TACO ZONE CONTROLS WIRING GUIDE
Pages
Switching Relays – Single Zone Wiring
2 –
2
Switching Relays – Oil Boiler Wiring Safety Notice
2
3 –
4
Switching Relays – NON EXP Connected Together with Priority
5 – 11
Switching Relays – EXP Connected Together with Priority
12 – 14
Switching Relays – Multiple Indirect Hot Water Heaters
15 – 16
Switching Relays – EXP Connected To Reset Controls (PC700, 702 & 705)
17 – 28
Zone Valve Controls – NON EXP Connected Together with Priority
29 – 34
Zone Valve Controls – EXP Connected Together with Priority
35 – 38
Zone Valve Controls – Connected To Reset Controls (PC700, 702 & 705)
39 – 46
Hydro Air Fan Controls (HAFC 101 & 201)
47 – 51
Specialty Thermostat and Zone Valve Wiring
52 – 56
Radiant Mixing Block
57 – 58
X-Pump Block
59 – 61
iSeries Mixing Valves
62 – 63
Low Water Cutoffs and Electric Water Feeders
64 – 79
Aquastat Wiring
80 – 86
Instruction Sheets
87 – 97
Standard Terms and Definitions
–
98
Cross Reference
99 – 100
Do it once.
Do it right.
TACO Zone Control Product Information
Switching Relays
Product No.
Description
SR501
1 Zone Switching Relay
SR501-845RP
1 Zone Switching Relay Replacement PC Board for
Honeywell R845, RA89A, RA832 or Comparable Relay
SR502
2 Zone Switching Relay with Priority
SR503
3 Zone Switching Relay with Priority
SR504
4 Zone Switching Relay with Priority
SR506
6 Zone Switching Relay with Priority
Switching Relays with PowerPort Options and Expandable to 20 Zones
Product No.
Description
SR501-EXP
1 Zone Switching Relay
SR503-EXP
3 Zone Switching Relay with Priority and 3 PowerPorts
SR504-EXP
4 Zone Switching Relay with Priority and 3 PowerPorts
SR506-EXP
6 Zone Switching Relay with Priority and 3 PowerPorts
Zone Valve Controls
Product No.
Description
ZVC403
3 Zone Valve Control
ZVC404
4 Zone Valve Control with Priority
ZVC405
5 Zone Valve Control
ZVC406
6 Zone Valve Control with Priority
Zone Valve Controls with PowerPort Options and Expandable to 20 Zones
Product No.
Description
ZVC404-EXP
4 Zone Valve Control with Priority and 2 PowerPorts
ZVC406-EXP
6 Zone Valve Control with Priority and 2 PowerPorts
Plug-In PowerPort Cards
(For use with all -EXP controls)
Product No.
Description
PC600
Post Purge Timer Plug-In Card
PC605
Priority Protection Plug-In Card
PC610
Universal Timer/Pump Exercise Plug-In Card
Add-On Power Controls
(For use with all -EXP controls)
Product No.
Description
PC700
Boiler Reset Control
PC702
2-Stage Boiler Reset Control
PC705
Variable Speed Pump Injection Mixing Control
Fan Controls
Product No.
Description
HAFC101
Hydro Air Fan Control
HAFC201
Hydro Air Fan Control with Optional Time Delays
Do it once.
Do it right.
AT TO: 120 V AC POWER CIRCULA TOR 120 V A C INPUT THERMOST
R
W
T
T
COM 24 VAC N/O N/C N/C N/ONH
3
44
6
6
5
TO: ZC SR501 1 ZONE SWITCHING RELAY POWER T STAT TO: ZR ALTERNATIVE WIRING (TANKLESS COIL)T
S
R
50
1 Switc
hing R
elay W
ir
ing
AT TO: 120 VAC POWER CIRCULA TOR JUMPER 120 V A C INPUT THERMOSTR
W
T
T
COM 24 VAC N/O N/C N/C N/ONH
3
44
6
6
5
TO: TT ON BOILER SR501 1 ZONE SWITCHING RELAY POWER T STATTYPICAL WIRING (COLD START)
T
TO: 120 V AC POWER CIRCULA TORR
W
T
T
COM 24 VAC N/O N/C N/C N/ONH
3
44
6
6
5
TO: TT ON BOILER SR501 1 ZONE SWITCHING RELAY POWER * T STAT * ALTERNATIVE WIRING(24 VAC POWERED INPUT SIGNAL) H N REMOVE JUMPER. DO NOT CONNECT POWER TO N AND H TERMINALS.
*
T
STAT LIGHT WILL GO ON AND OFF WITH 24 VAC SIGNAL. POWER LIGHT WILL ALWAYS BE OFF. 24 VAC SIGNAL
Note:
When using Alternative W
iring diagram, the boiler
oper-ating control’
s ZC terminal will see the load of the cir
culator(s).
W
a
rning:
When using Alternative W
iring diagram, wiring
instructions must be followed so power originates from the boiler aquastat. Failure to follow these wiring instructions may result in a secondar
y sour
ce of power being connected to the boiler that
may activate it under certain cir
cumstances, causing injur
(cont.)
NOTE: Tankless coil has priority.
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
THERMOSTAT
FUSE 1 AMP 24 VAC
POWER
ZONE 1 ZONE 2ZONE 3
120 VOLT CIRCULATORS ZC X1
ZONE1 ZONE2 ZONE3
SR 503 ZONE 2 POWER ZONE 1 ZONE 3 L1 L2 T T LINE VOLTAGE OIL BURNER RELAY
CIRCULATOR ON BOILER (IF ATTACHED) B2 C1 B1 ZR HONEYWELL L8124 OR EQUAL 120 VAC INPUT C2 ZC THERMOSTAT L1 L2 (NEUTRAL) (HOT) CIRCUIT BREAKER CUSTOMER EMERGENCY SWITCH THERMAL FUSE (FIROMATIC) SERVICE SWITCH LOW WATER CUTOFF NP H X2ZR
NOTE: The boiler operating control’s ZC terminal will see the load of the circulator(s).
