 63
6.5Out-of-box Audit... 63
Section 1:About This Manual
1.1Notes, Cautions & Warnings
The following graphics appear in this manual to indicate a note, a caution, or warning:
Note:
Information that highlights an important part of the preceding or subsequent text or illustration.
Cautions:
Information about procedures that could cause programming errors, runtime errors, or equipment damage.
Warnings:
Indicates information about procedures that could cause irreversible damage to the control panel, irreversible loss of programming data or personal injury.1.2Font Definition
Special font styles used in this manual are listed in Table 1-1, Specifications of Manual Characters:
Font Meaning Example
【Bold】 Key on the control panel Press the key 【 Signals Silenced】
Script Name of document N-6000 User Manual
Section 2:System Overview
2.1Introduction
The N-6000 is a new generation intelligent fire alarm control panel recently released by Notifier. This panel satisfies all related requirements defined in GB4717-2005.
This control panel combines both alarm and CBE control functions. The N-6000 can also be programmed off-line when using a PC with Notifier Verifire Tools (NVT).
The N-6000 fire alarm control panel has many intelligent characteristics; these include but are not limited to drift compensation, sensitivity adjustment and self-optimizing alarm.
The N-6000 control panel with CBE (control by event) control can manage both alarm paging and gas extinguishing systems. The N-6000 connected with a CRT display terminal forms a comprehensive and reliable fire alarm control system, perfect for medium to large-scale facilities.
2.2Characteristics of the Product
y Large LCD Display
This system uses a large 320x240 pixel LCD display. To ensure accurate and timely detection the LCD displays a full Chinese interface (up to 320 Chinese characters), equipment type, location, alarm level, loop number and address number upon alarming.
y User Friendly Interface
The Menu contains all programming options. Software supports both English and Chinese input, full suggest and user friendly dialogue prompts. A user can conveniently toggle between the alarm information and CBE information screens. y Convenient Programming Options
Multilevel pre-alarm and alarm sensitivity enable localizing detector sensitivity for different applications. Have the function of trouble disenable also can choose to disenable any addressing unit in loop bus. Auto programming allows the N-6000 to “learn” what devices are physically connected and automatically load them in the program with default values for all parameters. The functions mentioned above significantly ease system operation while reducing daily maintenance.
y Real-time Analogue Display Curve
Real-time threshold value variation monitoring is possible for both intelligent analogue detectors and/or compound detectors.
y Accurate and Detailed Event Records
The system automatically and categorically stores and records the latest fire alarm, trouble or system event. It can display and store up to 8000 historical events. y Automatic Compensation Functions
Drift compensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt or dust accumulates. It reduces maintenance requirements by allowing the system to automatically perform periodic sensitivity measurements. Smoothing filters are also provided by software to remove transient noise signals, usually caused by electrical interference. y Printing Settings
The system can be networked and prompted to print the latest alarm event using a Chinese printer.
y Equipped With 8 Bus Control Modules.
Built-in Degraded Mode option. In the event of a CPU failure, the system is capable of general alarm if a fire condition is present.
y Off-line Programming and CRT display terminal
Connected with PC through the RS-232 interface, Screen of the control panel to realize programming setting on circuit configuration, CBE control relation of the control panel. Also can be connected with NCS through this Screen to carry out centralized management.
Section 3:System Configuration &
Installation
3.1Features Main Performances
y Supports 1 to 30 Signaling Line Circuits (SLCs). Up to 199 detectors and 99 modules (N.O. manual stations, two-wire smoke, notification or relay) per SLC
y Loop connection ports available, expandable up to 15 loop circuit cards y Supports up to 64 remote LCD displays
y Supports up to 32 MCU control card y Micro printer port
y N-CRT port provided - seamless connection to a third party system y Fire alarm output and trouble output relays
y Real-time clock
3.2Electrical Specifications
y Voltage range
Input voltage: 220 VAC Output voltage:
Two – 24 VDC non-resetable outputs One – 24 VDC resetable output Two – 5 VDC outputs
Several dry contacts - power supply trouble relay output y Maximum output current: 14.6A
3.3System Configuration
y Intelligent control panel: N-6000 y Remote display: LCD-100B, LDM-64B y Intelligent detectors:
Intelligent photoelectric smoke detector: ND-751P Intelligent heat detector: ND-751T
Intelligent smoke detector: FSB-200S y Intelligent base:
B601 B501 y Intelligent modules:
Intelligent monitor module: MMX-7
Intelligent monitor/control module: CMX-7 Intelligent control module: CMX-7C
Monitor module for two-wire 24 VDC conventional detectors: MMX-7P
Isolator: ISO-7
Intelligent manual call point: M500K Intelligent manual call point: M700K y Micro printer: uPRT-380S
y Chinese graphic and text management software: N-NCS, N-VFT
3.4System Block Diagram
Fig. 3-1 System Block Diagram
If there are many addressable units in the loop bus, user should install the shortcut isolator in front of the loop bus. The addressable units are less than 25 units between adjacent two isolators.
3.5Installation & Connection
3.5.1Enclosures
Wall-mount designs use a standard NOTIFIER® C-type cabinet. This cabinet is shown in Fig. 3-2 Cabinet Appearance:
Fig. 3-2 Cabinet Appearance
Detailed cabinet dimensions are shown in Fig. 3-3:
Fig. 3-3 C-type Cabinet Dimension Diagram
All NOTIFIER cabinets are fabricated from 16-gauge steel. The cabinet assembly consists of two basic parts: a backbox and a locking door. The backbox has been
engineered to provide ease-of-entry for the installer. Knockouts are positioned at numerous points to aid the installer in bringing a conduit into the enclosure.
