A B C D E F G
5 4 1
2
3
8 7 6 1P
2P
4P
6P
8P
10P
12P
15P 14P
/ 1 M202
1 M700
A B C D E F G
5 4 1
2
3
8 7 6 1P
2P
4P
6P
8P
10P
12P
15P 14P
Stair C 090.15
Stair D 090.16
Court 050
Storage 042
T 2
M700
E-3 600 CFM 16x10NK
S-5 233 CFM 12x8NK S-5
233 CFM 12x8NK S-5
234 CFM 12x8NK
8'
0' 16'
Scale: 1/8" = 1'-0"
PROFESSIONAL SEAL CONSULTANT
PROJECT
KEY PLAN
SHEET TITLE
PROJECT #
SHEET #
© 2018 ROSSETTI
B 8
7 6 5 4 3 2 1
A C D E F G H J K
8 7 6 5 4 3 2 1
30x42
AE-SVR-FILE01\UserFolders\rzora\Documents\74670_WSGL_MECH_v20_rzora.rvt /2020 5:31:43 PM
2018-034
Event Level Floor Plan - HVAC (Area A)
M201
Wayne State University - Basketball Arena
1290 West Warren Avenue Detroit, Michigan 48202
M201 SCALE: 1/8" = 1'-0"
1 Event Level Floor Plan - HVAC (Area A)
THE FOLLOWING GENERAL NOTES APPLY TO ALL HVAC SHEETS INCLUDED WITHIN THIS DOCUMENT SET, EXCEPT WHERE OTHERWISE INDICATED.
1. SHEET METAL OFFSETS AND TRANSITIONS ARE SHOWN TO PROVIDE INDICATION OF PHYSICAL CONDITIONS WITHIN THE SPACE. IT IS NOT THE INTENT OF THE DRAWINGS TO SHOW ALL REQUIRED OFFSETS AND TRANSITIONS. THE CONTRACTOR SHALL FULLY COORDINATE THE MECHANICAL WORK WITHIN ITSELF AND WITH THE WORK OF ALL TRADES TO PROVIDE COMPLETE AND OPERABLE SYSTEMS WITHOUT INTERFERENCES.
2. COORDINATE GRILLE, REGISTER AND DIFFUSER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
3. ALL NEW DUCTWORK IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE OR SUSPENDED CEILING, UNLESS OTHERWISE NOTED.
4. ALL DUCT PENETRATIONS THROUGH 2-HOUR FIRE-RATED ASSEMBLIES SHALL BE PROVIDED WITH FIRE DAMPERS AND ACCESS DOORS.
5. ALL EXHAUST GRILLES SHALL BE HARD DUCT CONNECTION IN HARD CEILINGS.
6. ALL ROUND DUCT RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS INDICATED BY THE DIFFUSER TAG ON THE DRAWINGS.
7. SUPPLY DUCTWORK PRESSURE CONSTRUCTION SHALL BE 3" W.G. UPSTREAM OF TERMINAL UNITS AND 2" W.G. DOWNSTREAM OF TERMINAL UNITS.
8. MAINTAIN A MINIMUM 10'-0" CLEARANCE FROM EXHAUST FANS, EXHAUST TERMINATIONS AND FLUE GAS VENTS TO ANY SURROUNDING FRESH AIR INTAKES.
9. MAINTAIN REQUIRED CLEARANCES IN FRONT OF ELECTRICAL PANELS/EQUIPMENT. DO NOT ROUTE DUCTWORK ABOVE ELECTRICAL PANELS/EQUIPMENT OR THROUGH ELECTRICAL ROOMS.
10. ACCESS PANELS AND DOORS ARE REQUIRED THROUGHOUT BUILDING CONSTRUCTION ASSEMBLIES SUCH AS WALLS, HARD CEILINGS, PARTITIONS AND FLOORS TO SERVICE AND MAINTAIN TERMINAL UNITS, BALANCING DAMPERS, CONTROL MOTORS, ETC.
ACCESS PANELS AND DOORS SHALL BE PROVIDED AND INSTALLED PER
ARCHITECTURAL SPECIFICATIONS. MECHANICAL CONTRACTOR SHALL VERIFY THE EXACT QUANTITY, SIZE, FIRE-RATING AND LOCATION OF ACCESS PANELS AND DOORS FOLLOWING INSTALLATION OF SYSTEMS AND COMPONENTS REQUIRING ACCESS, BUT PRIOR TO THE CLOSURE OF THE AFFECTED CEILING AND BUILDING ASSEMBLIES.
MINIMUM ACCESS PANEL AND DOOR SIZE SHALL BE 24 INCHES BY 18 INCHES, UNLESS OTHERWISE NOTED.
11. WHERE VOLUME DAMPERS OCCUR ABOVE CEILINGS WITHOUT REMOVABLE TILE OR ACCESS PANEL, PROVIDE A FLUSH-MOUNTED CONCEALED DAMPER REGULATOR TO ALLOW FOR DAMPER ADJUSTMENT BELOW CEILING. UNIT TO BE EQUAL TO VENTLOCK NO. 666 IN 1/2" OR 3/8" ROD SIZE.
12. PROVIDE TRANSFER OPENING IN ALL FULL HEIGHT WALLS SIZED FOR 0.05" OF STATIC PRESSURE PER 100' OF DUCT. PROVIDE FIRE DAMPER IN ALL FIRE RATED
ASSEMBLIES.
13. PROVIDE VANDAL PROOF TEMPERATURE SENSORS IN PUBLIC AREAS.
# DESCRIPTION DATE
1 DESIGN DEVELOPMENT 11.21.2019
CONSTRUCTION DOCUMENT - PACKAGE 2 03.18.2020
FECFEC
5 4 2
3
8 7 6
40x20
16x1430x1440x2024x2030x20
40x20
40x2030x1620x14
SVAV-1-01 300 CFM
EVAV-1-01 400 CFM EVAV-1-04
450 CFM EVAV-1-03 450 CFM
EVAV-1-02 450 CFM
SVAV-1-06 950 CFM
SVAV-1-07 300 CFM
SVAV-1-08 1050 CFM
SVAV-1-09 2100 CFM EVAV-1-08
1150 CFM EVAV-1-07
200 CFM
EVAV-1-06 500 CFM
EVAV-1-09 2200 CFM
SVAV-1-19 2100 CFM
SVAV-1-11 1500 CFM SVAV-1-12
550 CFM
SVAV-1-14 1500 CFM
SVAV-1-15 1000 CFM
SVAV-1-17 700 CFM
SVAV-1-16 300 CFM
SVAV-1-18 700 CFM EVAV-1-16
400 CFM EVAV-1-15 1200 CFM
EVAV-1-14 1600 CFM EVAV-1-12
675 CFM
20x18 EVAV-1-11 1600 CFM
EVAV-1-19 2200 CFM EVAV-1-05
1600 CFM
AC-1 AC-2
G H J K
5 4 2
3
8 7 6
K.2
AC-3
F F
F F
SF-1 200 CFM
SF-2 200 CFM
SVAV-1-10 450 CFM
10"⌀ DRYER VENTS UP TO LVL 01 10ø
10ø
PROVIDE 10x10
TRANSFER OPENING WITH GRILLES ON BOTH SIDES AND FIRE DAMPER PROVIDE 10x10
TRANSFER OPENING WITH GRILLES ON BOTH SIDES AND FIRE DAMPER
40x20 SUPPLY DUCT UP TO GROUND LEVEL
40x20 EXHAUST DUCT UP TO GROUND LEVEL
40x20 SUPPLY DUCT UP TO GROUND LEVEL 40x20 EXHAUST DUCT UP TO GROUND LEVEL 12x12 EXHAUST DUCT UP TO GROUND LEVEL
AC-6
12x8
Stair B 090.02
Stair A 090.01 Elev. #1
090.03
G League Locker 011
Home Training 009 Training Office
009.4
JC Storage 027
Elec.
010
Hydro 009.3
Recovery/Media 023
IDF 024
WSU/GL Laundry 029
Visiting Training 028
WSU Women Locker
005
WSU Wet 005.1
WSU Men Locker 003
WSU Wet 003.1
WSU/G-L Visiting Locker
002
Visiting Wet 002.1
WSU Visiting Locker
006
Visiting Wet 006.1
Elev. Machine 012 Facility Office
008 GL Storage
025
Visiting Coaches 020 Off. Lockers
016 WSU Coaches
017 WSU Coaches
013
Elec.
021 G League
Conference 015
?
?
L.H.
027.1
Changing Room 020.1
Away Corridor 090.07 Home Corridor
090.06
L.H.
022
G League Wet 011.2
Fam. Toilet 026
Amp Storage 001 IDF
019
Training Storage 009.1 G League Coaches
Locker 011.1
L.H.
025.1
Hydration 007
Off. Lockers 018
Stair A Cooridor 090.05 Away Entry
090.09 Home Entry
090.08
090.04
R-2
14x10 14x10 S-1
500 CFM 12"NK
S-1 500 CFM 12"NK
S-1 500 CFM 12"NK
E-1 400 CFM 10"NK
E-1 400 CFM 10"NK E-1
400 CFM 10"NK
E-1 400 CFM 10"NK
12x10
18x10
18x14 8x14
18x12 24x12
12x14 S-1 250 CFM 8"NK S-1
250 CFM 8"NK
S-1 250 CFM 8"NK
E-1 600 CFM
12"NK E-1 600 CFM 12"NK
S-1 250 CFM 8"NK
10ø
S-1 520 CFM 12"NK E-1 550 CFM 12"NK
E-1 550 CFM 12"NK
E-1 550 CFM 12"NK
E-1 400 CFM 10"NK
E-1 400 CFM
10"NK E-1 400 CFM 10"NK E-1 400 CFM 10"NK
S-1 500 CFM 12"NK S-1
500 CFM 12"NK
S-1 500 CFM 12"NK
E-1 300 CFM 10"NK S-1
250 CFM 8"NK E-2
100 CFM 6"NK S-1
50 CFM 6"NK
10x14
24x14
24x14 40x20
S-1 520 CFM
12"NK E-1 550 CFM 12"NK E-1 550 CFM 12"NK E-1
550 CFM 12"NK
24x14
E-2 75 CFM 6"NK
E-1 300 CFM 10"NK
E-1 300 CFM 10"NK
8x1218x12
S-1 275 CFM 10"NK
S-1 275 CFM 10"NK
14x12
18x12
18x12 24x12
18x14 8x14
14x10
12x10
8x12
12x10
8ø 8x12
16x10
S-1 450 CFM 10"NK
E-1 500 CFM 12"NK E-1
500 CFM 12"NK
16x14
16x14
12ø
24x12
S-1 450 CFM 10"NK 14x14
14x12 8x12
E-1 400 CFM 10"NK
10x6
8x14 EVAV-1-20
1000 CFM
SVAV-1-20 900 CFM E-1
400 CFM 10"NK
S-1 300 CFM 10"NK
10ø
10ø
T C
CO2 SENSOR (TYP.)
