• No results found

Selectivity and Backup

N/A
N/A
Protected

Academic year: 2021

Share "Selectivity and Backup"

Copied!
43
0
0

Loading.... (view fulltext now)

Full text

(1)

SECTION CONTENTS

406 Definition of selectivity

416 Back-up protection

417 Selectivity tables

432 Back-up tables

SELECTIVITY

AND BACK-UP

A

B

C

D

E

405

405

CONTENTS

(2)

Selectivity between

electrical safety devices

DEFINITION OF SELECTIVITY

Selectivity between electrical safety devices is

necessary to guarantee maximum continuity of the

electric system.

The aim of selectivity is to ensure that in case of

fault, the necessary repair tripping will only affect

the safety devices immediately upstream the fault,

rather than the general ones, thus maintaining

service continuity for the branches of the system

not affected by the fault. Selectivity between

electric safety devices is obtained through correct

coordination of the individual electric features.

In general, selectivity is required in terms of:

overload;

short circuit;

earth fault (earth leakage).

Selectivity between two circuit breakers installed in

cascade can be

total when the downstream circuit

breaker (B) trips for all overcurrent values up to its

breaking capacity, or

partial when both circuit breakers

trip (A and B), when certain values are exceeded.

A

B

C

D

E

TOTaL SELECTIVITY

A

B

Icc no tripping tripping parTIaL SELECTIVITY

A

B

Icc no tripping tripping Is (selectivity limit)

In this second case, a “selectivity limit” (ls) is set. This

us the current value below which only the downstream

circuit breaker will trip, and above which botch circuit

breakers will. In accordance with IEC 60947-2 and IEC

60898 standards, selectivity can be assessed comparing

the various tripping and energy curves provided by the

manufacturers.

Total selectivity: only B trips for all Icc values up to its breaking capacity

Partial selectivity: B is selective compared to A for Icc values up to the Is. Above this value, selectivity is not guaranteed for Icc>Is, and both circuit breakers may trip.

(3)

I

s

Only B opens

Both A and B open

I

cc

(kA)

t (s)

A

B

A

B

OVErLOaD aMpErEMETEr SELECTIVITY

To ensure selectivity coordination of various devices,

the tripping curves of all selected circuit breakers

must be compared using a bi-logarithmic scale (Icc/t).

Graphically, selectivity is achieved when the curve of

the upstream circuit breaker (A) is on the right of the

curve of the downstream circuit breaker (B).

The intersection point of the magnetic curves is the

selectivity limit (Is).

Below this point, only the downstream circuit breaker

trips, while both will trip when this value is exceeded.

Overload selectivity is always guaranteed if the

tripping time delay of the upstream circuit breaker

is longer than the opening time of the downstream

circuit breaker for any overload current.

By selecting circuit breakers with nominal current

ratios equal or over 2, overload selectivity is always

guaranteed.

Overload selectivity can also be improved if devices

with adjustable tripping thresholds are used.

This type of selectivity is ensured using quick circuit

breakers without a device for the adjustment of the

release time delay.

This solution normally ensures partial selectivity.

407

GENEraL FEaTUrES

407

(4)

Selectivity between

electrical safety devices

ShOrT CIrCUIT aMpErEMETEr SELECTIVITY

To ensure an efficient selectivity level between

two automatic circuit breakers in series, it will

be necessary to select them with instantaneous

(magnetic) tripping thresholds as far away as

possible from each other.

Total selectivity is ensured when the short circuit

current is below the magnetic tripping threshold of

the upstream circuit breaker (Icc<Is). On the other

hand, if the short circuit current is higher (Icc>Is),

selectivity can only be obtained if the downstream

circuit breaker specific feed through power is not

enough to cause tripping of the upstream circuit

breaker.

In this case, the specific feed-through power curves

of the circuit breakers must be compared, taking

into account a tolerance of ±20% on the magnetic

tripping value.

Only B opens

I

s

Both A and B open

B

A

I

cc

(kA)

I

2

t

(A

2

s)

maximum

non activation

power value

A

B

By superimposing the line passing through the

maximum non activation value of the curve of the

specific power let through by the downstream circuit

breaker, the new Is limit value can be determined.

This must be higher than the magnetic tripping

threshold of the upstream circuit breaker.

(5)

time adjustment

In a short circuit, chronometric selectivity is achieved

by using circuit breakers capable of tripping with

an intentional time delay, either fixed or set by the

user. This tripping time delay provides the possibility

of distancing the magnetic curves, creating a step

in relation to the downstream circuit breaker. In this

way, selectivity is guaranteed because, should a short

circuit occur, the circuit breaker with the shortest

time delay will trip first.

When only “E” type electronic MEGATIKER Mccb’s are

used, the fixed time delay is equal to 0.05 s.

tA = fixed to 0.05s for “E” type MEGATIKER, adjustable to 0-0.01-0.2-0.3s for “S” and “T” type MEGATIKER.

I

s

= instantaneous fixed

tA

tB = instantaneous

Only B opens Both A and B open

I

cc

(kA)

t (s)

A

B

A

B

ChrONOMETrIC SELECTIVITY

In order to guarantee total selectivity also in short

circuit conditions, it is necessary that the downstream

circuit breaker trips in the presence of short circuit

currents before the upstream circuit breaker does.

This means that the magnetic curves of the circuit

breakers must be graphically separated. They cannot

be superimposed for any of the estimated short

circuit current values.

The separation between the curves is obtained by

setting such a magnetic tripping time delay on the

upstream circuit breaker that should a fault occur,

it will be the downstream circuit breaker that will

trip. By carefully selecting the current thresholds

and the tripping time delays on the various devices,

the selectivity concept can be extended to several

electric safety levels. This type of selectivity is

obtained by installing upstream circuit breakers with

adjustable tripping time delays, such as selective

electronic “E”, “S” and “T” type MEGATIKER Mccb’s

(classed as belonging to category B), and installing

downstream circuit breakers of the same type, or

thermal magnetic, with fixed time delay, depending

on system requirements. MEGATIKER electronic

Mccb’s provide two different types of adjustments:

magnetic tripping time delay adjustment

adjustment with constant I

2

t

With the “S” or “T” types, this value can adjusted to

four different levels: 0 - 0.1 - 0.2 - 0.3 s.

In general, for this type of adjustment, the specific

power fed through by the circuit breaker increases

proportionally, based on the set delay.

Circuit breakers that trip with an intentional delay

during a short circuit, loose all limitation features.

It is therefore necessary to ensure that they are able

to withstand any electric and mechanical stresses

which may be caused by the passage of the short

circuit currents.

409

GENEraL FEaTUrES

409

(6)

Selectivity between

electrical safety devices

Adjustment with constant i

2

t

The second type of adjustment can be performed by

maintaining a constant value of the circuit breaker

specific feed through power.

In this case, the adjustment ensures that the circuit

breaker tripping curve assumes the trend shown on

the figure.

The elimination of the bottom bend, obtained by

adjusting the constant l

2

t tripping time, provides an

advantage for selectivity.