3.5.2Connection Requirements
y All incoming/outgoing external conduits should use the control panel cabinet’s bottom knockout or opening for terminal connections.
y Loop transmission line adopts twisted pair cable, the type and specification are:
RVSP-2×1.5mm2
y Loop resistance (refers to loop resistance between the machine and two leads of the farthest addressing unit) should be less than 50 Ω.
y Power wiring should use two-color multiple plastic cable, red for male terminal, black for female terminal. The type and specification are: RV-2×2.5mm2
3.5.3Connection of Circuit Board
Terminals
3.5.3.1CPU Diagram
Control panel includes in a circuit board, it has CPU and extend device interface. You can order the board supports for 8, 16, 30 loops. The connections terminals, jumper and status lights are showed below:
Fig. 3-4 CPU Diagram
Connections terminal illuminate table:
Terminal Illumination
TB1 System Event Relay1,programmable;Default is fire alarm trigger TB2 System Event Relay12,programmable;Default is trouble trigger TB3 System Event Relay13,programmable;Default is reset trigger TB4 24VDCPower
TB5 RS-232 Micro printer port TB6 RS-232 NIC port
TB7 N-CRT Port(VFT、third party system) TB8 RPT port
TB9 Loop communication port
TB10 Extended device port(MCU/POM-8C/MPS) J10 Loudspeaker ,see J15
J15 Buzzer; user can select J10 or J15 to be system sound component Table 3-1 CPU-6000 Board Terminal Illuminate
Jumper illuminate table:
Terminal Illumination
JP2 System Event Relay 1,output selection ,24Vor trunk node JP3 System Event Relay 2,output selection ,24Vor trunk node JP5 System Event Relay 3,output selection ,24Vor trunk node JP9 ISP program write down jumper, user should cover jumper cap when
ISP upgrade program
JP18 Loop RS485 communication match terminal resistance selection jumper
JP19 Loop RS485 communication match terminal capacitance selection jumper
JP21 Extended device RS485 communication match terminal resistance selection jumper
JP22 Extended device RS485 communication match terminal capacitance selection jumper
JP23 RPT RS485 communication match terminal resistance selection jumper
JP24 RPT RS485 communication match terminal capacitance selection jumper
Table 3-2 CPU-6000 Board Jumper Illuminate
LED status illuminate table:
Terminal Illumination
LED1 System status normal;Green
LED2 System fire alarm and CBE event;Red LED3 System trouble event;Yellow
LED4 System supervise event;Blue LED5 Relay1;relay close is green LED6 Relay2;relay close is green LED7 Relay3;relay close is green LED8 24VDC;Green
LED9 5VDC;Green
LED10 Micro printer channel signal send; signal on is green LED11 N-CRT protocol channel signal send; signal on is green LED12 Micro printer channel signal receive; signal on is green LED13 N-CRT protocol channel signal receive; signal on is green LED15 RPT channel signal receive; signal on is green
LED17 RPT channel signal send; signal on is green
LED18 Extended device channel signal receive; signal on is green LED19 Loop channel signal receive; signal on is green
LED20 Extended device channel signal send; signal on is green LED21 Loop channel signal send; signal on is green
Table 3-3 CPU-6000 Status Light Illumination
3.5.3.2Power Supply Connection
The N-6000 fire alarm control panel is powered by the MPS-350W power supply module. This power module provides multi-path 24 VDC and 5 VDC outputs. During a power loss the MPS-350W battery will automatically engage and provide power. LED displays indicate the status of multiple functions, including: main power trouble, reserve power trouble, grounding trouble, storage battery charging trouble and power supply relay output trouble.
Refer to the MPS-350W user manual for additional information regarding function, connection and/or application of the MPS-350W power supply.
Fig. 3-5 Power Supply Connection Diagram
Connections terminal illuminate table:
TB1 Non-resetable 24VDC terminal TB2 Non-resetable 24VDC terminal TB3 Resetable 24VDC terminal TB4 Non-resetable 24VDC terminal TB5 Non-resetable 24VDC terminal TB12 Trouble relay trunk node terminal
TB13 RS-485 serial communication port terminal TB14 Extended system supervise signal terminal
Table 3-4 MPS-350 Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP1 Program jumper, user can not change JP2 RS-485 bus terminal match capacitance JP3 RS-485bus terminal match resistance JP4/ JP5 Earth trouble function enable, disable
Table 3-5 MPS-350 Jumper Illumination
LED status illuminate table:
LED Illumination
LED1 Non-resetable 24VDC fuse melt indication LED2 Non-resetable 24VDC fuse melt indication LED3 Resetable 24VDC fuse melt indication LED13 Non-resetable 5VDC fuse melt indication LED19 Non-resetable 5VDC fuse melt indication LED23 Battery cut protect indication
LED24 Battery fuse melt indication LED25 Power normal indication LED26 Power trouble indication LED27 Battery normal indication LED28 Battery trouble indication LED29 System running indication LED30 Earth trouble indication
3.5.3.3NIC-EC
When N-6000 connect into N-NET fire alarm network, each control panel must install a NIC-EC card. Connection terminal, jumper and indicative show as below:
Fig. 3-6 NIC-EC Connection Diagram
Connections terminal illuminate table:
Terminal Illumination
TB1 Network port A TB2 24VDC power port
TB3 NIC-EC and CPU-6000 communication port(RS232) TB5 Network port A
Table 3-7 NIC-EC Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP6 RS232 mode(leave factory set, not to change) JP7 Open (leave factory set, not to change) JP8 Open (leave factory set, not to change) JP9 RS232 mode(leave factory set, not to change)
Table 3-8 NIC-EC Jumper Illumination
LED1 Green Port B signal output Blink when signal output otherwise off LED2 Green Port B signal input Blink when signal input otherwise off LED23 Green Port B information status
Status overturn after send or receive a frame information
correctly LED24 Yellow Port B trouble
LED on when send or receive a frame information wrongly or check out communication error LED25 Red Port B circuit trouble LED on when any trouble occur
LED3 Green Port A signal output Blink when signal output otherwise off LED4 Green Port A signal input Blink when signal input otherwise off LED20 Green Port A information status
Status overturn after send or receive a frame information
correctly LED21 Yellow Port A trouble
LED on when send or receive a frame information wrongly or check out communication error LED22 Red Port A circuit trouble LED on when any trouble occur
LED5 Green System running indication Blink when running normally LED6 Yellow Control panel type indication LED on when connect to CPU-6000 LED7 Red Control panel type indication LED on when connect to N-NCS LED8 Green +24V power status light LED on when +24V power supply normally LED9 Green +5V power status light LED on when +5V power supply normally LED10 Green TB3 port signal input Blink when signal input otherwise off LED11 Green J9 signal input indication Blink when signal input otherwise off LED12 Green TB3 port signal
output
Blink when signal output otherwise off LED13 Green J9 signal output
indication
Blink when signal output otherwise off LED14 Green Function reserve — LED15 Green Function reserve — LED16 Red Function reserve —
LED17 Green information TB3 port Status overturn after send or receive a frame information
correctly LED18 Yellow TB3 port trouble LED on when receive information error LED19 Red TB3 port circuit trouble LED on when receive information error LED26 Blue Function reserve —
Table 3-9 NIC-EC Indicative Light Illumination
DIP switch network address setting table:
SW2 status Function ON 1 OFF ON 2 OFF ON 3 OFF ON 4 OFF ON 5 OFF ON 6 OFF 1~6bits switch ON for 1,OFF for 0 Composing a 6 bits binary number,
this number infer network card address. Network card address range is the number between 0~63. Network card address must be same
as the connect device’s address.
