• No results found

Fire Extinguishers Water Extinguishers

N/A
N/A
Protected

Academic year: 2021

Share "Fire Extinguishers Water Extinguishers"

Copied!
5
0
0

Loading.... (view fulltext now)

Full text

(1)

Technical Data

Model Capacity Type Fire

Rating Weight of charged exting.

Exting

agent Working Press. Disch. Times Range of jet horiz.

Temp

Range H x W x D Dims. (mm) WSP 9/2 9 litre Stored

pressure 21A 13.4 kg Water 9 bar 45 secs. 7-8 m -5

oC to +60oC 605H x 180D

WSP 6/2 6 litre Stored

pressure 13A 9.2 kg. Water 9 bar 30 secs. 4-6 m -5

oC to +60oC 549H x 160D

WASP 6/2 6 litre Stored

pressure 21A 9.2 kg. Water + additive 9 bar 30 secs 4-6 m -5

oC to +60oC 549H x 160D

WASP 3/2 3 litre Stored

pressure 13A 6.7 kg. Water + additive 9 bar 30secs. 4-6 m -5

oC to +60oC 445H x 160D

May be subject to technical change

Approvals: BS EN 3Kitemark Licence KM32490, BS EN ISO 9001: 2000 FM 32389, PED CE 05PED4667

Visit our website at: www.tycofis.co.uk

Description

Water extinguishers are suitable for Class A fires caused by combustion of solid materials such as wood, paper, straw, textiles and coal etc.

Water additive extinguishers use an environmentally friendly additive that greatly enhances the performance against Class A fires

Typical applications for these extinguishers include commercial offices, public places, restaurants, hotels, schools, industrial units and many others.

Features:

Robust design

Controlled discharge

High quality epoxy resin finish

(weather resistant)

Fully BS-EN3 approved

Quality lining

Benefits:

Effective fire fighting performance

Minimum space required

Rapid deployment

External thread

(2)

Technical Data

Model Capacity Type Fire Rating Weight of charged exting.

Working

Press. Disch. Times Range of jet horiz.

Temp

Range H x W x D Dims. (mm) FSP 2/1 2 litre Stored

pressure 8A/55B 3.2 kg. 12 bar 6secs 2 m -5

oC to +60oC 430H x 108D

FSP 3/2 3 litre Stored

pressure 13A/55B 6.1 kg. 9 bar 18 secs 2-4 m -5

oC to +60oC 450H x 160D

FSP 6/2 6 litre Stored

pressure 13A/113B 9.5 kg. 9 bar 30 secs 4-6 m -5

oC to +60oC 549H x 160D

FSP 9/2 9 litre Stored

pressure 21A/183B 13.5 kg. 9 bar 45 secs 4-6 m -5

oC to +60oC 605H x 180D

May be subject to technical change

Approvals: BS EN 3Kitemark Licence KM32490, BS EN ISO 9001: 2000 FM 32389, PED CE 05PED4667

Visit our website at: www.tycofis.co.uk

Description

Foam spray extinguishers, (AFFF-Aqueous Film Forming Foam), are ideal for multi-risk situations where both Class A combustible materials and Class B flammable liquid risk are likely to be found, or where Class B risks represent a direct hazard. Foam spray extinguishers are especially suitable for Class B fires involving flammable liquids such as oils, spirits, fats and certain plastics.

The blanketing effect of foam spray gives rapid knock down which smothers the flame and prevents re-ignition of flammable vapours by sealing the surface of the solution.

Features:

Available in Slimline design

Easy to handle

Effective spray application

Ergonomic design

Replaces bulkier 9 litre water extinguishers

Higher performance

Benefits:

Now available without torque

Uses 1% AFFF

Reduced service time

Reliability

(3)

Technical Data

Model Capacity Fire Rating Weight of

charged exting. Exting agent Disch. Times Range Temp H x W x D Dims. (mm) CD 2/2 2 kg. 34B 5.0 kg. CO2 6 secs. -20oC to +60oC 502H x 118D

CD 2/3 2 kg. 55B 5.0 kg. CO2 6 secs. -20oC to +60oC 502H x 118D

CD 5/2 5 kg. 55B 11.4 kg. CO2 9secs. -20oC to +60oC 677H x 152D

May be subject to technical change

Approvals: BS EN 3Kitemark Licence KM32490, BS EN ISO 9001: 2000 FM 32389, PED CE 05PED4667

Visit our website at: www.tycofis.co.uk

Description

Carbon Dioxide extinguishers are suitable for fires involving flammable liquids and electrical hazards. The non conductive qualities of carbon dioxide make it an ideal choice for dealing with fires involving electrical equipment and machinery. The carbon dioxide used in these extinguishers is a recovered industrial bi-product, thereby reducing the carbon levels that can contribute to the greenhouse effect.

