• No results found

Transformer Vector Group

N/A
N/A
Protected

Academic year: 2021

Share "Transformer Vector Group"

Copied!
11
0
0

Loading.... (view fulltext now)

Full text

(1)
(2)
(3)
(4)
(5)

TEST & INSPECTION PROCEDURE FOR POWER TRANSFORMERS (As per IEC 60076 & IS 2026)

Description of Test Type Test Routine Test

FAT (Factory Acceptance Test) or Inspection Test Pre-Commissioning Test Remarks Measurement of

Insulation Resistance Y Y Y Y Y - Yes

Measurement of

Winding Resistance Y Y Y Y

Ratio Test Y Y Y Y

Vector Group Test Y Y Y Y

Magnetic Core

Balance Test Y Y C Y C-Customer Choice

Measurement of No-load loss & Exciting Current

Y Y C Y

Measurement of Impedance Voltage & Load Loss

Y Y C Y

(6)

Efficiency & Voltage Regulation Temperature Rise Test Y N N N Measurement of Insulation Power Factor Y Y N N Lightning Impulse Test on Bushing Y N N N Separate Source Voltage Withstand Test Y Y N N Induced Overvolatge Withstand Test Y Y N N

Test on On-Load Tap Changer (If applicable) Y Y C Y Tests on Bushing CT (If Applicable) Y Y N Y Tests on Protective Devices (OTI, WTI, Buch Holz Relay & MOG) Y Y C Y General Inspection Y Y Y Y As per Approved Drawing Vacuum Test & Oil

Tightness Test Y Y N N

Tests on Insulation

Oil (If Applicable) Y Y C Y

1. MEASUREMENT OF INSULATION RESISTANCE: Transformer Temperature : oC

Make of Megger : Sl. No. of Megger :

Ø Recommended Test Voltage: 2.5kV or 5kV for all HV Windings & 500V or 1000V for all LV Windings

(7)

1 Minute Value

The Minimum values of IR Values shall be :

Voltage Class of Winding

Minimum IR Values in Mega

Ω

At 30 oC At 40 oC At 50 oC At 60 oC 66 & 132 kV 600 300 150 75 22 & 33 V 500 250 125 62.5 6.6 & 11 V 400 200 100 50 < 6.6 kV 200 100 50 25

2. MEASUREMENT OF WINDING RESISTANCE:

Ø Use a good quality low-resistance meter or use Kelvin's Double Bridge Ø Perform measurement on all Taps

Ø Check with the Transformer Routine Test Certificate Transformer Temperature: oC

Make of Meter/Bridge Sl. No. of Meter/Bridge

Tap No.Winding Resistance in Ohms

1U1V 1V1W 1W1U 2u2v 2v2w 2w2u 1

2

3. RATIO TEST:

Ø Perform the test on all taps

Ø Apply 3 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV winding open circuited and measure the voltage in the secondary winding

Ø Use good quality voltmeters for measurement; use same meter for measuring HT & LT Volts

(8)

Ø Check with the ratio declared in the transformer name plate/routine test certificate Ø Caution: Do not apply voltage to LV Terminals, as this would induce dangerously high voltages at the HV Terminals

Tap No.

Applied Volts Measured Volts Ratio Calculated Actual Ratio 1U1V 1V1W 1W1U 2u2v 2v2w 2w2u 1U1V/2u2v 1V1W/2v2w 1W1U/2w2u 1

2

4. VECTOR GROUP TEST:

Ø Short the terminals 1U & 2u using a wire of right size (say 2.5 sq.mm Cu.) Ø Apply 3 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV winding open circuited and measure the voltage in the HV/LV windings

Ø Use good quality voltmeters for measurement; use same meter for measuring HT & LT Volts

Ø Check if the equations for the relevant vector group are satisfied

Ø Caution: Do not apply voltage to LV Terminals, as this would induce dangerously high voltages at the HV Terminals

For example, for Dyn 11 Vector Group, the following equations must satisfy: i) 1V2w = 1V2v

ii) 1W2w < 1W2v

iii) 1U2n +1V2n = 1U1V

Similarly, equations could be derived for any other vector group and test results can be crosschecked.