Only B opens

I

s

= instantaneous fixed

Both A and B open

tB = instantaneous

Adjustment with

constant l

2

t

Standard

adjustment

I

cc

(kA)

t (s)

A

B

A

B

(7)

LOGIC SELECTIVITY

Logic selectivity is an advancement on chronometric

coordination. It ensures selectivity also for current

values higher than the instantaneous tripping value.

Logic selectivity is an “intelligent” type of logic.

It is performed through an exchange of information

among electronic MEGATIKER devices wired in

cascade and connected to each other using a pilot

cable.

The advantages of logic selectivity are:

reduction of thermal and electromechanic stresses

on cables and busbars;

total selectivity also for circuit breakers of the same

size;

selectivity on several levels.

In practice, logic selectivity is ensured by using

MEGATIKER electronic Mccb’s with “S” or “T” type

releases, connected in cascade, and interconnected

to each other by a cable on the removable terminal

strip, located at the side of the circuit breaker. This

circuit is operated by an external 12Vd.c. power

supply. In addition, the selector on the electronic

release of the circuit breakers must be set

low

for MEGATIKER circuit breakers set on the lowest

selectivity logic, and

High for all other circuit

breakers upstream. Logic selectivity is not possible

for adjustments with constant I

2

t.

The connection of the pilot cable to same level circuit

breakers can also be performed in parallel between

them, and not necessarily with the upstream circuit

breaker. The fundamental condition is that in both

circuit breakers the cable is connected on the out

terminal.

High Low SEL High Low SEL High Low SEL High Low SEL High Low SEL High Low SEL High Low SEL

out

in

SEL = High SEL = High SEL = High

SEL = Low SEL = Low SEL = Low SEL = Low

411

GENEraL FEaTUrES

411

(8)

Selectivity between

electrical safety devices

Operating principle

In case of short circuit, the circuit breakers detecting

the fault send a signal, through the connection

cable, to the upper level circuit breaker/s, while at

the same time checking for a signal from one or

more lower level circuit breakers. The circuit breaker

within the logic selectivity chain that detects the

short circuit, and does not receive any signal from

downstream circuit breakers, trips immediately,

resetting any set time delays to zero. The circuit

breaker detecting the fault, but also the presence

High Low SEL

Fault 2

High Low SEL High Low SEL High Low SEL High Low SEL High Low SEL High Low SEL SEL = High SEL = Low

SEL = High SEL = High

SEL = Low SEL = Low SEL = Low

Fault 1

A

B

of a signal from a downstream circuit breaker, stays

closed, and complies with the set time delays.

FAUlt 1

The A circuit breaker detects a fault. When no signal

is received from the lower level circuit breakers, A

immediately trips, resetting any set time delays to

zero.

FAUlt 2

A and B circuit breakers detect the fault. Circuit

breaker A receives a signal from the downstream

circuit breaker B and therefore remains closed,

complying with the set time delays. Circuit breaker B

does not receive any signal from lower level circuit

breakers, and therefore trips immediately, resetting

any set time delays to zero.

(9)

DYNaMIC SELECTIVITY

Dynamic selectivity is a special type of combination

used for increasing chronometric selectivity.

It is performed on two levels, with electronic “E”, “S”

and “T” MEGATIKER devices installed upstream, and

MEGATIKER (electronic “E”, “S” and “T”, thermal

magnetic) or BTDIN devices installed downstream.

This solution is recommended with systems featuring

high short circuit current values, when the circuit

breakers coordinated in dynamic selectivity are

within the same distribution board or at a maximum

distance of 3m from each other.

It is also recommended that the line (if in cable) is

installed with double insulation. In practice, dynamic

selectivity is achieved by adjusting the two-position

selector on the circuit breaker release on Low when

standard selectivity levels are required, and on High

when high selectivity levels are needed. Dynamic

coordination can be set for current values higher

than the instantaneous tripping value after checking,

through graphic analysis, the standard overload

and short circuit selectivity as shown in the figure.

Dynamic selectivity coordination applies in fact to

high short circuit current values, which must be

equal or higher than the fixed instantaneous tripping

values.

I

s

= instantaneous fixed

I

/

I

r

t (s)

Operating zone

overload selectivity

Operating zone

circuit selectivity

Operating zone

dynamic selectivity

413

GENEraL FEaTUrES

413

(10)

Selectivity between

electrical safety devices

High Low SEL High Low SEL SEL = Low SEL = Low High Low SEL High Low SEL SEL = Low SEL = High

Dynamic selectivity (“High”)

Selecting “

High” on the upstream circuit breaker,

and “

low” on the downstream one, the relay of

the starting circuit breaker is set to selective mode,

increasing the coordination(of a selective type),

between the two circuit breakers.

Operating principle

Standard selectivity (“low”)

When “

low” is selected, both on the upstream and

the downstream circuit breakers, chronometric or

amperemeter selectivity, as normally set using the

standard criteria, is maintained.

w

(11)

EarTh LEaKaGE SELECTIVITY

Earth fault selectivity is achieved using earth leakage

circuit breakers.

The necessary conditions to ensure an appropriate

level of selectivity are:

selecting circuit breakers with different rated earth

leakage currents, with a minimum ratio of at least

3 times (for example 30 mA downstream circuit

breakers and 100 mA upstream circuit breaker).

the tripping time delay of the upstream circuit

breaker must be longer than the total opening time

of the downstream circuit breaker.

Earth leakage selectivity can be split into two types:

Horizontal earth leakage selectivity

This is achieved with earth leakage circuit breakers

that individually protect one line of users. This

ensures service continuity, but not protection

upstream the circuits.

vertical earth leakage selectivity

This is achieved with earth leakage circuit breakers

installed in cascade. This guarantees maximum

protection, including of the circuits upstream the

individual earth leakage circuit breakers. In order

to optimize selective coordination, circuit breakers

with very different tripping thresholds must be used

(minimum ratio 3), or selective, or delayed devices.

The IEC 60364-5 standard prescribes that in order

to ensure selectivity between two earth leakage

devices, both the above conditions must be met.

Example of horizontal selectivity

id

id

IΔn = 0.03A IΔn = 0.03A

id

id

id

IΔn = 1A Δt = 1s IΔn = 0.3A Δt = 0.6s (type S) IΔn = 0.03A not delayed

Example of vertical selectivity

415

GENEraL FEaTUrES

415

(12)

Back-up protection is the condition, contemplated

by IEC 60364-5 standard, which is achieved when

in a system, a safety device (fuse or circuit breaker)

with breaking capacity lower than the estimated

short circuit current is used, provided that upstream

the device itself, another one is installed, capable of

acting as a support.

Back-up coordination between electrical safety

devices must be confirmed through specific lab

tests, which cannot certainly be performed by the

users or designers of electric systems. To resolve

this problem, Bticino provides a series of tables for

coordination at the various voltages.

This type of device effectively exploits the limitation

capabilities of the electrical safety devices in series.

