• No results found

generator protection

N/A
N/A
Protected

Academic year: 2021

Share "generator protection"

Copied!
50
0
0

Loading.... (view fulltext now)

Full text

(1)

LESSON

LESSON

 –

 –

25

25

GENERATOR PROTECTION

GENERATOR PROTECTION

(2)

OUTLINE OF THE LESSON

OUTLINE OF THE LESSON

1. STATOR WINDING PROTECTION 1. STATOR WINDING PROTECTION 2. OVERLOAD PROTECTION

2. OVERLOAD PROTECTION

3. OVER CURRENT PROTECTION 3. OVER CURRENT PROTECTION 4. OVER VOLTAGE PROTECTION 4. OVER VOLTAGE PROTECTION

(3)

OUTLINE OF THE LESSON

OUTLINE OF THE LESSON

1. STATOR WINDING PROTECTION 1. STATOR WINDING PROTECTION 2. OVERLOAD PROTECTION

2. OVERLOAD PROTECTION

3. OVER CURRENT PROTECTION 3. OVER CURRENT PROTECTION 4. OVER VOLTAGE PROTECTION 4. OVER VOLTAGE PROTECTION

(4)

STATOR WINDING PROTECTION

STATOR WINDING PROTECTION

 The most satisfactory method ofThe most satisfactory method of

protecting an alternator stator is the protecting an alternator stator is the Merz-Price circulating current

Merz-Price circulating current technique

technique

 Both longitudinal and transverseBoth longitudinal and transverse

differential; protection systems are differential; protection systems are used

(5)

LONGITUDINAL DIFFERENTIAL

LONGITUDINAL DIFFERENTIAL

PROTECTION OF DIRECT

PROTECTION OF DIRECT

CONNECTE

(6)

Phase and earth fault

Phase and earth fault protectionprotection system

(7)

PROTECTION SCHEME FOR

EARTH FAULTS ONLY

(8)
(9)

This arrangement is likely to be used

only when the individual phases are not brought out at the neutral end.

(10)

Example: A 6600V, 4000KVA star

connected alternator has a reactance of 2 ohms/phase and negligible

resistance. It is protected by Merz-Price longitudinal differential protection which operates when out of balance current

exceeds 30% of the full load current. If Rn= 7.5 ohms, Determine % of winding which remains unprotected. Show that the effect of the generator reactance can

(11)

 The portion of the stator winding

which remains unprotected following earth fault depends on earthing

resistance and relay setting

 Virtually the whole winding is

protected against interphase faults since no limiting impedance is

(12)

 Longitudinal differential protection System does not detect interturn faults

(13)

EARTH FAULT PROTECTION FOR

THE COMPLETE STATOR

WINDING

The earth fault protection schemes

(percentage bias differential protection or neutral overcurrent relay or voltage relay) protect a certain portion of the

winding leaving a part of winding at the neutral end unprotected.

(14)

For large machines there is a

requirement for detection of earth fault occurring anywhere in the

(15)

Two different schemes are available for complete protection of the stator

winding:

1. Low frequency injection scheme.

(16)

LOW FREQUENCY INJECTION

SCHEME

 In this scheme a sub harmonic voltage is applied via an injection transformer

connected in series with the neutral earthing resistance.

(17)

A relay which monitors the sub harmonic current is arranged to

operate when current increases due to an earth fault on the stator winding.

(18)

This scheme provides effective coverage of the complete stator

winding. However, the cost of the implementation tends to be high due to the cost of the injection equipment.

(19)

THIRD HARMONIC VOLTAGE

SCHEME

This scheme utilizes the third harmonic voltage produced by non linearities

(20)

Under healthy conditions, this voltage causes the circulation of third harmonic capacitive charging currents resulting in third harmonic voltage appearing

between the neutral of the generator and ground.

(21)

The value of the voltage will depend on 1. The relative values of the impedance

of the earthing devices.

2. The capacitance to earth of the stator

windings, the capacitance to earth of the busbars, cables and transformer windings connected to the generator.

(22)

When fault occurs close to the

neutral of the generator, the third harmonic voltage between the

neutral and ground will reduce to near zero-value.

(23)

For high resistance earthed

generators, measurement of this

voltage provides a clear discrimination between the faults in the neutral

region of the stator winding and healthy conditions.

(24)

Fig given below shows the variation of

a) The third harmonic voltage during fault and

b) The pre-fault third harmonic voltage as the function of earth fault position.

(25)
(26)

It may be noted that the pre-fault third harmonic voltage depends on the

power output of the machines.

Fig shows the band over which the prefault voltage may vary.

(27)

The third harmonic voltage developed by faults at a distance x to y from the neutral of the generator lies in the

same range as produced by pre-fault operating condition.