5. MAGNETIC CORE BALANCE TEST:

Ø Apply 2 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV winding open circuited and measure the voltage in the HV windings

Ø Use good quality voltmeters for measurement; use same meter for measuring applied & measured Volts

(9)

Ø Check if the balance conditions are satisfied

Ø Caution: Do not apply voltage to LV Terminals, as this would induce dangerously high voltages at the HV Terminals

Applied Volts Measured Volts

Remarks (Equations

for Balance

Conditions)

1U1V 1V1W 1W1U 1U1V 1V1W 1W1U

(415) --- --- --- (398) (17)

1V1W > 1W1U

--- (415) ---- (212) ---- (213) 1U1V =1W1U ---- ---- (415) (31) (384) ---- 1U1V <1V1W

6. MEASUREMENT OF NO-LOAD LOSS & EXCITING CURRENT: Ø Perform the test on normal tap

Ø Apply 3 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV winding open circuited and measure the voltage, current & power in the HV winding Ø Use good quality meters for measurement

Ø Check with the exciting current/no-load loss declared in the transformer routine test certificate

Ø Caution: Do not apply voltage to LV Terminals, as this would induce dangerously high voltages at the HV Terminals

Applied Volts (V) Measured Current (mA) Terminal Volts Winding Current

1U1V 1U

1V1W 1V

1W1U 1W

Note: From the above data, we can calculate that if the exciting current is 'x' milliamperes for the test voltage applied (say 415V), what would be the exciting current for the rated primary volts of the transformer.

(10)

of the transformer.

The current calculated above shall be approximately 2% to 4% of the rated transformer primary current.

7. MEASUREMENT OF IMPEDANCE VOLATGE & LOAD LOSS Ø Perform the test on normal tap

Ø Apply 3 Phase, 50Hz, Low Voltage, say, 415V to the HV Winding with the LV winding short circuited and measure the voltage in the HV winding and current & power in the LV winding

Ø Use good quality meters for measurement

Ø Check with the % impedance/load loss declared in the transformer name plate/routine test certificate

Ø Caution: Do not apply voltage to LV Terminals, as this would induce dangerously high voltages at the HV Terminals

Applied Volts (V) Measured Current in LV Winding (A) Terminal Volts

1U1V 1V1W 1W1U

Note: From the above, we can calculate that if for the test voltage (say 415V), the SC Current is 'y' amps, then what it would be for the rated primary voltage of the transformer.

Rated SC Current = ('y'/415) x Rated Primary Voltage Then, we can calculate % impedance:

% Impedance = (Rated Secondary FLC/Rated SC Current) x 100 8. Test on On-Load Tap Changer: All operational checks (Manual & Motorised Operations)

9. Tests on Bushing CT: All tests as per IS 2705 like Polarity, Winding Resistance, Accuracy, Ratio Test, Mag.Characteristics, etc.

(11)

10. Tests on Protective Devices: Check all protective devices for correct operation, settings, calibration, etc.

11. General Inspection: Check for Physical Dimensions, Clearances, Creepages, etc, as per approved drawings; Inspect for any visual damages to any components. 12. Tests on Insulating Oil: BDV shall be 60kV across a gap of 2.5mm with 12.5mm Dia. Spheres. Ask for test certificate.

References

Related documents

Submission Guidelines General Rules Ø All submissions should be emailed to the Director Participant List Ø Alphabetized by last name; last name, first name Ø Times

Arun Mittal &amp; Associates Architects, Interior Designers Valuers &amp; Industrial Planner KOTHI No.. Bansal &amp; Associates Architects, Engineers,

Securities and Exchange Commission (the “SEC” or “Commission”) to enact a whistleblower program to pay financial awards to individuals who provide information about possible

The resistance of the connection tested by the Current Cycle Submersion Test method in accordance with clause 6 shall be stable between the tenth cycle and the completion of the

LJMU is committed to providing research students with relevant and appropriate opportunities to develop both specialist and generic research skills in line with its Researcher

In the TESLA Control Panel, you will enter the information about the AØ analog voltage input, selecting channel, Module Type and ratio of the phase to neutral voltage (Ø-Ø)

Option 3 does not create a new regulatory environment for the independent healthcare sector, as the use of electronic signatures, and the subsequent electronic transmission

Solution Early involvement of procurement and suppliers RFx cycle reduction Improved negotiating leverage Standardized sourcing processes Supplier collaboration Reduced sourcing