ISSUE

固网产品课程开发室

Training About DDF Survey

1.0

Auxiliary equipment Product Line

JUNE, 2005

(2)

华为机密,未经许可不得扩散 文档密级:内部公开

2

Contents

1.DDF(Digital Distribution Frame) Product Profile

2.Introduction to Huawei DDF Products

(Particular Description refer to Appendix)

(3)

华为机密,未经许可不得扩散 文档密级:内部公开

3

DDF Product Profile

1.DDF products in traditional communication network

SDH D W D M D W D M SDH SDH SDH SDH SDH SDH ODF ODF DWDM ODF ODF ODF ATM875 Optix W32 C&C08 ODF DDF EAST8000 DDF ODF DDF ODF PDH DDF DDF DDF

CATV ODF ODF

SDH C&C08 OptiX 155/622/2500/10G OptiX W32 OptiX METRO DDF DDF HONET METRO IP Copper cable C&C08 C&C08 HONET HONET OptiX 155/622/2500/10G OptiX 155/622/2500/10G OptiX 155/622/2500/10G OptiX 155/622/2500/10G MDF MDF MDF MDF MDF

(4)

华为机密,未经许可不得扩散 文档密级:内部公开

4

DDF Product Profile

2. Technical Terms of DDF Products

Digital

Distribution

Frame

(DDF)

DDF is a distribution and connection

device between digital multiplex, and

between a digital multiplex device

and a program-controlled exchange

device or a non-voice service device.

The loops in DDF formed by the

branch circuits of receiving and

transmitting ( also named as loop,

system or E1)

(2M/bit)

(5)

华为机密,未经许可不得扩散 文档密级:内部公开

5

Digital unit

Adopting balanced cable and the

connector unit with 120Ω

characteristic impedance.

DDF Product Profile

120Ω/120Ω

Balanced

connector

unit

75Ω/75Ω

Unbalanced

connector

unit

Functional assemblies

composed by numbers of E1

(also called unit).

Adopting RF coaxial cable and the

connector unit with 75Ω

(6)

华为机密,未经许可不得扩散 文档密级:内部公开 6

75Ω/120Ω

Impedance

transforming

connector unit

Transform the connecting mode of RF

coaxial cables with 75Ω characteristic

impedance to the mode of balanced

cables with 120Ω characteristic

impedance.

DDF Product Profile

Impedance

matching

The internal resistance of signal source is

the same with characteristic impedance of

the transmission line in quantity and phase;

or characteristic impedance of the

transmission line is the same with

impedance of load in quantity and phase;

which means respectively input or output

impedance matching of transmission line.

(7)

华为机密,未经许可不得扩散 文档密级:内部公开

7

1.6/5.6 RF

coaxial

connector

In fact, the RF coaxial connector is also a coaxial

transmission line, in which there are separable

electric contact unit, connecting unit and other

device for installation and termination.

DDF Product Profile

BNC RF coaxial

connector

(8)

华为机密,未经许可不得扩散 文档密级:内部公开 8

Contents

1.DDF Product Description

2.Introduction to Huawei DDF Products

Particular Description refer to Appendix

(9)

华为机密,未经许可不得扩散 文档密级:内部公开 9

Huawei DDF Product

75ΩDDF

MPX286-R

MPX272-FM600

MPX286-DR

120ΩDDF

MPX272-F

MPX272-R

MPX272-FM800

MPX272-CM600

MPX272-CM800

Open-type

frame

Enclosed

-type

cabinet

(10)

华为机密,未经许可不得扩散 文档密级:内部公开 10

75ΩDDF

MPX272-F1M600/

F2M600/F3M600

MPX272-F1/F2/F3

MPX272-F4/F5/F6

MPX272-F1M800/

F2M800/F3M800

Open-type

frame

Huawei DDF Product

19“ standard

double-side frame

19“ standard single-side

frame

Double-side cabling

management

800 width frame

Double-side cabling

management

600 width frame

(11)

