FMI Energy Conference 2006
HVAC
Load Calculations
Perry Morrow & John Parker Brandt Engineering, Inc.
Key Concepts to Consider
as we look at Load Calculations
• Interior Design Criteria
• Exterior Design Criteria
• Kitchen Hoods and Make Up air
• Walls that aren’t as well insulated as they
appear.
Why is moisture control important?
Where does the moisture come from?
• Infiltration
• Ventilation
• Makeup Air
Makeup Air
• There have been
many attempts at
using tempered
makeup air. This
one appears the
most successful;
however, some of
the humid air
introduced here
doesn’t go out the
hood.
Image Courtesy of Food Service Technology Center publication
Summer Weather Data – Richmond, VA & Phoenix, AZ
HVAC Load Basic Terms
• Zone: A single area withsimilar thermal and use characteristics.
• Envelope Loads or • Skin Loads: Loads
associated with the Roof, Walls, Windows, Doors, Floor and Partitions.
• Infiltration: Air that leaks into a building through the building envelope.
• Humidity: The quantity of water vapor present in air. It can be expressed as an absolute, specific or a relative value.
Humidity Measurement Terms
• Absolute humidity is the actual mass of water vapor present in the air water vapor mixture. The absolute humidity may be expressed in pounds of water vapor (lb).
• Specific Humidity Ratio or Humidity Ratio is the ratio between the actual mass of water vapor present in moist air - to the mass of the dry air.
Humidity Ratio is normally expressed in pounds of water vapor per pound of dry air or in Grains of moisture per pound of dry air. There are
approximately 7000 grains in a pound.
• Relative Humidity: The ratio of the amount of water vapor in the air at a specific temperature to the maximum amount that the air could hold at that temperature, expressed as a percentage.
• Dew Point temperature: The temperature below which moisture will condense out of air. - Air at a given Humidity Ratio has a constant Dew Point. If air is cooled below this point, moisture condenses out thus changing its humidity ratio.
Relative Humidity vs. Humidity Ratio
As a given mass of moisture laden air is heated or cooled the air volume changes but the moisture does not. Thus there is a change in Relative Humidity, without a change in actual water content. The mass of both water and air remain unchanged, so the humidity ratio (Grains/Lb ) does not change. If the air continues to cool, the relative humidity will reach 100% and water will begin to condense on surfaces at 63oF so this is the Dew Point of the air.
Load Calculation Methods
• Manual Calculations
• Spreadsheet
• Specialized Software:
Elite Software - Chvac - Commercial HVAC
Loads
Carrier - Hourly Analysis Program
Trane - Trace family of programs
Department of Energy – ENERGYPlus, BLAST
and DOE-2. Text based software with graphic
interfaces sold by 3
rdparty software vendors.
Loads the New Way
HVAC Load Basics
Although HVAC load calculation includes a
significant amount of number crunching, it
begins with digging out the answers to a
number of questions.
A lack of good information up front can mean
bad answers at the end of the process.
HVAC Load Questions
11. Establish allowable Indoor Temperature and Humidity Range.
2. Determine Outdoor Weather Conditions to use.
Choices are 0.4%, 1% and 2% Ashrae data or Other.
3. Determine mass and insulation value of all building
envelope components (Walls, Roof, Glass, Doors…).
4. Determine all internal load components (Anything that
consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).
5. Calculate heat flow into and out of each zone, at summer
and winter outdoor weather conditions, varying
temperature and sun location for each hour of the day and each day or month of the year.
6. Repeat steps 4 & 5 for every zone (thermally similar
ASHRAE Indoor Air Temperature and
Humidity Recommendations
• … The industry chose 75°F db and 64°F wb
(55% rh, 57.5°F dew point{71.8 grains}) as
summer design conditions. This is the
ambient condition at which refrigeration
load for food store display refrigerators is
normally rated. Store humidity is one of the
most critical variables that can affect
performance of display refrigerators and
refrigeration systems.