T
T
T
T T
T
T
T
T
T T
T T
T T
T
10ø
10ø
12ø
10ø
12x10 10ø 10ø
E-1 450 CFM 10"NK
S-1 350 CFM 10"NK
S-1 500 CFM 12"NK E-1
450 CFM 10"NK
E-1 450 CFM 10"NK
T T
T
T T
SVAV-1-03 500 CFM
T
S-6 8"NK 200 CFM S-5
1400 CFM 24x12NK
E-1 550 CFM 12"NK
S-1 225 CFM 8"NK S-1 225 CFM 8"NK
S-1 525 CFM 12"NK S-1
525 CFM 12"NK
S-1 300 CFM 10"NK
E-1 200 CFM 8"NK
E-3 200 CFM 12x6NK S-1
250 CFM 8"NK 2
M700
T
24x12
10x12
SVAV-1-21 1400 CFM
E-3 400 CFM 14x8NK
RVAV-1-21 400 CFM
12x8
EF-8
800 CFM EF-9
800 CFM
1
1
1
1 1
2 2
2
S-5 500 CFM 16x10NK S-5
100 CFM 12x8NK
S-5 100 CFM 12x8NK
E-1 250 CFM 8"NK
E-3 250 CFM 12x6NK
10x10
16x10
16x10
10x10
12x10
EVAV-1-17 600 CFM
40x20
T-2 T-2
T-2 T-2
T-2 T-2
20x14
T-2 10x10
M BMS
100
100
100
100
100
BMS M
75 100
50
100
200 150
100
100
E-1 575 CFM 12"NK E-1 575 CFM 12"NK
100
100 200
200 200
100
100
E-1 400 CFM 10"NK
E-1 400 CFM 10"NK E-1 400 CFM 10"NK S-1
450 CFM 10"NK S-1
525 CFM 12"NK S-1
525 CFM 12"NK
18x14
SVAV-1-05 1500 CFM 10x14
100
50
100
S-5 300 CFM 12x8NK
S-5 200 CFM 12x8NK
M BMS BMS M
1 M701 BMS USER
WORKSTATION
10x1010x10
12ø
12ø
16ø
14ø
14ø
52x8 16ø
24x14
40x20 30x20
3
4 4
5 5
6 6
3
52x8
16ø 14ø
16ø
4 4
5 5
6 6
12ø
12ø
12ø
12ø
12ø
8'
0' 16'
Scale: 1/8" = 1'-0"
PROFESSIONAL SEAL CONSULTANT
KEY PLAN
SHEET TITLE
PROJECT #
© 2018 ROSSETTI
8 7 6 5 4 3 2
8 7 6 5 4 3 2
cuments\74670_WSGL_MECH_v20_r.zora.rvt 4 AM
2018-034
Event Level Floor Plan - HVAC (Area B)
Wayne State University - Basketball Arena
1290 West Warren Avenue Detroit, Michigan 48202
1 Event Level Floor Plan - HVAC (Area B)
TRADES TO PROVIDE COMPLETE AND OPERABLE SYSTEMS WITHOUT INTERFERENCES.
2. COORDINATE GRILLE, REGISTER AND DIFFUSER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
3. ALL NEW DUCTWORK IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE OR SUSPENDED CEILING, UNLESS OTHERWISE NOTED.
4. ALL DUCT PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROVIDED WITH FIRE DAMPERS AND ACCESS DOORS.
5. ALL EXHAUST GRILLES SHALL BE HARD DUCT CONNECTION IN HARD CEILINGS.
6. ALL ROUND DUCT RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS INDICATED BY THE DIFFUSER TAG ON THE DRAWINGS.
7. SUPPLY DUCTWORK PRESSURE CONSTRUCTION SHALL BE 3" W.G. UPSTREAM OF TERMINAL UNITS AND 2" W.G. DOWNSTREAM OF TERMINAL UNITS.
8. MAINTAIN A MINIMUM 10'-0" CLEARANCE FROM EXHAUST FANS, EXHAUST TERMINATIONS AND FLUE GAS VENTS TO ANY SURROUNDING FRESH AIR INTAKES.
9. MAINTAIN REQUIRED CLEARANCES IN FRONT OF ELECTRICAL PANELS/EQUIPMENT. DO NOT ROUTE DUCTWORK ABOVE ELECTRICAL PANELS/EQUIPMENT.
10. ACCESS PANELS AND DOORS ARE REQUIRED THROUGHOUT BUILDING CONSTRUCTION ASSEMBLIES SUCH AS WALLS, HARD CEILINGS, PARTITIONS AND FLOORS TO SERVICE AND MAINTAIN TERMINAL UNITS, BALANCING DAMPERS, CONTROL MOTORS, ETC.
ACCESS PANELS AND DOORS SHALL BE PROVIDED AND INSTALLED PER
ARCHITECTURAL SPECIFICATIONS. MECHANICAL CONTRACTOR SHALL VERIFY THE EXACT QUANTITY, SIZE, FIRE-RATING AND LOCATION OF ACCESS PANELS AND DOORS FOLLOWING INSTALLATION OF SYSTEMS AND COMPONENTS REQUIRING ACCESS, BUT PRIOR TO THE CLOSURE OF THE AFFECTED CEILING AND BUILDING ASSEMBLIES.
MINIMUM ACCESS PANEL AND DOOR SIZE SHALL BE 24 INCHES BY 18 INCHES, UNLESS OTHERWISE NOTED.
11. WHERE VOLUME DAMPERS OCCUR ABOVE CEILINGS WITHOUT REMOVABLE TILE OR ACCESS PANEL, PROVIDE A FLUSH-MOUNTED CONCEALED DAMPER REGULATOR TO ALLOW FOR DAMPER ADJUSTMENT BELOW CEILING. UNIT TO BE EQUAL TO VENTLOCK NO. 666 IN 1/2" OR 3/8" ROD SIZE.
12. PROVIDE TRANSFER OPENING IN ALL FULL HEIGHT WALLS SIZED FOR 0.05" OF STATIC PRESSURE PER 100' OF DUCT.
13. PROVIDE VANDAL PROOF TEMPERATURE SENSORS IN PUBLIC AREAS.
HVAC KEY NOTES
SEAL FLOOR PENETRATION AND PACK SPACE BETWEEN DUCT WITH FIRE RATED MATERIAL PER MICHIGAN BUILDING CODE.
PROVIDE FLUSH MOUNTED CLEANOUT PORTS ON DRYER VENT DUCTWORK AT EVERY 20' OF DUCT AND ALL ELBOWS AND TURNS.
12" EXHAUST DUCT DOWN TO 16" EXHAUST OUTLET ABOVE PERFORATED CEILING.
PROVIDE WIREMESH GRILLE ON OPEN ENDED DUCTWORK. BALANCE TO 550 CFM.
PROVIDE 10' CONTINUOUS SLOT DIFFUSER, TITUS MODEL FL-25 JET THROW ONE SLOT AND 2.5" SLOT WIDTH. PROVIDE (2) 12" OVAL TAPS INTO CUSTOM PLENUM.
BALANCE TO 560 CFM.
PROVIDE 2' SLOT DIFFUSER, TITUS MODEL FL-25 JET THROW ONE SLOT AND 2.5"
SLOT WIDTH. PROVIDE 12" OVAL TAP INTO CUSTOM PLENUM. BALANCE TO 115 CFM.
PROVIDE ROUND DUCT IN SEGMENTS TO FIT IN CHASE AS INDICATED.
1
2
# DESCRIPTION DATE
1 DESIGN DEVELOPMENT 11.21.2019
CONSTRUCTION DOCUMENT - PACKAGE 2 03.18.2020
ASI-002 06.03.2020
ASI-006 02.26.2021
3
4
5
6
A B C D E F G
5 4 1
2
3
8 7 6 1P
2P
4P
6P
8P
10P
12P
15P 14P
137 Premium
Seating
?
? 190.13
Concourse North
022 L.H.
143 North Stadia Seating
142 South Stadia Seating
190.16 Stair D 190.15 Stair C
?
?
190.14 Concourse
South 050
Court
144 Camera 148
Camera
/ 1 M212
1 M700
A B C D E F G
5 4 1
2
3
8 7 6 1P
2P
4P
6P
8P
10P
12P
15P 14P
2 M700
T C
CO2 SENSOR
RTU-2 TEMPERATURE SENSOR ONLY. COORDINATE FINAL LOCATION WITH ARCH TRADES.
RTU-1 TEMPERATURE SENSOR ONLY. COORDINATE FINAL LOCATION WITH ARCH TRADES.
T C
CO2 SENSOR
8'
0' 16'
Scale: 1/8" = 1'-0"
PROFESSIONAL SEAL CONSULTANT
PROJECT
KEY PLAN
SHEET TITLE
PROJECT #
SHEET #
© 2018 ROSSETTI
B 8
7 6 5 4 3 2 1
A C D E F G H J K
8 7 6 5 4 3 2 1
30x42
AE-SVR-FILE01\UserFolders\rzora\Documents\74670_WSGL_MECH_v20_rzora.rvt /2020 5:31:58 PM
2018-034
Ground Level Floor Plan - HVAC (Area A)
M211
Wayne State University - Basketball Arena
1290 West Warren Avenue Detroit, Michigan 48202
M211 SCALE: 1/8" = 1'-0"
1 Ground Level Floor Plan - HVAC (Area A)
# DESCRIPTION DATE
CONSTRUCTION DOCUMENT - PACKAGE 2 03.18.2020 THE FOLLOWING GENERAL NOTES APPLY TO ALL HVAC SHEETS INCLUDED WITHIN THIS
DOCUMENT SET, EXCEPT WHERE OTHERWISE INDICATED.
1. SHEET METAL OFFSETS AND TRANSITIONS ARE SHOWN TO PROVIDE INDICATION OF PHYSICAL CONDITIONS WITHIN THE SPACE. IT IS NOT THE INTENT OF THE DRAWINGS TO SHOW ALL REQUIRED OFFSETS AND TRANSITIONS. THE CONTRACTOR SHALL FULLY COORDINATE THE MECHANICAL WORK WITHIN ITSELF AND WITH THE WORK OF ALL TRADES TO PROVIDE COMPLETE AND OPERABLE SYSTEMS WITHOUT INTERFERENCES.