ON Relay mode
7
OFF Bus mode
ON N-NCS 8
OFF CPU-6000 Table 3-10 NIC-EC Address Setting
3.5.3.4Loop Control Module Connection
N-6000 support 15 LCM-2 cards, and 30 loops. LCM-2 support style 4 or T-type wiring. TB2 in LCM-2 board connect to CUP-6000 interface, the rest connect each other. LCM-2 can connect with twisted shielded pair cable: signal connect to TB2, power connect to TB3; also can connect each other through J2 and J4.
Fig. 3-7 Loop Control Module Connection Diagram
Connection terminal illuminate table:
Terminal Illumination
TB2 Connect to CPU-6000(RS485),also can connect to LCM card TB3 24VDC power port
TB4 Loop 1 port(the loop number is SW1’s value) TB5 Loop 2 port(the loop number is SW1’s value+1)
J2 Interlink port J4 Interlink port
Table 3-11 LCM-2 Card Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP1 Communication to CPU-6000 port terminal resistance (normal open) JP2 Communication to CPU-6000 port terminal capacitance (normal
open)
JP4 Switch to RS232 mode(leave factory set, not to change) JP5 Switch to RS232 mode(leave factory set, not to change)
Table 3-12 LCM-2 Card Jumper Illumination
LED Status Illuminate table:
Terminal Illumination
LED1 3.3V system power supply indication LED2 24 V system power supply indication
LED3 5 V system power supply indication
LED4 CPU-6000 communication/LCM card local mode indecation LED5 Loop 1 running indication
LED6 Loop 1 trouble indication LED7 Loop 1 fire alarm indication LED8 Loop 2 running indication LED9 Loop 2 trouble indication LED10 Loop 2 fire alarm indication
LED11 Communication to CPU-6000send indication LED12 Communication to CPU-6000send indication
Table 3-13 LCM-2 Card Status Light Illumination
DIP Switch Loop Number Setting table:
SW1~8 1~8bits switch
ON for 1,OFF for 0
Composing a 8 bits binary number, infer LCM card address. SW1 setting range is the odd number between
1~29
Table 3-14 LCM-2 Loop Number Setting
3.5.3.5MCU-16B Annunciator Control Module
Connection
N-6000 can connect MCU-16B. Support the manual control to output point of control module, and use LED to show the status of controlled points.
MCU-16B includes 16 output indicative light, 16 feedback statuses light, 16 button to manual control, a complex function button, a enable/disable button and a manual/auto status light.
Each manual control module can be programmed to any control module. Each feedback statuses light can be programmed to control an input device. Enable/disable button use to enable or disable 16 manual control buttons.
MCU-16B connects to N-6000 by RS-485 port, this port can support 32 MCU-16B.
Fig. 3-8 Annunciator Control Module Connection Diagram
Connection terminal illuminate table:
Terminal Illumination
TB1 24VDC power port
TB2 Connect to CPU-6000(RS485) J1 Interlink port
J3 Interlink port
Table 3-15 MCU-16B Terminal Illumination
Jumper illuminate table:
Terminal Illumination
JP1 Open(leave factory set, not to change)
JP2 Communication to CPU-6000 port terminal resistance (normal open)
JP3 Communication to CPU-6000 port terminal capacitance (normal open)
JP4 Switch to RS232 mode(leave factory set, not to change) JP5 Switch to RS232 mode(leave factory set, not to change) JP6 Buzzer switch(default shortcut, enable)
Table 3-16 MCU-16B Jumper Illumination
Terminal Illumination
LED1 24 V system power supply indication LED2 5 V system power supply indication LED3 3.3 V system power supply indication LED4 System running indication
LED39 Communication to CPU-6000send indication LED40 Communication to CPU-6000send indication
Table 3-17 MCU-16B Status Light Illumination
DIP Switch Loop Number Setting table:
SW2 status function ON 1 OFF ON 2 OFF ON 3 OFF ON 4 OFF ON 5 OFF 1~8bits switch ON for 1,OFF for 0
Composing a 5 bits binary number, this number +1 infer MCU’s address. MCU’s address range is the number
between 1~29 ON 6 OFF NONE ON 7 OFF NONE 8 ON NONE
Table 3-18 MCU-16B Network address setting
3.6Equipment Debugging
3.6.1Connection Inspection
y Visually inspect the control panel condition y Visually inspect the external connection ports
y Open the control panel and visually inspect all connections. Confirm connections are correct, that there are no loose connections, no short circuits, unplugged or
disconnected connectors as well as confirm the power supply does not have any short circuit trouble.
y Visually inspect the jumpers in the circuit to confirm there are no duplicate numbers.