Back-up

protection

Ib B A A B Icc (kA) I 2t (A 2s) Br ea ki ng c ap ac ity li m it of A P Ib B A A B Icc (kA) I 2t (A 2s) Br ea ki ng c ap ac ity li m it of A As so cia tio n br ea ki ng c ap ac ity B + A Br ea ki ng c ap ac ity li m it of B

COOrDINaTION BETWEEN FUSES UpSTrEaM

aND CIrCUIT BrEaKEr DOWNSTrEaM

When creating back-up coordination between a

fuse and a circuit breaker, as shown in the figure,

the respective power curves can be compared and

superimposed. This type of comparison may identify

an intersection point P between the two curves near

a current value “Ib”, called “switching current”. This

value is the current value below which only the circuit

breaker trips, and above which also the support fuse

trips.

On the other hand, if considering the curves

represented below, for the bands delimited by the

minimum and maximum breaking limits around the lb

value, one would obtain an area of possible tripping

of the two devices at the same time, with two arcs

in series forming at the same time. For currents

definitely superior to Ib, the circuit breaker may also

not trip, and be totally protected by the fuse.

COOrDINaTION BETWEEN UpSTrEaM aND

DOWNSTrEaM CIrCUIT BrEaKErS

In case of back-up coordination between two circuit

breakers in series, the analysis on the power curves

show that there are no intersecting points.

The two curves extend up to the breaking capacity

limits of the individual circuit breakers. The power

curve resulting from the coordination between the

two devices is certainly lower than the curves of each

single circuit breaker taken on its own. This is because

of the limitation effect due to the in series impedance

of the circuit breakers. From this consideration, it

results that the breaking capacity of the association

of two circuit breakers is higher than the one of the

downstream circuit breaker, and that such breaking

capacity can reach the short circuit current value

with which the specific feed through power of the

association, is the same as the maximum that can be

withstood by the device downstream.

(13)

SECTION CONTENTS

418 Reading and understanding the selectivity tables

419 Selectivity with fuses upstream and BTDIN downstream

420 MEGATIKER and gG fuses

421 MEGATIKER upstream and BTDIN downstream (230V a.c.)

422 MEGATIKER upstream and BTDIN downstream (400V a.c.)

423 Thermal magnetic MEGATIKER upstream and downstream (230V a.c.)

424 Thermal magnetic MEGATIKER upstream and downstream (400V a.c.)

425 Thermal magnetic MEGATIKER upstream and downstream (500V a.c.)

426 Electronic MEGATIKER with SEL on Low upstream and MEGATIKER

downstream (230V a.c.)

427 Electronic MEGATIKER with SEL on Low upstream and MEGATIKER

downstream (400V a.c.)

428 Electronic MEGATIKER with SEL on Low upstream and MEGATIKER

downstream (500V a.c.)

429 Electronic MEGATIKER with SEL on High upstream and MEGATIKER

downstream (400V a.c.)

430 MEGABREAK upstream and MEGATIKER downstream

431 BTDIN upstream and motor protectors downstream

SELECTIVITY

TaBLES

417

417

CONTENTS

(14)

reading and understanding

the selectivity tables

400V a.c.

Below are the various tables showing the selectivity between Bticino automatic circuit breakers in accordance with IEC 60947-2 standard requirements.

The coordination tables at the various power supply voltages in three-phase and one-phase systems have been included:

• 230V a.c. • 400V a.c. • 500V a.c.

The values shown represent the selectivity limit starting from the instantaneous (expressed as a kA value), which can be reached from the downstream device, taking into account the breaking capacities of the upstream and downstream devices in compliance with IEC 60947-2 standards. The letter “T” indicates total selectivity up to the breaking capacity limit of the downstream device.

“O” indicates that the selectivity limit corresponds to the Magnetic tripping value of the upstream device.

In situations of coordination with devices fitted with magnetic tripping threshold adjustment, the data shown in the tables refer to the maximum settable values.

In case of coordination with devices fitted with tripping time delay adjustment, the data shown on the table must be considered with the time delay set to “0” (instantaneous tripping).

Unless otherwise stated, the coordination tables with BTDIN Mcb’s refer to C type circuit breakers, with magnetic tripping threshold between 5 and 10 In.

The selectivity between BTDIN Mcb’s is an amperemeter type selectivity, which can be assessed taking into account the corresponding magnetic tripping.

Where coordination with circuit breakers with selectivity limits higher than 20 kA is concerned, time adjustment has no effect and does not improve selectivity itself.

Time adjustments between electronic circuit breakers can be performed with benefits to selectivity, in case of short circuit currents lower than 20 kA.

example of selectivity check

In order to better understand how to use the selectivity tables see the following example.

The aim is to determine the selectivity limit in the coordination between an upstream MEGATIKER Mccb ME125B with In = 125 and a BTDIN Mcb 60 with In = 32A, in a 230V a.c. one-phase system.

Refer to the coordination table on page 419.

Go to the ME125B circuit breaker and look for the 125A value. Scroll through the 125A value column, until the intersection with the BTDIN Mcb 60 at 32A is found.

The value found is 8kA.

This is the coordination selectivity limit, below which only the BTDIN Mcb 60 will trip, and above which both the BTDIN Mcb 60 and the MEGATIKER Mccb ME125B will trip.

In (A) BTDIN 45/60/100/250 C curve upstream

6 10 16 20 25 32 Downstream fuses 2 T T T T T T (Icn=100 kA) 4 – T T T T T 5 – – T T T T 8 – – – T T T 10 – – – – T T 16 – – – – – T

Downstream In (A) aM fuses upstream gG fuses upstream

Mcb’s 32 40 50 63 80 100 125 32 40 50 63 80 100 125 BtDIn 60 6 1.2 1.6 2.2 4 4.2 8 T 1.4 2 2.7 5.5 T T T D curve 10 – 1.4 2 3 3.5 6 9.5 1 1.5 2.2 4.5 7 T T 16 – 1.2 1.5 2.4 3 5 7.5 – 1.3 1.8 3.5 6.5 8 T 20 – 1 1.3 2 2.5 4.2 6 – 1.2 1.6 3 4.7 6.5 T 25 – – 1.2 1.8 2.1 3.7 5 – 1 1.5 2.7 4 5.5 9 32 – – 1 1.5 1.8 3 4 – – 1.1 2.1 3.5 4.7 7.5 40 – – – – 1.7 2.6 3.5 – – – 1.8 1.7 3 6 50 – – – – 1.4 2 3 – – – 1.8 2.5 3.5 5.5 63 – – – – – 2 3 – – – – 2.5 3.5 5.5 BtDIn 100 6 1.2 1.6 2.2 4 4.2 8 14 1.4 2 2.7 5.5 T T T D and K curve 10 – 1.4 2 3 3.5 6 9.5 1 1.5 2.2 4.5 7 11 T 16 – 1.2 1.5 2.4 3 5 7.5 – 1.3 1.8 3.5 6.5 8 15 20 – 1 1.3 2 2.5 4.2 6 – 1.2 1.6 3 4.7 6.5 12 25 – – 1.2 1.8 2.1 3.7 5 – 1 1.5 2.7 4 5.5 9 32 – – 1 1.5 1.8 3 4 – – 1.1 2.1 3.5 4.7 7.5 40 – – – – 1.7 2.6 3.5 – – – 1.8 2.8 4 6 50 – – – – 1.4 2 3 – – – 1.8 2.5 3.5 5.5 63 – – – – – 2 3 – – – – 2.5 3.5 5.5

(15)

Selectivity:

fuses upstream and BTDIN downstream (three-phase system)

400V a.c.