2. COORDINATE GRILLE, REGISTER AND DIFFUSER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
3. ALL NEW DUCTWORK IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE OR SUSPENDED CEILING, UNLESS OTHERWISE NOTED.
4. ALL DUCT PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROVIDED WITH FIRE DAMPERS AND ACCESS DOORS.
5. ALL EXHAUST GRILLES SHALL BE HARD DUCT CONNECTION IN HARD CEILINGS.
6. ALL ROUND DUCT RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS INDICATED BY THE DIFFUSER TAG ON THE DRAWINGS.
7. SUPPLY DUCTWORK PRESSURE CONSTRUCTION SHALL BE 3" W.G. UPSTREAM OF TERMINAL UNITS AND 2" W.G. DOWNSTREAM OF TERMINAL UNITS.
8. MAINTAIN A MINIMUM 10'-0" CLEARANCE FROM EXHAUST FANS, EXHAUST TERMINATIONS AND FLUE GAS VENTS TO ANY SURROUNDING FRESH AIR INTAKES.
9. MAINTAIN REQUIRED CLEARANCES IN FRONT OF ELECTRICAL PANELS/EQUIPMENT. DO NOT ROUTE DUCTWORK ABOVE ELECTRICAL PANELS/EQUIPMENT.
10. ACCESS PANELS AND DOORS ARE REQUIRED THROUGHOUT BUILDING CONSTRUCTION ASSEMBLIES SUCH AS WALLS, HARD CEILINGS, PARTITIONS AND FLOORS TO SERVICE AND MAINTAIN TERMINAL UNITS, BALANCING DAMPERS, CONTROL MOTORS, ETC.
ACCESS PANELS AND DOORS SHALL BE PROVIDED AND INSTALLED PER
ARCHITECTURAL SPECIFICATIONS. MECHANICAL CONTRACTOR SHALL VERIFY THE EXACT QUANTITY, SIZE, FIRE-RATING AND LOCATION OF ACCESS PANELS AND DOORS FOLLOWING INSTALLATION OF SYSTEMS AND COMPONENTS REQUIRING ACCESS, BUT PRIOR TO THE CLOSURE OF THE AFFECTED CEILING AND BUILDING ASSEMBLIES.
MINIMUM ACCESS PANEL AND DOOR SIZE SHALL BE 24 INCHES BY 18 INCHES, UNLESS OTHERWISE NOTED.
11. WHERE VOLUME DAMPERS OCCUR ABOVE CEILINGS WITHOUT REMOVABLE TILE OR ACCESS PANEL, PROVIDE A FLUSH-MOUNTED CONCEALED DAMPER REGULATOR TO ALLOW FOR DAMPER ADJUSTMENT BELOW CEILING. UNIT TO BE EQUAL TO VENTLOCK NO. 666 IN 1/2" OR 3/8" ROD SIZE.
12. PROVIDE TRANSFER OPENING IN ALL FULL HEIGHT WALLS SIZED FOR 0.05" OF STATIC PRESSURE PER 100' OF DUCT.
13. PROVIDE VANDAL PROOF TEMPERATURE SENSORS IN PUBLIC AREAS.
FEC FEC
FEC
FEC FEC
D D
CD D
C - -
- --
- --
--- -
5 4 2
3
8 7 6
117 Conference
119 WSU
Film
112 Main Elec.
114 MDF
118 Trash/
Sorting
111 Head Coach
113 Ast.
Coach
109 Head Coach
105 Ast.
Coach 107
Ast.
Coach 127
Concession
125 Family
Toilet
128 Concession
103 Open Office
118.1 Boiler Room 120
Broadcast Control
101 Retail
116 Building Command 104
First Aid
110.1 Staff Lockers 129
Elec.
Closet
129.1 IDF
108 Ticketing 190.08
Atrium
100 Ticket Queuing 137
Premium Seating
190.06 Vestibule
136 Premium
Seating 027.1
L.H.
110 BOH Hallway 022
L.H.
190.07 Concourse
Ticket Queue 190.11
Concourse Concession
North
190.01 Stair A 190.03
Elev. #1
190.02 Stair B
190.05 Concourse
Stair Access 130
East Stadia Seating
190.04 Stair Access
190.10 Concourse
East
190.12 Concourse Concession
South 132 High Camera
190.09 BOH Vestibule 123
Men
126 Supply
124 Men
122 Women
106 Storage
102 Guest Services 121.1
Supply
108.1 Ticket Office 121
Women
123.1 Supply
124.1 Supply
122.1 Supply
66x30
66x30
40x20
30x26
30x2024x1616x12
40x20
66x30
24x12
40x30
24x16 24x20
66x30
66x30 40x20
20x14
VAV-2-01 500 CFM VAV-2-02
650 CFM
VAV-2-03 450 CFM
VAV-2-04 450 CFM
VAV-2-05 800 CFM
VAV-2-06 600 CFM
VAV-2-08 500 CFM
VAV-2-12 800 CFM VAV-2-13 500 CFM
VAV-2-09 300 CFM
CUH-2 AC-5
AC-4
12x12
24x12
G H J K L
5 4 2
3
8 7 6
K.2 K.6
F
F
F SF-3
200 CFM
EUH-1
EUH-2
EUH-3
M
M CUH-4
CUH-3 190.08
Atrium
24x18 INTAKE LOUVER BY ARCH TRADES SIZED FOR 50% FREE AREA
18x12 INTAKE LOUVER BY ARCH TRADES SIZED FOR 50% FREE AREA
PROVIDE 16x10 TRANSFER OPENING WITH GRILLES ON BOTH SIDES AND FIRE DAMPER PROVIDE 16x10
TRANSFER DUCT WITH ACOUSTIC BOOT AND FIRE DAMPER
24x20 RETURN DUCT UP TO RTU-4 ON RTU WELL SOUTH 24x20 RETURN DUCT UP. PROVIDE 1/2"x1/2"
WIRE MESH GRILLE ON OPEN ENDED DUCT (OED)
30x40 SUPPLY DUCT UP TO RTU-4 ON RTU WELL SOUTH PROVIDE 10x10
TRANSFER OPENING WITH GRILLES ON BOTH SIDES AND FIRE DAMPER
30x24 RETURN DUCT UP TO RTU-3 ON RTU WELL NORTH 30x24 RETURN DUCT UP. PROVIDE 1/2"x1/2"
WIRE MESH GRILLE ON OPEN ENDED DUCT (OED)
30x40 SUPPLY DUCT UP TO RTU-3 ON RTU WELL NORTH
66x30 SUPPLY DUCT UP TO RTU-1 ON RTU WELL NORTH
66x30 RETURN DUCT UP TO RTU-1 ON RTU WELL NORTH
66x30 SUPPLY DUCT UP TO RTU-2 ON RTU WELL SOUTH
66x30 RETURN DUCT UP TO RTU-2 ON RTU WELL SOUTH F
VAV-2-11 650 CFM 66x30 SUPPLY
DUCT UP THROUGH SHAFT TO MEZZANINE LEVEL
40x20 SUPPLY DUCT DOWN TO EVENT LEVEL
40x20 EXHAUST DUCT DOWN TO EVENT LEVEL
60x32 SUPPLY DUCT UP THROUGH SHAFT TO MEZZANINE LEVEL
40x20 SUPPLY DUCT DOWN TO EVENT LEVEL 40x20 EXHAUST DUCT DOWN TO EVENT LEVEL
10"⌀ DRYER VENTS UP THRU ROOF 10"⌀ DRYER
VENTS DN TO EVENT LEVEL
(2)10"⌀
STACKED
40x20 EXHAUST
DUCT UP 20x14
EXHAUST DUCT UP 12x12 EXHAUST DUCT DOWN TO EVENT LEVEL
12x12 EXHAUST DUCT UP TO EF-3 ON RTU WELL NORTH 26x26 EXHAUST DUCT UP TO EF-2 ON RTU WELL NORTH
26x26 EXHAUST DUCT UP TO EF-1 ON RTU WELL NORTH
VAV-2-15 1800 CFM
VAV-2-14 1800 CFM
FCU-1 FCU-2
FCU-3
R-2
14x12
12ø20x10
R-2 VAV-2-10
600 CFM
R-1 R-1
10x12 8x12
8x12
10x12
12x10
12x128x12 12ø
8x1012x10
10x12
10ø
E-1 320 CFM 10"NK
E-1 320 CFM 10"NK
E-1 310 CFM 10"NK
E-1 275 CFM 10"NK E-1 275 CFM 10"NK E-1
100 CFM 6"NK
10x12
R-2 R-2
8x8
24x14
24x14
24x14 24x16
24x16
24x16
10ø 10ø
VAV-2-07 750 CFM
E-1 475 CFM 12"NK E-1 475 CFM 12"NK E-1
275 CFM 10"NK
E-1 275 CFM 10"NK
T T
T C CO2
SENSOR (TYP.)
T
T
T C
T T
T
T
T
T T
T
T T T
T
24x12
12x12 14x12
12x12 14x12
24x12
S-3 18x6NK 450 CFM S-3
18x6NK 450 CFM S-3
18x6NK 450 CFM S-3
18x6NK 450 CFM
S-3 18x6NK 450 CFM
S-3 18x6NK 450 CFM
S-3 18x6NK 450 CFM
S-3 18x6NK 450 CFM
S-6 10"NK 350 CFM
S-6 10"NK 350 CFM
S-6 10"NK 350 CFM S-6
10"NK 350 CFM S-6
6"NK 150 CFM
S-6 6"NK 150 CFM
S-6 12"NK 500 CFM S-6
12"NK 500 CFM
S-6 8"NK 200 CFM
S-6 10"NK 400 CFM S-6
10"NK 400 CFM
S-6 12"NK 450 CFM
S-6 8"NK 200 CFM S-6
8"NK 200 CFM
S-2
12"OVAL NK 1130 CFM
14x12
S-6 10"NK 450 CFM S-6 6"NK 100 CFM
S-6 8"NK 250 CFM 8"NK 250 CFM S-6
10"NK 275 CFM
R-3 24x20NK 2260 CFM
R-3 24x20NK 2260 CFM
R-3 24x20NK 2260 CFM 2
M700
72x128
S-2
12"OVAL NK 1130 CFM
S-2
12"OVAL NK 1130 CFM
S-2
12"OVAL NK 1130 CFM
S-2
12"OVAL NK 1130 CFM
S-2
12"OVAL NK 1130 CFM T
T
PROVIDE 1/2"x1/2"
WIRE MESH GRILLE ON OPEN ENDED DUCT (OED)
12x10
S-5 300 CFM 12x8NK E-2
100 CFM 6"NK
E-2 100 CFM 6"NK E-2
100 CFM 6"NK
14x14 EXHAUST DUCT.