3.6.2Power-on Inspection
After you have finished the visual inspection, power-on the battery power supply. With the battery started a buzzer should be heard and the LCD should temporarily function normally. Once the control panel enters normal operation status, a buzzer and LED horn/strobe will indicate a troubled status because main power is not connected. Power-down and disconnect the battery power supply then connect and power on the main power supply. Once the control panel enters normal operation status, a buzzer and LED horn/strobe will indicate a troubled status because the battery power supply is not connected. At this time, connect the battery power supply. Soon after the control panel will return to normal operating status.
During normal operation, if both the main and battery power supplies are connected the power supply status lamp (on the main panel of the control panel) will maintain normal illumination.
When the main power supply fails because of loss of power, poor power connection, an over-voltage or under-voltage of 5V and 24V, or a short circuit with rack earth and communication trouble with the mainframe, the power supply status lamp (on main panel of the control panel) illumination will stop. Then both a buzzer and LED horn/strobe will indicate a troubled status while additional information will be shown on the control panel LCD.
3.6.3External Connection
Look for any short-circuits or disconnections to and from the control panel. Once everything has been inspected, connect the control panel.
Batch installation -- connecting 10-20 detectors or modules on the loop per time -- is highly recommended. After installing the detectors or modules restart the control panel to ensure the newly installed devices are recognized and installed correctly. If the control panel gives a trouble signal recheck the circuit and addressable devices are installed properly. Once the trouble signal has been solved, continue batch installation and power testing. After all the devices have been installed, the simulated trouble, fire alarm and CBE event functions maybe tested. Confirm that the control panel alarms normally, properly links field equipment and accurately prints corresponding alarm information. Continue testing and adjusting until panel maintains normal operating status.
3.6.4Important Points
y Avoid touching the circuit board IC chip during installation y Pay attention to polarity during connection and installation
y Before starting the system, check for short circuits, disconnection or reverse polarity
y Connectors among leads shall be wielded and inter-line insulation shall be guaranteed.
3.6.5Inspection Methods for Addressable Device
Connections
To test the function of the multi-meter, connect the loop in reverse polarity (the positive pole connects with the loop negative and the negative pole connects with the loop positive). The multi-meter should indicate a bias value for the diode. Then connect the multi-meter normally (positive pole connects with the loop positive and negative pole connects with the loop negative). The multi-meter should indicate a low resistance value that increases with the charging of the loop capacitor. If after proper polarity connection the multi-meter still indicates a bias value for the diode, there is one or more addressable device(s) connected in reverse polarity.
Section 4:Operation
4.1LED Indicators and Keys
4.1.1Control Panel Display LED
Indicators and Keys
The N-6000 is an intelligent addressable Fire Alarm Control Panel (FACP) with advanced features ideal for a variety of applications. The CPU-6000 includes a front display/keypad enabling localized control panel viewing and programming. The display/keypad provides an easy-to-use keypad and large LCD (liquid crystal display) that simplifies the programming process.
The display is 53 characters wide by 20 lines long and displays all programming screens. These include the events, history, devices as well as other additional information.
Fields may be entered or changed and commands may be issued using the display keypad.
• LED Lamp Status
LED Indicator Color Functions
Fire alarm Red Illuminates when at least one fire alarm event exists. It will flash if any of these events are unacknowledged.
Pre-alarm Red Illuminates when at least one pre-alarm event exists. It will flash if any of these events are unacknowledged.
Trouble Yellow Illuminates when at least one trouble event exists. It will flash if any of these events are unacknowledged.
Power Green Indicates current status of the power supply. During normal communication with the power supply, the lamp will flash. Self-test Yellow Indicates the system is in self-test status. The LED will
remain lit during the self-test.
CBE Red I/O module is functioning properly or there is a feedback signal.
Delay Red If the control panel has a delayed control output the LED will remain illuminated throughout the delay period. It will turn off upon termination of the delay period.
Signal Silenced Yellow Illuminates if NFS-3030 Notification Appliances have been silenced. It flashes if some but not all of the N-6000 NACs have been silenced.
Point Disabled Yellow Illuminates when at least one device has been disabled. It will flash until all disabled points have been acknowledged. Supervisory Red Illuminates when at least one supervisory event exists. It will
flash if any of these events are unacknowledged.
CPU Failure Yellow Illuminates if there is an abnormal hardware or software condition. Contact technical support. The panel is out of service when this LED is illuminated or flashing.
Table 4-1 LED Indicator Description • Operation Keys:
【A-a】: Caps lock key
【Space】: During programming, change the status of the check box to and change back to when finished
【Backspace】 : Backspace key 【Menu】 : Press to enter the menu 【Help】 : Help key
【ESC】 : Escape key
【Enter】: Key to acknowledge input
【TAB】 : Switch key, same as the 【NEXT】 key 【<】 / 【>】 : Previous page/next page
【△】 / 【▽】 : Previous event/next event • Fixed Function Keys:
【Acknowledge】: Acknowledge event operation 【Signals Silenced】:
1. Press for less than 1 second: carries out silencing operation on peripheral equipment
2. Press for longer than 1 second: system exercise (please refer to relevant topics under loop card setting)
【Fire alarm/Pre-alarm】:
1. Press for less than 1 second: query fire alarm event 2. Press for longer than 1 second: query pre-alarm event
【Trouble/ Horn / Strobe】: Carry out query operation during trouble event
1. Press for less than 1 second: query trouble event 2. Press for longer than 1 second: query horn/strobe event
【Supervision/Feedback】: Carry out query operation on supervision event
1. Press for less than 1 second: query supervision event 2. Press for longer than 1 second: query feedback event 【CBE/Delay】:
1. Press for less than 1 second: query CBE event information
2. Press for longer than 1 second: query the logic zone in delay status with a logic value of TRUE
【Manual/Automatic】: Control manual/automatic execution link 【Lamp inspection/Self-test】: System lamp inspection/self-test 【Reset】 : Reset system operation
4.1.2Annunciator Control Module LED
Indicators and Keys
Fig. 4-2 Bus Control Module Schematic Diagram
The annunciator control module has a total of 32 indicating lamps, 16 keys and 16 feedback signals.