华为机密,未经许可不得扩散 文档密级:内部公开 11

75ohmDDF

MPX272-C1M600/C2M600/C3M600

MPX272-C1M800/C2M800/C3M800

Enclosed

-type

cabinet

Huawei DDF Product

Double-side cabling

management

600 width cabinet

Double-side cabling

management

800 width cabinet

(12)

华为机密,未经许可不得扩散 文档密级:内部公开 12

Huawei DDF Product

MPX286-R

MPX286-DR

120ohmDDF

Open-type

frame

Single-side frame

Double-side frame

(13)

华为机密,未经许可不得扩散 文档密级:内部公开 13

Contents

1.DDF Product Description

2.Introduction to Huawei DDF Products

(Particular Description refer to Appendix)

(14)

华为机密,未经许可不得扩散 文档密级:内部公开

14

Engineering

surveys

Surveys of Huawei DDF Products

Net

height of

room &

height of

antistatic

floor

Impedance of DDF connector Capacity expansion project

coaxial

connector

Net height of room &height of room;

Height of raised floor;

length of grounding wire;

Dimension of product-frame/cabinet

(main height)

The outer diameter of cable sheath and

insulating layer should be known if the cable

model is unknown

; the connector is male:

connected the coaxial cable with inner

conductor by welding and with external

conductor by crimping;

Generally, the model of transmission side

differs from that of the exchange side;

Needed information , such as manufacture ,model

and specifications of existing DDF;

Ensure the equipment compatible and in accordance

with the existing ones ;

75 ΩOr

120Ω

(15)

华为机密,未经许可不得扩散 文档密级:内部公开

15

Surveys of Huawei DDF Products

µ¥Ôª »¤Ì ×

Í âµ¼Ì å

£¨ ±àÖ¯Ï ß£©

¾øÔµ ÄÚµ¼Ì å

½ÓµØÏ ß

ÖÐ¼Ì µçÀÂ75-2-1

µ¥Ôª »¤Ì ×

Ò»´ Î ±àÖ¯ ¶þ´ Î ±àÖ¯

¾øÔµ ÄÚµ¼Ì å

½ÓµØÏ ß

ÖÐ¼Ì µçÀÂ75-2-2

Structure of coaxial cable

Unit Jacket

Extennal Insulation Inner Conductor

Conductor

(Braid Shield)

Ground Wire

Trunk cable

Unit Jacket

First Braid Shield

Sencond

Braid

Shield

Insulation

Inner

Conductor

(16)

华为机密,未经许可不得扩散 文档密级:内部公开

16

Type of 75 Ohm Trunk Cable

Type of 75 Ohm

Trunk Cable

Solid Conductor-ø (mm)

Insulation-

ø(mm)

Jacket -ø (mm)

SYV-75-2-1

0.34

2.10

3.40

SYV-75-2-2

0.34

2.10

4.10

SYV-75-3-2

0.50

3.00

6.50

SYV-75-4-2

0.61

3.80

7.50

SFYZ75-2-1

0.25

1.45

2.57

SFYV75-2-1

0.25

1.45

2.6-2.8

SYFVZ-75-1-1

0.25

1.20

2.20

SYFVZP-75-1-1

0.25

1.20

2.20

(17)

华为机密,未经许可不得扩散 文档密级:内部公开

17

Surveys of Huawei DDF Products

Structure of coaxial connector

(18)

华为机密,未经许可不得扩散 文档密级:内部公开

18

Surveys of Huawei DDF Products

Specifications of coaxial connector

Coaxial

Connector

1.6/5.6

1.6/5.6

1.6/5.6

1.6/5.6

1.5/6.5

1.5/6.5

1.5/6.5

1.6/5.6

1.6/5.6

1.5/6.5

Trunk Cable

Non-standard

Diamet-er

Diamet-er

Diamet-er

Diamet-er

Diamet-er

(19)

华为机密,未经许可不得扩散 文档密级:内部公开

19

Specification Technique of SYFVZ-75-1-1 E1 Cable

Solid Conductor:

Ø 0.25 mm

Insulation:

Ø 1.20 mm

Shield: Ø 1.8 mm

Material: Polyvinyl Chloride (PVC)

Material: Polyethylene (PE)