PROVIDE 1/2"x1/2"
WIRE MESH GRILLE ON OPEN ENDED DUCT (OED)
14x8 EXHAUST DUCT.
PROVIDE 1/2"x1/2"
WIRE MESH GRILLE ON OPEN ENDED DUCT (OED)
RATED CEILING ENCLOSURE
PROVIDED BY ARCH.
TRADES TO CONCEAL RETURN DUCT
S-1 50 CFM 6"NK
S-5 650 CFM 16x10NK 12x10
VAV-2-16 650 CFM
T-1 T-1
T-1 R-4
72x128NK 24000 CFM
R-4 72x128NK 24000 CFM
72x128
14x14
14x8
14x14 EXHAUST DUCT UP TO EF-10 ON RTU WELL SOUTH
14x8 EXHAUST DUCT UP TO EF-7 ON RTU WELL SOUTH
T T-2
T-2 T-2
14x10 SUPPLY DUCT UP
14x10 RETURN DUCT UP
(3)S-7 10"OVAL NK 250 CFM
T-3
T-3
M
T T
T T PROVIDE 16x10
TRANSFER DUCT WITH ACOUSTIC BOOTS ON BOTH SIDES
16x10 20x20
PROVIDE 20x20 TRANSFER DUCT WITH ACOUSTIC BOOTS ON BOTH SIDES
M
BMS
M
BMS
EF-10 EUH-2 R-5
R-5 R-5 R-5 R-5
R-5
R-5
R-6
3 3
4 4
4
4 4
3
4 4
4
3 3
3
1 M701 M701
3 M701
EUH-5 T
EUH-3 EF-7 EF-12
325 CFM
SF-4 1400 CFM
R-8 1400 CFM 24x24NK
S-1 350 CFM 10"NK
E-1 325 CFM 10"NK
S-1 350 CFM 10"NK S-1 350 CFM 10"NK S-1
350 CFM
10"NK 12x1220x12 12x10
SF-5 1400 CFM
R-8 1400 CFM 24x24NK
S-1 350 CFM 10"NK
S-1 350 CFM 10"NK S-1 350 CFM 10"NK S-1
350 CFM 10"NK
20x1212x12
16"x12" EXHAUST LOUVER BY ARCH TRADES BASED ON 50% FREE AREA EF-13
325 CFM E-1 325 CFM 10"NK
12x10
22x22 22x22
T T
8'
0' 16'
Scale: 1/8" = 1'-0"
PROFESSIONAL SEAL CONSULTANT
KEY PLAN
SHEET TITLE
PROJECT #
© 2018 ROSSETTI
8 7 6 5 4 3 2
8 7 6 5 4 3 2
cuments\74670_WSGL_MECH_v20_r.zora.rvt 7 PM
2018-034
Ground Level Floor Plan - HVAC (Area B)
Wayne State University - Basketball Arena
1290 West Warren Avenue Detroit, Michigan 48202
1 Ground Level Floor Plan - HVAC (Area B)
TRADES TO PROVIDE COMPLETE AND OPERABLE SYSTEMS WITHOUT INTERFERENCES.
2. COORDINATE GRILLE, REGISTER AND DIFFUSER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
3. ALL NEW DUCTWORK IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE OR SUSPENDED CEILING, UNLESS OTHERWISE NOTED.
4. ALL DUCT PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROVIDED WITH FIRE DAMPERS AND ACCESS DOORS.
5. ALL EXHAUST GRILLES SHALL BE HARD DUCT CONNECTION IN HARD CEILINGS.
6. ALL ROUND DUCT RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS INDICATED BY THE DIFFUSER TAG ON THE DRAWINGS.
7. SUPPLY DUCTWORK PRESSURE CONSTRUCTION SHALL BE 3" W.G. UPSTREAM OF TERMINAL UNITS AND 2" W.G. DOWNSTREAM OF TERMINAL UNITS.
8. MAINTAIN A MINIMUM 10'-0" CLEARANCE FROM EXHAUST FANS, EXHAUST TERMINATIONS AND FLUE GAS VENTS TO ANY SURROUNDING FRESH AIR INTAKES.
9. MAINTAIN REQUIRED CLEARANCES IN FRONT OF ELECTRICAL PANELS/EQUIPMENT. DO NOT ROUTE DUCTWORK ABOVE ELECTRICAL PANELS/EQUIPMENT.
10. ACCESS PANELS AND DOORS ARE REQUIRED THROUGHOUT BUILDING CONSTRUCTION ASSEMBLIES SUCH AS WALLS, HARD CEILINGS, PARTITIONS AND FLOORS TO SERVICE AND MAINTAIN TERMINAL UNITS, BALANCING DAMPERS, CONTROL MOTORS, ETC.
ACCESS PANELS AND DOORS SHALL BE PROVIDED AND INSTALLED PER
ARCHITECTURAL SPECIFICATIONS. MECHANICAL CONTRACTOR SHALL VERIFY THE EXACT QUANTITY, SIZE, FIRE-RATING AND LOCATION OF ACCESS PANELS AND DOORS FOLLOWING INSTALLATION OF SYSTEMS AND COMPONENTS REQUIRING ACCESS, BUT PRIOR TO THE CLOSURE OF THE AFFECTED CEILING AND BUILDING ASSEMBLIES.
MINIMUM ACCESS PANEL AND DOOR SIZE SHALL BE 24 INCHES BY 18 INCHES, UNLESS OTHERWISE NOTED.
11. WHERE VOLUME DAMPERS OCCUR ABOVE CEILINGS WITHOUT REMOVABLE TILE OR ACCESS PANEL, PROVIDE A FLUSH-MOUNTED CONCEALED DAMPER REGULATOR TO ALLOW FOR DAMPER ADJUSTMENT BELOW CEILING. UNIT TO BE EQUAL TO VENTLOCK NO. 666 IN 1/2" OR 3/8" ROD SIZE.
12. PROVIDE TRANSFER OPENING IN ALL FULL HEIGHT WALLS SIZED FOR 0.05" OF STATIC PRESSURE PER 100' OF DUCT.
13. PROVIDE VANDAL PROOF TEMPERATURE SENSORS IN PUBLIC AREAS.
1
2
HVAC KEY NOTES
SEAL FLOOR PENETRATION AND PACK SPACE BETWEEN DUCT WITH FIRE RATED MATERIAL PER MICHIGAN BUILDING CODE.
PROVIDE FLUSH MOUNTED CLEANOUT PORTS ON DRYER VENT DUCTWORK AT EVERY 20' OF DUCT AND ALL ELBOWS AND TURNS.
PROVIDE 1" ARMAFLEX DUCT LINER FOR FIRST 20' OF DUCT FROM ROOF TOP UNIT (RTU) FOR SUPPLY AND RETURN DUCTS.
PROVIDE 1" ARMAFLEX DUCT LINER AND DUCT GAGE 2 EVEN SIZES THICKER THAN REQUIRED ON SUPPLY AND EXHAUST DUCTS FROM RTU/FAN TO ABOVE TOILET ROOMS.
# DESCRIPTION DATE
1 DESIGN DEVELOPMENT 11.21.2019
CONSTRUCTION DOCUMENT - PACKAGE 2 03.18.2020
ASI-002 06.03.2020
ASI-004 09.29.2020
3
4
A B C D E F G
5 4 1
2
3
8 7 6 1P
2P
4P
6P
8P
10P
12P
15P 14P
/ 1 M222
1 M700
A B C D E F G
5 4 1
2
3
8 7 6 1P
2P
4P
6P
8P
10P
12P
15P 14P
48ø CABLE SUPPORTED
FABRIC DUCT 2
M700
CABLE SUPPORTED FABRIC DUCT
48ø
8'
0' 16'
Scale: 1/8" = 1'-0"
PROFESSIONAL SEAL CONSULTANT
PROJECT
KEY PLAN
SHEET TITLE
PROJECT #
SHEET #
© 2018 ROSSETTI
B 8
7 6 5 4 3 2 1
A C D E F G H J K
8 7 6 5 4 3 2 1
30x42
AE-SVR-FILE01\UserFolders\rzora\Documents\74670_WSGL_MECH_v20_rzora.rvt /2020 5:32:12 PM
2018-034
Mezzanine Level Floor Plan - HVAC (Area A)
M221
Wayne State University - Basketball Arena
1290 West Warren Avenue Detroit, Michigan 48202
M221 SCALE: 1/8" = 1'-0"
1 Mezzanine Level Floor Plan - HVAC (Area A)
THE FOLLOWING GENERAL NOTES APPLY TO ALL HVAC SHEETS INCLUDED WITHIN THIS DOCUMENT SET, EXCEPT WHERE OTHERWISE INDICATED.
1. SHEET METAL OFFSETS AND TRANSITIONS ARE SHOWN TO PROVIDE INDICATION OF PHYSICAL CONDITIONS WITHIN THE SPACE. IT IS NOT THE INTENT OF THE DRAWINGS TO SHOW ALL REQUIRED OFFSETS AND TRANSITIONS. THE CONTRACTOR SHALL FULLY COORDINATE THE MECHANICAL WORK WITHIN ITSELF AND WITH THE WORK OF ALL TRADES TO PROVIDE COMPLETE AND OPERABLE SYSTEMS WITHOUT INTERFERENCES.
2. COORDINATE GRILLE, REGISTER AND DIFFUSER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
3. ALL NEW DUCTWORK IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE OR SUSPENDED CEILING, UNLESS OTHERWISE NOTED.
4. ALL DUCT PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROVIDED WITH FIRE DAMPERS AND ACCESS DOORS.
5. ALL EXHAUST GRILLES SHALL BE HARD DUCT CONNECTION IN HARD CEILINGS.
6. ALL ROUND DUCT RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS INDICATED BY THE DIFFUSER TAG ON THE DRAWINGS.
7. SUPPLY DUCTWORK PRESSURE CONSTRUCTION SHALL BE 3" W.G. UPSTREAM OF TERMINAL UNITS AND 2" W.G. DOWNSTREAM OF TERMINAL UNITS.
8. MAINTAIN A MINIMUM 10'-0" CLEARANCE FROM EXHAUST FANS, EXHAUST TERMINATIONS AND FLUE GAS VENTS TO ANY SURROUNDING FRESH AIR INTAKES.
