Causes of failure:
Environment
System
Mal operation
Wrong design
Manufacture
Material
Maintenance
Transformer failures classification :
Transformer failures classification :
Transformer failures classification :
Transformer failures classification :
1. Internal failure
1. Internal failure
1. Internal failure
1. Internal failure
Causes: Causes: Causes: Causes:➢ Winding & terminal faults
➢ Core faults
➢ Onload tap changer faults
➢ Overheating faults
2. External failure
2. External failure
2. External failure
2. External failure
Causes: Causes: Causes: Causes:➢ Abnormal operating condition
Abnormal operating condition
Abnormal operating condition
Abnormal operating condition
➢ sustained or unclear faults
sustained or unclear faults
sustained or unclear faults
sustained or unclear faults
Transformer failures classification :
Transformer failures classification :
Transformer failures classification :
Transformer failures classification :
Vector Groups
Vector Groups
Vector Groups
Vector Groups
Phase displacement Phase displacement Phase displacement Phase displacement 0 00 0 Group 1 Group 1 Group 1 Group 1 Phase displacement Phase displacement Phase displacement Phase displacement 180 180 180 180 Group 2 Group 2 Group 2 Group 2Lag phase displacement Lag phase displacement Lag phase displacement Lag phase displacement 30 30 30 30 Group 3 Group 3 Group 3 Group 3
Lead phase displacement Lead phase displacement Lead phase displacement Lead phase displacement 30 30 30 30 Group 4 Group 4 Group 4 Group 4 Yy0 Yy0Yy0 Yy0 Dd0 Dd0Dd0 Dd0 Zd0 Zd0Zd0 Zd0 Yy6 Yy6Yy6 Yy6 Dd6 Dd6Dd6 Dd6 Dz6 Dz6Dz6 Dz6 Yd1 Yd1Yd1 Yd1 Dy1 Dy1Dy1 Dy1 Yz1 Yz1Yz1 Yz1 Yd11 Yd11Yd11 Yd11 Dy11 Dy11Dy11 Dy11 Yz11 Yz11Yz11 Yz11
Fault current distribution
Earth fault on Transformer winding
V2 R T2 T1 V1 X Fig.3 If Fig.N
Fault current distribution
ThereforeTherefore Therefore
Therefore C.T.secondary current C.T.secondary current C.T.secondary current C.T.secondary current ( on primary side of transformer) =, X( on primary side of transformer) =, X( on primary side of transformer) =, X( on primary side of transformer) =, X2222
If differential setting =20% If differential setting =20% If differential setting =20% If differential setting =20% For relay For relay For relay
For relay operation Xoperation Xoperation Xoperation X2222 20% 20% 20% 20%
Thus X > 59 Thus X > 59 Thus X > 59 Thus X > 59% % % ie% ieieie. 59% of winding is unprotected.. 59% of winding is unprotected.. 59% of winding is unprotected.. 59% of winding is unprotected. Differential relay settingDifferential relay settingDifferential relay settingDifferential relay setting % of winding protected % of winding protected% of winding protected% of winding protected 10 10 10 10% 58%% 58%% 58%% 58% 20 20 20 20% 41%% 41%% 41%% 41% 30 30 30 30% 28%% 28%% 28%% 28% 40 40 40 40% 17%% 17%% 17%% 17% √ √ √ √3333 √ √√ √3333
>
>
>
>
Differential
Basic Protection
Restricted Earthfault
Overfluxing
Differential Protection
Where protection co-ordination is difficult /
not possible using time delayed elements
For fast fault clearance
Applied
∗
Works on Merz-price current comparison
principle
∗
Relays with bias characteristic should only be
used
Differential Protection
Consideration for applying differential
protection
Phase correction
Filtering of zero sequence currents
Ratio correction
Magnetizing inrush during energisation
Overfluxing
Differential Protection - Principle
R I diff = 0I diff = 0I diff = 0I diff = 0
• Nominal current through the protected equipmentNominal current through the protected equipmentNominal current through the protected equipmentNominal current through the protected equipment I Diff = 0 :
I Diff = 0 : I Diff = 0 :
Differential Protection
-Principle
• Through fault currentThrough fault currentThrough fault currentThrough fault current
I Diff = 0 : I Diff = 0 :I Diff = 0 :
I Diff = 0 : No trippingNo trippingNo trippingNo tripping
Differential Protection
-Principle
Tripping Tripping Tripping Tripping•
Internal Fault
Internal Fault
Internal Fault
Internal Fault
I Diff = 0 : I Diff = 0 : I Diff = 0 : I Diff = 0 :