60% 70% 80% 90% 100% 110% 30 40 50 60 70 80
Refrigerated Case Loads
Data From 2003 ASHRAE Applications Handbook 2.3
Percent L
o
ad
36.7 42.3 48.5 53 57.2 60.8 Dew Point (oF)
$8,000 $10,000 $12,000 $14,000 $16,000 $18,000 $20,000 $22,000 $24,000 $26,000 $28,000 $30,000 $32,000 $34,000 40 42 44 46 48 50 52 54 56 58 60
Store Dewpoint Setpoint
E n er g y C o st t o o p e ra te A /C f o r 1 year (e xc lu d e s au xi la ry h e at c o s t) BALTIMORE MIAMI In Miami $3,000 A/C energy COST if “setpoint” is 50 versus 58 dewpoint In Baltimore $400 A/C energy COST if “setpoint” is 50 versus 58 dewpoint
In Miami: 90% of a year the store needs humidity control
In Baltimore: 45% of a year the store needs humidity
control
Building HVAC Cost vs. Store Dewpoint
Building HVAC Cost vs. Store Dewpoint
$70,000 $72,000 $74,000 $76,000 $78,000 $80,000 $82,000 $84,000 $86,000 $88,000 $90,000 $92,000 $94,000 $96,000 $98,000 $100,000 $102,000 $104,000 $106,000 $108,000 $110,000 40 42 44 46 48 50 52 54 56 58 60
Store Dewpoint SETPOINT
Cost to Operate 3 Racks
(annual)
Baltimore, MD Miami, FL Salt Lake City Pittsburg, PA Houston, TX In Baltimore $8,000 rack energy savings if “setpoint” is 50 versus 58 dewpoint In Miami $18,000 rack energy savings if “setpoint” is 50 versus 58 dewpoint
Excerpt from 2002 FMI Presentation by Lee Churchill of Seasons-4 Inc.
HVAC + Rack Energy
Cost vs. Store Dewpoint
$80,000 $85,000 $90,000 $95,000 $100,000 $105,000 $110,000 $115,000 $120,000 $125,000 $130,000 40 42 44 46 48 50 52 54 56 58 60
Store Dewpoint SETPOINT
C o st to O p er ate 3 R acks & A /C (an n u a l) Baltimore, MD Miami, FL
Excerpt from 2002 FMI Presentation by Lee Churchill of Seasons-4 Inc.
Conclusion to study: 50 F dewpoint is an
HVAC Load Questions
21. Establish allowable Indoor Temperature and Humidity
Range.
2. Determine Outdoor Weather Conditions to use.
Choices are 0.4%, 1% and 2% Ashrae data or Other.
3. Determine mass and insulation value of all building
envelope components (Walls, Roof, Glass, Doors…).
4. Determine all internal load components (Anything that
consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).
5. Calculate heat flow into and out of each zone, at summer
and winter outdoor weather conditions, varying
temperature and sun location for each hour of the day and each day or month of the year.
6. Repeat steps 4 & 5 for every zone (thermally similar
ASHRAE Weather Data
• 2 Types of Summer Data
• Cooling Dehumidification
DB / MCWB & DP / MCDB
# of Hours Exceeding Summer Data
– 0.4% 35 hr/Yr
– 1% 88 hr/Yr
– 2% 175 hr/Yr
• Types of Winter Data
# of Hours Exceeding Winter Data
– 99% 88 hr/Yr
Hours by City 7,000 to 9,000 6,000 to 6,999 5,000 to 5,999 4,000 to 4,999 3,000 to 3,999 2,000 to 2,999 1,000 to 1,999 0 to 999
Dehumidification Hours
by City
• Based on 74oF/55% RH• ( 67.5 Gr/lb ) Internal Set point
2005 Richmond, VA
Summer Weather
0.4% 1.0%
HVAC Load Questions
31. Establish allowable Indoor Temperature and Humidity
Range.
2. Determine Outdoor Weather Conditions to use.
Choices are 0.4%, 1% and 2% Ashrae data or Other.
3. Determine mass and insulation value of all building envelope components (Walls, Roof, Glass, Doors…).
4. Determine all internal load components (Anything that
consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).
5. Calculate heat flow into and out of each zone, at summer
and winter outdoor weather conditions, varying
temperature and sun location for each hour of the day and each day or month of the year.
