• No results found

07 Transformer

N/A
N/A
Protected

Academic year: 2021

Share "07 Transformer"

Copied!
81
0
0

Loading.... (view fulltext now)

Full text

(1)
(2)

Causes of failure:

 Environment

 System

 Mal operation

 Wrong design

 Manufacture

 Material

 Maintenance

(3)

Transformer failures classification :

Transformer failures classification :

Transformer failures classification :

Transformer failures classification :

1. Internal failure

1. Internal failure

1. Internal failure

1. Internal failure

Causes: Causes: Causes: Causes:

➢ Winding & terminal faults

➢ Core faults

➢ Onload tap changer faults

➢ Overheating faults

(4)

2. External failure

2. External failure

2. External failure

2. External failure

Causes: Causes: Causes: Causes:

➢ Abnormal operating condition

Abnormal operating condition

Abnormal operating condition

Abnormal operating condition

➢ sustained or unclear faults

sustained or unclear faults

sustained or unclear faults

sustained or unclear faults

Transformer failures classification :

Transformer failures classification :

Transformer failures classification :

Transformer failures classification :

(5)

Vector Groups

Vector Groups

Vector Groups

Vector Groups

Phase displacement Phase displacement Phase displacement Phase displacement 0 00 0 Group 1 Group 1 Group 1 Group 1 Phase displacement Phase displacement Phase displacement Phase displacement 180 180 180 180 Group 2 Group 2 Group 2 Group 2

Lag phase displacement Lag phase displacement Lag phase displacement Lag phase displacement 30 30 30 30 Group 3 Group 3 Group 3 Group 3

Lead phase displacement Lead phase displacement Lead phase displacement Lead phase displacement 30 30 30 30 Group 4 Group 4 Group 4 Group 4 Yy0 Yy0Yy0 Yy0 Dd0 Dd0Dd0 Dd0 Zd0 Zd0Zd0 Zd0 Yy6 Yy6Yy6 Yy6 Dd6 Dd6Dd6 Dd6 Dz6 Dz6Dz6 Dz6 Yd1 Yd1Yd1 Yd1 Dy1 Dy1Dy1 Dy1 Yz1 Yz1Yz1 Yz1 Yd11 Yd11Yd11 Yd11 Dy11 Dy11Dy11 Dy11 Yz11 Yz11Yz11 Yz11

(6)

Fault current distribution

Earth fault on Transformer winding

V2 R T2 T1 V1 X Fig.3 If Fig.N

(7)

Fault current distribution

Therefore

Therefore Therefore

Therefore C.T.secondary current C.T.secondary current C.T.secondary current C.T.secondary current ( on primary side of transformer) =, X( on primary side of transformer) =, X( on primary side of transformer) =, X( on primary side of transformer) =, X2222

If differential setting =20% If differential setting =20% If differential setting =20% If differential setting =20% For relay For relay For relay

For relay operation Xoperation Xoperation Xoperation X2222 20% 20% 20% 20%

Thus X > 59 Thus X > 59 Thus X > 59 Thus X > 59% % % ie% ieieie. 59% of winding is unprotected.. 59% of winding is unprotected.. 59% of winding is unprotected.. 59% of winding is unprotected. Differential relay settingDifferential relay settingDifferential relay settingDifferential relay setting % of winding protected % of winding protected% of winding protected% of winding protected 10 10 10 10% 58%% 58%% 58%% 58% 20 20 20 20% 41%% 41%% 41%% 41% 30 30 30 30% 28%% 28%% 28%% 28% 40 40 40 40% 17%% 17%% 17%% 17% √ √ √ √3333 √ √√ √3333

>

>

>

>

(8)

 Differential

Basic Protection

 Restricted Earthfault

 Overfluxing

(9)

Differential Protection

 Where protection co-ordination is difficult /

not possible using time delayed elements

 For fast fault clearance

Applied

Works on Merz-price current comparison

principle

Relays with bias characteristic should only be

used

(10)

Differential Protection

Consideration for applying differential

protection

 Phase correction

 Filtering of zero sequence currents

 Ratio correction

 Magnetizing inrush during energisation

 Overfluxing

(11)