• One composite button: Time function key has 3 functions
1、Press for about 1 second: LED lamp below the key will illuminate locking the control key module
2、Press for more than 1 second: LED lamp on the right side of the key will illuminate with manual/automatic allowed
3、Press for more than 4 seconds: horn/strobe self-test • No. 1-16 Start Keys:
- Press a key and the corresponding feedback signal a (Lamp 1-16) flash, which means corresponding key has been pressed.
- When a feedback indicating lamp (Lamp 1-16) flashes, it indicates that an operational signal from CBE equipment has been received and the corresponding CBE equipment will be started.
4.2Power-on
Connect 220V AC power, and then turn on the main power supply using the switch inside the cabinet. Power-on Screen is shown in Fig. 4-4:
Fig.4-3 Power-on Screen
4.3System Self-test
Fig. 4-4 System Self-test Screen
After the N-6000 has been turned on, it will self-test both the hardware and software of the system. During the self-test all LED indicating lamps on the left side of the mainframe panel will flash. Once the self-test has finished a buzzer will sound and LEDs will temporarily illuminate after which the panel will return to a
normal operation status. Additionally, the system will show the display screen while the power supply indicating lamp continues to flash.
After a self-test, the system will show the following screen:
Fig. 4-5 Normal System Screen
The normal system screen is divided into three bars; these include the event statistics bar, the alarm screen bar and the status bar. The event statistics bar shows fire alarms, trouble alarms, supervision, CBE and point disabled locations. The status bar shows the node number, manual/automatic status, transmission equipment status, main or reserved power supply status, the current date/delay status of the latest logic zone as well as the current time.
①Manual/Automatic Status
——System in manual status ——System in automatic status
②Transmission Equipment Status ——Both delivery and feedback
——Transmission equipment in delivery status ——Transmission equipment in feedback status
——Transmission equipment in normal status without delivery or feedback ——Transmission equipment in Point disabled status
——Transmission equipment in trouble status
③Operation Status of the Main or Reserved Power Supply ——Main power normal
——Low voltage in main power ——Trouble in main power ——Battery normal
——Low voltage in battery ——Battery disconnected
Current date/delay status of the latest logic zone, this item can show the current date. When CBE appears, it will also show delay status information of the latest
logic zone. For example: , where “ZL0099” means logic zone
number 99 and “00001” means that CBE will output after a 1 second delay.
4.4Event Display
• Event Order:
First: Fire alarm, CBE, feedback Second: Supervision
Third: Trouble
Fourth: Point Disabled - disabled
4.4.1Trouble Screen
Fig. 4-6 Trouble Screen
When the control panel detects a failing power supply or other trouble, it will execute a series of operations:
• A trouble relay will be activated and the control panel will alarm
• A system trouble indicating lamp on the control panel display will flash and the LCD will show a trouble screen
• Detailed trouble type will show the exact geographic location and occurrence time on the LCD
• A trouble event will be saved to the native Flash ROM and the printer will print a record of the trouble event
Press the 【△】 key or the 【▽】 key on the main panel to review the previous or next trouble event and press the 【<】 key or the 【>】 key to page up or down. Press 【ACK】 key on the main panel to acknowledge, and all trouble events will be shown one by one. Once the alarm has silenced and all trouble events have been acknowledged, the system trouble indicating lamp on the main panel will return to its normal illumination.
The most common trouble events include but are not limited to: equipment off-line, grounding the equipment’s positive terminal, grounding the equipment’s negative terminal, the equipment’s positive terminal is disconnected, the equipment’s negative terminal is disconnected, power supply shows low voltage, power supply shows high voltage, unmatched load types, low threshold values, database errors.
4.4.2Fire Alarm Screen
Fig. 4-7 Fire Alarm Screen
When a detector or monitoring module is activated (fire alarm detected), the control panel will execute a series of operations:
• A system alarm relay will be activated and the control panel will alarm
• A fire alarm indicating lamp on control panel display will flash and the LCD will show a fire alarm screen.
• Detailed fire alarm name will show the exact geographic location and occurrence time on the LCD.
• Alarm information will be saved to the native Flash and the printer will print a record of the alarm event.
Press the 【△】 key or the 【▽】 key on main panel to review the previous or next fire alarm event and press the 【<】 key or the 【>】 key to page up or down. Press the 【OK】 key on main panel to acknowledge, and all fire alarm events will be shown one by one. Once the alarm has silenced and all fire alarm events have been
acknowledged, the system fire alarm indicating lamp on the main panel will return to its normal illumination.
4.4.3Supervisory Screen
Fig. 4-8 Supervision Screen
The monitoring modules produce monitoring style codes. Once a monitoring module has been activated, the control panel will execute a series of operations: • A monitoring relay will be activated and the control panel will alarm
• A supervision indicating lamp on the control panel will flash and the display will show the supervision screen
• Monitoring information will be saved to the native Flash and the printer will print a record of the supervision event
Press the 【△】 key or the 【▽】 key on main panel review the previous or next fire alarm event and press the 【<】 key or the 【>】 key to page up or down. Press the 【OK】 key on main panel to acknowledge all supervision information has been shown. Once the alarm has silenced and all the supervision events have been acknowledged, the supervision indicating lamp on the main panel will return to its normal illumination.
4.4.4Point Disabled Screen
Fig. 4-9 Point Disabled Screen
When a point disabled location exists in a loop, each disabled point (detector, module, and loop) will be shown one by one (see Fig. 4-10). The control panel will execute a series of operations:
• A point disabled indicating lamp on the control panel will flash but the control panel will not alarm
• A point disabled indicating lamp will be illuminated
• The point disabled information will be saved to the native Flash and the printer will print the current point disabled information
Press the 【△】 key or the 【▽】 key on main panel of the control panel to review the previous or next point disabled event and press the 【<】 key or the 【>】 key to page up or down. Press 【OK】 key on main panel of the control panel to acknowledge all Point disabled information has been shown. Once the alarm has silenced and all point disabled events have been acknowledged, the point disabled indicating lamp on the main panel will return to its normal illumination.