Jacket: Ø 2.2 mm

Ø 2.2 mm

Material: Bare Copper

(20)

华为机密,未经许可不得扩散 文档密级:内部公开

20

Specification of JIS 2.5C-2V Coaxial Cable

Inner Conductor:

Ø 0.4 mm

Sheath: Ø 4.0mm

Insulation:

Ø 2.4 mm

Outer Conductor: Ø 3.0mm

Material: Black Polyvinyl Chloride(PVC)

Material: Polyethylene (PE)

Material: Copper Braid

Ø 4.0 mm

(21)

华为机密,未经许可不得扩散 文档密级:内部公开

21

Specification Technique of 2.5C-2V E1 Cable

S: Strand inner conductor

CS: Copper-clad steel wire inner conductor

V: Single braid outer conductor

W: Double braid outer conductor

2 : PE Insulation dielectric core

C :Characteristic impedance 75 ohm

D :Characteristic impedance 50 ohm

3 :Approx. diameter of dielectric core

(22)

华为机密,未经许可不得扩散 文档密级:内部公开

22

Specification Technique of SYFVZP-75-1-1 E1 Cable

Product Code

Descriptions

Conductor (Dia)

Insulation (Dia)

Shield (Dia)

Jacket (Dia)

2.5C-2V-04/96

2.5C-2V

0.4 mm BC

2.4 mm PE

0.12 mm x 96 BC

4.0 mm PVC

3C-2V-05/48

3C-2V

0.5 mm BC

3.0 mm PE

0.12 mm x 48 BC

5.0 mm PVC

3C-2V-05/96

3C-2V

0.5 mm BC

3.0 mm PE

0.12 mm x 96 BC

5.0 mm PVC

3C-2V-05/112

3C-2V

0.5 mm BC

3.0 mm PE

0.12 mm x112 BC

5.4 mm PVC

3C-2V-06/64

3C-2V

0.6 mm BC

3.0 mm PE

0.12 mm x 64 BC

5.0 mm PVC

3C-2V-06/96

3C-2V

0.6 mm BC

2.6 mm PE

0.12 mm x 96 BC

5.2 mm PVC

5C-2V-07/80

5C-2V

0.7 mm BC

4.5 mm PE

0.12 mm x 80 BC

6.9 mm PVC

5C-2V-07/96

5C-2V

0.7 mm BC

4.5 mm PE

0.12 mm x 96 BC

6.9 mm PVC

5C-2V-07/80

5C-2V

0.8 mm BC

4.5 mm PE

0.12 mm x 80 BC

6.9 mm PVC

5C-2V-07/96

5C-2V

0.8 mm BC

4.5 mm PE

0.12 mm x 96 BC

6.9 mm PVC

(23)

ISSUE

固网产品课程开发室

Training About ODF Survey

1.0

Auxiliary Equipment Product Line

JUNE,2005

(24)

华为机密,未经许可不得扩散 文档密级:内部公开

24

Contents

1. ODF (Optical-fiber Distribution Frame)

Product Profile

2. Introduction to Huawei ODF Product

(Particular Description refer to Appendix)

(25)

华为机密,未经许可不得扩散 文档密级:内部公开

25

ODF Product Profile

EAST8000

(26)

华为机密,未经许可不得扩散 文档密级:内部公开

26

2. Technical terms in ODF

Patch cord( Fiber jumper): a optical cable with adapter on both ends;

Tail fiber (Pigtail fiber): a optical cable with adapter on one end;

Adapter: is the devices that make optical connection between tail fibers and patch

cords. FC/PC adapters are usually used in ODF, SC/PC adapters are used in

some ODF.

ODF Product Profile

(27)

华为机密,未经许可不得扩散 文档密级:内部公开

27

ODF Product Profile (Function)

3.Introduce to functions of ODF product

⑴.