Biased differential protection
•
Fast operation
•
Adjustable characteristic
•
High through fault stability
•
CT ratio compensation
•
Magnetising inrush restraint
Biased differential protection
1 A 100/50 KV 100 / 1 200 / 1 1 A 0 A LOAD = 200 AWhy bias characteristic ?
OLTC Setting is at mid tap
R
Biased differential protection
100/50 KV
100 / 1 200 / 1
0.9 A 1 A
0.1 A
Relay pickup setting = O.2 A, So the Relay restrains
LOAD
= 200 A
OLTC SETTING IS AT 10%
Differential current = 0.1 A
Biased differential protection
100/50 KV
100 / 1 200 / 1
9 A 10 A
1 A
Relay Pickup Setting is O.2 A
OLTC SETTING IS AT 10%
2000 A
R
Operates
Role of Bias
Setting range (0.1 - 0.5)
Effective bias (x In) = I + I + I + I1 2 3 4 2
Differential current (x In) = I + I + I + I1 2 3 4 0 1 2 3 4 1 2 3
Operate
Restrain
80% Slop e 20% SlopeBased on Current operated relay with an external stabilising res Based on Current operated relay with an external stabilising res Based on Current operated relay with an external stabilising res
Based on Current operated relay with an external stabilising resistoristoristoristor
• Requires matched current transformers of low reactance design,Requires matched current transformers of low reactance design,Requires matched current transformers of low reactance design,Requires matched current transformers of low reactance design, typically class X or equivalent
typically class X or equivalent typically class X or equivalent typically class X or equivalent
• Equal CT ratiosEqual CT ratiosEqual CT ratiosEqual CT ratios
• NonNon----linear resistor may be required to limit voltage across relay NonNon linear resistor may be required to limit voltage across relay linear resistor may be required to limit voltage across relay linear resistor may be required to limit voltage across relay circuit during internal faults
circuit during internal faults circuit during internal faults circuit during internal faults
• Suitable for zones up to 200 Suitable for zones up to 200 ---- 300 metres (typically)Suitable for zones up to 200 Suitable for zones up to 200 300 metres (typically)300 metres (typically)300 metres (typically)
High Impedance Principle
High Impedance Principle
TC saturé M RCT ZM RCT 2RL 2RL A M ZM RCT 2RL 2RL RCTHigh Impedance Principle
RCT ZM RCT ZM 2RL 2RL A M MHigh Impedance Principle
RCT ZM RCT ZM 2RL 2RL TC saturé A M MHigh Impedance Principle
RCT ZM RCT ZM 2RL 2RL A M MHigh Impedance Principle
RCT ZM RCT ZM 2RL 2RL TC saturé A M MHigh Impedance Principle
RCT ZM RCT ZM 2RL 2RL A M MHigh Impedance Principle
RCT ZM RCT ZM 2RL 2RL TC sa tu ré A M MHigh Impedance Principle
RCT ZM RCT ZM=0 2RL 2RL RCT 2RL 2RL RCT A M MCT Saturation
False trippingHigh Impedance Principle
RCT ZM RCT ZM=0 2RL 2RL TC saturé RCT 2RL 2RL RCT A RS M MHigh Impedance Principle
RCT ZM RCT ZM=0 2RL 2RL TC saturé RCT 2RL 2RL RCT A RS M M Stabilising resistor Stabilising resistor Stabilising resistor Stabilising resistorRCT ZM RCT ZM 2RL 2RL A RS M M RCT 2RL 2RL RCT Vset
RCT ZM RCT ZM=0 2RL 2RL RCT 2RL 2RL RCT A RS M M
Z
M
= 0 (CT "short circuited" ) VsetA RCT ZM RCT ZM 2RL 2RL 2RL RCT 2RL RCT RS M M Vset
High Impedance Principle
2RL RCT 2RL RCT M Vset A RCT ZM RCT ZM 2RL 2RL RS MHigh Impedance Principle
M A RCT ZM RCT ZM 2RL 2RL RS M Vset Metrosil MetrosilMetrosilMetrosil may be may be may be may be required for voltage required for voltage required for voltage required for voltage
limitation limitation limitation limitation 2RL RCT 2RL RCT M
Restricted Earthfault
Protection
Increased sensitivity for earth faults