4.4.5CBE Screen
Fig. 4-10 CBE Screen
4.4.6Pre-alarm Screen
To enter the pre-alarm screen and also query the pre-alarm screen keep pressing the 【Fire alarm/Pre-alarm】 composite key on the main panel. The pre-alarm screen is shown below:
4.4.7Horn / strobe Screen
To enter the horn/strobe screen and also query the horn/strobe screen keep pressing the 【Trouble/Horn/Strobe】 composite key on the main panel. The horn/strobe screen is shown below:
Fig. 4-12 Horn/Strobe Screen
4.4.8Feedback Screen
To enter the supervision/feedback screen and also query the supervision/feedback screen keep pressing the 【Supervision/Feedback】 composite key on the main panel. The supervision/feedback screen is shown below:
Section 5:Programming
System Management Device Configuration CBE Programming Device Control History Event System Setting Modify Password Main Reset LCM DCU MCU Remote Display General Zone Logic Zone Manual Output Status Track Walk Test Power Management Setting Auto Programming Point Programming Setting Point Programming Setting Point Programming Setting Point Programming Status Track Download Labels Menu
When programming the control panel or reviewing history events, press the 【Menu】 key to view thefollowing screen:
Fig. 5-2 User Login Screen
Once a user has entered the correct password, he/she will enter the main menu and view the following screen. In the main menu screen, he/she can update or change the system management, device configuration, CBE programming, device control and history events.
Fig. 5-3 Main Menu Screen
5.2System Management
Under “System management” the operator has 3 options; (1) System setting, (2) Modify Password, or (3) Main Reset. The system management screen is shown as follows:
Fig. 5-4 System Management Screen
5.2.1System setting
Under “System Setting” the following screen will be shown:
Fig. 5-5 System Setting Screen
Line 1: The node is the control panel’s address within the network while the label is a description of the control panel
Line 2: If “ (YES)” is selected for the time server option, then this control panel is the time master within the network and all other panels will synchronous accordingly. Click the button “time & date” to set the time and date of the control panel
Line 3: Language—determines the language of the control panel display. At present two languages are currently available: Chinese and English
Line 4: Backlight—the duration of time the LED display remains lit. There are four choices available: Normal Open, Normal Close, Off in 30 Seconds and No Display.
Line 5 to Line 7: Relays—there are 3 relays each with 7 operational modes: ① Disabled—the relay is disabled
② Fire alarm output—the relay will close upon fire alarm ③ Trouble output—the relay will close during trouble status ④ CBE—the relay will close during CBE
⑤ Supervision—the relay will close during supervision
⑥ CBE logic output—the relay will only be used in CBE output expression. When the value of located expression is true, the relay will close and re-open in the opposite condition
⑦ Reset output—the relay will close during normal operation or when the system is being reset.
Line 8& Line 9: COM—2 serial ports each with 4 operational modes:
Degradation CBE: “ (YES)”/ “ (NO).” The default status “ (YES)” is Normal Open. Degradation CBE only works when enabled
Fire Alarm Verification: “ (YES)”/ “ (NO).” The default status is “ (YES).” This function has a time sensitive fire alarm, ensuring an alarmed status will be accurate. This setting can greatly reduce false alarms and improve system efficiency
Failover: “ (YES)”/ “ (NO).” The default status is “ (NO).” Failover is the trouble display switch for the whole control panel. If “ (YES)” is chosen, all trouble signals will be disabled without any display or alarm although a history record is still maintained
Main Power Supply: “ (YES)”/ “ (NO).” The default status is “ (YES),” which installs the main power supply for the control panel
Reserved Power Supply: “ (YES)”/ “ (NO).” The default status is “ (YES),” which installs the reserved power supply for the control panel
Reset Verification: “ (YES)”/ “ (NO).” The default status is “ (NO).” If “ (YES)” is chosen, a password needs to be entered before resetting. If “ (NO)” is chosen, a password does not need to be entered before resetting
5.2.2Password modification
Under “Password modification,” a user can modify his/her password according to their system status (Admin, Engineer, or Guest). The password modification screen is shown below:
Fig. 5-6 Password Modification Screen
The N-6000 has 3 different user levels, each level is password protected. The three levels are (ordered from highest to lowest) Administrator, Engineer and User. Each level has its own password. The Administrator user can modify any password in the system (including the Administrator level). The User can only operate on the 4th setting, “Device Control” and the 5th setting, “History event.” The Engineer can operate all five settings in the menu but will be interrupted (exit programming) when an alarm event occurs. The Administrator can operate all five settings in the menu and will not be interrupted during an alarm event.
Factory default passwords are as follows: 333333 for Administrator, 222222 for Engineer and 111111 for User.
After the initial login the user will enter the password modification screen. He/she can change the password by entering a new password in the “Enter new password” dialogue box and then re-entering the new password in the “Confirm new password” dialogue box. Once the system has confirmed the two passwords are the same, the user should press 【OK】 to confirm the password change. After the user has pressed 【OK】 the password will be successfully modified, to cancel the previous operation press the 【Cancel】 button.
Note: If an incorrect password is entered, the system will show another dialogue box requesting the correct password be entered.
5.2.3Main Reset
In the “System Setting” screen choose “Main Reset” to reset the system to all default factory settings.
Fig. 5-7 Main Reset Screen
After the correct Administrator password has been entered, a dialogue box will prompt to verify the “Main Reset” choice. Press “OK” to confirm the reset and restore default factory settings. Press “Cancel” to cancel the operation and exit the screen.
5.3Device Configuration
Choose the “Device Configuration” screen to adjust the settings of the loop cards, multi-line control modules, annunciator control modules and repeaters. Screen shown below:
Fig. 5-8 Device Configuration Screen
5.3.1Loop card
In the “Device Configuration” screen, choose the “LCM” option to enter the screen shown below in Fig. 4-23:
Fig. 5-9 Loop Card Screen
5.3.1.1Parameter setting
In the “LCM” screen, to adjust the settings and program options, choose “Setting,” “Auto Programming,” or “Point programming.” The screen is shown in Fig. 4-24:
Fig. 5-10 Parameter Setting Screen
Line 1: LCM- Loop number. Line 2: Name- Loop Description
Line 3: Installation status – these include: Uninstalled, Normal, and Disabled. Line 4: Time Rapid Polling - the number of preferential in-process checks, the default value is 0. This option controls both the point and card level settings. The card level setting determines the preferential times while the point level setting determines whether the point needs the preferential in-process check. The loop card will carry out preferential in-process checks on the load points where “Preferential in-process check” has been activated.