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
THERMOSTATS ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VOLT CIRCULATORS ZC ZR
X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT SR 504 ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 L1 L2 T T LINE VOLTAGE OIL BURNER RELAY
CIRCULATOR ON BOILER (IF ATTACHED) B2 C1 B1 ZR HONEYWELL L8124 OR EQUAL 120 VAC INPUT C2 ZC THERMOSTAT L1 L2 (NEUTRAL) (HOT) CIRCUIT BREAKER CUSTOMER EMERGENCY SWITCH THERMAL FUSE (FIROMATIC) SERVICE SWITCH LOW WATER CUTOFF
SR502/503 Switching Relay Controlling Another SR502/503 Switching Relay
SR 503
24 VAC POWER
FUSE 1 AMP
ZONE1 ZONE2 ZONE3
120 VOLT CIRCULATORS ZONE1 ZONE2 ZONE3
TO: "TT" ON AQUASTAT CONTROL
JUMPER N P ZC H X ZR1 X2 ZONE 2 POWER ZONE 1 ZONE 3 THREE ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
T
T T
SR 503
ZONE1 ZONE2 ZONE324 VAC POWER
FUSE 1 AMP
120 VOLT CIRCULATORS ZONE1 ZONE2 ZONE3
120 VAC POWER
JUMPER
N P ZC H X ZR1
X2
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
T A T
BOILER
H
N
SLAVE
MASTER
AQUASTAT ON DHW HEATER ZONE 2 POWER ZONE 1 ZONE 3 DHW HEATER CIRCULATOR PRIORITY ON VIA JUMPER PLACEMENT PRIORITY OFF VIA JUMPER PLACEMENTSR502/503 Switching Relay Controlling Another SR504/506 Switching Relay
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 6 ON OFF PRIORITY 120V RELAY 120 VOLT CIRCULATORS ZC ZR X X END SWITCH POWER INPUT 120 VAC INPUT TO: "TT" ON BOILER
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
FUSE 1 AMP 24 VAC POWER
SR 506
ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 ZONE 5 ZONE 6 THERMOSTATS BOILER H NSR 503
ZONE1 ZONE2 ZONE324 VAC POWER
FUSE 1 AMP
120 VOLT CIRCULATORS ZONE1 ZONE2 ZONE3
JUMPERS
N P ZC H X ZR1
X2
THREE ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
T A T
MASTER
ZONE 2 POWER ZONE 1 ZONE 3SLAVE
T PRIORITY ON VIA JUMPER PLACEMENT REMOVE JUMPER PRIORITY OFF AQUASTAT ON DHW HEATERTwo SR504/506 Switching Relays Connected Together
BOILERH
N
A AQUASTAT ON DHW HEATER T T TFOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT
SR 504
ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER T T TFOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT TO: "TT" ON BOILER 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT
SR 504
ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER DHW HEATER CIRCULATOR OUTPUT NOT USED PRIORITY ON PRIORITY ONPriority Zoning Circulator Controlling SR504/506 Switching Relay
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 6 ON OFF PRIORITY 120V RELAY 120 VOLT CIRCULATORS ZC ZR X X END SWITCH POWER INPUT 120 VAC INPUT TO: "TT" ON BOILER
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
FUSE 1 AMP 24 VAC POWER
SR 506
ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ON OFF PRIORITY POWER IN 120 VAC INPUT THERMOSTAT BOILER PRIORITYPRIORITY ZONING CIRCULATOR
PR-IN PR-OUT LIVE NEUT
1 2 3 4 THERMOSTATS
BOILER
H N A AQUASTAT ON DHW HEATERMASTER
SLAVE
PRIORITY ON REMOVE JUMPER PRIORITY OFF TP
rior
it
y Zoning Cir
culator Contr
olling 2 S
R
504/5
06
Switc
hing R
elays
ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP ZONE 1 Z ONE 2 ZONE 3 Z ONE 4 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUTSR 504
ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
T T T BOILER ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP 24 VAC POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 120 VAC INPUT TO: "TT" ON BOILER 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT
SR 504
ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
T
T
T
H N
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
SLAVE
SLAVE
PRIORITY OFF PRIORITY OFF T T 24 VAC POWER ON OFF PRIORITY POWER IN THERMOSTAT BOILER PRIORITYPRIORITY ZONING CIRCULATOR
PR-IN PR-OUT LIVE NEUT 1 2 3 4 A AQUASTAT ON DHW HEATER 120 VAC INPUT
MASTER
PRIORITY ON REMOVE JUMPER REMOVE JUMPERS
R
50
2/5
03
Switc
hing R
elay Contr
olling 2 S
R
504/5
06
Switc
hing R
elays
ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP ZONE 1 ZONE 2 ZONE 3 ZONE 4 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUTSR 504
ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
T T T BOILER ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP 24 VAC POWER ZONE 1 Z ONE 2 ZONE 3 ZONE 4 120 VAC INPUT TO: "TT" ON BOILER 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT
SR 504
ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
T T T H N A
SR 503
ZONE1 ZONE2 ZONE3 24 V A C POWER FUSE 1 AMP ZONE1 ZONE2 ZONE3 JUMPER N P ZC H X ZR 1 X2 ZONE 2 POWER ZONE 1TWO ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
PRIORITY
ON
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
MASTER
SLAVE
SLAVE
PRIORITY OFF PRIORITY OFF T T T T 24 VAC POWER ZONE 3 REMOVE JUMPER REMOVE JUMPER AQUASTAT ON DHW HEATERFOUR ZONE SWITCHING RELA
Y
WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP ZONE 1 ZONE 2 ZONE 3 ZONE 4 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT
SR 504
ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
T
T
T
BOILER
FOUR ZONE SWITCHING RELA
Y
WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP ZONE 1 ZONE 2 ZONE 3 ZONE 4 120 VAC INPUT TO: "TT" ON BOILER 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT
SR 504
ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
T T T H N T DHW CIRCULATOR JUMPER
R
W
T
T
COM 24 VA C N/O N/C N/C N/ONH
3
44
5
6
6
SR501
POWER T STAT 120 VAC INPUT1 ZONE SWITCHING RELAY
AQUASTAT ON DHW HEATER A T
MASTER
SLAVE
SLAVE
REMOVE JUMPER REMOVE JUMPER PRIORITY OFF PRIORITY OFF 24 VAC POWER 24 VAC POWERS
R
50
1 Switc
hing R
elay Contr
olling 2 S
R
504/5
06
Switc
hing R
elays
SR501-EXP Switching Relay Controlling Another SR504/506 Switching Relay
SIX ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 6 ON OFF PRIORITY 120V RELAY 120 VOLT CIRCULATORS ZC ZR X X END SWITCH POWER INPUT 120 VAC INPUT TO: "TT" ON BOILER
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
FUSE 1 AMP 24 VAC POWER
SR 506
ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 ZONE 5 ZONE 6 THERMOSTATS BOILER H NMASTER
SLAVE
T REMOVE JUMPER PRIORITY OFF DHW CIRCULATOR POWER T STAT TO: "TT" ON BOILER AQUASTAT ON DHW HEATER NZC ZRHH H POWER INPUT 120VAC INPUT 120VAC OUTPUT CIRC OUTPUT PRIORITY OUTPUT RESET POWER CONTROLS FUSE 1 AMP NORMAL MASTER SLAVE END SWITCH ZONE VALVE THERMOSTAT EXPANSION X X1 223 4T/RT/WCOM1 JUMPERTO: OPTIONAL ZONE VALVE OR iSeries MIXING VALVE
MODE
FUSE 5 AMP
SR 501-EXP
S
R
50
1-E
XP Switc
hing R
elay Contr
olling a Z
VC
404/4
06
Zone V
alve Contr
ol
24 V A C ZONE 1 Z ONE 2 ZONE 3 ZONE 4 Z ONE 5 ZONE 6 MODE NORMAL RESETFUSE (7 AMP MAX)
TT TT TT TT TT TT ZONE 6 PRIORITY OFF ON
ZVC 406
12 34 12 34 12 34 12 34 12 34 ZONE 1 ZONE 2 ZONE 3 ZONE 4 Z ONE 5 2 WIRE ZONE V A LV E(NO END SWITCH)
JUMPER 3 & 4 T ACO 3 WIRE ZONE V A L V E 1 2 3 MOTOR END SWITCH THERMOSTAT THERMOSTAT THERMOSTAT 4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK N/O COM ZONE 6 RELAY END SWITCH EXTRA END SWITCH MAIN N/C
TO BOILER AQUASTAT RELAY
BOILER
H
N
SYSTEM PUMP
BOILER TURNS ON WHEN ANY ZONE VALVE OPENS.