REF elements for each transformer winding
CTs may be shared with differential element
Uses high impedance principle
64
64 64
Restricted Earthfault Protection
P1 P1P1 P1 S1 S1S1 S1 P2 P2P2 P2 S2 S2 S2 S2 P1 P1 P1 P1 S1 S1S1 S1 P2 P2 P2 P2 S2 S2S2 S2 P1 P1 P1 P1 S1 S1S1 S1 P2 P2 P2 P2 S2 S2S2 S2 P1 P1 P1 P1 P2 P2 P2 P2 S1 S1 S1 S1 S2 S2 S2 S2Stability level : usually maximum through fault level of tran Stability level : usually maximum through fault level of tran Stability level : usually maximum through fault level of tran
Stability level : usually maximum through fault level of transformersformersformersformer
REF Case I : Normal Condition
Under normal conditions no current flows thro’ Relay
So,
No Operation
Restricted Earthfault Protection
REF Case II : External Earth Fault
External earth fault - Current circulates between the phase & neutral CTs; no current thro’ the relay
Restricted Earthfault Protection
REF Case III : Internal Earth Fault
For an internal earth fault the unbalanced current flows thro’ the relay
Restricted Earthfault Protection
Restricted Earth Fault Protection Setting
Restricted Earth Fault Protection Setting
Restricted Earth Fault Protection Setting
Restricted Earth Fault Protection Setting
1MVA (5%) 11000V 415V 1600/1 RCT = 4.9Ω 80MVA RS 1600/1 RCT = 4.8Ω MCAG14 IS = 0.1 Amp 2 Core 7/0.67mm (7.41Ω/km) 100m Long
Setting will require Setting will require Setting will require Setting will require calculation of : calculation of : calculation of : calculation of : 1) 1) 1)
1) Setting stability Setting stability Setting stability Setting stability voltage (V voltage (V voltage (V voltage (VSSSS)))) 2) 2) 2)
2) Value of stabilising Value of stabilising Value of stabilising Value of stabilising resistor required resistor required resistor required resistor required 3) 3) 3)
3) Peak voltage Peak voltage Peak voltage Peak voltage developed by developed by developed by
developed by CTCTCTCT’’’’ssss for internal fault for internal fault for internal fault for internal fault
Restricted Earthfault Protection
Example : Earth fault calculation : Example : Earth fault calculation : Example : Earth fault calculation : Example : Earth fault calculation :----Using 80MVA base
Using 80MVA base Using 80MVA base Using 80MVA base
Source impedance = 1 p.u. Source impedance = 1 p.u. Source impedance = 1 p.u. Source impedance = 1 p.u.
Transformer impedance = 0.05 x 80 = 4 p.u. Transformer impedance = 0.05 x 80 = 4 p.u. Transformer impedance = 0.05 x 80 = 4 p.u. Transformer impedance = 0.05 x 80 = 4 p.u.
1 1 1 1
Total impedance = 14 p.u. Total impedance = 14 p.u. Total impedance = 14 p.u. Total impedance = 14 p.u. ∴
∴ ∴
∴ I1111 = 1 = 0.0714 p.u.= 1 = 0.0714 p.u.= 1 = 0.0714 p.u.= 1 = 0.0714 p.u. 14 14 14 14 Base current = 80 x 10 Base current = 80 x 10 Base current = 80 x 10 Base current = 80 x 106666 √ √ √ √3 x 4153 x 4153 x 4153 x 415 = 111296 Amps = 111296 Amps = 111296 Amps = 111296 Amps ∴ ∴ ∴ ∴ IFFFF = 3 x 0.0714 x 111296= 3 x 0.0714 x 111296= 3 x 0.0714 x 111296= 3 x 0.0714 x 111296 = 23840 Amps (primary) = 23840 Amps (primary) = 23840 Amps (primary) = 23840 Amps (primary) = 14.9 Amps (secondary) = 14.9 Amps (secondary)= 14.9 Amps (secondary) = 14.9 Amps (secondary) 1 P.U. 1 4 I1 4 I2 4 I0 1 1
Restricted Earthfault Protection
(1) (1) (1)
(1) Setting voltageSetting voltageSetting voltageSetting voltage V V V VSSSS = = I= = FFFF (R(R(R(RCTCTCTCT + 2+ 2+ 2+ 2RLRLRLRL)))) Assuming Assuming Assuming
Assuming ““““earthearthearthearth”””” CT saturates,CT saturates,CT saturates,CT saturates, R