Differential Protection - Principle

R I diff = 0I diff = 0I diff = 0I diff = 0

• Nominal current through the protected equipmentNominal current through the protected equipmentNominal current through the protected equipmentNominal current through the protected equipment I Diff = 0 :

I Diff = 0 : I Diff = 0 :

(12)

Differential Protection

-Principle

• Through fault currentThrough fault currentThrough fault currentThrough fault current

I Diff = 0 : I Diff = 0 :I Diff = 0 :

I Diff = 0 : No trippingNo trippingNo trippingNo tripping

(13)

Differential Protection

-Principle

Tripping Tripping Tripping Tripping

Internal Fault

Internal Fault

Internal Fault

Internal Fault

I Diff = 0 : I Diff = 0 : I Diff = 0 : I Diff = 0 :

(14)

Biased differential protection

Fast operation

Adjustable characteristic

High through fault stability

CT ratio compensation

Magnetising inrush restraint

(15)

Biased differential protection

1 A 100/50 KV 100 / 1 200 / 1 1 A 0 A LOAD = 200 A

Why bias characteristic ?

OLTC Setting is at mid tap

R

(16)

Biased differential protection

100/50 KV

100 / 1 200 / 1

0.9 A 1 A

0.1 A

Relay pickup setting = O.2 A, So the Relay restrains

LOAD

= 200 A

OLTC SETTING IS AT 10%

Differential current = 0.1 A

(17)

Biased differential protection

100/50 KV

100 / 1 200 / 1

9 A 10 A

1 A

Relay Pickup Setting is O.2 A

OLTC SETTING IS AT 10%

2000 A

R

Operates

(18)

Role of Bias

Setting range (0.1 - 0.5)

Effective bias (x In) = I + I + I + I1 2 3 4 2

Differential current (x In) = I + I + I + I1 2 3 4 0 1 2 3 4 1 2 3

Operate

Restrain

80% Slop e 20% Slope

(19)

Based on Current operated relay with an external stabilising res Based on Current operated relay with an external stabilising res Based on Current operated relay with an external stabilising res

Based on Current operated relay with an external stabilising resistoristoristoristor

• Requires matched current transformers of low reactance design,Requires matched current transformers of low reactance design,Requires matched current transformers of low reactance design,Requires matched current transformers of low reactance design, typically class X or equivalent

typically class X or equivalent typically class X or equivalent typically class X or equivalent

• Equal CT ratiosEqual CT ratiosEqual CT ratiosEqual CT ratios

• NonNon----linear resistor may be required to limit voltage across relay NonNon linear resistor may be required to limit voltage across relay linear resistor may be required to limit voltage across relay linear resistor may be required to limit voltage across relay circuit during internal faults

circuit during internal faults circuit during internal faults circuit during internal faults

• Suitable for zones up to 200 Suitable for zones up to 200 ---- 300 metres (typically)Suitable for zones up to 200 Suitable for zones up to 200 300 metres (typically)300 metres (typically)300 metres (typically)

High Impedance Principle

(20)

High Impedance Principle

TC saturé M RCT ZM RCT 2RL 2RL A M ZM RCT 2RL 2RL RCT

(21)

High Impedance Principle

RCT ZM RCT ZM 2RL 2RL A M M

(22)

High Impedance Principle

RCT ZM RCT ZM 2RL 2RL TC saturé A M M

(23)

High Impedance Principle

RCT ZM RCT ZM 2RL 2RL A M M

(24)

High Impedance Principle

RCT ZM RCT ZM 2RL 2RL TC saturé A M M

(25)

High Impedance Principle

RCT ZM RCT ZM 2RL 2RL A M M

(26)

High Impedance Principle

RCT ZM RCT ZM 2RL 2RL TC sa tu ré A M M

(27)

High Impedance Principle

RCT ZM RCT ZM=0 2RL 2RL RCT 2RL 2RL RCT A M M

CT Saturation

False tripping

(28)

High Impedance Principle

RCT ZM RCT ZM=0 2RL 2RL TC saturé RCT 2RL 2RL RCT A RS M M

(29)

High Impedance Principle

RCT ZM RCT ZM=0 2RL 2RL TC saturé RCT 2RL 2RL RCT A RS M M Stabilising resistor Stabilising resistor Stabilising resistor Stabilising resistor

(30)