Fixing and protection function

Entry unit of

optical-fibers in C

series cabinet

Entry unit of

optical-fibers in R

series cabinet

(28)

华为机密,未经许可不得扩散 文档密级:内部公开

28

Splicing function (Splice

tray)

ODF Product Profile (Function)

⑶ Patch Function

(Patch panel)

(29)

华为机密,未经许可不得扩散 文档密级:内部公开

29

ODF Product

Profile

4. Protection function for fiber-core and bare fiber

5.Fiber storage function

Fiber-core protection

(Coiled protection sleeve)

Bare fiber protection

(30)

华为机密,未经许可不得扩散 文档密级:内部公开

30

ODF Product Profile

5.Connection of optical-fiber

ODF is mainly used for optical-fibers splicing, fixing, and connection. The connection modes

are given as following:

(31)

华为机密,未经许可不得扩散 文档密级:内部公开

31

ODF Product

Profile

⑵. Cross connection between optical cable and optical equipment

(32)

华为机密,未经许可不得扩散 文档密级:内部公开

32

ODF Product Profile

⑷. Connection between optical cables through adapter

(33)

华为机密,未经许可不得扩散 文档密级:内部公开

33

Contents

1.

ODF (optical-fiber Distribution Frame)

Product Profile

2. Introduction to Huawei ODF Product

(34)

华为机密,未经许可不得扩散 文档密级:内部公开

34

Introduce to Huawei ODF Product

ODF Product

Wall mount

Frame Series

Cabinet Series

Management

Frame Series

Box

GPX147-B

GPX147-R

GPX147-C,PX147-CZ

GPX147-F

GPX147-OMF

GPX147-E

(35)

华为机密,未经许可不得扩散 文档密级:内部公开

35

Contents

1.

ODF

(optical-fiber

Distribution

Frame)

Product Profile

2. Introduction to Huawei ODF Product

(Particular Description refer to appendix)

(36)

华为机密,未经许可不得扩散 文档密级:内部公开

36

Surveys of Huawei ODF Product

Engineering survey

Net height of room & height of antistatic floor Adapter model Capacity expansion project

 Height of room & net height of room ;

 height of raised floor;

 length of grounding wire;

 Dimension of frame/cabinet (main height)

Cable outlet mode ( upper outlet or lower outlet) ;

Adapter model;

Model of tail fiber, such as :

single tail fiber

(main), bundle tail fiber, Ribbon tail fiber

Needed information , such as manufacture ,model

and specifications of existing ODF;

 Ensure the equipment compatible and in

(37)

ISSUE

固网产品课程开发室

Training About MDF Survey

1.0

Auxiliary equipment Product Line

JUNE, 2005

(38)

华为机密,未经许可不得扩散 文档密级:内部公开

38

Contents

1. MDF (Main Distribution Frame)

Product Profile

2. Introduction to Huawei MDF

Products (Particular Description refer to

Appendix)

3. MDF Survey

(39)

华为机密,未经许可不得扩散 文档密级:内部公开

39

1. MDF products in traditional communication network

MDF Product Profile

IP HONET Trunk cable Optical-fiber D W D M D W D M Optical

transmissi-on

network ODF ODF DWDM ODF ODF ATM875 Optix W32 C&C08 ODF DDF EAST8000 DDF ODF DDF ODF DDF DDF DDF ODF ODF C&C08 Optix 155/622/2500/10G Optix W32 Optix METRO DDF DDF Copper cable C&C08 C&C08 HONET HONET Optix 155/622/2500/10G Optix 155/622/2500/10G Optix 155/622/2500/10G Optix 155/622/2500/10G

MDF

METRO

MDF

MDF

MDF

MDF

ODF CATV SDH SDH SDH SDH SDH SDH SDH SDH SDH JPX202 JPX202 JPX202 JPX202 JPX256

MDF

JPX256

(40)

华为机密,未经许可不得扩散 文档密级:内部公开

40

MDF Product Profile

2.MDF product in local connection

Main functions of MDF: connection, testing, protection, give alarm;

MDF is a connection and protection device in the local communication lines. One end

of MDF is connected with cables of local communication lines, another end is connected

to the subscribers lines of exchange . MDF have functions, such as connection with

internal and external lines cables, providing protection to lines, giving alarm and testing

lines.