Downstream In (A) aM fuses upstream gG fuses upstream

Mcb’s 25 32 40 50 63 80 100 125 160 32 40 50 63 80 100 125 160 BtDIn 45 6 1 1.6 2.1 3.2 T T T T T 1.3 1.9 2.5 4 T T T T C curve 10 – 1.1 1.7 2.5 T T T T T – 1.6 2.2 3.2 3.6 T T T 16 – 1 1.4 2.1 4 T T T T – 1.4 1.8 2.6 3 T T T 20 – – 1.3 1.8 3.4 T T T T – 1.2 1.5 2.2 2.5 T T T 25 – – 1.1 1.6 3 T T T T – – 1.3 2 2.2 4.1 T T 32 – – – 1.3 2.4 3.8 T T T – – 1.2 1.7 1.9 3.5 T T 40 – – – – 2.1 3.1 4.2 T T – – – – 1.7 3 4 T 50 – – – – 2 2.9 3.7 T T – – – – 1.6 2.6 3.5 4.5 63 – – – – – 2.8 3.5 T T – – – – – 2.4 3.3 4.5 BtDIn 60 6 1 1.6 2.1 3.2 6.2 T T T T 1.3 1.9 2.5 4 4.6 T T T C curve 10 – 1.1 1.7 2.5 5 7.8 T T T – 1.6 2.2 3.2 3.6 7 T T 16 – 1 1.4 2.1 4 6 9 T T – 1.4 1.8 2.6 3 5.6 8 T 20 – – 1.3 1.8 3.4 5.1 7 T T – 1.2 1.5 2.2 2.5 4.6 6.3 T 25 – – 1.1 1.6 3 4.5 6 9.3 T – – 1.3 2 2.2 4.1 5.5 9 32 – – – 1.3 2.4 3.8 5 7.7 9 – – 1.2 1.7 1.9 3.5 4.5 8 40 – – – – 2.1 3.1 4.2 6.4 7 – – – – 1.7 3 4 6 50 – – – – 2 2.9 3.7 6 6 – – – – 1.6 2.6 3.5 5 63 – – – – – 2.8 3.5 5.5 6 – – – – – 2.4 3.3 5 BtDIn 100 6 1 1.6 2.1 3.2 6.2 T T T T 1.3 1.9 2.5 4 4.6 11 T T C curve 10 – 1.1 1.7 2.5 5 7.8 12 T T – 1.6 2.2 3.2 3.6 7 11 T 16 – 1 1.4 2.1 4 6 9 T T – 1.4 1.8 2.6 3 5.6 8 14 20 – – 1.3 1.8 3.4 5.1 7 14 T – 1.2 1.5 2.2 2.5 4.6 6.3 10 25 – – 1.1 1.6 3 4.5 6 9.3 14 – – 1.3 2 2.2 4.1 5.5 7 32 – – – 1.3 2.4 3.8 5 7.7 10 – – 1.2 1.7 1.9 3.5 4.5 6 40 – – – – 2.1 3.1 4.2 6.4 7 – – – – 1.7 3 4 5 50 – – – – 2 2.9 3.7 6 6 – – – – 1.6 2.6 3.5 4 63 – – – – – 2.8 3.5 5.5 6 – – – – – 2.4 3.3 4 80 – – – – – – 3 6 8 – – – – – 3 3 4 100 – – – – – – – 4 5 – – – – – – 3 3.5 125 – – – – – – – – 4 – – – – – – – 3.5 BtDIn 250 6 1 1.6 2.1 3.2 6.2 15 25 25 T 1.3 1.9 2.5 4 4.6 11 25 T C curve 10 – 1.1 1.7 2.5 5 7.8 12 25 T – 1.6 2.2 3.2 3.6 7 11 20 16 – 1 1.4 2.1 4 6 9 21 T – 1.4 1.8 2.6 3 5.6 8 15 20 – – 1.3 1.8 3.4 5.1 7 14 20 – 1.2 1.5 2.2 2.5 4.6 6.3 10 25 – – 1.1 1.6 3 4.5 6 9.3 14 – – 1.3 2 2.2 4.1 5.5 8 32 – – – 1.3 2.4 3.8 5 7.7 10 – – 1.2 1.7 1.9 3.5 4.5 7 40 – – – – 2.1 3.1 4.2 6.4 8 – – – – 1.7 3 4 5 50 – – – – 2 2.9 3.7 6 7 – – – – 1.6 2.6 3.5 4.5 63 – – – – – 2.8 3.5 5.5 7 – – – – – 2.4 3.3 4.5 BtDIn 250H 25 – – 1.1 1.6 3 4.5 6 9.3 14 – – 1.3 2 2.2 4.1 5.5 8 C curve 32 – – – 1.3 2.4 3.8 5 7.7 10 – – 1.2 1.7 1.9 3.5 4.5 7 40 – – – – 2.1 3.1 4.2 6.4 8 – – – – 1.7 3 4 5 50 – – – – 2 2.9 3.7 6 7 – – – – 1.6 2.6 3.5 4.5 63 – – – – – 2.8 3.5 5.5 7 – – – – – 2.4 3.3 4.5

419

419

SELECTIVITY TaBLES

(16)

Selectivity:

MEGaTIKEr and gG fuses (three-phase system)

400V a.c.

Downstream Mccb’s GG fuses upstream

In (A) 200 250 400 800 1000 MA125 125 6 – – – – ME125B 125 – 7.5 – – – ME125n 125 – 10 10 – – ME160B/n/H 160 – – 10 – – ME250B/n/H 250 – – 10 – – MA/MH160 160 – – 10 – – MA/MH/ML250 250 – – 10 – – MA/MH/ML250E 250 – – 10 – – MA400 400 – – – 10 – MH/ML400 400 – – – 25 – MA/MH/ML400E 400 – – – 25 – MA/MH/ML630E 630 – – – – 40 MA/MH/ML630Mt 630 – – – – 40 MA/MH630 630 – – – – 50 ML630 630 – – – – 60 MA/MH/ML800 800 – – – – 60

MEgaTIkEr upstream Icu = 16-25ka Ma ME ME ME 125 125B 160B 250B gg fuse In (A) 125 125 160 250

downstream 50 16 25 – –

80 – – 25 25

MEgaTIkEr upstream Icu = 100ka

ML250 ML400 ML630MT ML630 ML800 ML250E ML400E ML630E

gg fuse In (A) 250 400 630 630 800

downstream 125 100 – – – –

250 – 100 – – –

310 – – 100 100 100

MEgaTIkEr upstream Icu = 70ka

MH160 MH250 MH400 MH630MT MH630 MH800 MH250E MH400E MH630E

gg fuse In (A) 160 250 400 630 630 800 downstream 50 – – – – – – 80 70 – – – – – 125 – 70 – – – – 250 – – 70 – – – 310 – – – 70 70 70

MEgaTIkEr upstream Icu = 36ka

ME125N ME160N ME250N Ma160 Ma250 Ma400 Ma630MT Ma250E Ma400E Ma630E gg fuse In (A) 125 160 250 160 250 400 630 downstream 50 36 – – – – – – 80 – 36 36 36 – – – 125 – – – – 36 – – 250 – – – – – 36 – 310 – – – – – – 36

MEgaTIkEr upstream Icu = 50ka

ME ME Ma Ma 160H 250H 630 800 gg fuse In (A) 160 250 630 800

downstream 80 50 50 – –

(17)

Selectivity:

MEGaTIKEr upstream and BTDIN downstream (one-phase system)

230V a.c.