Line 5: Style 4 Wiring - “ (YES)”/ “ (NO).” The system default status is “ (YES).” Using style 4 wiring the circuit status can be monitored through the ring circuit line voltage. The system will detect differences between the positive and negative circuits to monitor if a disconnection trouble within the loop occurs. If the wiring connection does not use style 4 configuration, the mainframe will report a disconnection trouble.
Line 6: Local Mode - “ (YES)”/ “ (NO).” If “ (YES)” is selected, the local CBE setting will be effective within the loop.
Line 7: Silenceable - “ (YES)”/ “ (NO).” This option controls both the point and card level settings. By programming definition the point level setting is the same as the card level setting. When “ (YES)” is chosen and a horn/strobe alarm or alarm bell activates, the user can press 【Signals Silenced】 on main panel of the control panel to silence the alarmed equipment. If “ (NO)” is selected, the user cannot silence the alarmed equipment using the 【Signals Silenced】 button.
Line 8: Address Conflict - “ (YES)”/ “ (NO).” If “ (YES)” is selected, during inspection the system will search for device address duplications within a loop. If duplication is found, the panel will show a prompt with further instructions. If “ (NO)” is chosen, the detector will not report duplicate addresses.
Line 9: L+ Ground Fault Detect - “ (YES)”/ “ (NO).” When “ (YES)” is selected and a positive end of the loop is grounded, the system will report positive
end grounding trouble. If “ (NO)” is chosen, the system will not report positive end grounding trouble.
There are three function keys, “Sync,” “Save,” and “Quit” in the status bar. The “Sync” button allows the operator to download parameter settings (both card level and point level settings). The “Save” button saves the changes that have been selected. The “Quit” button allows the user to quit without saving the changes.
5.3.1.2Auto Programming
Fig. 5-1 Automatic Login Screen
Each loop has 3 status options: Installed, Uninstalled, and Disabled. During normal installation, the programmer may enter the “Auto Programming” screen. When he/she selects a loop number for automatic programming and then presses “OK,” the system will verify each device on the selected loop.
Caution: When either a CMX-2 control module or a M500K call point are on a loop using “Auto Programming” the control panel will misidentify the CMX-2 as a CMX-7(C) and misidentify the M500K as an MMX-7. When this happens, the user should enter 4.5.2.1.3 Point Programming screen (device configuration→ LCM→point programming) to modify the device identity by selecting the proper equipment type.
Fig. 5-12 Automatic Programming
Upon completion of auto-programming, the quantity, type, and status of each device on the loop will be automatically shown. This is a convenient time for system operators to inspect, check, and manage the connected field devices. Press the 【△】 key or the 【▽】 key to review the address and type of each point installed on the loop. The screen is shown in Fig. 5-13:
5.3.1.3Point Programming
Fig. 5-14 Point Programming Screen
To set all loop points, select the programming screen.
Line 1: Displays the loop number, device address, and installation status. These include: Uninstalled, Normal, and Disabled.
Line 2 & Line 3: Displays the selected address point description and additional details. Programmer can individualize entries.
Line 4: Displays the alarm type of the selected address point. These include: Fire alarm, Supervision, Feedback or General Output.
Line 5 & Line 6: Displays the type and model of the connected equipment.
Line 7: Displays the LED mode of the selected equipment. These include: NORMAL BLINK, NORMAL ON and Normal OFF.
Line 8: Displays the current loops correlation mode. These include: none, previous point correlation, next point correlation, or both next and previous point correlation.
Line 9 & Line 10: Displays the Fire alarm, Pre-alarm, and Trouble level settings. Note: Different detector models will have different corresponding alarm thresholds even when the control panel setting is the same. See Appendix A for details. • Coincident Address Code: “ (YES)”/ “ (NO).” If “ (YES)” is selected,
during inspection the system will search for device address duplications within a loop. If duplication is found, the panel will show a prompt with further instructions. If “ (NO)” is chosen the system will not report duplicate addresses.
• Walk Test: “ (YES)”/ “ (NO).” If “ (YES)” is selected, pressing the 【Self-test】 key on the mainframe will cause the system to inspect all connected devices within the loop. During inspection all verification lamps will be normally illuminated. If a verification lamp does not illuminate, that device has failed inspection. If “ (NO)” is selected, the condition shall be opposite.
• Local Mode: “ (YES)”/ “ (NO).” The factory default setting is “ (NO).” This option controls both the point and card level settings. By programming definition the point level setting is the same as the card level setting. If the loop card and mainframe have a communication failure all selected modules (degradation mode) will automatically output a fire alarm signal.
• Silenceable: “ (YES)”/ “ (NO).” When “ (YES)” is chosen and a horn/strobe alarm or alarm bell activates, the user can press 【Signals Silenced】 on main panel of the control panel to silence the alarmed equipment. If “ (NO)” is selected, the user cannot silence the alarmed equipment using the 【Signals Silenced】 button.
• Switch Inhibited: “ (YES)”/ “ (NO).” When “ (YES)” is chosen manual output point operation is inhibited.
• Resetable: “ (YES)”/ “ (NO).” When “ (YES)” is selected, the equipment will automatically reset all output signals when the system is reset.
• Drift Compensation: “ (YES)”/ “ (NO).” When “ (YES)” is selected, the system will restrain individual sensors from automatically performing drift compensation.
• Rapid Polling: “ (YES)”/ “ (NO).” When “ (YES)” is selected, the system will increase the frequency of in-process inspection on the loop thus increasing the sensitivity of the equipment.