12
34
ZONE 6 PRIORITY ZONE
JUMPER 3 & 4
SEE NOTE
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
TT
T
120 VAC INPUT DHW HEATER CIRCULATOR POWER T STAT AQUASTAT ON DHW HEATER NZ C Z R HH H POWER INPUT 120VAC INPUT 120VAC OUTPUT CIRC OUTPUT PRIORITY OUTPUT RESET POWERCONTROLS FUSE 1 AMP
NORMAL SLAVE MASTER
END SWITCH ZONE VALVE THERMOSTAT EXPANSION X COM T/W T/R X1 1 22 4 3 JUMPER
TO: OPTIONAL ZONE VALVE OR iSeries MIXING VALVE
MODE
FUSE 5 AMP
SR 501-EXP
A
TO BOILER AQUASTAT RELAY
MASTER
SLAVE
2 Expandable Switching Relays Connected Together
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE POWER CONTROL INTERFACE POWER CONTROL INTERFACE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT SR 504-EXP ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER BOILER SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
120 VAC INPUT H N SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On 12 34 EXPANSION 12 34 EXPANSION
SR504-EXP
SIX ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
ZONE 6 ON OFF PRIORITY 120V RELAY PLUG-IN CARDS FUSE 1 AMP SLAVE MASTER RESET NORMAL 120 VOLT CIRCULATORS ZC ZR X X END SWITCH POWER INPUT TO: "TT" ON BOILER
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
ZONE1 ZONE2 ZONE3 ZONE4 ZONE5 ZONE6
SR 506-EXP
ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 ZONE 5 ZONE 6 JUMPER DHW CIRCULATOR THERMOSTATSSLAVE
MASTER
A AQUASTAT ON DHW HEATER T TZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP 24 V A C POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT
SR 504
ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
T T T BOILER ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP 24 V A C POWER ZONE 1 ZONE 2 ZONE 3 ZONE 4 120 VAC INPUT TO: "TT" ON BOILER 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT
SR 504
ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
T T T H N A JUMPER JUMPER
SR 502
ZONE1 ZONE2 ZONE3 24 V A C POWER FUSE 1 AMP ZONE1 ZONE2 ZONE3 JUMPERS N P ZC H X ZR 1 X2 ZONE 2 POWER ZONE 1TWO ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
A
PRIORITY
OFF
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
FOUR ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
ZONE NOT USED ZONE NOT USED
MASTER
SLAVE
SLAVE
PRIORITY ON PRIORITY ON AQUASTATS ON DHW HEATERS2 Indir
ect W
ater Heater
s with P
rior
it
y Connected to St
andar
d Switc
hing R
elays
BOILER 120 V AC INPUT TO: "TT" ON BOILER H N A
SR 502
ZONE1 ZONE2 ZONE3 24 V A C POWER FUSE 1 AMP ZONE1 ZONE2 ZONE3 JUMPERS N P ZC H X ZR 1 X2 ZONE 2 POWER ZONE 1TWO ZONE SWITCHING RELAY
WITH OPTIONAL PRIORITY
A PRIORITY OFF 12 34 EXPANSION
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP 24 V A C POWER MASTER PLUG-IN CARDS RESET NORMAL SLA VE
POWER CONTROL INTERF
ACE ZONE 1 Z ONE 2 Z ONE 3 ZONE 4 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT SR 504-EXP ZONE 2
POWER ZONE 1 ZONE 3 ZONE 4
JUMPER
SWITCH SETTINGS
Master/Slave: Master Reset/Normal: Normal Priority Zone: On
12
34
EXPANSION
SR504-EXP
T
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP 24 V A C POWER MASTER PLUG-IN CARDS RESET NORMAL SLA VE
POWER CONTROL INTERF
ACE ZONE 1 Z ONE 2 Z ONE 3 ZONE 4 120 VOL T CIRCULA TORS ZC ZR X X END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT SR 504-EXP ZONE 2
POWER ZONE 1 ZONE 3 ZONE 4
JUMPER
SWITCH SETTINGS
Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
SR504-EXP
T DHW CIRCULATORS AQUASTATS ON DHW HEATERSMASTER
SLAVE
ZONE NOT USED
2 Indir
ect W
ater Heater
s with P
rior
it
y Connected to E
XP Switc
hing R
elays
PC700 Boiler Reset Control Connected to SR501-EXP Switching Relay
ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSORPC700
BOILER SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset 120 VAC INPUT SYSTEM CIRCULATOR POWER T STAT TO: "TT" ON BOILER THERMOSTAT NZC ZRHH H POWER INPUT 120VAC INPUT 120VAC OUTPUT CIRC OUTPUT PRIORITY OUTPUT RESET POWER CONTROLS FUSE 1 AMP NORMAL MASTER SLAVE END SWITCH ZONE VALVE THERMOSTAT EXPANSION X X1 223 4T/RT/WCOM1 JUMPERTO: OPTIONAL ZONE VALVE OR iSeries MIXING VALVE MODE FUSE 5 AMP
SR 501-EXP
H NT
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY 120 VOLT CIRCULATORS ZC ZR X X END SWITCH POWER INPUT 120 VAC INPUT ZONE1 ZONE2 ZONE3 ZONE4
ZONE1 ZONE2 ZONE3 ZONE4 FUSE 1 AMP 24 VAC POWER SR 504 ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 THERMOSTATS BOILER H N MASTER EXISTING ZONE CONTROL T PRIMARY SYSTEM CIRCULATOR (Optional) POWER T STAT TO: "TT" ON BOILER AQUASTAT ON DHW HEATER NZC ZRHH H POWER INPUT 120VAC INPUT 120VAC OUTPUT CIRC OUTPUT PRIORITY OUTPUT END SWITCH RESET OVERRIDE THERMOSTAT EXPANSION XX1 2234T/RT/WCOM1 JUMPER SR 501-EXP A RESET POWER CONTROLS FUSE 1 AMP NORMAL MASTER SLAVE MODE FUSE 5 AMP JUMPER DHW HEATER CIRCULATOR
Note: If Zone Control comes on without a call for heat, reverse Reset Override input (1 & 2) wires on SR501-EXP.
ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC700 K1-A K1-B K2-A K2-A K1 K2
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Switching Relay
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY 120 VOLT CIRCULATORS ZC ZR X X END SWITCH POWER INPUT 120 VAC INPUT ZONE1 ZONE2 ZONE3 ZONE4
ZONE1 ZONE2 ZONE3 ZONE4 FUSE 1 AMP 24 VAC POWER SR 504 ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 THERMOSTATS BOILER H N MASTER EXISTING ZONE CONTROL T POWER T STAT TO: "TT" ON BOILER AQUASTAT ON DHW HEATER END SWITCH RESET OVERRIDE THERMOSTAT EXPANSION XX1 2234T/RT/WCOM1 JUMPER A RESET POWER CONTROLS FUSE 1 AMP NORMAL MODE REMOVE JUMPER DHW HEATER CIRCULATOR ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC700 SLAVE NZC ZRHH H POWER INPUT 120VAC INPUT 120VAC OUTPUT CIRC OUTPUT PRIORITY OUTPUT SR 501-EXP MASTER SLAVE FUSE 5 AMP K1-A K1-B K2-A K2-A K1 K2
Connecting a DHW Heater to an Existing Heating Only Switching Relay
Using an SR501-EXP and PC700 Boiler Reset Control
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing Zone Valve Control
120 VAC INPUT BOILER H N EXISTING ZONE CONTROL PRIMARY SYSTEM CIRCULATOR (Optional) POWER T STAT TO: "TT" ON BOILER END SWITCH RESET OVERRIDE THERMOSTAT EXPANSION XX12234T/RT/WCOM1 JUMPER RESET POWER CONTROLS FUSE 1 AMP NORMAL MODE DHW HEATER CIRCULATORNote: If Zone Control comes on without a call for heat, reverse Reset Override input (1 & 2) wires on SR501-EXP.
ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC700 24 VAC POWER IN
ZONE 2 ZONE 3 ZONE 4
MODE NORMAL RESET FUSE (3 AMP MAX) ZONE 1 TT TT TT TT ZONE 4 PRIORITY OFF ON N/O COM N/C
ZONE 4 RELAY 12 34ZONE 1 12 34ZONE 2
2 WIRE ZONE VALVE (NO END SWITCH) JUMPER
3 & 4
TACO 3 WIRE ZONE VALVE
1 2 3 12 34ZONE 3 MOTOREND SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING) T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 POWER END SWITCH EXTRA END SWITCH MAIN 24 VAC FACTORYINSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK ZVC 404 FOUR ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY 12 34ZONE 4 PRIORITY ZONE JUMPER 3 & 4 SEE NOTE THERMOSTATS T T T
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
AQUASTAT ON DHW HEATER
A
ZONE VALVE SYSTEM CIRCULATOR NZC ZRHH H POWER INPUT 120VAC INPUT 120VAC OUTPUT CIRC OUTPUT PRIORITY OUTPUT SR 501-EXP MASTER SLAVE FUSE 5 AMP K1-A K1-B K2-A K2-A K1 K2
Connecting a DHW Heater to an Existing Heating Only Zone Valve Control
Using an SR501-EXP and PC700 Boiler Reset Control
120 VAC INPUT BOILER H N EXISTING ZONE CONTROL DHW HEATER CIRCULATOR POWER T STAT TO: "TT" ON BOILER END SWITCH RESET OVERRIDE THERMOSTAT EXPANSION XX12234T/RT/WCOM1 JUMPER RESET POWER CONTROLS FUSE 1 AMP NORMAL MODE ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC700 24 VAC POWER IN
ZONE 2 ZONE 3 ZONE 4
MODE NORMAL RESET FUSE (3 AMP MAX) ZONE 1TT TT TT TT ZONE 4 PRIORITY OFF ON N/O COM N/C
ZONE 4 RELAY 12 34ZONE 1 12 34ZONE 2
2 WIRE ZONE VALVE (NO END SWITCH)
JUMPER 3 & 4
TACO 3 WIRE ZONE VALVE
1 2 3 12 34 ZONE 3 MOTOREND SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING) T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 POWER END SWITCH EXTRA END SWITCH MAIN 24 VAC FACTORYINSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK ZVC 404 FOUR ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY 12 34ZONE 4
PRIORITY ZONE
JUMPER
3 & 4 SEE NOTE
THERMOSTATS
T T T
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
AQUASTAT ON DHW HEATER A
ZONE VALVE SYSTEM CIRCULATOR MASTER SLAVE NZC ZRHH H POWER INPUT 120VAC INPUT 120VAC OUTPUT CIRC OUTPUT PRIORITY OUTPUT SR 501-EXP MASTER SLAVE FUSE 5 AMP K1-A K1-B K2-A K2-A K1 K2
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing
Tankless Coil Boiler – Zoning with Circulators
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY 120 VOLT CIRCULATORS ZC ZR X X END SWITCH POWER INPUT 120 VAC INPUT ZONE1 ZONE2 ZONE3 ZONE4
ZONE1 ZONE2 ZONE3 ZONE4 FUSE 1 AMP 24 VAC POWER SR 504 ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 THERMOSTATS BOILER H N EXISTING ZONE CONTROL T POWER T STAT