The table refers to upstream circuit breakers on a 400-415V a.c.

three-phase line, and downstream circuit breakers on a 230V a.c. one-phase line (for all tripping curves B - C - D - K - Z).

Ma125 ME125B ME160B ME250B Ma160 Ma250-250E ME125N ME160N ME250N MH160 MH250-250E ME160H ME250H ML250-250E

In (A) 40 63 100 125 40 63 100 125 100 160 100 160 250 63 100 160 100 160 250 BTDIN 6 to 25 T T T T T T T T T T T T T T T T T T T 45 32 4 4 T T 4 4 T T T T T T T 4 4 T 4 T T 40 – 3.5 T T – 3.5 T T 4 T 4 T T 3.5 3.5 T 3.5 T T 50 – – T T – – T T – T 2 T T – 3 T 3 T T 63 – – T T – – T T – T – T T – 3 T 3 T T BTDIN 6-10 T T T T T T T T T T T T T T T T T T T 60 16 9 9 T T 9 9 T T T T T T T T T T T T T 20 6 6 T T 6 6 T T T T T T T 5 5 T 5 T T 25 5 5 10 10 5 5 10 10 4 T 4 T T 4.5 4.5 T 4.5 T T 32 – 4 8 8 – 4 8 8 4 T 4 T T 4 4 T 4 14 T 40 – 3.5 6 6 – 3.5 6 6 4 T 4 T T 3.5 3.5 T 3.5 9.5 T 50 – – 5 5 – – 5 5 – T 2 T T – 3 T 3 7 T 63 – – 4.5 4.5 – – 4.5 4.5 – T 2 T 7 – 3 T 3 6 T BTDIN 6 T T T T T T T T T T T T T T T T T T T 100 16 9 9 T T 9 9 T T 8 T 8 T T 9 T T T T T 20 6 6 T T 6 6 T T 6 T 6 T T 5 8 T 8 T T 25 5 5 10 10 5 5 10 10 6 10 6 10 T 4.5 6 T 6 T T 32 – 4 7 7 – 4 7 7 4 8 4 8 T 4 6 T 6 T T 40 – 3.5 5.5 5.5 – 3.5 5.5 5.5 3 6 3 6 T 4 6 T 6 T T 50 – – 5 5 – – 5 5 3 6 3 6 9 – 6 8 6 8 T 63 – – 4.5 4.5 – – 4.5 4.5 2 5 2 5 8 – 3 8 3 8 T 80 – – – 2 – – – 2 – 5 – 5 7 – – 8 – 8 T 100 – – – – – – – – – 4 – 4 6 – – 6 – 6 T 125 – – – – – – – – – 2 – 2 5 – – 3 – 3 8 BTDIN 6 – – – – T T T T T T T T T T T T T T T 250 10 – – – – T T T T 9 T T T T T T T T T T 16 – – – – 9 9 T T 7 T 9 T T 9 12 T 12 T T 20 – – – – 6 6 17 17 6 20 9 T T 5 10 T 10 T T 25 – – – – 5 5 10 10 4 10 7 10 T 4.5 8 T 8 T T 32 – – – – – 4 7 7 4 10 5 8 T 4 6 T 6 T T 40 – – – – – 3.5 5.5 5.5 2.5 7 4 6 12 3.5 6 12 6 12 T 50 – – – – – – 5 5 – 7 3 6 9 – 6 8 6 10 T 63 – – – – – – 4.5 4.5 – 7 3 6 7 – 6 8 6 10 T BTDIN 25 – – – – 5 5 10 10 4 10 7 10 T 4.5 8 T 8 T T 250H 32 – – – – – 4 7 7 4 10 5 8 T 4 6 T 6 T T 40 – – – – – 3.5 5.5 5.5 2.5 7 4 6 12 3.5 6 12 6 12 T 50 – – – – – – 5 5 – 7 3 6 9 – 6 8 6 10 T 63 – – – – – – 4.5 4.5 – 7 3 6 7 – 6 8 6 10 T

Ma400 Ma630MT Ma400-630E Ma630 to 1250 Ma630 to 1600ES MH400 MH630MT MH400-630E MH630 to 1250 MH630 to 1600ES ML400 ML630MT ML400-630E ML630 to 1250 In (A) 250 320 400 500 630 160 250 400 630 500 630 800 1000 1250 630 800 1250 1600 BTDIN 45 6 to 63 T T T T T T T T T T T T T T T T T T BTDIN 60 6 to 63 T T T T T T T T T T T T T T T T T T BTDIN 100 6 to 125 T T T T T T T T T T T T T T T T T T BTDIN 250 6 to 63 T T T T T T T T T T T T T T T T T T BTDIN 250H 25 to 63 T T T T T T T T T T T T T T T T T T

421

421

SELECTIVITY TaBLES

(18)

Selectivity:

MEGaTIKEr upstream and BTDIN downstream (three-phase system)

400V a.c.