• Alarm Verification: “ (YES)”/ “ (NO).” When “ (YES)” is selected, there will be an adjustable delay in the alarm period after a preliminary alarm has registered, allowing time for the alarm to be verified before sending a general alarm. Should an alarm condition still exist after verification, the panel will then go into alarm. Verification time is adjustable (in second’s intervals) and can be customized by using the edit feature on the right side of the alarm verification label.
5.3.2Annunciator Control Module
In the “MCU” screen, a programmer can access the “Setting” and “Point programming” options for an annunciator control module.
Fig. 5-15 Annunciator Control Module Screen
5.3.2.1Parameter setting
Fig. 5-16 Parameter setting Screen
Line 1: MCU—Select the MCU number.
Line 2: Description—Describe the selected MCU.
Line 3: Set the current MCU status. These include: Uninstalled, Normal and Disabled.
Press “Save” to save the current settings. If the user presses “Exit” without saving, the following dialogue box will be prompted. At this time the user can also save the current settings. The user can also exit the current screen to retain previous settings; the current settings will not be saved.
5.3.2.2Point Programming
Point Programming of MCU can access to set the relative module address of keys and feedback led.
Fig. 5-17 Point Programming Screen
5.3.3Remote Display
In the “Remote Display” screen, a programmer can access the “Setting,” “Download Label” and “Point Programming” option screens. One N-6000 fire alarm control panel can have up to 64 remote displays.
5.3.3.1Parameter setting
Fig. 5-19 Parameter setting Screen
Line 1: Remote display—Displays the remote display number. Line 2: Description—Describes the selected remote display.
Line 3: Set the current remote display status. These include: Normal, Disabled and Uninstalled.
Press “Save” to save the current settings. If the user presses “Exit” without saving, the following dialogue box will be prompted. At this time the user can also save the current settings. The user can also exit the current screen to retain previous settings; the current settings will not be saved.
5.3.3.2Label Download
Fig. 5-20 Download Label Screen
In the “Download Label” screen a programmer can view detailed information by selecting the desired floor repeater number and pressing “OK.” At this time, the
system will download relative content for each point in the selected repeater floor display. If past events have occurred in the selected equipment points, all previously downloaded contents will also be shown on the remote display. This allows field operators to update equipment settings for optimal device function.
5.3.3.3Point Programming
Fig. 5-21 Point Programming Screen
Line 1: Displays the remote display number, point number and installation status. These include: Uninstalled, Normal, and Disabled.
Line 2: Displays the current remote display point description
Line 3: Point Mapping—Each remote display can have up to 64 points. Each point must have a specific zone and loop address. After each point has been mapped, during an event (fire alarm, trouble, etc) the mapped equipment’s location and event will be shown on the relative remote display screen.
Press “Save” to save the current settings. If the user presses “Exit” without saving, the following dialogue box will be prompted. At this time the user can also save the current settings. The user can also exit the current screen to retain previous settings; the current settings will not be saved.
5.3.4CBE Programming
In the “CBE Programming” screen programmers can access both the “General Zone” and “Logic Zone” setting screens.
Fig. 5-22 CBE Programming Screen
5.3.4.1General Zone
Within the “General Zone” screen a user can select zones 0-499 to review the relative logic equation of a particular zone. Use the VFT programming software to modify the logic equations as necessary.
Fig. 5-23 General Zone
5.3.4.2Logic Zone
Within the “Logic Zone” screen a user can select zones 0-999 to review the relative equation of a particular zone. Use the VFT programming software equation to modify the logic equations as necessary.
Fig. 5-24 Logic Zone
5.3.5Device Control
In the “Device Control” screen a user can access the “Point Output,” “Status Tracking,” “Walking Test,” “Loop Exercise” and “Power Supply Management” setting screens.
5.3.5.1Manual Output
Fig. 5-26 Manual Output Screen
Within the “Point Output” screen a user can set the loop number, address number, type of equipment, label and the inspection lamp ON/OFF status. Press the 【△】 key or the 【▽】 key to review a points’ status.
Line 1: Displays the current loop number, address and status. These include: Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description. Line 4: Displays the current point alarm type. These include: Fire Alarm, Supervision, Feedback and General Output.
Line 5 & Line 6: Displays the current equipment type and model.
Line 7: Displays the selected output module status. If the user chooses “Start” and then presses “OK”, the point in the current loop will be output by the module; if set at “Close”, the point will not be output by the module.
5.3.5.2Status Tracking
Fig. 5-27 Status Tracking Screen
Within the “Status Track” screen a user can set the loop number, address number, address type as well as monitor the point.
Line 1: Displays the current loop number, loop address and its status. These include: Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description. Line 4: Displays the current point alarm type. These include: Fire Alarm, Supervision, Feedback and General Output.
Line 5 & Line 6: Display the current equipment type and model. Line 7: Displays the current point status.
5.3.5.3Walk Test
Within the “Walk Test” screen a user can set the loop number, address number, address type as well as run a walking test on a particular loop.
Line 1: Displays the loop number, current address and installation status. These include: Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description. Line 4: Displays the current point alarm type. These include: Fire Alarm, Supervision, Feedback and General Output.
Line 5 & Line 6: Displays the current equipment type and model.
After adjusting the systems settings, pressing the 【Lamp inspection/Self-test】 key on main panel will cause the control panel to run a self-test on the current loop. During this test, both the self-test indicating lamp and the load verification lamp will be normally illuminated. Press “Review the Result” to view every address in the current walk test, the addresses will be displayed on the right hand side of the walk test interface screen (Fig. 4-50).
Fig. 5-29 Walk Test Address Screen
5.3.5.4Loop Drill
Fig. 5-30 Loop Drill Screen
5.3.5.5Power Supply Management
Fig. 5-31 Power Management Screen
N-6000 fire alarm control panel uses the MPS-350W power supply. Within the “Power Management” screen the user can review the current status of each power supply.
Line 1: Displays the currently connected power supply type. The MPS-350W is the primary power supply for the N-6000.
Line 2: Displays the current status and voltage of the main power supply. Line 3: Displays the current status and voltage of the reserved power supply. Line 4: Press 【Discharge】 to discharge the power supply. Press 【Stop】 to stop discharging. Press 【Exit】 to exit the power supply control screen.