6. Repeat steps 4 & 5 for every zone (thermally similar
Typical Wall Constructions
Similar Calculation for 6” Metal Studs with
R-19 insulation, No Insulated Sheathing
Simplified parallel Path calculation for Example purposes.
Insulated CMU Walls
R-12 or R-5 ?
• CMU walls exhibit similar thermal bridging to the Stud Wall example with the addition of heat flow parallel to the wall surface around the insulated cores.
• One insulating product’s published data indicates a 12” CMU wall with their product including air film coefficients provides R-12.5. The fine print indicates that more detailed calculations are available. We requested the calculations, they indicate R=9.6.
• Often for structural reasons, one in four of the CMU cores are grouted solid and have rebar added. This added thermal bridging brings the wall assembly down to
approximately R=5.1
• Note that the problem is not with the insulating material, but with the fact that there are numerous paths around the insulation.
Carrier Hourly Analysis Program – Opening Screen
• Information describing the Roof, Windows, Doors and any overhangs (Canopies) are entered in the library so they will be available as we define spaces. • When equipment will be operated, when
the lights are programmed to be on, and estimated hourly occupancy rates are entered under schedules.
Ventilation Air
The minimum quantity of ventilation air required is set by the building code in most areas. In most spaces, this is defined as
X
cfm / person. In some spaces, usually ones that are sparsely populated, ventilation rates may be set on a cfm / sq. ft. (floor area) basis.In general, people exhale a predictable quantity of CO2 as they breathe. The CO2 level can be monitored and used to control outdoor air dampers to reduce the amount of Ventilation air during lightly occupied hours.
HVAC Load Questions
41. Establish allowable Indoor Temperature and Humidity
Range.
2. Determine Outdoor Weather Conditions to use.
Choices are 0.4%, 1% and 2% Ashrae data or Other.
3. Determine mass and insulation value of all building
envelope components (Walls, Roof, Glass, Doors…).
4. Determine all internal load components (Anything that consumes electricity, gas, solid fuel or food. Also
anything that has energy piped to it or away from it.).
5. Calculate heat flow into and out of each zone, at summer
and winter outdoor weather conditions, varying
temperature and sun location for each hour of the day and each day or month of the year.
6. Repeat steps 4 & 5 for every zone (thermally similar
Internal Loads
Mixed
(Contain Sensible & Latent Components)
• People
• Steam table
• Holding Cabinets • Coffee Brewer • Case Credits
Dry (Sensible Heat)
• Lights
• Equipment:
– Self Contained Display Cases – Slicers, Registers, Computers • Hooded Equipment – Broilers – Ranges – Ovens
Hooded Loads – Where Applicable
• Spreadsheets or pads of paper are good ways to total
the various components that make up the
Case Credit - Summary
• Case Credits can be calculated a number of different ways that will be discussed in up coming slides.
Case Credit Calculation
Simplified Method
• We have seen this fairly simple method recommended by at least one refrigerated case manufacturer and more than one client. Although relatively simple, the results appear to be fairly accurate.
Case Credit Calculation
Ashrae Method
Ashrae publishes a table listing Sensible and Latent Case
Credit values on a BTU/Foot basis for various case types. Some case manufacturers have this type of data available for their specific cases.
Case Credit Calculation
BTU / Ft & Return Air
One client has taken the BTU/LF or Ashrae method a step further. This calculation bases the case credits on a btu/lf method and then assigns only a portion of this credit to the space. Where under case returns are utilized, the remainder of the credit is assigned to the unit cooling coil.
Infiltration
• From Carrier HAP 4.20a - Help File
– Items in the CFM/sqft column define infiltration in terms of airflow per unit of exterior wall area. Because infiltration occurs through exterior walls - especially through windows and doors in these walls - rule of thumb infiltration rates are sometimes tabulated in this CFM/sqft format.
• From: Ashrae 2005 Fundamentals – Chapter 27, Page 23
– NONRESIDENTIAL AIR LEAKAGE
– …Typical air leakage values per unit wall area at 0.30 in. of water are 0.10, 0.30, and 0.60 cfm/ft2 for tight, average, and leaky walls,
respectively.