TO: "ZR" ON BOILER CONTROL END SWITCH RESET OVERRIDE THERMOSTAT EXPANSION X X1 2234T/RT/WCOM1 JUMPER RESET POWER CONTROLS FUSE 1 AMP NORMAL MODE REMOVE JUMPER PRIMARY SYSTEM CIRCULATOR (Optional) ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC700
Boiler and Zone Control(s) need to be on same power supply (same circuit breaker). TO: "ZC" ON BOILER CONTROL
NZC ZRHH H POWER INPUT 120VAC INPUT 120VAC OUTPUT CIRC OUTPUT PRIORITY OUTPUT SR 501-EXP MASTER SLAVE FUSE 5 AMP K1-A K1-B K2-A K2-A K1 K2
SR501-EXP and PC700 Boiler Reset Control Connected to an Existing
Tankless Coil Boiler – Zoning with Zone Valves
120 VAC INPUT BOILER H N EXISTING ZONE CONTROL POWER T STAT END SWITCH RESET OVERRIDE THERMOSTAT EXPANSION X X12234T/RT/WCOM1 JUMPER RESET POWER CONTROLS FUSE 1 AMP NORMAL MODE ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC700
Boiler and Zone Control(s) need to be on same power supply (same circuit breaker). 24 VAC
POWER IN
ZONE 2 ZONE 3 ZONE 4
MODE NORMAL RESET FUSE (3 AMP MAX) ZONE 1 TT TT TT TT ZONE 4 PRIORITY OFF ON N/O COM N/C
ZONE 4 RELAY 12 34ZONE 1 12 34ZONE 2
2 WIRE ZONE VALVE (NO END SWITCH) JUMPER
3 & 4
TACO 3 WIRE ZONE VALVE
1 2 3 12 34 ZONE 3 MOTOREND SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING) T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 POWER END SWITCH EXTRA END SWITCH MAIN 24 VAC FACTORYINSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK ZVC 404
FOUR ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
12 34ZONE 4
PRIORITY ZONE
JUMPER
3 & 4 SEE NOTE
THERMOSTATS
T T T
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
ZONE VALVE SYSTEM CIRCULATOR
MASTER
SLAVE
TO: "ZR" ON BOILER CONTROL
PRIMARY SYSTEM CIRCULATOR
(Optional)
TO: "ZC" ON BOILER CONTROL
NZC ZRHH H
POWER
INPUT 120VACINPUT120VACOUTPUTOUTPUTCIRC PRIORITYOUTPUT
SR 501-EXP MASTER SLAVE FUSE 5 AMP K1-A K1-B K2-A K2-A K1 K2
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP 24 V A C POWER MASTER 1234 PLUG-IN CARDS RESET NORMAL SLA VE
POWER CONTROL INTERF
ACE THERMOST A T S ZONE 1 ZONE 2 ZONE 3 ZONE 4 120 V AC INPUT TO: "TT" ON BOILER 120 VOL T CIRCULA TORS ZC ZR
X X
END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
JUMPER H N ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR
PC700
BOILER
SWITCH SETTINGSMaster/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
SR 504-EXP
T
P
C700 Boiler R
eset Contr
ol Connected to E
XP Switc
hing R
elay
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP 24 V A C POWER MASTER 1234 PLUG-IN CARDS RESET NORMAL SLA VE
POWER CONTROL INTERF
ACE THERMOST A T S ZONE 1 ZONE 2 ZONE 3 ZONE 4 120 V AC INPUT 120 VOL T CIRCULA TORS ZC ZR
X X
END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
JUMPER
H N
ZONE
CONTROL
BOIL SEN
OUT SEN BOILER SENSOR OUTDOOR SENSOR
PC702
ST AGE 1 ST AGE 2 BOILER #2 BOILER #1 DHW DEMAND SWITCH SETTINGSMaster/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
SR 504-EXP
WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW
SYSTEM CIRCULATOR (OPTIONAL)
T
P
C70
2 2–St
age Boiler R
eset Contr
ol Connected to E
XP Switc
hing R
elay
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY ZONE 4 ON OFF PRIORITY 120V RELA Y FUSE 1 AMP 24 V A C POWER MASTER 1234 PLUG-IN CARDS RESET NORMAL SLA VE THERMOST A T S ZONE 1 ZONE 2 ZONE 3 ZONE 4 120 V AC INPUT TO: "TT" ON BOILER 120 VOL T CIRCULA TORS ZC ZR
X X
END SWITCH ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2POWER ZONE 1 ZONE 3 ZONE 4
JUMPER
H
N
BOILER
SWITCH SETTINGS
Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR
PC705-2
SUP SEN SUPPL Y SENSOR INJECTION CIRCULATOR SYSTEM CIRCULATOR AND/OR BOILER BLACK BLUE RED GREEN/GROUNDSR 504-EXP
(SEE NOTE B) NOTE A:WHEN SYSTEM CIRCULATOR IS CONNECTED TO ZR TERMINAL ON SWITCHING RELAY, THE MODE SWITCH MUST BE SET TO NORMAL. THE PC705-2 WILL NOT RESET THE BOILER WHEN IN THE NORMAL MODE.
NOTE B:
WHEN SYSTEM CIRCULATOR IS CONNECTED TO RED WIRE ON PC705-2, THE CIRCULATOR WILL OPERATE ONLY WHEN THERMOSTAT CALLS FOR H
EAT
AND THE OUTDOOR TEMPERATURE IS BELOW THE WARM WEATHER SHUT DOWN (WWSD) TEMPERATURE. THE WWSD CAN BE ADJUSTED OR TURNED OFF SO THAT THE CIRCULATOR IS NOT AFFECTED BY OUTDOOR TEMPERATURE.