Ma125 ME125B ME160B ME250B Ma160 Ma250-250E ME125N ME160N ME250N MH160 MH250-250E ME160H ME250H ML250-250E

In (A) 40 63 100 125 40 63 100 125 100 160 100 160 250 63 100 160 100 160 250 BTDIN 6-10 T T T T T T T T T T T T T T T T T T T 45 16-20 T T T T T T T T T T T T T 4 T T T T T 25 T T T T T T T T 4 T 4 T T 3 T T T T T 32 3 3 4 4 3 3 4 4 3.5 T 3.5 T T 2 T T T T T 40 – 3 3 3 – 3 3 3 2.5 T 2.5 T T 2 T T T T T 50 – – 3 3 – – 3 3 2 T 2 T T – 4 T 4 T T 63 – – 3 3 – – 3 3 – T – T T – 4 T 4 T T BTDIN 6 T T T T T T T T T T T T T T T T T T T 60 10 5 5 T T 5 5 T T T T T T T 5 T T T T T 16 4 4 T T 4 4 T T T T 8 T T 4 T T T T T 20 4 4 5 5 4 4 5 5 5 T 6 T T 4 T T T T T 25 3 3 4.5 4.5 3 3 4.5 4.5 4 T 5 T T 3 T T T T T 32 3 3 4 4 3 3 4 4 3.5 T 4 T T 2 5 T 5 T T 40 – 3 3 3 – 3 3 3 2.5 T 3.5 T T 2 5 T 5 T T 50 – – 3 3 – – 3 3 2 5.5 3 5.5 T – 4 T 4 T T 63 – – 3 3 – – 3 3 – 5 2 5 5 – 4 T 4 T T BTDIN 6 6 6 T T 6 6 T T T T T T T 6 T T T T T 100 10 5 5 6 6 5 5 6 6 7 T T T T 5 T T T T T 16 4 4 6 6 4 4 6 6 6 T 8 T T 4 T T T T T 20 3 3 5 5 3 3 5 5 5 T 6 T T 4 8 T 8 T T 25 3 3 4.5 4.5 3 3 4.5 4.5 4 8.5 5 8.5 T 3 6 T 6 T T 32 – 2 4 4 – 2 4 4 3.5 7 4 7 T 2 5 T 5 T T 40 – 2 3 3 – 2 3 3 2.5 6 3.5 6 T 2 5 T 5 T T 50 – – 3 3 – – 3 3 2 5.5 3 5.5 7 – 4 8 4 8 T 63 – – 3 3 – – 3 3 2 5 – 5 5 – 4 8 4 8 T 80 – – – 2 – – – 2 – 5 – 5 5 – – 8 – 8 T 100 – – – – – – – – – 4 – 4 4 – – 6 – 6 T 125 – – – – – – – – – 2 – 2 3 – – 3 – 3 8 BTDIN 6 – – – – 6 6 13 13 12 T T T T 6 T T T T T 250 10 – – – – 5 5 7.5 7.5 7 T T T T 5 15 T 15 T T 16 – – – – 4 4 6 6 6 18 8 T T 4 10 T 10 T T 20 – – – – 3 3 5 5 5 12 6 T T 4 8 T 8 T T 25 – – – – 3 3 4.5 4.5 4 8.5 5 8.5 T 3 6 T 6 T T 32 – – – – – 2 4 4 3.5 7 4 7 T 2 5 T 5 T T 40 – – – – – 2 3 3 2.5 6 3.5 6 10 2 5 10 5 10 T 50 – – – – – – 3 3 2 5.5 3 5.5 7 – 4 8 4 8 T 63 – – – – – – 3 3 – 5 2 5 5 – 4 8 4 8 T BTDIN 25 – – – – 3 3 4.5 4.5 4 8.5 5 8.5 T 3 6 T 6 T T 250H 32 – – – – – 2 4 4 3.5 7 4 7 T 2 5 T 5 T T 40 – – – – – 2 3 3 2.5 6 3.5 6 10 2 5 10 5 10 T 50 – – – – – – 3 3 2 5.5 3 5.5 7 – 4 8 4 8 T 63 – – – – – – 3 3 – 5 2 5 5 – 4 8 4 8 T

Ma400 Ma630MT Ma400-630E Ma630 to 1250 Ma630 to 1600ES MH400 MH630MT MH400-630E MH630 to 1250 MH630 to 1600ES ML400 ML630MT ML400-630E ML630 to 1250 In (A) 250 320 400 500 630 160 250 400 630 500 630 800 1000 1250 630 800 1250 1600 BTDIN 45 6 to 63 T T T T T T T T T T T T T T T T T T BTDIN 60 6 to 63 T T T T T T T T T T T T T T T T T T BTDIN 100 6 to 125 T T T T T T T T T T T T T T T T T T BTDIN 250 6 to 63 T T T T T T T T T T T T T T T T T T BTDIN 250H 25 to 63 T T T T T T T T T T T T T T T T T T

(19)

Selectivity: thermal magnetic MEGaTIKEr upstream

and downstream (one-phase system)

230V a.c.

MEGAtIKER MEGAtIKER upstream

downstream MA125 ME160B ME250B MA160 MA250 MA400 MA630Mt MA630 MA800 MA1250 ME125B ME160n ME250n MH160 MH250 MH400 MH630Mt MH630 MH800 MH1250 ME125n ME160H ME250H ML250 ML400 ML630Mt ML630 ML800 ML1250

In (A) 40 63 100 to 125 40 63 100 160 250 63 100 160 250 250 320 400 500 630 500 630 800 1000 1250 MA125 16 0.8 1 1.2 – 0.6 1 1.6 2.5 0.6 1 1.6 2.5 6 6 6 6 8 12 16 16 16 16 ME125B/n 25 0.8 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 12 16 16 16 16 40 – 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 12 16 16 16 16 63 – – 1.2 – – – 1.6 2.5 – – 1.6 2.5 6 6 6 6 8 12 16 16 16 16 100 – – – – – – 1.6 2.5 – – 1.6 2.5 4 4 4 6 8 12 16 16 16 16 125 – – – – – – 1.6 2.5 – – 1.6 2.5 4 4 4 6 8 12 16 16 16 16 ME160B/n/H 25 – – – 0.4 0.6 1 1.6 2.5 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 ME250B/n/H 40 – – – – 0.6 1 1.6 2.5 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 63 – – – – – 1 1.6 2.5 – 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 100 – – – – – – 1.6 2.5 – – 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 160 – – – – – – – 2.5 – – – 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 250 – – – – – – – – – – – – – 3.2 4 5 6.3 12 16 16 16 16 MA/MH160 25 – – – – – – – – 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 MA/MH/ML250 40 – – – – – – – – 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 63 – – – – – – – – – 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 100 – – – – – – – – – – 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 160 – – – – – – – – – – – 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 250 – – – – – – – – – – – – – 3.2 4 5 6.3 12 16 16 16 16 MA/MH/ML250E 40 – – – – – – – – – – – – – – 4 5 6.3 12 16 16 16 16 63 – – – – – – – – – – – – – – 4 5 6.3 12 16 16 16 16 100 – – – – – – – – – – – – – – 4 5 6.3 12 16 16 16 16 160 – – – – – – – – – – – – – – 4 5 6.3 12 16 16 16 16 250 – – – – – – – – – – – – – – 4 5 6.3 12 16 16 16 16 MA/MH/ML400 250 – – – – – – – – – – – – – 3.2 4 5 6.3 12 16 16 16 16 MA/MH/ML630Mt 320 – – – – – – – – – – – – – – 4 5 6.3 12 16 16 16 16 400 – – – – – – – – – – – – – – – 5 6.3 12 16 16 16 16 500 – – – – – – – – – – – – – – – – 6.3 – – – – – 630 – – – – – – – – – – – – – – – – – – – – – – MA/MH/ML400E 160 – – – – – – – – – – – – – – – – 6.3 5 6.3 8 6 8 MA/MH/ML630E 250 – – – – – – – – – – – – – – – – 6.3 5 6.3 8 6 8 400 – – – – – – – – – – – – – – – – 6.3 5 6.3 8 6 8 630 – – – – – – – – – – – – – – – – – – – 8 6 8 MA/MH/ML 500 – – – – – – – – – – – – – – – – – – 5 8 – 7.5 630 to 1250 630 – – – – – – – – – – – – – – – – – – – 8 – 7.5 800 – – – – – – – – – – – – – – – – – – – – – – 1000 – – – – – – – – – – – – – – – – – – – – – 7.5 1250 – – – – – – – – – – – – – – – – – – – – – –

423

423

SELECTIVITY TaBLES

(20)

Selectivity: thermal magnetic MEGaTIKEr upstream and

downstream (three-phase system)

400V a.c.