Wall Construction Infiltration rate (cfm/ft2) Tight 0.10
Average 0.30
HAP – Partition Input
• Partitions are internal walls, ceilings or floors that
separate conditioned spaces from un-conditioned or
partially conditioned spaces. Machine rooms and
Receiving Areas can be partition loads to the
HAP – Partition U Value Calculation
• Use the built in Wall and Roof property calculation portions of the program to calculate the U-Value for any partitions. Manually transfer this data to the partition tab of the space input form.
HVAC Load Questions
51. Establish allowable Indoor Temperature and Humidity
Range.
2. Determine Outdoor Weather Conditions to use.
Choices are 0.4%, 1% and 2% Ashrae data or Other.
3. Determine mass and insulation value of all building
envelope components (Walls, Roof, Glass, Doors…).
4. Determine all internal load components (Anything that
consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).
5. Calculate heat flow into and out of each zone, at summer and winter outdoor weather conditions, varying
temperature and sun location for each hour of the day and each day or month of the year.
6. Repeat steps 4 & 5 for every zone (thermally similar
HVAC Load Questions
61. Establish allowable Indoor Temperature and Humidity
Range.
2. Determine Outdoor Weather Conditions to use.
Choices are 0.4%, 1% and 2% Ashrae data or Other.
3. Determine mass and insulation value of all building
envelope components (Walls, Roof, Glass, Doors…).
4. Determine all internal load components (Anything that
consumes electricity, gas, solid fuel or food. Also anything that has energy piped to it or away from it.).
5. Calculate heat flow into and out of each zone, at summer
and winter outdoor weather conditions, varying
temperature and sun location for each hour of the day and each day or month of the year.
6. Repeat steps 4 & 5 for every zone (thermally similar space of interest) in the building.
Systems
1• After all spaces to be conditioned have been entered, we can begin grouping them together into zones and systems. • Only spaces with similar thermal and occupancy
characteristics should be grouped together as a zone. There will be one thermostat per zone generally
• The systems usually correspond to air handling units. These can be split systems, central station air handling units or rooftop units..
• A typical rooftop unit or split system can only serve one zone, and is controlled by one thermostat. So in this case each system consists of only one zone.
• There are other system types that allow one unit to serve multiple zones, but in our experience, they are not often applied to supermarkets.
Systems
2• When we were describing spaces, we entered information that will give us the total outside air required for ventilation.
• In stores with cooking, this is only part of the outside air story. You need make-up air for hoods and other exhaust sources. The software is aware of this, so all you need to do is enter this value as an exhaust quantity as you describe the system.
• If the zones where the exhaust loads occur are open to the main sales area and each other you have a decision to make. Where to allocate the make up air.
• You can either design for one large semi-custom unit capable of handling most of the outside air or multiple semi-custom units.
• If the zones are not open to one another, you have no choice. Make Up air must be provided in the system where it is actually exhausted.
Load Software
Air System Sizing Summary Output
Load Software
Heating Load Calculation – “Case Credits
”
• Heating loads are calculated for the maximum required heating from the system without taking credit for any internal lights, equipment and people. External heating credits such as solar effects are also omitted. Because the software ignores miscellaneous loads while calculating the heating load, the “case credits”, which in heating mode are an additional heating load not a credit, they must be added to the required unit capacity manually.
• If sufficient heat from the refrigeration rack is reclaimed by the mechanical systems, it may not be necessary to increase the unit heating capacity to offset this added
heating load. But be careful, often the reclaim heat is not available.
Summary
- Pie • Dry Climate • Humid Climate 119.7 Total Tons 0.97 Coil SHR 129.4 Total Tons 0.67 Coil SHRSummary
– Stacked Bar119.7 Total Tons 0.97 Coil SHR 129.4 Total Tons
Take Home Points
• Infiltration / Transmission Load thru Walls.
• Interior & Exterior Design Conditions
• Costs of Controlling vs. Not controlling
space humidity.
Credits
Presentation includes excerpts from:
• ASHRAE 2003, 2005 and 2006 Handbooks
• Screen Outputs from Carrier Hourly Analysis Program HAP version 4.20a
• Humidity illustrations provided by Todd Smith of Munters Corporation.
• Rack Energy Cost vs. Store Dewpoint data provided by Lee Churchill of Seasons-4 Inc