RCT ZM RCT ZM 2RL 2RL A RS M M RCT 2RL 2RL RCT Vset

(31)

RCT ZM RCT ZM=0 2RL 2RL RCT 2RL 2RL RCT A RS M M

Z

M

= 0 (CT "short circuited" ) Vset

(32)

A RCT ZM RCT ZM 2RL 2RL 2RL RCT 2RL RCT RS M M Vset

(33)

High Impedance Principle

2RL RCT 2RL RCT M Vset A RCT ZM RCT ZM 2RL 2RL RS M

(34)

High Impedance Principle

M A RCT ZM RCT ZM 2RL 2RL RS M Vset Metrosil MetrosilMetrosil

Metrosil may be may be may be may be required for voltage required for voltage required for voltage required for voltage

limitation limitation limitation limitation 2RL RCT 2RL RCT M

(35)

Restricted Earthfault

Protection

 Increased sensitivity for earth faults

 REF elements for each transformer winding

 CTs may be shared with differential element

 Uses high impedance principle

64

64 64

(36)

Restricted Earthfault Protection

P1 P1P1 P1 S1 S1S1 S1 P2 P2P2 P2 S2 S2 S2 S2 P1 P1 P1 P1 S1 S1S1 S1 P2 P2 P2 P2 S2 S2S2 S2 P1 P1 P1 P1 S1 S1S1 S1 P2 P2 P2 P2 S2 S2S2 S2 P1 P1 P1 P1 P2 P2 P2 P2 S1 S1 S1 S1 S2 S2 S2 S2

Stability level : usually maximum through fault level of tran Stability level : usually maximum through fault level of tran Stability level : usually maximum through fault level of tran

Stability level : usually maximum through fault level of transformersformersformersformer

REF Case I : Normal Condition

Under normal conditions no current flows thro’ Relay

So,

No Operation

(37)

Restricted Earthfault Protection

REF Case II : External Earth Fault

External earth fault - Current circulates between the phase & neutral CTs; no current thro’ the relay

(38)

Restricted Earthfault Protection

REF Case III : Internal Earth Fault

For an internal earth fault the unbalanced current flows thro’ the relay

(39)

Restricted Earthfault Protection

Restricted Earth Fault Protection Setting

Restricted Earth Fault Protection Setting

Restricted Earth Fault Protection Setting

Restricted Earth Fault Protection Setting

1MVA (5%) 11000V 415V 1600/1 RCT = 4.9Ω 80MVA RS 1600/1 RCT = 4.8Ω MCAG14 IS = 0.1 Amp 2 Core 7/0.67mm (7.41Ω/km) 100m Long

Setting will require Setting will require Setting will require Setting will require calculation of : calculation of : calculation of : calculation of : 1) 1) 1)

1) Setting stability Setting stability Setting stability Setting stability voltage (V voltage (V voltage (V voltage (VSSSS)))) 2) 2) 2)

2) Value of stabilising Value of stabilising Value of stabilising Value of stabilising resistor required resistor required resistor required resistor required 3) 3) 3)

3) Peak voltage Peak voltage Peak voltage Peak voltage developed by developed by developed by

developed by CTCTCTCT’’’’ssss for internal fault for internal fault for internal fault for internal fault

(40)

Restricted Earthfault Protection

Example : Earth fault calculation : Example : Earth fault calculation : Example : Earth fault calculation : Example : Earth fault calculation :----Using 80MVA base

Using 80MVA base Using 80MVA base Using 80MVA base

Source impedance = 1 p.u. Source impedance = 1 p.u. Source impedance = 1 p.u. Source impedance = 1 p.u.

Transformer impedance = 0.05 x 80 = 4 p.u. Transformer impedance = 0.05 x 80 = 4 p.u. Transformer impedance = 0.05 x 80 = 4 p.u. Transformer impedance = 0.05 x 80 = 4 p.u.