Cross-connection

Cabinet

Cable Dis-

tribution

Box

Intra-office cable

Intra-office

Outside office

Main cables

MDF

Switch/

Exchange

Distribution cables

Subscriber

Termination

Equiptment

(41)

华为机密,未经许可不得扩散 文档密级:内部公开 41

FRAME

Cable side

terminal block

Alarm system

Exchange

side

terminal

block

MDF Product Profile

FRAME/CABINET

Cable side Terminal block Exchange side terminal block Protective unit Alarm system

Accessories

3. Structure of MDF

(42)

华为机密,未经许可不得扩散 文档密级:内部公开

42

MDF Product Profile

Exchange side terminal block

Cable side terminal block

(43)

华为机密,未经许可不得扩散 文档密级:内部公开

43

4. Correlative Definition for MDF

Main Distribution Frame (MDF):

is a device for connection and protection in the local

communication lines, the external lines of MDF connect the

copper-core twisted pair local

call cables

and the

internal lines connect the subscriber lines of telecom exchange or

access equipment .

Double-side

jumper MDF:

is composed of back-to-back horizontal and vertical rows, in

which the

horizontal rows are used to install exchange side

terminal blocks, and the

vertical rows are used to install cable side terminal blocks

.

Single-side

jumper MDF:

has both the jumper terminals of external and internal lines set

on the same side. A single-side jumper MDF is constructed by terminal frames and

corresponding horizontal and vertical wiring troughs, and can be lined in

multiple columns

.

The cable side terminal blocks and exchange side terminal blocks can be either

separately installed on different terminal frames or mixed installed on the same terminal

frames.

Cable side terminal block:

is used for terminating external cables and connecting

jumpers, and also

can be equipped with a protective unit

(generally known as vertical

terminal block, protective-testing connecting block, protective connecting block, external

cable terminal block , and so on ).

Exchange side terminal block:

is used for terminating intra-office cables and connecting

jumpers, and is able to implement test (generally known as horizontal terminal block,

testing connecting block, internal cable terminal connecting block , and so on ) .

Protective unit:

is used to prevent injury on the operator and damage on equipment

caused by

over-voltage and over-current

, also known as protector.

(44)

华为机密,未经许可不得扩散 文档密级:内部公开

44

5.Composing of MDF

MDF Product Profile

Frame:

can be sorted as double-sided frame, single-sided frame, and

wall-mounted frame according to cabling mode or installation mode.

Cabinet :

can be sorted as double-sided cabinet, single-sided cabinet, and

wall-mounted cabinet according to cabling mode or installation mode.

Cable side terminal block:

can be sorted as 10/20 pair terminal strip, 100/200

pair terminal block according to distribution capacity;

Can be sorted as welding connection type, wrapping connecting type, half IDC and

half wrapping connection type and IDC connection type according to connection

mode;

Can be sorted as stationary type, revolving type according to structure;

Exchange side terminal block:

can be sorted as 8/16 pair terminal strip, 128/256

pair terminal block according to distribution capacity;

Can be sorted as welding connection type, wrapping connecting type, half IDC and

half wrapping connection type and IDC connection type according to connection

mode;

Can be sorted as stationary type, revolving type according to structure;

Protective unit: can be sorted as gas discharge tube type and semiconductor

arrester type according to the type of discharge tube;

Can be sorted as non-self-recovery type and self-recovery type according to the

characteristic of over-current device.

(45)

华为机密,未经许可不得扩散 文档密级:内部公开

45

MDF Product Profile

6.Alarm system and Accessories

Ac

cess

ories

IDC tool

Testing plug

Open-circuit plug

Ladder

Alarm system

(46)

华为机密,未经许可不得扩散 文档密级:内部公开

46

(47)

华为机密,未经许可不得扩散 文档密级:内部公开

47

(48)

华为机密,未经许可不得扩散 文档密级:内部公开

48

7. Alarm system and Accessories of MDF

MDF Product Profile

Alarm system:

when

protective unit is plugged

in the cable side terminal block

properly, it connects with grounding terminal and alarm signal terminal

;

connect

every single-column alarm in series by using the wires in the back of MDF and

then connect to the general alarm, thus a completed alarm system is formed.