MEgaTIkEr MEgaTIkEr upstream

downstream Ma125 ME160B ME250B Ma160 Ma250 Ma400 Ma630MT Ma630 Ma800 Ma1250 ME125B ME160N ME250N MH160 MH250 MH400 MH630MT MH630 MH800 MH1250 ME125N ME160H ME250H ML250 ML400 ML630MT ML630 ML800 ML1250

In (A) 40 63 100-125 40 63 100 160 250 63 100 160 250 250 320 400 500 630 500 630 800 1000 1250 Ma125 16 0.8 1 1.2 – 0.63 1 1.6 2.5 0.63 1 1.6 2.5 6 6 6 6 8 12 16 16 16 16 25 0.8 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 12 16 16 16 16 40 – 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 12 16 16 16 16 63 – – 1.2 – – – 1.6 2.5 – – 1.6 2.5 6 6 6 6 8 12 16 16 16 16 100-125 – – – – – – 1.6 2.5 – – 1.6 2.5 4 4 4 6 8 12 16 16 16 16 ME125B 16 0.8 1 1.2 – 0.63 1 1.6 2.5 0.63 1 1.6 2.5 6 6 6 6 8 12 16 16 16 16 ME125N 25 0.8 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 12 16 16 16 16 40 – 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 12 16 16 16 16 63 – – 1.2 – – – 1.6 2.5 – – 1.6 2.5 6 6 6 6 8 12 16 16 16 16 100-125 – – – – – – 1.6 2.5 – – 1.6 2.5 4 4 4 6 8 12 16 16 16 16 ME160B/N/H 25 – – – 0.4 0.63 1 1.6 2.5 0.63 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 ME250B/N/H 40 – – – – 0.63 1 1.6 2.5 0.63 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 63 – – – – – 1 1.6 2.5 – 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 100 – – – – – – 1.6 2.5 – – 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 160 – – – – – – – 2.5 – – – 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 250 – – – – – – – – – – – – – 3.2 4 5 6.3 12 16 16 16 16 Ma/MH160 25-40 – – – – – – – – 0.63 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 Ma/MH/ML250 63 – – – – – – – – – 1 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 100 – – – – – – – – – – 1.6 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 160 – – – – – – – – – – – 2.5 2.5 3.2 4 5 6.3 12 16 16 16 16 250 – – – – – – – – – – – – – 3.2 4 5 6.3 12 16 16 16 16 Ma250E 40 to 250 – – – – – – – – – – – – – – 4 5 6.3 12 16 16 16 16 MH/ML250E 40 to 250 – – – – – – – – – – – – – 3.2 4 5 6.3 12 16 16 16 16 Ma/MH/ML400 250 – – – – – – – – – – – – – 3.2 4 5 6.3 10 10 10 10 10 Ma/MH/ML630MT 320 – – – – – – – – – – – – – – 4 5 6.3 10 10 10 10 10 400 – – – – – – – – – – – – – – – 5 6.3 10 10 10 6 7.5 500 – – – – – – – – – – – – – – – – 6.3 – 10 10 6 7.5 630 – – – – – – – – – – – – – – – – – – – 10 6 7.5 Ma/MH/ML400E 160 – – – – – – – – – – – – – – – – 6.3 5 6.3 8 6 8 Ma/MH/ML630E 250 – – – – – – – – – – – – – – – – 6.3 5 6.3 8 6 8 400 – – – – – – – – – – – – – – – – 6.3 5 6.3 8 6 8 630 – – – – – – – – – – – – – – – – – – – 8 6 8 Ma/MH/ML 500 – – – – – – – – – – – – – – – – – – 5 8 – 7.5 630 to 1250 630 – – – – – – – – – – – – – – – – – – – 8 7.5 7.5 800 – – – – – – – – – – – – – – – – – – – – 7.5 7.5 1000 – – – – – – – – – – – – – – – – – – – – – 7.5 1250 – – – – – – – – – – – – – – – – – – – – – –

(21)

500V a.c.

MEgaTIkEr MEgaTIkEr upstream

downstream Ma125 ME160B ME250B Ma160 Ma250 Ma400 Ma630MT Ma630 Ma800 Ma1250 ME125B ME160N ME250N MH160 MH250 MH400 MH630MT MH630 MH800 MH1250 ME125N ME160H ME250H ML250 ML400 ML630MT ML630 ML800 ML1250

In (A) 40 63 100-125 40 63 100 160 250 63 100 160 250 250 320 400 500 630 500 630 800 1000 1250 Ma125 16 0.8 1 1.2 – 0.6 1 1.6 2.5 0.6 1 1.6 2.5 6 6 6 6 8 T T T T T ME125B 25 0.8 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 T T T T T 40 – 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 T T T T T 63 – – 1.2 – – – 1.6 2.5 – – 1.6 2.5 6 6 6 6 8 T T T T T 100-125 – – – – – – 1.6 2.5 – – 1.6 2.5 4 4 4 6 8 T T T T T ME125N 16 0.8 1 1.2 – 0.6 1 1.6 2.5 0.6 1 1.6 2.5 6 6 6 6 8 12 12 12 12 12 25 0.8 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 12 12 12 12 12 40 – 1 1.2 – – 1 1.6 2.5 – 1 1.6 2.5 6 6 6 6 8 12 12 12 12 12 63 – – 1.2 – – – 1.6 2.5 – – 1.6 2.5 6 6 6 6 8 12 12 12 12 12 100-125 – – – – – – 1.6 2.5 – – 1.6 2.5 4 4 4 6 8 12 12 12 12 12 ME160B/N 25 – – – 0.4 0.6 1 1.6 2.5 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 T T T T T ME250B/N 40 – – – – 0.6 1 1.6 2.5 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 T T T T T 63 – – – – – 1 1.6 2.5 – 1 1.6 2.5 2.5 3.2 4 5 6.3 T T T T T 100 – – – – – – 1.6 2.5 – – 1.6 2.5 2.5 3.2 4 5 6.3 T T T T T 160 – – – – – – – 2.5 – – – 2.5 2.5 3.2 4 5 6.3 T T T T T 250 – – – – – – – – – – – – – 3.2 4 5 6.3 T T T T T ME160H 25 – – – 0.4 0.6 1 1.6 2.5 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 ME250H 40 – – – – 0.6 1 1.6 2.5 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 63 – – – – – 1 1.6 2.5 – 1 1.6 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 100 – – – – – – 1.6 2.5 – – 1.6 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 160 – – – – – – – 2.5 – – – 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 250 – – – – – – – – – – – – – 3.2 4 5 6.3 12 12 12 12 12 Ma/MH160 25 – – – – – – – – 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 Ma/MH/ML250 40 – – – – – – – – 0.6 1 1.6 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 63 – – – – – – – – – 1 1.6 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 100 – – – – – – – – – – 1.6 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 160 – – – – – – – – – – – 2.5 2.5 3.2 4 5 6.3 12 12 12 12 12 250 – – – – – – – – – – – – – 3.2 4 5 6.3 12 12 12 12 12 Ma/MH/ML250E 40 – – – – – – – – – – – – – – 4 5 6.3 12 12 12 12 12 63 – – – – – – – – – – – – – – 4 5 6.3 12 12 12 12 12 100 – – – – – – – – – – – – – – 4 5 6.3 12 12 12 12 12 160 – – – – – – – – – – – – – – 4 5 6.3 12 12 12 12 12 250 – – – – – – – – – – – – – – 4 5 6.3 12 12 12 12 12 Ma/MH/ML 250 – – – – – – – – – – – – – 3.2 4 5 6.3 12 12 12 12 12 400 to 630MT 320 – – – – – – – – – – – – – – 4 5 6.3 12 12 12 12 12 400 – – – – – – – – – – – – – – – 5 6.3 12 12 12 12 12 500 – – – – – – – – – – – – – – – – – – – – – – 630 – – – – – – – – – – – – – – – – – – – – – – Ma/MH/ML400E 160 – – – – – – – – – – – – – – – – 6.3 5 6.3 8 6 8 Ma/MH/ML630E 250 – – – – – – – – – – – – – – – – 6.3 5 6.3 8 6 8 400 – – – – – – – – – – – – – – – – 6.3 5 6.3 8 6 8 630 – – – – – – – – – – – – – – – – – – – 8 6 8 Ma/MH/ML 500 – – – – – – – – – – – – – – – – – – 5 8 – 7.5 630 to 1250 630 – – – – – – – – – – – – – – – – – – – 8 – 7.5 800 – – – – – – – – – – – – – – – – – – – – – – 1000 – – – – – – – – – – – – – – – – – – – – – 7.5 1250 – – – – – – – – – – – – – – – – – – – – – –