1 1 1 1

Total impedance = 14 p.u. Total impedance = 14 p.u. Total impedance = 14 p.u. Total impedance = 14 p.u. ∴

∴ ∴

∴ I1111 = 1 = 0.0714 p.u.= 1 = 0.0714 p.u.= 1 = 0.0714 p.u.= 1 = 0.0714 p.u. 14 14 14 14 Base current = 80 x 10 Base current = 80 x 10 Base current = 80 x 10 Base current = 80 x 106666 √ √ √ √3 x 4153 x 4153 x 4153 x 415 = 111296 Amps = 111296 Amps = 111296 Amps = 111296 Amps ∴ ∴ ∴ ∴ IFFFF = 3 x 0.0714 x 111296= 3 x 0.0714 x 111296= 3 x 0.0714 x 111296= 3 x 0.0714 x 111296 = 23840 Amps (primary) = 23840 Amps (primary) = 23840 Amps (primary) = 23840 Amps (primary) = 14.9 Amps (secondary) = 14.9 Amps (secondary)= 14.9 Amps (secondary) = 14.9 Amps (secondary) 1 P.U. 1 4 I1 4 I2 4 I0 1 1

(41)

Restricted Earthfault Protection

(1) (1) (1)

(1) Setting voltageSetting voltageSetting voltageSetting voltage V V V VSSSS = = I= = FFFF (R(R(R(RCTCTCTCT + 2+ 2+ 2+ 2RLRLRLRL)))) Assuming Assuming Assuming

Assuming ““““earthearthearthearth”””” CT saturates,CT saturates,CT saturates,CT saturates, R

R R

RCTCTCTCT = 4.8 ohms= 4.8 ohms= 4.8 ohms= 4.8 ohms 2

2 2

2RLRLRLRL = 2 x 100 x 7.41 x 10= 2 x 100 x 7.41 x 10= 2 x 100 x 7.41 x 10= 2 x 100 x 7.41 x 10----3333 = 1.482 ohms= 1.482 ohms= 1.482 ohms= 1.482 ohms ∴

∴ ∴

∴ Setting voltage = 14.9 (4.8 + 1.482)Setting voltage = 14.9 (4.8 + 1.482)Setting voltage = 14.9 (4.8 + 1.482)Setting voltage = 14.9 (4.8 + 1.482) = 93.6 Volts = 93.6 Volts = 93.6 Volts = 93.6 Volts (2) (2) (2)

(2) Stabilising Resistor (RStabilising Resistor (RStabilising Resistor (RStabilising Resistor (RSSSS)))) R R R RSSSS = = = = {Vs - [VA/(Is^2)]} /Is Where Where Where

Where ISSSS = relay current setting= relay current setting= relay current setting= relay current setting ∴

∴ ∴

(42)

Restricted Earthfault Protection

3) 3) 3)

3) Peak voltage = 2Peak voltage = 2√Peak voltage = 2Peak voltage = 2√√√2 2 √2 2 √√√VVVVKKKK (V(V(V(VFFFF ---- VVVVKKKK)))) V

VV

VFFFF = 14.9 x V= 14.9 x V= 14.9 x V= 14.9 x VSSSS = 14.9 x 936 = 13946 Volts= 14.9 x 936 = 13946 Volts= 14.9 x 936 = 13946 Volts= 14.9 x 936 = 13946 Volts

ISSSS

For For For

For ‘‘‘‘EarthEarthEarth’’’’ CT, VEarth CT, VCT, VCT, VKKKK = 1.4 x 236 = 330 Volts (from = 1.4 x 236 = 330 Volts (from = 1.4 x 236 = 330 Volts (from = 1.4 x 236 = 330 Volts (from graph) graph)graph) graph) ∴ ∴ ∴

∴ VVVVPEAKPEAKPEAKPEAK = 2= 2= 2= 2√√2 √√2 2 √2 √√√330 (13946 330 (13946 330 (13946 330 (13946 ---- 330)330)330)330) = 6kV = 6kV = 6kV = 6kV Thus, Thus, Thus,

(43)

Magnetising Inrush

• Transient condition - occurs when a

transformer is energised

• Normal operating flux of a transformer is close to saturation

level

• Residual flux can increase the mag-current

• In the case of three phase transformer, the point-on-wave at

switch-on differs for each phase and hence, also the inrush

currents

(44)

Transformer Magnetising Characteristic

Transformer Magnetising Characteristic

Transformer Magnetising Characteristic

Transformer Magnetising Characteristic

Twice Twice Twice Twice Normal Flux Normal Flux Normal Flux Normal Flux Normal NormalNormal Normal Flux FluxFlux Flux Normal Normal Normal Normal No Load Current No Load Current No Load Current No Load Current No Load Current at No Load Current at No Load Current at No Load Current at Twice Normal Flux Twice Normal FluxTwice Normal Flux Twice Normal Flux