R R
RCTCTCTCT = 4.8 ohms= 4.8 ohms= 4.8 ohms= 4.8 ohms 2
2 2
2RLRLRLRL = 2 x 100 x 7.41 x 10= 2 x 100 x 7.41 x 10= 2 x 100 x 7.41 x 10= 2 x 100 x 7.41 x 10----3333 = 1.482 ohms= 1.482 ohms= 1.482 ohms= 1.482 ohms ∴
∴ ∴
∴ Setting voltage = 14.9 (4.8 + 1.482)Setting voltage = 14.9 (4.8 + 1.482)Setting voltage = 14.9 (4.8 + 1.482)Setting voltage = 14.9 (4.8 + 1.482) = 93.6 Volts = 93.6 Volts = 93.6 Volts = 93.6 Volts (2) (2) (2)
(2) Stabilising Resistor (RStabilising Resistor (RStabilising Resistor (RStabilising Resistor (RSSSS)))) R R R RSSSS = = = = {Vs - [VA/(Is^2)]} /Is Where Where Where
Where ISSSS = relay current setting= relay current setting= relay current setting= relay current setting ∴
∴ ∴
Restricted Earthfault Protection
3) 3) 3)
3) Peak voltage = 2Peak voltage = 2√Peak voltage = 2Peak voltage = 2√√√2 2 √2 2 √√√VVVVKKKK (V(V(V(VFFFF ---- VVVVKKKK)))) V
VV
VFFFF = 14.9 x V= 14.9 x V= 14.9 x V= 14.9 x VSSSS = 14.9 x 936 = 13946 Volts= 14.9 x 936 = 13946 Volts= 14.9 x 936 = 13946 Volts= 14.9 x 936 = 13946 Volts
ISSSS
For For For
For ‘‘‘‘EarthEarthEarth’’’’ CT, VEarth CT, VCT, VCT, VKKKK = 1.4 x 236 = 330 Volts (from = 1.4 x 236 = 330 Volts (from = 1.4 x 236 = 330 Volts (from = 1.4 x 236 = 330 Volts (from graph) graph)graph) graph) ∴ ∴ ∴
∴ VVVVPEAKPEAKPEAKPEAK = 2= 2= 2= 2√√2 √√2 2 √2 √√√330 (13946 330 (13946 330 (13946 330 (13946 ---- 330)330)330)330) = 6kV = 6kV = 6kV = 6kV Thus, Thus, Thus,
Magnetising Inrush
• Transient condition - occurs when a
transformer is energised
• Normal operating flux of a transformer is close to saturation
level
• Residual flux can increase the mag-current
• In the case of three phase transformer, the point-on-wave at
switch-on differs for each phase and hence, also the inrush
currents
Transformer Magnetising Characteristic
Transformer Magnetising Characteristic
Transformer Magnetising Characteristic
Transformer Magnetising Characteristic
Twice Twice Twice Twice Normal Flux Normal Flux Normal Flux Normal Flux Normal NormalNormal Normal Flux FluxFlux Flux Normal Normal Normal Normal No Load Current No Load Current No Load Current No Load Current No Load Current at No Load Current at No Load Current at No Load Current at Twice Normal Flux Twice Normal FluxTwice Normal Flux Twice Normal Flux
Magnetising Inrush
m
Φ
Φ
Φ
Φ
+
SWITCH ON AT VOLTAGE
ZERO - NO RESIDUAL FLUX
m
Φ
Φ
Φ
Φ
-m
Φ
Φ
Φ
Φ
2
STEADY STATE
VΦ
Φ
Φ
Φ
m I m I VΦ
Φ
Φ
Φ
Inrush Current
Magnetising Inrush
•
Appears on one side of transformer only
- Seen as fault by differential relay
- Transient magnetising inrush could cause
relay to operate
•
Makes CT transient saturation
- Can make mal-operation of Zero sequence
relay at primary
Effect of magnetising current Effect of magnetising currentEffect of magnetising current Effect of magnetising current
P1 P1 P1 P1 S1 S1 S1 S1 P2 P2 P2 P2 S2 S2 S2 S2 P1 P1P1 P1 S1 S1S1 S1 P2 P2P2 P2 S2 S2 S2 S2 P1 P1P1 P1 S1 S1S1 S1 P2 P2P2 P2 S2 S2 S2 S2 IR IR IR IR IS IS IS IS IT ITIT IT
IR + IS + IT = 3Io = 0
IR + IS + IT = 3Io = 0
IR + IS + IT = 3Io = 0
IR + IS + IT = 3Io = 0
Magnetising Inrush
Effect of magnetising current Effect of magnetising currentEffect of magnetising current Effect of magnetising current
Example of Example of Example of
Example of disurbancedisurbancedisurbancedisurbance records records records records with detail
with detail with detail with detail
2nd (and 5th) harmonic restraint
2nd (and 5th) harmonic restraint
2nd (and 5th) harmonic restraint
2nd (and 5th) harmonic restraint
•