IDC (Insulation Displacement Connection) tool:

the special tool used to

terminate the cables to corresponding terminals, which can be sorted as wrapping

connection gun and IDC tool;

Testing plug:

is the plug-in unit used to testing internal and external lines;

Open-circuit plug:

is the plastic insulating unit used to disconnect the connection

of internal and external lines;

Ladder:

is used for maintenance, which can be sorted as movable ladder, slide

ladder and high stool according to structure

.

(49)

华为机密,未经许可不得扩散 文档密级:内部公开

49

Contents

1.

MDF (Main Distribution Frame)

Product Profile

2. Introduction to Huawei MDF

Products (

Particular Description

refer to Appendix)

3. MDF Surveys

(50)

华为机密,未经许可不得扩散 文档密级:内部公开

50

Introduction to Huawei MDF Products

1.JPX202 MDF series product

Double-sided frame F Single-sided frame SF Wall-mounted

frame GQ Cabinet B Cabinet C

Frame/

cabinet

Cable side

terminal block

FA8-72

Exchange side

terminal block

STO-83A

STO-83B

Protective

unit

FA9-81B

FA9-83

Alarm

IDC tool

Testing plug

CSS

Open-circuit

plug KLS

Ladder

JPX

202

MDF

(51)

华为机密,未经许可不得扩散 文档密级:内部公开

51

Introduction to Huawei MDF Products

2.Application of JPX202 MDF

Double-sided frame

F

: applicable to large office or equipment room

with sufficient space;

Wall-mounted frame

GQ

: applicable to enterprise or the office where

MDF need to be installed on walls;

Cabinet

B/C

: applicable to small capacity office or equipment where

there are distribution frames and other cabinet-type devices.

JP

X

202

MDF

Single-sided frame

SF

: applicable to small office or equipment room

(52)

华为机密,未经许可不得扩散 文档密级:内部公开

52

3.JPX256 MDF

(mainly applicable to access network ONU built-in type):

Introduction to Huawei MDF Products

Double-sided frame F

Single-sided

frame SF

Wall-mounted frame GQ Cabinet A

Frame/cabinet

Cable side

terminal block

FA8-123

Exchange side

terminal block

STO-128

Protective

unit

FA9-173

FA9-172

Alarm

IDC tool

Testing plug

CSS

Open-circuit

plug KLS

Ladder

JP

X

256

MDF

Using parts of JPX202 MDF

Proprietary

parts of JPX256 MDF

(53)

华为机密,未经许可不得扩散 文档密级:内部公开

53

4.Cable side terminal block FA8-123 and exchange side terminal block STO-128

FA8-123 is a 10-pair

cable side terminal block ;

The protective unit is unplugged from the front of

terminal block, and the visual alarm is display in front of

the terminal block too, which is convenient for

troubleshooting;

introduce cables from the back of the terminal block,

connect jumpers on both side , insert or remove

wires

with IDC tool in front the terminal blocks.

STO-128 is a 8-pair exchange side terminal block ;

introduce cables from the back of the terminal block,

connect jumpers on both side , insert or remove

wires

with IDC tool in front the terminal blocks.

Introduction to Huawei MDF Products

FA8-123

(54)

华为机密,未经许可不得扩散 文档密级:内部公开

54

5.Protective unit FA9-173 and FA9-172

FA9-173 gas discharge tube protective unit:

is the plug-in unit with over-current and

over-voltage protection functions and FS

alarm function , it can be used in

FA8-123

cable side terminal block.

FA9-172 semiconductor arrester

protective unit: is the plug-in unit with

over-current and over-voltage protection

functions and alarm function , it can be

used in FA8-123 cable side terminal block.

Introduction to Huawei MDF Products

FA9-173

(55)

华为机密,未经许可不得扩散 文档密级:内部公开

55

6.Testing cord and open-circuit plug

Testing cord: is the plug-in unit used to

test the internal and external lines. A pair

of clips are connected to the external

lines tester, the other pair of clips are

connected to internal lines tester or

telephone set.