9. MAINTAIN REQUIRED CLEARANCES IN FRONT OF ELECTRICAL PANELS/EQUIPMENT. DO NOT ROUTE DUCTWORK ABOVE ELECTRICAL PANELS/EQUIPMENT.
10. ACCESS PANELS AND DOORS ARE REQUIRED THROUGHOUT BUILDING CONSTRUCTION ASSEMBLIES SUCH AS WALLS, HARD CEILINGS, PARTITIONS AND FLOORS TO SERVICE AND MAINTAIN TERMINAL UNITS, BALANCING DAMPERS, CONTROL MOTORS, ETC.
ACCESS PANELS AND DOORS SHALL BE PROVIDED AND INSTALLED PER
ARCHITECTURAL SPECIFICATIONS. MECHANICAL CONTRACTOR SHALL VERIFY THE EXACT QUANTITY, SIZE, FIRE-RATING AND LOCATION OF ACCESS PANELS AND DOORS FOLLOWING INSTALLATION OF SYSTEMS AND COMPONENTS REQUIRING ACCESS, BUT PRIOR TO THE CLOSURE OF THE AFFECTED CEILING AND BUILDING ASSEMBLIES.
MINIMUM ACCESS PANEL AND DOOR SIZE SHALL BE 24 INCHES BY 18 INCHES, UNLESS OTHERWISE NOTED.
11. WHERE VOLUME DAMPERS OCCUR ABOVE CEILINGS WITHOUT REMOVABLE TILE OR ACCESS PANEL, PROVIDE A FLUSH-MOUNTED CONCEALED DAMPER REGULATOR TO ALLOW FOR DAMPER ADJUSTMENT BELOW CEILING. UNIT TO BE EQUAL TO VENTLOCK NO. 666 IN 1/2" OR 3/8" ROD SIZE.
12. PROVIDE TRANSFER OPENING IN ALL FULL HEIGHT WALLS SIZED FOR 0.05" OF STATIC PRESSURE PER 100' OF DUCT.
# DESCRIPTION DATE
1 DESIGN DEVELOPMENT 11.21.2019
CONSTRUCTION DOCUMENT - PACKAGE 2 03.18.2020
TV TV
5 4 2
3
8 7 6
201 RTU Well South 290.04
Mezz.
Bridge
200 RTU Well North
224 Toilet
222 Suite Pantry 220
Donor Suite
290.05 Vestibule
48ø 66x30
RTU-1
RTU-2
RTU-3
RTU-4 VAV-3-01
850 CFM
60x32
14x10 14x10
EF-2 1700 CFM
EF-1 7000 CFM
ACCU-1
ACCU-2
ACCU-3
ACCU-4 EF-3 600 CFM
VAV-3-02 200 CFM
G H J K L
5 4 2
3
8 7 6
K.2 K.6
ACCU-5 EF-4
1700 CFM EF-5
6350 CFM
EF-6 100 CFM
30x18 EXHAUST LOUVER PROVIDED BY ARCH TRADES SIZED FOR 50%
FREE AREA 48x30 EXHAUST LOUVER
PROVIDED BY ARCH TRADES SIZED FOR 50%
FREE AREA
66x30 SUPPLY DUCT DOWN THROUGH SHAFT TO GROUND LEVEL
66x30 SUPPLY DUCT DOWN THROUGH SHAFT TO GROUND LEVEL
10"⌀ GOOSENECK DRYER VENT TERMINATION MIN 36" ABOVE ROOF.
PROVIDE CURB.
12"x12" EXHAUST LOUVER BY ARCH TRADES BASED ON 50% FREE AREA
ACCU-6 223
Storage 226
Donor Suite Bacony
12x12
10x8
R-2 T
T S-7
10"NK 375 CFM S-7 10"NK 375 CFM
S-6 6"NK 50 CFM
S-6 10"NK 150 CFM 2
M700
EF-10 1000 CFM
EF-7 500 CFM CABLE SUPPORTED
FABRIC DUCT
PROVIDE MIN.
10' OF SPIRAL DUCT
M M
20x14
40x20
40x20 EXHAUST DUCT DOWN TO GROUND LEVEL
20x14 EXHAUST DUCT DOWN TO GROUND LEVEL
14x10 SUPPLY DUCT DOWN TO GROUND LEVEL
14x10 RETURN DUCT DOWN TO GROUND LEVEL CABLE SUPPORTED
FABRIC DUCT
CUH-5
S-6 6"NK 100 CFM
EUH-4
6" BOILER/WATER HEATER INTAKE (TYP. 5)
6" BOILER/WATER HEATER VENT (TYP. 5) METAL DUCT
FABRIC DUCT
PROVIDE MIN.
10' OF SPIRAL DUCT
METAL DUCT FABRIC DUCT
48ø
BD
REFER TO DETAIL 5 ON M-502 FOR ADDITIONAL DETAILS REFER TO DETAIL 5 ON M-502 FOR ADDITIONAL DETAILS
1 M701 M701
3 M701
2
2
2
2 EF-11
200 CFM
12"x12" EXHAUST LOUVER BY ARCH TRADES BASED ON 50% FREE AREA 8ø
8ø E-4
8"NK 200 CFM
R-7
8'
0' 16'
Scale: 1/8" = 1'-0"
PROFESSIONAL SEAL CONSULTANT
KEY PLAN
SHEET TITLE
PROJECT #
© 2018 ROSSETTI
8 7 6 5 4 3 2
8 7 6 5 4 3 2
cuments\74670_WSGL_MECH_v20_r.zora.rvt 4 PM
2018-034
Mezzanine Level Floor Plan - HVAC (Area B)
Wayne State University - Basketball Arena
1290 West Warren Avenue Detroit, Michigan 48202
1 Mezzanine Level Floor Plan -HVAC (Area B)
TRADES TO PROVIDE COMPLETE AND OPERABLE SYSTEMS WITHOUT INTERFERENCES.
2. COORDINATE GRILLE, REGISTER AND DIFFUSER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
3. ALL NEW DUCTWORK IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE OR SUSPENDED CEILING, UNLESS OTHERWISE NOTED.
4. ALL DUCT PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROVIDED WITH FIRE DAMPERS AND ACCESS DOORS.
5. ALL EXHAUST GRILLES SHALL BE HARD DUCT CONNECTION IN HARD CEILINGS.
6. ALL ROUND DUCT RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS INDICATED BY THE DIFFUSER TAG ON THE DRAWINGS.
7. SUPPLY DUCTWORK PRESSURE CONSTRUCTION SHALL BE 3" W.G. UPSTREAM OF TERMINAL UNITS AND 2" W.G. DOWNSTREAM OF TERMINAL UNITS.
8. MAINTAIN A MINIMUM 10'-0" CLEARANCE FROM EXHAUST FANS, EXHAUST TERMINATIONS AND FLUE GAS VENTS TO ANY SURROUNDING FRESH AIR INTAKES.
9. MAINTAIN REQUIRED CLEARANCES IN FRONT OF ELECTRICAL PANELS/EQUIPMENT. DO NOT ROUTE DUCTWORK ABOVE ELECTRICAL PANELS/EQUIPMENT.
10. ACCESS PANELS AND DOORS ARE REQUIRED THROUGHOUT BUILDING CONSTRUCTION ASSEMBLIES SUCH AS WALLS, HARD CEILINGS, PARTITIONS AND FLOORS TO SERVICE AND MAINTAIN TERMINAL UNITS, BALANCING DAMPERS, CONTROL MOTORS, ETC.
ACCESS PANELS AND DOORS SHALL BE PROVIDED AND INSTALLED PER
ARCHITECTURAL SPECIFICATIONS. MECHANICAL CONTRACTOR SHALL VERIFY THE EXACT QUANTITY, SIZE, FIRE-RATING AND LOCATION OF ACCESS PANELS AND DOORS FOLLOWING INSTALLATION OF SYSTEMS AND COMPONENTS REQUIRING ACCESS, BUT PRIOR TO THE CLOSURE OF THE AFFECTED CEILING AND BUILDING ASSEMBLIES.
MINIMUM ACCESS PANEL AND DOOR SIZE SHALL BE 24 INCHES BY 18 INCHES, UNLESS OTHERWISE NOTED.
11. WHERE VOLUME DAMPERS OCCUR ABOVE CEILINGS WITHOUT REMOVABLE TILE OR ACCESS PANEL, PROVIDE A FLUSH-MOUNTED CONCEALED DAMPER REGULATOR TO ALLOW FOR DAMPER ADJUSTMENT BELOW CEILING. UNIT TO BE EQUAL TO VENTLOCK NO. 666 IN 1/2" OR 3/8" ROD SIZE.
12. PROVIDE TRANSFER OPENING IN ALL FULL HEIGHT WALLS SIZED FOR 0.05" OF STATIC PRESSURE PER 100' OF DUCT.
HVAC KEY NOTES
SEAL FLOOR PENETRATION AND PACK SPACE BETWEEN DUCT WITH FIRE RATED MATERIAL PER MICHIGAN BUILDING CODE.
RTU IS MOUNTED ON STRUCTURAL STEEL APPROXIMATELY 36" ABOVE THE ROOF.
PROVIDE CONTINUOUS NEOPRENE PAD ON STRUCTURAL STEEL TO MOUNT UNIT ON.
PROVIDE FLEXIBLE CONNECTOR OFF OF BOTTOM OF UNITS. EXTEND DUCTWORK OUTSIDE BELOW UNIT TO CURBED DUCT OPENINGS IN ROOF. INSULATE DUCTS ON ROOF AND PROVIDE WITH ALUMINUM JACKET. PROVIDE FLASHING AROUND JACKET TO CURB EDGE FOR A WATER TIGHT INSTALLATION.
1
# DESCRIPTION DATE
1 DESIGN DEVELOPMENT 11.21.2019
CONSTRUCTION DOCUMENT - PACKAGE 2 03.18.2020
ASI-003 09.16.2020
2
GAS FIRED HOT WATER HEATER SCHEDULE GAS FIRED BOILER SCHEDULE
PACKAGED SPLIT SYSTEM AC UNIT SCHEDULE
DOMESTIC WATER BOOSTER PUMP SCHEDULE EXHAUST FAN SCHEDULE
SUMP PUMP SCHEDULE RECIRCULATION PUMP SCHEDULE
HOT WATER UNIT HEATER SCHEDULE ELECTRIC UNIT HEATER SCHEDULE
FAN COIL UNIT SCHEDULE
GRILLE, REGISTER AND DIFFUSER SCHEDULE
NOTES/
ACCESS MCA
4.3 ESP
"WC
277/1/60 VOLT/PH/HZ
ELECTRICAL
GPM WPD LWT FT EWT
HEATING
MBH
MOUNTING KEY HR - HORIZONTAL RECESSED LVC - LOW VERTICAL CONCEALED CFM
2260 MOUNTING
TITUS HHP-20
& MODEL No.