SYSTEM
CIRCULATOR
AND/OR BOILER (SEE NOTE A)
T
P
C70
5 V
ar
iable Speed P
ump Injection Contr
ol Connected to E
XP Switc
hing R
PC700 Boiler Reset Control Connected to 2 EXP Switching Relays
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE POWER CONTROL INTERFACE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT TO: "TT" ON BOILER 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC700 BOILER SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE POWER CONTROL INTERFACE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER H N SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority
12 34 EXPANSION 12 34 EXPANSION
SR 504-EXP
SR 504-EXP
MASTER
SLAVE
SYSTEM CIRCULATOR (OPTIONAL)T
T
PC702 2–Stage Boiler Reset Control Connected to 2 EXP Switching Relays
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE POWER CONTROL INTERFACE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
12 34 EXPANSION ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC702 STAGE 1 STAGE 2 BOILER #2 BOILER #1 DHW DEMAND
SR 504-EXP
WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW
MASTER
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE POWER CONTROL INTERFACE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER H N SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority
12 34 EXPANSION
SR 504-EXP
SLAVE
SYSTEM CIRCULATOR (OPTIONAL)T
T
PC705 Variable Speed Pump Injection Control Connected to 2 EXP Switching Relays
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT TO: "TT" ON BOILER 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER BOILER SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE POWER CONTROL INTERFACE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER H N SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority
12 34 EXPANSION 12 34 EXPANSION ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC705-2 SUP SEN SUPPLY SENSOR INJECTION CIRCULATOR SYSTEM CIRCULATOR BLACK BLUE RED GREEN/GROUND
SR 504-EXP
SR 504-EXP
MASTER
SLAVE
SYSTEM CIRCULATOR (OPTIONAL) (SEE NOTE A ON PAGE 23) (SEE NOTE BON PAGE 23)
T
PC700 and PC705 Controls Connected to 2 EXP Switching Relays
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE POWER CONTROL INTERFACE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 V AC INPUT TO: "TT" ON BOILER 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC700 BOILER SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 H N SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority
12 34 EXPANSION 12 34 EXPANSION ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC705-2 SUP SEN SUPPLY SENSOR INJECTION CIRCULATOR SYSTEM CIRCULATOR BLACK BLUE RED GREEN/GROUND SYSTEM CIRCULATOR (OPTIONAL LOCATION) (SEE NOTE A ON PAGE 23)
SR 504-EXP
SR 504-EXP
MASTER
SLAVE
JUMPER (SEE NOTE B ON PAGE 23)T
T
PC702 and PC705 Controls Connected to 2 EXP Switching Relays
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE POWER CONTROL INTERFACE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY
ZONE 4 ON OFF PRIORITY 120V RELAY FUSE 1 AMP 24 VAC POWER MASTER PLUG-IN CARDS RESET NORMAL SLAVE THERMOSTATS
ZONE 1 ZONE 2 ZONE 3 ZONE 4
120 VAC INPUT 120 VOLT CIRCULATORS ZC ZR X X END SWITCH
ZONE1 ZONE2 ZONE3 ZONE4 POWER INPUT ZONE 2 POWER ZONE 1 ZONE 3 ZONE 4 JUMPER H N SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: No Priority
12 34 EXPANSION 12 34 EXPANSION ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC705-2 SUP SEN SUPPLY SENSOR INJECTION CIRCULATOR SYSTEM CIRCULATOR BLACK BLUE RED GREEN/GROUND SYSTEM CIRCULATOR (OPTIONAL LOCATION) (SEE NOTE A ON PAGE 23) ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC702 STAGE 1 STAGE 2 BOILER #2 BOILER #1 DHW DEMAND
SR 504-EXP
WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW
SR 504-EXP
MASTER
SLAVE
(SEE NOTE B ON PAGE 23)T
T
24 V A C ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5
FUSE (5 AMP MAX)
TT TT TT TT TT
ZVC 405
12 34 12 34 12 34 12 34 12 34 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 2 WIRE ZONE V A LV E(NO END SWITCH)
JUMPER 3 & 4 T ACO 3 WIRE ZONE V A L V E 1 2 3 MOTOR END SWITCH THERMOSTAT THERMOSTAT
THERMOSTAT 4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 POWER
FIVE ZONE ZONE VALVE CONTROL
24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK END SWITCH N/O COM N/C
TO BOILER AQUASTAT RELAY
POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
BOILER
H N SYSTEM PUMPSYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
TT
T
ZV
C
40
3/4
05
with S
ystem P
ump
24 V A C ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 MODE NORMAL RESET
FUSE (7 AMP MAX)
TT TT TT TT TT TT ZONE 6 PRIORITY OFF ON
ZVC 406
12 34 12 34 12 34 12 34 12 34 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 2 WIRE ZONE V A LV E(NO END SWITCH)
JUMPER 3 & 4 T ACO 3 WIRE ZONE V A L V E 1 2 3 MOTOR END SWITCH THERMOSTAT THERMOSTAT THERMOSTAT 4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK N/O COM ZONE 6 RELAY DRY CONT ACTS END SWITCH EXTRA END SWITCH MAIN N/C
TO BOILER AQUASTAT RELAY
BOILER
H N SYSTEM PUMP A AQUASTAT ON DHW HEATERSYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
12
34
ZONE 6 PRIORITY ZONE
JUMPER 3 & 4
SEE NOTE
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
TT
T
ZV
C
404/4
06
with S
ystem P
ump
24 V A C ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 MODE NORMAL RESET
FUSE (7 AMP MAX)
TT TT TT TT TT TT ZONE 6 PRIORITY OFF ON
ZVC 406
12 34 12 34 12 34 12 34 12 34 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 2 WIRE ZONE V A LV E(NO END SWITCH)
JUMPER 3 & 4 T ACO 3 WIRE ZONE V A L V E 1 2 3 MOTOR END SWITCH THERMOSTAT THERMOSTAT
THERMOSTAT 4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK N/O COM ZONE 6 RELAY END SWITCH EXTRA END SWITCH MAIN N/C 12 34
ZONE 6 PRIORITY ZONE
JUMPER 3 & 4
SEE NOTE
TO BOILER AQUASTAT RELAY
BOILER
H
N
DHW PUMP
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
A
AQUASTAT ON DHW HEATER
BOILER TURNS ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON
ONLY
WHEN PRIORITY ZONE CALLS.
TT
T
ZV
C
404/4
06
with Domestic Hot W
ater (D
H
W) P
24 V A C ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 MODE NORMAL RESET
FUSE (7 AMP MAX)
TT TT TT TT TT TT ZONE 6 PRIORITY OFF ON
ZVC 406
12 34 12 34 12 34 12 34 12 34 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 2 WIRE ZONE V A LV E(NO END SWITCH)
JUMPER 3 & 4 T ACO 3 WIRE ZONE V A L V E 1 2 3 MOTOR END SWITCH THERMOSTAT THERMOSTAT
THERMOSTAT 4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK N/O COM ZONE 6 RELAY END SWITCH EXTRA END SWITCH MAIN N/C 12 34
ZONE 6 PRIORITY ZONE
JUMPER 3 & 4
SEE NOTE
TO BOILER AQUASTAT RELAY
BOILER
H
N
DHW PUMP
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
A
AQUASTAT ON DHW HEATER
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON
ONLY
WHEN PRIORITY ZONE CALLS.
SYSTEM PUMP
TT
T
ZV
C
404/4
06
with S
ystem and D
H
W P
umps
24 V A C ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 MODE NORMAL RESET
FUSE (7 AMP MAX)
TT TT TT TT TT TT ZONE 6 PRIORITY OFF ON
ZVC 406
12 34 12 34 12 34 12 34 12 34 ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 2 WIRE ZONE V A LV E(NO END SWITCH)
JUMPER 3 & 4 T ACO 3 WIRE ZONE V A L V E 1 2 3 MOTOR END SWITCH THERMOSTAT THERMOSTAT
THERMOSTAT 4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER
SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK N/O COM ZONE 6 RELAY END SWITCH EXTRA END SWITCH MAIN N/C 12 34
ZONE 6 PRIORITY ZONE
JUMPER 3 & 4
SEE NOTE
TO BOILER AQUASTAT RELAY
BOILER
H
N
DHW PUMP
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
A
AQUASTAT ON DHW HEATER
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON
ONLY
WHEN PRIORITY ZONE CALLS.