(45)

Magnetising Inrush

m

Φ

Φ

Φ

Φ

+

SWITCH ON AT VOLTAGE

ZERO - NO RESIDUAL FLUX

m

Φ

Φ

Φ

Φ

-m

Φ

Φ

Φ

Φ

2

STEADY STATE

V

Φ

Φ

Φ

Φ

m I m I V

Φ

Φ

Φ

Φ

Inrush Current

(46)
(47)

Magnetising Inrush

Appears on one side of transformer only

- Seen as fault by differential relay

- Transient magnetising inrush could cause

relay to operate

Makes CT transient saturation

- Can make mal-operation of Zero sequence

relay at primary

Effect of magnetising current Effect of magnetising currentEffect of magnetising current Effect of magnetising current

(48)

P1 P1 P1 P1 S1 S1 S1 S1 P2 P2 P2 P2 S2 S2 S2 S2 P1 P1P1 P1 S1 S1S1 S1 P2 P2P2 P2 S2 S2 S2 S2 P1 P1P1 P1 S1 S1S1 S1 P2 P2P2 P2 S2 S2 S2 S2 IR IR IR IR IS IS IS IS IT ITIT IT

IR + IS + IT = 3Io = 0

IR + IS + IT = 3Io = 0

IR + IS + IT = 3Io = 0

IR + IS + IT = 3Io = 0

Magnetising Inrush

(49)

Effect of magnetising current Effect of magnetising currentEffect of magnetising current Effect of magnetising current

Example of Example of Example of

Example of disurbancedisurbancedisurbancedisurbance records records records records with detail

with detail with detail with detail

(50)

2nd (and 5th) harmonic restraint

2nd (and 5th) harmonic restraint

2nd (and 5th) harmonic restraint

2nd (and 5th) harmonic restraint

Makes relay immune to magnetising

inrush

Slow operation may result for genuine

transformer faults if CT saturation

occurs

(51)

Overfluxing - Basic Theory



Low frequency



High voltage



Geomagnetic disturbances

Causes

Overfluxing = V/F

(52)

Overfluxing - Basic Theory



Transient Overfluxing - Tripping of differential

element



Prolonged Overfluxing - Damage to transformers

Effects

m

Φ

Φ

Φ

Φ

2

Ie

m

Φ

Φ

Φ

Φ

V = kfΦ

Φ

Φ

Φ

(53)

Overfluxing - Condition

Differential element should be

blocked for transient overfluxing-+

25% OVERVOLTAGE CONDITION

Overfluxing waveform

contains very high 5th

Harmonic content

(54)

Φ

Φ

Φ

Φ

V

α

α

α

α

K

f

Trip and alarm outputs for clearing prolonged overfluxing

Alarm : Definite time characteristic to initiate corrective

action

Trip : IT or DT characteristic to clear overfluxing condition

(55)

Oil conservator Oil conservator Oil conservator Oil conservator Bucholz BucholzBucholz

Bucholz RelayRelayRelayRelay

(56)

Buchholz Relay Installation

Buchholz Relay Installation

Buchholz Relay Installation

Buchholz Relay Installation

5 x internal pipe 5 x internal pipe 5 x internal pipe 5 x internal pipe diameter (minimum) diameter (minimum) diameter (minimum) diameter (minimum) 3 x internal pipe 3 x internal pipe 3 x internal pipe 3 x internal pipe diameter (minimum) diameter (minimum) diameter (minimum) diameter (minimum) Transformer TransformerTransformer Transformer 76 mm typical 76 mm typical 76 mm typical 76 mm typical To oil conservator To oil conservator To oil conservator To oil conservator

BUCCHOLZ PROTECTION

(57)

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

Petcock Petcock Petcock Petcock From From From From transformer transformer transformer

transformer Trip bucketTrip bucketTrip bucketTrip bucket

To oil To oilTo oil To oil conservator conservatorconservator conservator Mercury switch Mercury switch Mercury switch Mercury switch Alarm bucket