Makes relay immune to magnetising
inrush
•
Slow operation may result for genuine
transformer faults if CT saturation
occurs
Overfluxing - Basic Theory
Low frequency
High voltage
Geomagnetic disturbances
Causes
Overfluxing = V/F
Overfluxing - Basic Theory
Transient Overfluxing - Tripping of differential
element
Prolonged Overfluxing - Damage to transformers
Effects
m
Φ
Φ
Φ
Φ
2
Ie
m
Φ
Φ
Φ
Φ
V = kfΦ
Φ
Φ
Φ
Overfluxing - Condition
Differential element should be
blocked for transient overfluxing-+
25% OVERVOLTAGE CONDITION
Overfluxing waveform
contains very high 5th
Harmonic content
Φ
Φ
Φ
Φ
V
α
α
α
α
K
f
•
Trip and alarm outputs for clearing prolonged overfluxing
•
Alarm : Definite time characteristic to initiate corrective
action
•
Trip : IT or DT characteristic to clear overfluxing condition
Oil conservator Oil conservator Oil conservator Oil conservator Bucholz BucholzBucholz
Bucholz RelayRelayRelayRelay
Buchholz Relay Installation
Buchholz Relay Installation
Buchholz Relay Installation
Buchholz Relay Installation
5 x internal pipe 5 x internal pipe 5 x internal pipe 5 x internal pipe diameter (minimum) diameter (minimum) diameter (minimum) diameter (minimum) 3 x internal pipe 3 x internal pipe 3 x internal pipe 3 x internal pipe diameter (minimum) diameter (minimum) diameter (minimum) diameter (minimum) Transformer TransformerTransformer Transformer 76 mm typical 76 mm typical 76 mm typical 76 mm typical To oil conservator To oil conservator To oil conservator To oil conservator
BUCCHOLZ PROTECTION
Buchholz Relay
Buchholz Relay
Buchholz Relay
Buchholz Relay
Petcock Petcock Petcock Petcock From From From From transformer transformer transformertransformer Trip bucketTrip bucketTrip bucketTrip bucket
To oil To oilTo oil To oil conservator conservatorconservator conservator Mercury switch Mercury switch Mercury switch Mercury switch Alarm bucket
Alarm bucketAlarm bucket
Alarm bucket
Accumulation of gaz
Accumulation of gaz
Accumulation of gaz
Accumulation of gaz
Oil
Oil
Oil
Oil Leakage
Leakage
Leakage
Leakage
Severe
Severe
Severe
Severe winding
winding
winding faults
winding
faults
faults
faults
Buccholz
Buccholz
Buccholz
Buccholz Protection Application
Protection Application
Protection Application
Protection Application
Interturn
Interturn
Interturn
Interturn faults
faults
faults
faults
Winding
Winding
Winding
Winding faults
faults
faults
faults to
to
to
to earth
earth
earth
earth with
with
with low
with
low
low
low
power (
power (
power (
power (fault
fault
fault close to
fault
close to
close to neutral
close to
neutral
neutral
neutral for
for
for
for
example
example
example
example))))
Accumulation of Gaz
Accumulation of Gaz
Accumulation of Gaz
Accumulation of Gaz
Inter-Turn Fault
Nominal turns ratio
Fault turns ratio Current ratio : 11,000 / 240 : 11,000 / 1 : 1 / 11,000 Shorted turn Load Primary Secondary CT CTCT CT E E E E
BUCCHOLZ PROTECTION
Nominal turns ratio
Fault turns ratio Current ratio : 11,000 / 240 : 11,000 / 1 : 1 / 11,000 CT CT CT CT E E E E Shorted turn Primary Secondary
Inter-Turn Fault
BUCCHOLZ PROTECTION
Interturn Fault Current / Number
of Turns Short Circuited
5 5 5
5 10101010 15151515 20202020 25252525
Turn short Turn shortTurn short
Turn short----circuited circuited circuited circuited (percentage of (percentage of (percentage of (percentage of winding) winding)winding) winding) Primary current Primary current Primary current Primary current (multiples of (multiples of (multiples of (multiples of rated current) rated current) rated current) rated current) Fault current Fault current Fault current Fault current (multiples of (multiples of (multiples of (multiples of rated current) rated current) rated current) rated current) 100 100 100 100 80 80 80 80 60 60 60 60 40 40 40 40 20 20 20 20