Open-circuit plug: is a plastic insulating

unit used to disconnect the connection of

the internal or external lines on MDF. It

can be used in STO-128 exchange side

terminal blocks.

Introduction to Huawei MDF Products

JPX256-CSS

(56)

华为机密,未经许可不得扩散 文档密级:内部公开

56

Contents

1. MDF (Main Distribution

Frame) Product Profile

2. Introduction to Huawei MDF

Products (Particular Description

refer to Appendix)

3. MDF Survey

(57)

华为机密,未经许可不得扩散 文档密级:内部公开

57

Huawei MDF Product Surveys

1:

JPX202 MDF

Engineering surveys

Four major

points for

confirmation

Height of raised floor (mm)

Length of power cable for alarm

device(m)

Net height of Room/Shelter (mm)

(58)

华为机密,未经许可不得扩散 文档密级:内部公开

58

2: Net Height of Room and

Frame/Cabinet

Size

H×D

W n≠1

double-sided MDF

3000×1250

250×n

F1

2600×1250

250×n

F2

2200×1000

250×n

F3

1800×1000

250×n

Configure

according to

size

H×D

W

single-sided MDF

3000×600

500×n

SF1

2600×600

500×n

SF2

2200×600

500×n

SF3

1800×600

500×n

H×W×D

wall-mounted MDF

530×250×210

GQ100

560×500×210

GQ200

970×500×210

H×W×D

Cabinet

2200×660×600

B1

800×660×220

A3

Height

Room

Depth

Width

Net height of room (mm): the vertical

distance from the lower surface of roof board

to the upper surface of the floor board (or

the ground level if there is no floor board)

;

Cabling method: the cable entry of external

line and internal line is from the upper or

lower side of the

frame (cabinet);

for upper

cable entry, the height of

cabling trough

should be considered.

(59)

华为机密,未经许可不得扩散 文档密级:内部公开

59

Huawei MDF Product Surveys

Height of Steel Base

250

280

300

330

350

380

Steel Base

Room/Shelter

Height

Floor board

Ground

Net height of Room/shelter floor (mm):

vertical distance from the ground surface

to the upper surface of the floor board

3: Net Height of Room/Shelter Floor

Configure

according to

height

(60)

华为机密,未经许可不得扩散 文档密级:内部公开

60

Huawei MDF Product Survey

4: Length of Power Wire for Alarm device

MDF

wire

power supply of -48V

Shelter

Length of power wire for alarm

device(m): length of power wire from

(61)

华为机密,未经许可不得扩散 文档密级:内部公开

61

Huawei MDF Product Survey

5: Length of Grounding Cable

MDF

General

grounding bus

of room/shelter

50mm~2 yellow-green round fireproof cable is adopted in frame

25mm~2 yellow-green round fireproof cable is adopted in cabinet

Length of grounding

cable (m): length of

grounding cable from

protection grounding bus

of room/shelter to MDF

grounding bar

(62)

华为机密,未经许可不得扩散 文档密级:内部公开

62

References

Related documents

PRO6000 Electronic Switch Hardy Instruments HI 5800 Switch 5550 Mechanical Switch Vibration Switches Applications: · Motors · Pumps · Blowers · Centrifuges · Fans · Centrifugal Pumps

El artículo parte de la definición clásica sobre detección y análisis del ciclo de negocios propuesta en Burns and Mitchell 1946.. En una segunda parte adoptamos una alternativa

Personal features of proposer and responder participants (such as names or other cues that modify social distance) also influence behavior in the ultimatum game in the predicted

In this way, the current study fills a niche role in showing that, with regard to the particular attitudes and behaviors measured (i.e., coworker satisfaction,

Parental death can have a negative impact on children’s lives with changes in economic resources, and lead to change in residence, loss of contact with friends and neighbors,

For: NEBOSH International General Certificate in Occupational Health and Safety NEBOSH International Certificate in Construction Health and Safety. WEDNESDAY 7 MARCH 2012 2

Therefore, to follow through on the counsel of Bishop Kyrillos, the following recommendation is offered for motion and approval: “Be it approved that the College of Bishops of