MANUFACTURER
VESTIBULE ENTRY SERVE AREA
FCU-1 TAG
VC - VERTICAL CONCEALED VCT - VERTICAL CABINET TYPE
HE - HORIZONTAL EXPOSED VE - VERTICAL EXPOSED HCT - HORIZONTAL CABINET TYPE
VR - VERTICAL RECESSED
LVCT - LOW VERTICAL CABINET TYPE HC - HORIZONTAL CONCEALED
HC
LAT EAT
0.41
NOTES AND ACCESSORIES DESIGNATION
70 115 125.8 140 120 12.0 8.3 A B C D
ROWS
6 MAX.
(2) PSC MOTORS
A B CONTROLS CONTRACTOR PROVIDE CONTROL C D HEATING ONLY
HP
(2) 1/3
UNIT MOUNTED DISCONNECT
4.3 277/1/60
TITUS 2260
HHP-20 VESTIBULE
ENTRY
FCU-2 HC 70 115 125.8 140 120 12.0 8.3 6 0.41 (2) 1/3 A B C D
4.3 277/1/60
TITUS 2260
HHP-20 VESTIBULE
ENTRY
FCU-3 HC 70 115 125.8 140 120 12.0 8.3 6 0.41 (2) 1/3 A B C D
MOP
15
15
15
RC - RECESSED CEILING MOUNTING KEY
RW - RECESSED WALL
VOLT ELECTRICAL DATA
KW INPUT AREA CFM
SERVED
MOUNTING MBH
TAG MANUFACTURER
& MODEL No. NOTES/
SW - SURFACE WALL
EUH-1 SUS 350 17.1 5.0 480/3 A B C
HUHAABERKO
112 MAIN ELEC
SUS - SUSPENDED
EUH-2 SUS 350 17.1 5.0 480/3 A B C
HUHAABERKO
118.1 BOILER ROOM
EUH-3 SUS 350 17.1 5.0 480/3 A B C
HUHAABERKO
118 TRASH/SORTING
EUH-4 SUS 250 10.2 3.0 480/3 A B C
HUHAA BERKO
223 STORAGE
EUH-5 SUS 350 17.1 5.0 480/3 A B C
HUHAA BERKO
118.1 BOILER ROOM
GAS DATA MANUFACTURER
& MODEL NO.
TAG
CAPACITIES
FLOW GPM
RECOVERY
GPH TYPE INPUT
MBH
NOTES/ACCESSORIES SERVICE
DOMESTIC HOT WATER
NATURAL GAS
OUTPUT MBH
ELECTRICAL DATA
VOLTAGE FLA
120/1/60 11 LOCATION
GWH-2
29.1 1,746 1,350 27:1
TURNDOWN
NOTES AND ACCESSORIES DESIGNATION A. PROVIDE EXPANSION TANK B. NOT USED
C. POLYPROPYLENE VENT AND CPVC INTAKE D. T & P RELIEF VALVE, PIPE TO FLOOR DRAIN
E. CONDENSATE NEUTRALIZATION KIT F. MODULATING BURNER
G. PROVIDE DEDICATED ELECTRICAL CIRCUIT H. BACNET IP CONNECTION
GWH-1
NATURAL
GAS 120/1/60 11
AERCO INN 1350
AERCO INN 1350
LWT °F EWT °F
45 135
1,350 27:1 TURNDOWN RTU-1
& MODEL NO. TOTAL
CFM DAIKIN
RPS110D
RTU WELL
NORTH (200) 24,000
EAT DB/WB °F
82.0/70.5
COIL LAT DB/WB °F TOTAL
MBH
SENS.
MBH
1,230.8 717.2 54.7/54.7
TYPE
DX R410A RPM
1227
BHP (EACH)
25.72 ESP
IN. W.C.
1.25 QTY.
1
TOTAL CFM
O.A.
CFM
24,000 12,000 (50%) HP
(EACH)
30
AMBIENT DB °F
95 SEE PLAN
RTU-2
RTU-3
TOTAL CFM
20,000
RPM
671
BHP (EACH)
5.56 ESP
IN. W.C.
0.80 QTY.
1
HP (EACH)
7.50
GWH-3 NATURAL
GAS 120/1/60 11
AERCO
INN 1350 1,350 27:1
TURNDOWN DOMESTIC
HOT WATER DOMESTIC HOT WATER MANUFACTURER
& MODEL NO.
TAG
B-1
NOTES/ACCESSORIES LOCATION TYPE
COND.
BOILER 1,000
GAS DATA
NAT. GAS
TYPE INPUT MBH
OUTPUT MBH
ELECTRICAL DATA
VOLTAGE AMPS BOILER
HP (MAX)
120/1/60 13 27.0
NOTES AND ACCESSORIES DESIGNATION A. POLYPROPYLENE VENT AND CPVC INTAKE B. T & P RELIEF VALVE, PIPE TO FLOOR DRAIN C. CONDENSATE NEUTRALIZATION KIT
D. MODULATING BURNER
E. PROVIDE DEDICATED ELECTRICAL CIRCUIT
F. 140°F DISCHARGE, 120°F RETURN G. 91.5% EFFICIENCY @ MIN. INPUT H. 90.5% EFFICIENCY @ MAX. INPUT I. AUTO SEQUENCING VALVE
B-2 COND.
BOILER AERCO
BMK 1000 27.0 NAT. GAS 1,000 120/1/60 13 A B C D E F G H I
AERCO BMK 1000
BOILER ROOM
(118.1) 905 A B C D E F G H I
905 RTU-4
RTU WELL SOUTH (201)
UNIT LAT DB/WB °F
57.5/55.6
SIZE (IN.) L x W x H
WEIGHT (LBS.) MCA MOCP
VOLTAGE
234.5 250
460/3/60 451.0 x 99.0 x 97.0 18,500
10.1 13.5
NOTES AND ACCESSORIES DESIGNATION
A. UNIT SHALL COMPLY WITH ANSI/ASHRAE/IES STANDARD 90.1-2013 B. DOUBLE WALL CONSTRUCTION
C. HINGED DOUBLE WALL ACCESS DOORS
D. UNIT MOUNTED ON STRUCTURAL STEEL DUNNAGE ABOVE THE ROOF.
PROVIDE COMPLETE DOUBLE WALL CLOSURE OF BOTTOM OF UNIT AND DESIGN UNIT TO BE MOUNTED ON CONTINUOUS NEOPRENE PAD ON STEEL DUNNAGE.
E. BOTTOM DISCHARGE/BOTTOM RETURN
F. MODULATING GAS HEAT WITH STAINLESS STEEL HEAT EXCHANGER G. DISCHARGE AIR TEMPERATURE AND HUMIDITY CONTROL
H. FACTORY MOUNTED AND WIRED DISCONNECT SWITCH I. VARIABLE FREQUENCY DRIVE (VFD) SUPPLY & EXHAUST FAN J. FAN SPEED PRESSURE CONTROL
K. VARIABLE SPEED COMPRESSORS
L. 0-100% MODULATING ENTHALPY ECONOMIZER M. LOW LEAK OUTDOOR AIR/RETURN AIR DAMPERS N. MODULATING HOT GAS REHEAT HUMIDITY CONTROL O. UNIT POWERED 120V CONVENIENCE OUTLET
P. SLOPED STAINLESS STEEL DRAIN PAN Q. 2" MERV 8 PRE-FILTERS
R. 12" MERV 14 SECONDARY FILTERS
S. DIGITAL CONTROLS WITH FACTORY INSTALLED BACNET IP CARD T. SMOKE DETECTOR IN RETURN DUCT AND SUPPLY DUCT
U. SINGLE ZONE VAV OPERATION V. MULTI-ZONE VAV OPERATION W. SPACE CO2 O.A. CONTROL EAT
DB °F
54.7 INPUT
MBH
OUTPUT MBH
1,875.0 1,500.0
TYPE TOTAL
CFM
O.A.
CFM
24,000 12,000 (50%) O.A.
DB °F
-10.0 NATURAL
GAS
LAT DB °F
70.0 A B C D E F G H I J L M N O
P Q R S T U W
DAIKIN MPS050F
RTU WELL
NORTH (200) SEE PLAN 15,000 DX 582.7 425.5 84.2/69.5 58.3/57.6
R410A
1,415 14.9
2.25
1 15,000 7,500
(50%)
20 3 14,000 0.50 - 1 - 95 60.8/58.5 15,000 7,500 800.0 640.0 30.0 10.1 13.9 460/3/60 124.0 125 245.5 x 97.5 x 73.2 7,300
(50%) -10.0
NATURAL
GAS 69.3 A B C D E F G H I J K L M O
P Q R S T V
MANUFACTURER
& MODEL NO.
TAG
NOTES/ACCESSORIES AREA
SERVED
INDOOR UNIT FAN
ESP IN. WG
CFM WATTS
ELECTRICAL DATA
VOLTAGE MCA MOCP
PHYSICAL DATA
SIZE (IN.) WEIGHT (LBS) REFRIGERANT
MANUFACTURER TYPE
& MODEL NO.