BUCCHOLZ PROTECTION
Interturn Fault Current / Number
of Turns Short Circuited
5 10 15 20 25 Primary current (multiples of rated current) Fault current (multiples of rated current) 100 80 60 40 20
Fault current very high
Primary phase current very low
Detected by Bucholz relay
Not detected by current
Interturn
Interturn
Interturn
Interturn faults
faults
faults
faults
Winding
Winding
Winding
Winding faults
faults
faults
faults to
to
to
to earth
earth
earth
earth with
with
with low
with
low
low
low
power (
power (
power (
power (fault
fault
fault close to
fault
close to
close to neutral
close to
neutral
neutral
neutral for
for
for
for
example
example
example
example))))
Accumulation of Gaz
Accumulation of Gaz
Accumulation of Gaz
Accumulation of Gaz
Earth Fault Current / Number of
Earth Fault Current / Number of
Earth Fault Current / Number of
Earth Fault Current / Number of
Turns Short Circuited
Turns Short Circuited
Turns Short Circuited
Turns Short Circuited
Turn short Turn short Turn short
Turn short----circuited circuited circuited circuited (percentage of
(percentage of (percentage of (percentage of
Primary current Primary currentPrimary current Primary current
Fault current Fault currentFault current Fault current 100 100100 100 80 80 80 80 60 60 60 60 40 40 40 40 20 20 20 20 multiples of multiples of multiples of multiples of max fault current max fault current max fault current max fault current
Operating
Operating
Operating
Operating principle
principle
principle
principle
Accumulation of Gaz
Accumulation of Gaz
Accumulation of Gaz
Accumulation of Gaz
Buchholz Relay
Buchholz Relay
Buchholz Relay
Buchholz Relay
Accumulation
Accumulation
Accumulation
Accumulation
of
of
of
of gaz
gaz
gaz
gaz
Accumulation
Accumulation
Accumulation
Accumulation
of
of
of
of gaz
gaz
gaz
gaz
Buchholz Relay
Buchholz Relay
Buchholz Relay
Buchholz Relay
Accumulation
Accumulation
Accumulation
Accumulation
of
of
of
of gaz
gaz
gaz
gaz
Buchholz Relay
Buchholz Relay
Buchholz Relay
Buchholz Relay
Color ColorColor
Color of of of of gazgazgazgaz indicates indicates indicates indicates the type of fault
the type of faultthe type of fault the type of fault
White or Yellow : White or Yellow : White or Yellow : White or Yellow : Insulation burnt Insulation burnt Insulation burnt Insulation burnt Grey : Grey : Grey : Grey : Dissociated oil Dissociated oil Dissociated oil Dissociated oil
Accumulation
Accumulation
Accumulation
Accumulation
of
of
of
of gaz
gaz
gaz
gaz
Accumulation
Accumulation
Accumulation
Accumulation
of
of
of
of gaz
gaz
gaz
gaz
Gaz GazGaz
Gaz can be extracted for can be extracted for can be extracted for can be extracted for detailled
detailleddetailled
detailled analysisanalysisanalysisanalysis
Buchholz Relay
Buchholz Relay
Buchholz Relay
Buchholz Relay
• After oil maintenance, false
tripping may occur because Oil
aeration
Effects of Oil Maintenance Effects of Oil Maintenance Effects of Oil Maintenance Effects of Oil Maintenance
Bucholz BucholzBucholz
Bucholz relay tripping inhibited during relay tripping inhibited during relay tripping inhibited during relay tripping inhibited during suitable period
suitable period suitable period suitable period
Need of electrical protection Need of electrical protectionNeed of electrical protection Need of electrical protection