SECONDARY PUMP COMES ON WHEN ANY ZONE CALLS
EXCEPT PRIORITY ZONE. SYSTEM PUMP SECONDARY PUMP
TT
T
ZV
C
404/4
06
with S
ystem, D
H
W and Secondary P
umps
2 ZVC404/406 Connected Together with Priority
24 VAC
POWER IN
ZONE 2 ZONE 3 ZONE 4 MODE
NORMAL RESET
FUSE (3 AMP MAX)
ZONE 1 TT TT TT TT ZONE 4 PRIORITY OFF ON N/O COM N/C ZONE 4 RELAY DRY CONTACTS 12 34 12 34 ZONE 1 ZONE 2
2 WIRE ZONE VALVE (NO END SWITCH) JUMPER
3 & 4
TACO 3 WIRE ZONE VALVE
1 2 3
THERMOSTAT THERMOSTAT THERMOSTAT
12 34 ZONE 3
MOTOR END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING) T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 POWER END SWITCH EXTRA END SWITCH MAIN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
ZVC 404
FOUR ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
12 34ZONE 4 PRIORITY ZONE JUMPER 3 & 4 SEE NOTE 24 VAC POWER IN
ZONE 2 ZONE 3 ZONE 4 MODE
NORMAL RESET
FUSE (3 AMP MAX)
ZONE 1 TT TT TT TT ZONE 4 PRIORITY OFF ON N/O COM N/C ZONE 4 RELAY
TO BOILER AQUASTAT RELAY
DRY CONTACTS
12 34 12 34
ZONE 1 ZONE 2
2 WIRE ZONE VALVE (NO END SWITCH) JUMPER
3 & 4
TACO 3 WIRE ZONE VALVE
1 2 3
THERMOSTAT THERMOSTAT THERMOSTAT
12 34 ZONE 3
MOTOR END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING) T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 POWER END SWITCH EXTRA END SWITCH MAIN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
FOUR ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
BOILER H N
A
AQUASTAT ON DHW HEATER PRIORITY ON PRIORITY ON TO BOILER AQUASTAT RELAYZVC 404
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
12 34ZONE 4 PRIORITY ZONE JUMPER 3 & 4 SEE NOTE
TT
T
TT
T
2 EXP Zone Valve Controls Connected Together with System Pump
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 12 34ZONE 6 MODE
NORMAL RESET
PRIORITY ZONE
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
1 2 3 JUMPER 3 & 4 MOTOR END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
JUMPER 3 & 4 12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 SEE NOTE EXPANSION ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY 24 VAC POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
TO BOILER AQUASTAT RELAY
N/O COM ZONE 6 RELAY N/C END SWITCH A PUMP END SWITCH B BOILER H N BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 MODE
NORMAL RESET
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE 1 2 3 JUMPER 3 & 4 MOTOR END SWITCH 4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 EXPANSION ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK DRY CONTACTS N/O COM ZONE 6 RELAYN/C END SWITCH A PUMP END SWITCH B BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
A
AQUASTAT ONDHW HEATERT
T
T
T
T
T
120 VAC INPUT 12 34 ZONE 6 PRIORITY ZONE JUMPER 3 & 4 SEE NOTEMASTER
SLAVE
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
SYSTEM PUMP
2 EXP Zone Valve Controls Connected Together with DHW Pump
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 12 34ZONE 6 MODE
NORMAL RESET
PRIORITY ZONE
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
1 2 3 JUMPER 3 & 4 MOTOR END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
JUMPER 3 & 4 12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 SEE NOTE EXPANSION ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY 24 VAC POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK TO BOILER AQUASTAT RELAY N/O COM ZONE 6 RELAY N/C END SWITCH A PUMP END SWITCH B BOILER H N BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 MODE
NORMAL RESET
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE 1 2 3 JUMPER 3 & 4 MOTOR END SWITCH 4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 EXPANSION ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK DRY CONTACTS N/O COM ZONE 6 RELAYN/C END SWITCH A PUMP END SWITCH B BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
A
AQUASTAT ONDHW HEATERT
T
T
T
T
T
120 VAC INPUT 12 34 ZONE 6 PRIORITY ZONE JUMPER 3 & 4 SEE NOTEMASTER
SLAVE
BOILER TURNS ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
DHW PUMP
2 EXP Zone Valve Controls Connected Together with System and DHW Pumps
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 12 34ZONE 6 MODE
NORMAL RESET
PRIORITY ZONE
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
1 2 3 JUMPER 3 & 4 MOTOR END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
JUMPER 3 & 4 12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 SEE NOTE EXPANSION ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY 24 VAC POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK TO BOILER AQUASTAT RELAY N/O COM ZONE 6 RELAY N/C END SWITCH A PUMP END SWITCH B BOILER H N BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 MODE
NORMAL RESET
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE 1 2 3 JUMPER 3 & 4 MOTOR END SWITCH 4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 EXPANSION ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK DRY CONTACTS N/O COM ZONE 6 RELAYN/C END SWITCH A PUMP END SWITCH B BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
A
AQUASTAT ONDHW HEATERT
T
T
T
T
T
120 VAC INPUT 12 34 ZONE 6 PRIORITY ZONE JUMPER 3 & 4 SEE NOTEMASTER
SLAVE
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
DHW PUMP
SYSTEM PUMP
2 EXP Zone Valve Controls Connected Together with System, DHW and Secondary Pumps
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 12 34ZONE 6 MODE
NORMAL RESET
PRIORITY ZONE
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
1 2 3 JUMPER 3 & 4 MOTOR END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
JUMPER 3 & 4 12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 SEE NOTE EXPANSION ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY 24 VAC POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK TO BOILER AQUASTAT RELAY N/O COM ZONE 6 RELAY N/C END SWITCH A PUMP END SWITCH B BOILER H N BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 MODE
NORMAL RESET
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE 1 2 3 JUMPER 3 & 4 MOTOR END SWITCH 4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 EXPANSION ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY
POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK DRY CONTACTS N/O COM ZONE 6 RELAYN/C END SWITCH A PUMP END SWITCH B BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
A
AQUASTAT ONDHW HEATERT
T
T
T
T
T
120 VAC INPUT 12 34 ZONE 6 PRIORITY ZONE JUMPER 3 & 4 SEE NOTEMASTER
SLAVE
SYSTEM PUMP AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW PUMP TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
SECONDARY PUMP TURNS ON WHEN ANY ZONE CALLS, EXCEPT PRIORITY ZONE.