(28)

 Thus the location of fault anywhere from x to y represents a blind zone.

 The relay operates if the magnitude of the third harmonic voltage is

a) Less than OA/or b) more than OB

(29)
(30)

The problem of blind-zone is overcome by providing two protection system

operating simultaneously

1) The one system monitors the fundamental component of the neutral voltage.

2) Monitors the third harmonic voltage of neutral

(31)

The fig. shows relative operation zones of complementary stator earth fault relay elements

(32)

With the combined protection system, each relay element covers the blind

zone of the other and the combined protection system will detect earth faults anywhere on stator winding

(33)

INTERTURN FAULT PROTECTION

OF THE

(34)

INTER-TURN PROTECTION BY

ZERO SEQUENCE VOLTAGE

MEASUREMENT

 Interturn faults in a generator with a single winding can be detected by observing the zero-sequence

voltage across the machine terminals.

(35)

Normally, no zero sequence voltage should exist but a short circuit of

one or more turns on one phase will cause the generated e.m.f. to contain such a component

(36)

The zero-sequence voltage based interturn fault protection must

discriminate against

1. External earth fault will also

produce a zero sequence voltage on a directly connected generator.

(37)

b) The zero sequence voltage at the terminals w.r.t. the neutral of the generator rather than w.r.t. earth

a) Most of the voltage will be expended on the earthing resistor, the drop on the generator winding being small

and the zero-sequence voltage being limited to one or two percent

(38)

c) This is done by a voltage

transformer connected to the line terminals, with the neutral point of the primary windings connected

to the generator neutral, above the earthing resistor

(39)

d)The voltage transformer has a broken -delta connected secondary winding

that energizes a relay which therefore receives a quantity proportional to the zero-sequence component only

(40)

1. The third harmonic component of

the e.m.f. is of zero-sequence and is likely to be of a magnitude

exceeding the required relay setting. It is therefore necessary to provide a filter to extract the third harmonic

component from the VT output and apply it as a relay bias

(41)

a) With a direct connected machine it is still possible that a close-up earth fault will produce a zero-sequence

voltage drop greater than that produced by the short-circuiting of one-turn.

It is therefore necessary to apply a short-time delay to tripping outlet

(42)

b) An external earth fault cannot draw zero-sequence current

through the generator-transformer unit and hence will produce no

residual voltage from the voltage transformer. NO TIME DELAY IS REQUIRED IN THIS CASE

(43)

OVERLOAD PROTECTION

Overload in terms of current or MVA as distinct from megawatts is possible.

It is desirable to provide an overload relay having a suitable time

(44)

For monitoring the stator winding

temperature embedded thermocouples or resistance thermometer elements

are provided.

The rotor winding temperature is

checked by measuring the resistance of the field winding.

(45)

OVER CURRENT PROTECTION

 It is usual to provide overcurrent relays of the IDMT pattern to

generators, as a general ‘back-up’’

feature. These relays are in no way related to the thermal characteristics of the generator and are intended to operate only under fault conditions.

(46)

OVER VOLTAGE PROTECTION

Transient overvoltage

(47)

TRANSIENT OVERVOLTAGE

Surge overvoltages originate largely in the transmission system because of switching and atmospheric

(48)

Surge diverters are provided on the incoming lines or the station bus

bars

Sometimes surge diverters are connected also to the generator terminals.

(49)

POWER FREQUENCY

OVERVOLTAGE

 Overvoltages should not occur on a machine fitted with a voltage

(50)

Over voltage may be caused by the following contingencies:

1. Defective operation of the AVR 2. Operation under manual control

with the AVR out of service

3. Sudden loss of load (due to line tripping) may cause the hydro set to over-speed.

References

Related documents

Orchestrated by Dave Metzger Concert Score... Don't let

Therefore, this study proposes a conceptual framework based on two factors (perceived usefulness and perceived ease of use) with a view to investigate

the design are consistent across the SoS Clm8 Security requirements are identified adequately across the SoS Clm10 Verification/validation of SoS security features is adequately

Including regular season and postseason games in Wild history, Minnesota has played 101 contests against Vancouver, the second-most games against any NHL opponent (Colorado,

“22.9 If additional load materializes during the test period, for example from either new industrial or retail customers or from increased load from Ocean Falls Blockchain, please

Home Software Hardware Benchmarks Services Store Support Forums About Us.. Home » CPU Benchmarks »

Z tejto tabuľky budú generované všetky súbory, ktoré sú potrebné na správny chod prehliadača vzhľadom na časť prepisu reči.. Dáta by mohli ostať v XML, ale v

9 Preparation of new updated DC By-law including the new DC rates.. Finance staff will begin working with the technical teams to calculate the increased capital