TAG SIZE (IN.) WEIGHT (LBS)
INDOOR UNIT OUTDOOR UNIT
OUTDOOR UNIT INDOOR UNIT
AC-1 IDF
(026) 920 N/A 56 NOTE B 14.88 H x 46.06 W 46 A B C D E F G H
x 11.63 D R410A
ACCU-1 52.69 H x 41.31 W 211
x 14.19 D
NOTES AND ACCESSORIES DESIGNATION
A. FACTORY MOUNTED AND WIRED DISCONNECT SWITCH
B. INDOOR UNIT TO RECEIVE FIELD-WIRED POWER FROM OUTDOOR UNIT, WIRING PROVIDED BY MECH. & INSTALLED BY ELEC.
C. PROVIDE LINE SET FOR EXTENDED LENGTH OF PIPING (FIELD VERIFY LENGTH OF PIPING REQUIRED)
D. WIRED REMOTE THERMOSTAT
E. OUTDOOR UNIT MOUNTED ON ROOF EQUIPMENT RAILS PROVIDED BY MECHANICAL CONTRACTOR
F. LOW AMBIENT COOLING WIND BAFFLE KIT G. INDEPENDENTLY POWERED CONDENSATE PUMP H. PROVIDE WALL BRACKET FOR INDOOR UNIT I. ULTRA LOW AMBIENT TO -13° F
INDOOR UNIT COOLING
TOTAL MBH
EAT °F DB/WB SENSIBLE
MBH
36.0 25.2 80.0/67.0
AMBIENT
°F DB
MITSUBISHI 95.0 PKA-A36KA7
SEER EER
18.8 10.8
INDOOR UNIT TYPE
MITSUBISHI PUY-A36NKA7
AC-2 920 N/A 56 14.88 H x 46.06 W 46
x 11.63 D R410A
ACCU-2 52.69 H x 41.31 W 211
x 14.19 D
36.0 25.2 95.0 80.0/67.0
MITSUBISHI
PKA-A36KA7 MITSUBISHI 18.8 10.8
PUY-A36NKA7
HUMIDIFIER (LB/HR)
N/A ELECTRIC REHEAT (KW)
N/A N/A
N/A
WALL MOUNTED WALL MOUNTED
A B C D E F G H INDOOR EVAPORTOR OUTDOOR CONDENSER
208/1/60 25.0 30
208/1/60 25.0 30
NOTE B NOTE B
NOTE B NOTE B NOTE B
VOLTAGE MCA MOCP
IDF (013)
IDF (129)
775 N/A 56 NOTE B 14.88 H x 46.06 W 46 A B C D E F G H
x 11.63 D R410A
ACCU-3 37.13 H x 37.41 W 151
x 14.19 D
24.0 18.5 95.0 80.0/67.0 21.4 12.2
MITSUBISHI PUY-A24NHA7
920 N/A 56 14.88 H x 46.06 W 46
x 11.63 D R410A
ACCU-4 52.69 H x 41.31 W 211
x 14.19 D
36.0 25.2 95.0 80.0/67.0 18.8 10.8
MITSUBISHI PUY-A36NKA7
N/A
N/A N/A
N/A
WALL MOUNTED WALL MOUNTED
A B C D E F G H
208/1/60 19.0 25
208/1/60 25.0 30
NOTE B NOTE B
NOTE B NOTE B NOTE B ELEV MACHINE
(012) AC-3 MITSUBISHI
PKA-A24KA7
AC-4 MITSUBISHI PKA-A36KA7
TAG LOCATION SERVICE PUMP
TYPE GPM BOOST
(PSI)
VOLTAGE MOTOR
NOTES/ACCESSORIES
DWBP-1 DUPLEX
BOOSTER
210 34 460/3/60
HP
10
FLA
DOMESTIC WATER
INDIVIDUAL PUMP MANUFACTURER
& MODEL NO.
210 34 460/3/60
PUMP PACKAGE MANUFACTURER
& MODEL NO.
BELL & GOSSETT V2VHE6J10D1GCK
BELL & GOSSETT
46SV10NJ4F60 29
NOTES AND ACCESSORIES DESIGNATION A. PACKAGED PUMPING SYSTEM
B. VARIABLE FREQUENCY DRIVE FOR EACH PUMP C. REMOTE EXPANSION TANK
D. MOUNT ON NEOPRENE ISOLATION PAD E. PROVIDE FLEXIBLE CONNECTIONS F. PROVIDE CHECK VALVE ON DISCHARGE
G. PROVIDE DIELECTRIC FLANGES ON INLET AND DISCHARGE
H. SINGLE POINT POWER SUPPLY WITH DISCONNECT I. BACNET IP CONNECTION
J. 100% + STANDBY PUMP CONFIGURATION K. FULL SIZED VALVED BYPASS
A B C D E F G H I J K MANUFACTURER
& MODEL NO.
TAG LOCATION SERVICE
CFM ESP
IN. W.C.
MOTOR
NOTES/ACCESSORIES VOLTAGE
FAN
TYPE RPM HP
FAN
BHP DRIVE
TYPE
EF-1 ROOF NORTH LOCKER 7,000 2.5
ROOMS EXH 460/3/60
LOREN COOK
365 ACRUB-XP UPBLAST 948 4.78 7.5
CENTRIFUGAL
NOTES AND ACCESSORIES DESIGNATION A. 18" TALL INSULATED ROOF CURB
B. FACTORY MOUNTED AND WIRED DISCONNECT SWITCH
C. MOTORIZED DAMPER D. BIRDSCREEN
E. PROVIDE VFD FOR FAN
F. STAINLESS STEEL HOUSING & IMPELLER G. EC MOTOR - 0-10V VARIABLE SPEED H. LORENIZED COATING
I. INDUCTION DUTY RATED MOTOR WITH AEGIS GROUNDING RINGS
EF-2 1,700 1.5 1,115 0.721 1
EF-3 LOREN COOK BELT 750 0.75
120 ACRUB OR91 1,530
ROOF
ROOF UPBLAST
CENTRIFUGAL
460/3/60
120/1/60 0.271 1/3
A B C D E I
UPBLAST
CENTRIFUGAL A B C D
A B C D
MANUFACTURER
& MODEL NO.
TAG LOCATION SERVICE PUMP
TYPE GPM HEAD
(FT) VOLTAGE HP RPM
MOTOR
NOTES/ACCESSORIES
3/4 460/3/60 ELEVATOR #1
(E-1)
SUBMERSIBLE EFFLUENT GOULDS
WE0734H
ELEVATOR SUMP PUMP
SP-1 50 25 3,500
NOTES AND ACCESSORIES DESIGNATION A. 2" INLET AND DISCHARGE
B. PROVIDE CHECK VALVE ON DISCHARGE C. PACKAGED EQUIPMENT
D. ALARM PANEL WITH 3 FLOAT CONTROL SYSTEM E. HIGH LEVEL ALARM TO DDC
F. SINGLE POINT ELECTRICAL CONNECTION WITH FACTORY INSTALLED DISCONNECT
G. DUPLEX PUMP SYSTEM
H. PROVIDE 48" DIA. x 108" H BASIN I. PROVIDE 48" DIA. x 144" H BASIN
A B C D E F
MANUFACTURER
& MODEL NO.
TAG LOCATION SERVICE PUMP
TYPE GPM HEAD
(FT) VOLTAGE HP RPM
MOTOR
NOTES/ACCESSORIES
RCP-1 DOMESTIC
HOT WATER BELL & GOSSETT
ECOCIRC XL N 36-45 IN-LINE 10 20 120/1/60 1/6 3,377
NOTES AND ACCESSORIES DESIGNATION
A. STAINLESS STEEL LEAD-FREE CONSTRUCTION B. VARIABLE SPEED EC MOTOR
C. PRESSURE TAPS
D. VARIABLE FREQUENCY DRIVE (VFD) E. NON-OVERLOADING BRAKE HORSEPOWER F. NEOPRENE PAD
A B
HHWP-1 HEATING
HOT WATER BELL & GOSSETT
e-1510 1.5BC
BASE MOUNTED
CENTRIFUGAL 100 60 460/3/60
FLA
2.7
EF-4 MEN 124 &
WOMEN 122 LOREN COOK
225 SQN-HP CEILING INLINE BELT 1,700 1.50 1,033 460/3/60 0.955 1.5 B D H
5 460/3/60 JC STORAGE
(027)
SUBMERSIBLE GRINDER GOULDS
2GA81J4ED
EVENT LEVEL SANITARY
SP-2A 50 30 7.6 3,450 A B C D E F G H
SP-2B
SP-3A
SP-3B
BOILER ROOM (118.1)
BOILER ROOM (118.1) BOILER ROOM
(118.1) BOILER ROOM
(118.1)
HOT WATER COIL
LAT DB °F
MBH EAT
DB °F EWT °F GPM WPD
FT. H2O ROWS MANUFACTURER
& MODEL NO.
TAG AREA MOUNTING
SERVED
MOTOR
VOLTAGE TOTAL
FLA HP
(EACH) QTY.
NOTES/ACCESSORIES
LWT °F SIZE (IN.)
L x W x D
WEIGHT (LBS.) PHYSICAL DATA
CFM ESP
IN. W.C.
FAN
NOTES AND ACCESSORIES DESIGNATION A. FACTORY DISCONNECT
B. DIGITAL CONTROLS 5
460/3/60 SUBMERSIBLE
GRINDER GOULDS
2GA81J4ED
EVENT LEVEL
SANITARY 50 30 7.6 3,450 A B C D E F G H
HHWP-2 1
460/3/60 GOULDS
WS1034BHF
SUBSURFACE
DRAINAGE 50 30 3.8 3,500 A B C D E F G I
1 460/3/60 GOULDS
WS1034BHF
SUBSURFACE
DRAINAGE 50 30 3.8 3,500 A B C D E F G I
JC STORAGE (027) JC STORAGE
(027) JC STORAGE
(027)
SUBMERSIBLE EFFLUENT SUBMERSIBLE
EFFLUENT
BOILER ROOM (118.1) BOILER ROOM
(118.1) BOILER ROOM
(118.1)
IMPELLER SIZE (IN.)