Alarm bucketAlarm bucket

Alarm bucket

(58)

Accumulation of gaz

Accumulation of gaz

Accumulation of gaz

Accumulation of gaz

Oil

Oil

Oil

Oil Leakage

Leakage

Leakage

Leakage

Severe

Severe

Severe

Severe winding

winding

winding faults

winding

faults

faults

faults

Buccholz

Buccholz

Buccholz

Buccholz Protection Application

Protection Application

Protection Application

Protection Application

(59)

Interturn

Interturn

Interturn

Interturn faults

faults

faults

faults

Winding

Winding

Winding

Winding faults

faults

faults

faults to

to

to

to earth

earth

earth

earth with

with

with low

with

low

low

low

power (

power (

power (

power (fault

fault

fault close to

fault

close to

close to neutral

close to

neutral

neutral

neutral for

for

for

for

example

example

example

example))))

Accumulation of Gaz

Accumulation of Gaz

Accumulation of Gaz

Accumulation of Gaz

(60)

Inter-Turn Fault

Nominal turns ratio

Fault turns ratio Current ratio : 11,000 / 240 : 11,000 / 1 : 1 / 11,000 Shorted turn Load Primary Secondary CT CTCT CT E E E E

BUCCHOLZ PROTECTION

(61)

Nominal turns ratio

Fault turns ratio Current ratio : 11,000 / 240 : 11,000 / 1 : 1 / 11,000 CT CT CT CT E E E E Shorted turn Primary Secondary

Inter-Turn Fault

BUCCHOLZ PROTECTION

(62)

Interturn Fault Current / Number

of Turns Short Circuited

5 5 5

5 10101010 15151515 20202020 25252525

Turn short Turn shortTurn short

Turn short----circuited circuited circuited circuited (percentage of (percentage of (percentage of (percentage of winding) winding)winding) winding) Primary current Primary current Primary current Primary current (multiples of (multiples of (multiples of (multiples of rated current) rated current) rated current) rated current) Fault current Fault current Fault current Fault current (multiples of (multiples of (multiples of (multiples of rated current) rated current) rated current) rated current) 100 100 100 100 80 80 80 80 60 60 60 60 40 40 40 40 20 20 20 20

BUCCHOLZ PROTECTION

(63)

Interturn Fault Current / Number

of Turns Short Circuited

5 10 15 20 25 Primary current (multiples of rated current) Fault current (multiples of rated current) 100 80 60 40 20

Fault current very high

Primary phase current very low

Detected by Bucholz relay

Not detected by current

(64)

Interturn

Interturn

Interturn

Interturn faults

faults

faults

faults

Winding

Winding

Winding

Winding faults

faults

faults

faults to

to

to

to earth

earth

earth

earth with

with

with low

with

low

low

low

power (

power (

power (

power (fault

fault

fault close to

fault

close to

close to neutral

close to

neutral

neutral

neutral for

for

for

for

example

example

example

example))))

Accumulation of Gaz

Accumulation of Gaz

Accumulation of Gaz

Accumulation of Gaz

(65)

Earth Fault Current / Number of

Earth Fault Current / Number of

Earth Fault Current / Number of

Earth Fault Current / Number of

Turns Short Circuited

Turns Short Circuited

Turns Short Circuited

Turns Short Circuited

Turn short Turn short Turn short

Turn short----circuited circuited circuited circuited (percentage of

(percentage of (percentage of (percentage of

Primary current Primary currentPrimary current Primary current

Fault current Fault currentFault current Fault current 100 100100 100 80 80 80 80 60 60 60 60 40 40 40 40 20 20 20 20 multiples of multiples of multiples of multiples of max fault current max fault current max fault current max fault current

(66)

Operating

Operating

Operating

Operating principle

principle

principle

principle

Accumulation of Gaz

Accumulation of Gaz

Accumulation of Gaz

Accumulation of Gaz

(67)

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

Accumulation

Accumulation

Accumulation

Accumulation

of

of

of

of gaz

gaz

gaz

gaz

(68)

Accumulation

Accumulation

Accumulation

Accumulation

of

of

of

of gaz

gaz

gaz

gaz

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

(69)

Accumulation

Accumulation

Accumulation

Accumulation

of

of

of

of gaz

gaz

gaz

gaz

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

(70)