DHW PUMP
SYSTEM
PUMP SECONDARY
P
C700 Boiler R
eset Contr
ol Connected T
o E
XP Zone V
alve Contr
ol
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6FUSE 7 AMP MAX
TT TT TT TT TT TT ZONE 6 OFF ON 12 34 ZONE 1 12 34 ZONE 2 12 34 ZONE 3 12 34 ZONE 4 12 34 ZONE 5 12 34 ZONE 6 MODE NORMAL RESET
INDIRECT WATER HEA
TER AQUAST AT OR THERMOST AT PRIORITY ZONE 2 WIRE ZONE V A LV E
(NO END SWITCH)
TA C O 3 WIRE ZONE V A LV E 1 2 3 JUMPER 3 & 4 MOTOR END SWITCH THERMOSTAT THERMOSTAT
THERMOSTAT 4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
JUMPER 3 & 4 12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER ON
SEE NOTE
EXPANSION
ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
24 VAC POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK TO BOILER AQUASTAT RELAY DRY CONT ACTS N/O COM ZONE 6 RELAY N/C END SWITCH A PUMP END SWITCH B BOILER ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR
PC700
SYSTEM CIRCULATOR H N BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.SWITCH SETTINGS
Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
TT
P
C70
2 2–St
age Boiler R
eset Contr
ol Connected T
o E
XP Zone V
alve Contr
ol
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6FUSE 7 AMP MAX
TT TT TT TT TT TT ZONE 6 OFF ON 12 34 ZONE 1 12 34 ZONE 2 12 34 ZONE 3 12 34 ZONE 4 12 34 ZONE 5 12 34 ZONE 6 MODE NORMAL RESET
INDIRECT WATER HEA
TER AQUAST AT OR THERMOST AT PRIORITY ZONE 2 WIRE ZONE V A LV E
(NO END SWITCH)
TA C O 3 WIRE ZONE V A LV E 1 2 3 JUMPER 3 & 4 MOTOR END SWITCH THERMOSTAT THERMOSTAT
THERMOSTAT 4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
JUMPER 3 & 4 12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER ON
SEE NOTE
EXPANSION
ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
24 VAC POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK N/O COM ZONE 6 RELAY N/C END SWITCH A PUMP END SWITCH B BOILER SYSTEM CIRCULATOR H N BOILER #2 ZONE CONTROL BOIL SEN
OUT SEN BOILER SENSOR OUTDOOR SENSOR
PC702
ST AGE 1 ST AGE 2 BOILER #1 DHW DEMAND 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.SWITCH SETTINGS Master/Slave: Master Reset/Normal: Normal Priority Zone: On or Off
WIRING NEEDED ONLY IF PRIORITY ZONE IS DHW
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW CIRCULATOR TURNS ON
ONLY
WHEN PRIORITY ZONE CALLS.
DHW
CIRCULATOR
TT
P
C70
5 V
ar
iable Speed P
ump Injection Contr
ol Connected T
o E
XP Zone V
alve Contr
ol
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6FUSE 7 AMP MAX
TT TT TT TT TT TT ZONE 6 OFF ON 12 34 ZONE 1 12 34 ZONE 2 12 34 ZONE 3 12 34 ZONE 4 12 34 ZONE 5 12 34 ZONE 6 MODE NORMAL RESET
INDIRECT WATER HEA
TER AQUAST AT OR THERMOST AT PRIORITY ZONE 2 WIRE ZONE V A LV E
(NO END SWITCH)
TA C O 3 WIRE ZONE V A LV E 1 2 3 JUMPER 3 & 4 MOTOR END SWITCH THERMOSTAT THERMOSTAT
THERMOSTAT 4 WIRE ZONE VALVE
(POWER OPEN, SELF CLOSING)
JUMPER 3 & 4 12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 VALVE 3 T STAT 4 VALVE 4 T STAT 5 VALVE 5 T STAT 6 VALVE 6 POWER ON
SEE NOTE
EXPANSION
ZVC 406-EXP
SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
24 VAC POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK TO BOILER AQUASTAT RELAY DRY CONT ACTS N/O COM ZONE 6 RELAY N/C END SWITCH A PUMP END SWITCH B BOILER H N BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR
PC705-2
SUP SEN SUPPL Y SENSOR INJECTION CIRCULATOR SYSTEM CIRCULATOR(SEE NOTE B ON PAGE 23)
BLACK
BLUE
RED
GREEN/GROUND
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
SWITCH SETTINGS
Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
SYSTEM CIRCULATOR (OPTIONAL LOCATION)
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS.
TT
PC700 Boiler Reset Control Connected To 2 EXP Zone Valve Controls
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 12 34ZONE 6 MODE
NORMAL RESET
PRIORITY ZONE
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
1 2 3 JUMPER 3 & 4 MOTOR END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
JUMPER 3 & 4 12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 SEE NOTE EXPANSION ZVC 406-EXP SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK TO BOILER AQUASTAT RELAY N/O COM ZONE 6 RELAYN/C END SWITCH A PUMP END SWITCH B BOILER ZONE CONTROL BOIL SEN OUT SEN BOILER SENSOR OUTDOOR SENSOR PC700 SYSTEM CIRCULATOR H N BOILER
Note: When a circulator is used on the priority zone instead of a zone valve, jumper 3 and 4 of the priority zone.
24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6
FUSE 7 AMP MAX
TT TT TT TT TT TT
ZONE 6
OFF ON
12 34ZONE 1 12 34ZONE 2 12 34ZONE 3 12 34ZONE 4 12 34ZONE 5 12 34ZONE 6 MODE
NORMAL RESET
PRIORITY ZONE
2 WIRE ZONE VALVE (NO END SWITCH)
TACO 3 WIRE ZONE VALVE
1 2 3 JUMPER 3 & 4 MOTOR END SWITCH
4 WIRE ZONE VALVE (POWER OPEN, SELF CLOSING)
JUMPER 3 & 4 12 34 MASTER SLAVE POWER CONTROLS PLUG-IN CARDS PRIORITY
TACO, INC ZVC406-EXP
T STAT 1 T STAT 2 T STAT 3 T STAT 4 T STAT 5 T STAT 6 POWER ON VALVE 1 VALVE 2 VALVE 3 VALVE 4 VALVE 5 VALVE 6 SEE NOTE EXPANSION ZVC 406-EXP SIX ZONE ZONE VALVE CONTROL
WITH OPTIONAL PRIORITY
POWER IN 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK DRY CONTACTS N/O COM ZONE 6 RELAYN/C END SWITCH A PUMP END SWITCH B BOILER 24 VAC FACTORY INSTALLED TRANSFORMER 120 VAC INPUT WHITE BLACK SWITCH SETTINGS Master/Slave: Master Reset/Normal: Reset Priority Zone: On or Off
SWITCH SETTINGS Master/Slave: Slave Reset/Normal: Normal Priority Zone: Off
MASTER
SLAVE
INDIRECT WATER HEATER AQUASTAT OR THERMOSTAT 24 VAC T T T 24 VAC T T T
SYSTEM CIRCULATOR AND BOILER TURN ON WHEN ANY ZONE VALVE OPENS. DHW CIRCULATOR TURNS ON ONLY WHEN PRIORITY ZONE CALLS.
DHW CIRCULATOR