HEATING HOT WATER
BASE MOUNTED
CENTRIFUGAL 9.0 100 60 460/3/60 5 1,466
-
BHP
0.15
2.37 BELL & GOSSETT
e-1510 1.5BC 9.0 5 2.37 1,466 C D E F
C D E F
BOILER ROOM (118.1)
CUH-1 TRANE RECESSED 72.9 70.0 120.8 140.0 7.3 10.43 4
WALL STAIR B
169 120.0 1200 0.17 2 120/1/60 0.22 7.0 78 x 30 x 10 275 A B
FFHB1201K
CUH-2 TRANE RECESSED 30.8 70.0 125 140.0 3.1 5.38 4
CEILING VESTIBULE
M136 120.0 385 - 1 120/1/60 0.22 3.88 51 x 30 x 10 150 A B
FFCB0601K
CUH-3 TRANE RECESSED 72.9 70.0 120.8 140.0 7.3 10.43 4
WALL CONCOURSE
134 120.0 1200 0.17 2 120/1/60 0.22 7.0 78 x 30 x 10 275 A B
FFHB1201K
CUH-4 TRANE RECESSED 72.9 70.0 120.8 140.0 7.3 10.43 4
STAIR A WALL 120.0 1200 0.17 2 120/1/60 0.22 7.0 78 x 30 x 10 275 A B
FFHB1201K MDF
(114)
ACCU-5 WALL MOUNTED
AC-5
INDOOR UNIT HEATING
TOTAL MBH
- - - - BELT
LOREN COOK
225 ACRUB-XP BELT
EF-5 SOUTH LOCKER
ROOMS EXH LOREN COOK
300 SQN-HP CEILING INLINE BELT 6,350 2.50 1,047 460/3/60 5.12 7.5 B C D E H I
EF-7 TRASH/SORTING
ROOF 118
SF-1 LOREN COOK ELEC 013.1
100SQN12D CEILING INLINE DIRECT 500 0.50 1,500 120/1/60 1/4 B G
SF-2 CEILING ELEC 010 INLINE 500 0.50 1,500 120/1/60 1/4 B G
SF-3 ELEC CLOSET
129.1
CEILING INLINE 500 0.50 1,500 120/1/60 1/4 B G
EF-6 LOREN COOK TOILET 224
GC-148 CEILING INLINE DIRECT 100 0.30 1,075 120/1/60 45 WATT - B C D
MEN 123 &
WOMEN 121
BELL & GOSSETT 10
46SV10NJ4F60 29
ACCESSORIES
NOTES AND ACCESSORIES DESIGNATION A. FACTORY DISCONNECT
B. REMOTE THERMOSTAT C. MOUNTING BRACKET
A B C D E F G H A B C D E F G H
A B C D E F G H EF-8
EF-9
DRYER BOOSTER FAN ENERVEX
BEF300
WSU/GL LAUNDRY (029)
BOX VENTILATOR
DIRECT
EC MOTOR 800 1.80 2,000 460/3/60 2.2 F
AMPS 1
DRYER BOOSTER FAN ENERVEX
BEF300
WSU/GL LAUNDRY (029)
BOX VENTILATOR
DIRECT
EC MOTOR 800 1.80 2,000 460/3/60 2.2 F
AMPS 1
AC-6 AMP STORAGE
(001) 920 N/A 56 NOTE B 14.88 H x 46.06 W 46 A B C D E F G H
x 11.63 D R410A
ACCU-6 52.69 H x 41.31 W 211
x 14.19 D
36.0 25.2 95.0 80.0/67.0
MITSUBISHI
PKA-A36KA7 MITSUBISHI 18.8 10.8
PUY-A36NKA7 WALL MOUNTED - N/A N/A NOTE B NOTE B 208/1/60 25.0 30
NOTES AND ACCESSORIES DESIGNATION TAG MANUFACTURER
& MODEL NO. SERVICE TYPE MOUNTING NECK SIZE OVERALL
SIZE CFM
48"L, 1-SLOT, 2.5"SLOT WIDTH 48"L, 1-SLOT, 3"SLOT WIDTH
26" x 22" 2260
R-3 TITUS GRILLE SURFACE 24" x 20"
350RL RETURN
12" OVAL LAY-IN
TITUS SLOT
FL-30JT SUPPLY
S-2
24" x 24" SEE PLAN SEE PLANS
LAY-IN DIFFUSER
TITUS
OMNI-AA SUPPLY
S-3 TITUS DIFFUSER SURFACE 18" x 6"
DL SUPPLY
S-1
STANDARD WHITE FINISH
ALL ALUMINUM CONSTRUCTION
JET THROW C
B A
20" x 8"
SUPPLY TITUS
DL DIFFUSER SURFACE 40" x 12" 42" x 14"
S-4
SUPPLY TITUS
300RL
12" x 8"
SURFACE DIFFUSER
14" x 10"
S-5
NOTES/ACCESSORIES
A A B
A C
A A
A SEE PLAN
SEE PLAN
SEE PLAN
0-300 16" x 10" 18" x 12" 301-700
S-6 TITUS SUPPLY
OMNI DIFFUSER LAY-IN SEE PLANS 24" x 24" SEE PLAN A
S-7 TITUS SUPPLY
FL-25 SLOT LAY-IN 10" OVAL SEE PLAN A F
RETURN TITUS
50F GRILLE LAY-IN 22" x 22"
R-1 24" x 24" - A B
RETURN TITUS
50F GRILLE LAY-IN 22" x 10"
R-2 24" x 12" - A B
EXHAUST TITUS
50F GRILLE LAY-IN SEE PLAN
E-1 24" x 24" - A B
EXHAUST TITUS
50F GRILLE LAY-IN SEE PLAN
E-2 12" x 12" - A B
920 N/A 56 14.88 H x 46.06 W 46
x 11.63 D
R410A 52.69 H x 41.31 W 211
x 14.19 D
36.0 25.2 95.0 80.0/67.0 18.8 10.8
MITSUBISHI
PUY-A36NKA7 N/A N/A NOTE B NOTE B NOTE B 208/1/60 25.0 30 A B C D E F G H
MITSUBISHI
PKA-A36KA7 -
EXHAUST TITUS
350RL GRILLE SURFACE 14" x 8"
E-3 16" x 10" 201-400 A
12" x 6" 14" x 8" 0-200
16" x 10" 18" x 12" 401-600 LOREN COOK
100 ACRUB OR80
UPBLAST
CENTRIFUGAL BELT 500 0.75 1,727 120/1/60 0.216 1/4 A B C D
EF-10 BOILER ROOM
118.1 LOREN COOK ROOF
120 ACRUB
UPBLAST
CENTRIFUGAL BELT 1000 0.75 1,725 120/1/60 0.264 1/3 A B C D
24,000 DX 1,230.8 717.2 82.0/70.5 54.7/54.7
R410A
1227 25.72
1.25
1 24,000 12,000
(50%)
30 95
SEE PLAN 1 20,000 0.80 671 7.50 5.56 57.5/55.6 24,000 12,000 1,875.0 1,500.0 54.7 10.1 13.5 460/3/60 234.5 250 451.0 x 99.0 x 97.0 18,500
(50%) -10.0
NATURAL
GAS 70.0 A B C D E F G H I J L M N O
P Q R S T U W
DAIKIN
MPS050F SEE PLAN 15,000 DX 582.7 425.5 84.2/69.5 58.3/57.6
R410A
1,415 14.9
2.25
1 15,000 7,500
(50%)
20 3 14,000 0.50 - 1 - 95 60.8/58.5 15,000 7,500 800.0 640.0 30.0 10.1 13.9 460/3/60 124.0 125 245.5 x 97.5 x 73.2 7,300
(50%) -10.0
NATURAL
GAS 69.3 A B C D E F G H I J K L M O
P Q R S T V RTU WELL
SOUTH (201) DAIKIN
RPS110D
24" x 12" 26" x 14" 1400
TITUS
350RL GRILLE SURFACE
T-1 16" x 10" 18" x 12" - A
RETURN TITUS
33RS GRILLE SURFACE 72" x 128"
R-4 74" x 130" 24000 D
D MATCH WALL COLOR. REFER TO ARCH. DRAWINGS FOR DETAILS TITUS
350RL GRILLE SURFACE
T-2 10" x 10" 12" x 12" - A
CUH-5 TRANE RECESSED 63.5 70.0 120.8 140.0 8.0 10.43 4
WALL 120.0 1200 0.17 2 120/1/60 0.22 7.0 61 x 30 x 10 275 A B
FFHB0801K VESTIBULE 290.05
TRANSFER TITUS
350RL GRILLE SURFACE
T-3 24" x 20" 26" x 22" - A
TRANSFER TRANSFER DIRECT
DIRECT
145 WATT
TURNDOWN
20:1 TURNDOWN
20:1 TURNDOWN FLOW
GPM
100
100 LOREN COOK
100SQN12D LOREN COOK
100SQN12D
145 WATT
145 WATT
29.1 1,746 45 135
29.1 1,746 45 135
RETURN TITUS
50F GRILLE LAY-IN 22" x 10"
R-5 24" x 12" - A B E
RETURN GRILLE LAY-IN 22" x 22"
R-6 TITUS 24" x 24" -
50F A B E
E PROVIDE ACOUSTIC BOOT
F HIGH THROW STORAGE 009.1
HYDRO 009.3
EF-11 DONOR SUITE
220 LOREN COOK
GC-422 CEILING INLINE DIRECT 200 0.50 1,355 120/1/60 85 WATT - B C D
48"L, 1-SLOT, 2.5"SLOT WIDTH
R-7 TITUS RETURN
FL-25 SLOT LAY-IN - SEE PLAN A
48"L, 1-SLOT, 2.5"SLOT WIDTH
E-4 TITUS EXHAUST
FL-25 SLOT LAY-IN 8" OVAL SEE PLAN A
EF-12 LOREN COOK CONCESSION 127
100SQN17DH CEILING INLINE DIRECT 325 0.75 1,708 120/1/60 0.105 1/4 B G
EF-13
SF-4
SF-5
CONCESSION 128 LOREN COOK
100SQN17DH CEILING INLINE DIRECT 325 0.75 1,708 120/1/60 0.105 1/4 B G
CONCESSION
CEILING 127 INLINE DIRECT 1400 1.00 1,519 120/1/60 3/4 B G
LOREN COOK
135SQN17DEC 0.49
CONCESSION
CEILING 128 INLINE DIRECT 1400 1.00 1,519 120/1/60 0.49 3/4 B G
RETURN TITUS
350RLF1 GRILLE SURFACE 24" x 24"
R-8 26" x 26" 1400 D G
G FILTERED RETURN.
RCP-2 DOMESTIC
HOT WATER BELL & GOSSETT
ECOCIRC 19-16 SUPPLY IN-LINE 5 10 120/1/60 60 WATTS 3,377 A B
(123.1) - -
RCP-3 DOMESTIC
HOT WATER BELL & GOSSETT
ECOCIRC 19-16 SUPPLY IN-LINE 5 10 120/1/60 60 WATTS 3,377 A B
(126) - -
PROVIDE 1" MERV 8 FILTER LOREN COOK
135SQN17DEC
16'
0' 32'
Scale: 1/16" = 1'-0"
PROFESSIONAL SEAL CONSULTANT
PROJECT
KEY PLAN
SHEET TITLE
PROJECT #
SHEET #
© 2018 ROSSETTI
B 8
7 6 5 4 3 2 1
A C D E F G H J K
8 7 6 5 4 3 2 1
30x42
:\Users\rzora\Documents\74670_WSGL_MECH_v20_r.zora.rvt 0/2020 12:06:48 PM
2018-034
Mechanical Schedules
M400
Wayne State University - Basketball Arena
1290 West Warren Avenue Detroit, Michigan 48202
# DESCRIPTION DATE
1 DESIGN DEVELOPMENT 11.21.2019
CONSTRUCTION DOCUMENT - PACKAGE 2 03.18.2020
ASI-002 06.03.2020
ASI-003 09.16.2020
ASI-004 09.29.2020