Typical applications can be found in hospitals, supermarkets, hotels and restaurants, paint shops, fast food chains, clothing and fabric industries, industrial units, offices, etc..

Features:

Robust design

Safe and easy to handle

Hose and horn or swivel horn

Ergonomic design

Lightweight aluminium cylinder or lightweight steel

Higher performance

Benefits:

Excellent fire ratings

Powerful extinguisher

Reduced service time

High reliability

High fire fighting performance

(4)

Technical Data

Model Capacity Type Fire Rating Weight of charged exting. Exting agent (Glutex) Working

Press. Disch. Times Range of jet horiz.

Temp

Range H x W x D Dims. (mm) PSP/GP 1/3 1 kg. Stored

pressure 5A/34B 2.1 kg. ABC powder 12 bar 6 secs >4 m -20

oC to +60oC 340H x 86D

PSP/GP 2/3 2 kg. Stored

pressure 13A/70B 3.7 kg. ABC powder 12 bar 6 secs >4 m -20

oC to +60oC 415H x 110D

PSP/GP 4/2 4 kg. Stored

pressure 21A/113B 6.7 kg. ABC powder 12 bar 9. secs >4 m -20

oC to +60oC 445H x 160D

PSP/GP 6/2 6 kg. Stored

pressure 34A/113B 9.3 kg. ABC powder 12 bar 12 secs >6 m -20

oC to +60oC 549H x 160D

PSP/GP 9/2 9 kg. Stored

pressure 55A/183B 13.1 kg. ABC powder 12 bar 15 secs. >6 m -20

oC to +60oC 605H x 180D

May be subject to technical change

Approvals: BS EN 3Kitemark Licence KM32490, BS EN ISO 9001: 2000 FM 32389, PED CE 05PED4667

Visit our website at: www.tycofis.co.uk

Description

Powder Extinguishers are suitable for use on Class A, B and also Class C type fires involving flammable gases such as propane and butane. They are also highly effective for electrical hazards. This multi-purpose extinguisher interferes with the combustion process and provides rapid fire knock down. They are ideal for mixed fire risk environments and especially suited for the protection of flammable liquids, storage of liquid gases and heating oils used for industry, garages and workshops, etc..

Features:

Squeeze grip operation

Controlled discharge

Pressure gauge

Compact design

Ease of use

Benefits:

Effective fire fighting performance

Easy to service and maintain

Unique valve system

Covers many types of risk

(5)

Technical Data

Model Capacity Type Fire Rating Weight of charged exting.

Working

Press. Disch. Times Range of jet horiz.

Temp

Range H x W x D Dims. (mm) WCSP 6 litre Stored

Pressure 13A/113B 9.5 kg. 9 bar >30 secs. 4-6 m 5

oC to 60oC 549H x 160D

May be subject to technical change

Approvals:, PED CE 05PED4667

Visit our website at: www.tycofis.co.uk

Description

These extinguishers have been specifically designed for Class F fire risks involving cooling oils. The wet chemical agent rapidly knocks down the flames, cools burning oil and seals the surface to extinguish the fire and prevent re-ignition.

Features:

Long discharge hose with controlled discharge

Effective spray application

Ergonomic design

High performance

Benefits:

Effective fire fighting performance

Minimum space required

Rapid deployment

Knockdown performance of powder applied like foam

References

Related documents

Keep going till time runs out or you die, Get the highest score that you can Enemies Sea mines, Poachers. Sea

4.8 External Thermal Circuit, Cable Buried in Earth, Load May Be Cyclic, External Heat Source May Be Present...

According to NFPA, extinguishers suitable for Class A fires should be identified by a triangle containing the letter “A.” If in colour, the triangle should be green.. These fire

Burning metal is very difficult to extinguish, and only Class D extinguishers are recommended on burning metal.. Class D fire extinguishers are not used on any other class

Dry chemical extinguishers with powder designed for Class B and C fires (“BC” extinguishers) may be located in places such as commercial kitchens and areas with flammable liquids..

6.2.1.3 Certain smaller fire extinguishers that are charged with a multipurpose dry chemical or a halogenated agent rated on Class B and Class C fires but have insufficient

• Appropriate fire extinguishers are to be mounted within 75 feet of outside areas containing flammable liquids, and within 10 feet of any inside storage area for such materials.. •

If a water-based extinguisher is used to fight a fire in or near electrical equipment (Class C fire), the user could suffer an electric shock... Follow these steps in