Color ColorColor

Color of of of of gazgazgazgaz indicates indicates indicates indicates the type of fault

the type of faultthe type of fault the type of fault

White or Yellow : White or Yellow : White or Yellow : White or Yellow : Insulation burnt Insulation burnt Insulation burnt Insulation burnt Grey : Grey : Grey : Grey : Dissociated oil Dissociated oil Dissociated oil Dissociated oil

Accumulation

Accumulation

Accumulation

Accumulation

of

of

of

of gaz

gaz

gaz

gaz

(71)

Accumulation

Accumulation

Accumulation

Accumulation

of

of

of

of gaz

gaz

gaz

gaz

Gaz GazGaz

Gaz can be extracted for can be extracted for can be extracted for can be extracted for detailled

detailleddetailled

detailled analysisanalysisanalysisanalysis

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

(72)

• After oil maintenance, false

tripping may occur because Oil

aeration

Effects of Oil Maintenance Effects of Oil Maintenance Effects of Oil Maintenance Effects of Oil Maintenance

Bucholz BucholzBucholz

Bucholz relay tripping inhibited during relay tripping inhibited during relay tripping inhibited during relay tripping inhibited during suitable period

suitable period suitable period suitable period

Need of electrical protection Need of electrical protectionNeed of electrical protection Need of electrical protection

BUCCHOLZ PROTECTION

(73)

Accumulation of gaz

Accumulation of gaz

Accumulation of gaz

Accumulation of gaz

Oil

Oil

Oil

Oil Leakage

Leakage

Leakage

Leakage

Severe

Severe

Severe

Severe winding

winding

winding faults

winding

faults

faults

faults

Bucholtz

Bucholtz

Bucholtz

Bucholtz Protection Application

Protection Application

Protection Application

Protection Application

(74)

Oil Leakage

Oil Leakage

Oil Leakage

Oil Leakage

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

(75)

Oil Leakage

Oil Leakage

Oil Leakage

Oil Leakage

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

(76)

Oil Leakage

Oil Leakage

Oil Leakage

Oil Leakage

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

(77)

Oil Leakage

Oil Leakage

Oil Leakage

Oil Leakage

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

(78)

Accumulation of gaz

Accumulation of gaz

Accumulation of gaz

Accumulation of gaz

Oil

Oil

Oil

Oil Leakage

Leakage

Leakage

Leakage

Severe

Severe

Severe

Severe winding

winding

winding faults

winding

faults

faults

faults

Buccholz

Buccholz

Buccholz

Buccholz Protection Application

Protection Application

Protection Application

Protection Application

(79)

Severe winding fault

Severe winding fault

Severe winding fault

Severe winding fault

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

(80)

Severe winding fault

Severe winding fault

Severe winding fault

Severe winding fault

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

(81)

Severe winding fault

Severe winding fault

Severe winding fault

Severe winding fault

Buchholz Relay

Buchholz Relay

Buchholz Relay

Buchholz Relay

References

Related documents

Test rig to be developed for testing of a wide range of transformers with a minimum of 3 to 5 tappings.Transformer test schematic developed with consultation of the

geometrical/analytical equations, the minimum required diameter of a resizable cylinder traversing through a curved pipe is calculated, which is a function of the

If minimum trench w idth is exceeded, and embedment compaction is required, pipe zone haunching should be compacted at least one pipe diameter from the pipe on both sides of

Style 54 Sleeves - Size specifi cations for Steel Pipe (500 psi) Nominal Size Steel (D) Outside Diameter (OD).. End Bolts No./ Diameter

The design minimum for pipe material greater than 30-inch diameter is to be ductile iron pipe; C-76 reinforced concrete; ASTM D3262 centrifugally cast fiberglass reinforced

Diametro base inferiore / Inferior base diameter 220 mm Diametro esterno tubo / External pipe diameter 80 mm Diametro interno tubo / Tube internal diameter 60 mm. Altezza /

Though various researchers investigated the influence of pipe diameter on the efficiency of DRP, the effect of variation in the internal diameter (ID) of the conduit or pipe on

The back-of-wall drain systems should be installed with a minimum 3-inch diameter perforated pipe placed a minimum of 4 inches below the top of the footing (preferably at the base