425

425

SELECTIVITY TaBLES

(22)

Selectivity: electronic MEGaTIKEr with SEL on Low

upstream and MEGaTIKEr downstream

230V a.c.

MEgaTIkEr MEgaTIkEr upstream

downstream Ma250E Ma400E Ma630E Ma630 to 800ES (E) Ma800ES (E–S–T) Ma1250ES (E–S–T) Ma1600ES (E–S–T) MH250E MH400E MH630E MH630 to 800ES (E) MH800ES (E–S–T) MH1250ES (E–S–T) MH1600ES (E–S–T) ML250E ML400E ML630E

In (A) 40 63 100 160 250 160 250 400 630 630 800 630 800 1250 1600 Ma125 16-25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 16 16 T T T T ME125B/N 40 – 3.5 3.5 3.5 3.5 6 6 6 6 16 16 T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 16 16 T T T T 100-125 – – – 3.5 3.5 6 6 6 6 16 16 T T T T ME160B/N/H 25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 20 20 T T T T ME250B/N/H 40 – 3.5 3.5 3.5 3.5 8 8 8 8 20 20 T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 20 20 T T T T 100 – – – 3.5 3.5 6 6 6 6 20 20 T T T T 160 – – – – 3.5 – 6 6 6 20 20 T T T T 250 – – – – – – – 6 6 20 20 T T T T Ma/MH160 25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 20 20 40 40 40 40 Ma/MH/ML250 40 – 3.5 3.5 3.5 3.5 8 8 8 8 20 20 40 40 40 40 63 – – 3.5 3.5 3.5 6 8 8 8 20 20 40 40 40 40 100 – – – 3.5 3.5 6 8 8 8 20 20 40 40 40 40 160 – – – – 3.5 – 8 8 8 20 20 40 40 40 40 250 – – – – – – – 6 6 20 20 40 40 40 40 Ma/MH/ML250E 40 – 0.63 1 1.6 2.5 8 8 8 8 20 20 40 40 40 40 63 – – 1 1.6 2.5 6 6 6 6 20 20 40 40 40 40 100 – – – 1.6 2.5 6 6 6 6 20 20 40 40 40 40 160 – – – – 2.5 – 6 6 6 20 20 40 40 40 40 250 – – – – – – – 6 6 20 20 40 40 40 40 Ma/MH/ML400 250-320 – – – – – – – 6 6 20 20 40 40 40 40 Ma/MH/ML630MT 400 – – – – – – – – 6 20 20 40 40 40 40 Ma/MH/ML400E 160 – – – – – – 5 5 5 20 20 40 40 40 40 Ma/MH/ML630E 250 – – – – – – – 5 5 20 20 40 40 40 40 400 – – – – – – – – 5 20 20 40 40 40 40 630 – – – – – – – – – – 20 – 40 40 40 Ma/MH/ML630 500 – – – – – – – – – 20 20 30 30 30 30 to 1250 630 – – – – – – – – – – 20 – 30 30 30 800-1000 – – – – – – – – – – – – – 30 30 1250 – – – – – – – – – – – – – – 30 Ma/MH630ES (E–S–T) 630 – – – – – – – – – – 20 – 20 20 20 Ma/MH800ES (E–S–T) 800 – – – – – – – – – – – – – 20 20 Ma/M1250ES (E–S–T) 1250 – – – – – – – – – – – – – – 20

(23)

400V a.c.

MEgaTIkEr MEgaTIkEr upstream

downstream Ma250E Ma400E Ma630E Ma630 to 800ES (E) Ma800ES (E–S–T) Ma1250ES (E–S–T) Ma1600ES (E–S–T) MH250E MH400E MH630E MH630 to 800ES (E) MH800ES (E–S–T) MH1250ES (E–S–T) MH1600ES (E–S–T) ML250E ML400E ML630E

In (A) 40 63 100 160 250 160 250 400 630 630 800 630 800 1250 1600 Ma125 16-25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 T T T T T T ME125B 40 – 3.5 3.5 3.5 3.5 6 6 6 6 T T T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 T T T T T T 100-125 – – – 3.5 3.5 6 6 6 6 T T T T T T ME125N 16-25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 25 25 T T T T 40 – 3.5 3.5 3.5 3.5 6 6 6 6 25 25 T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 25 25 T T T T 100-125 – – – 3.5 3.5 6 6 6 6 25 25 T T T T ME160B/N/H 25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 20 20 T T T T ME250B/N/H 40 – 3.5 3.5 3.5 3.5 8 8 8 8 20 20 T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 20 20 T T T T 100 – – – 3.5 3.5 6 6 6 6 20 20 T T T T 160 – – – – 3.5 – 6 6 6 20 20 T T T T 250 – – – – – – – 6 6 20 20 T T T T Ma160 25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 20 20 T T T T Ma250 40 – 3.5 3.5 3.5 3.5 8 8 8 8 20 20 T T T T 63 – – 3.5 3.5 3.5 6 8 8 8 20 20 T T T T 100 – – – 3.5 3.5 6 8 8 8 20 20 T T T T 160 – – – – 3.5 – 8 8 8 20 20 T T T T 250 – – – – – – – 6 6 20 20 T T T T MH/ML160 25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 20 20 30 30 30 36 MH/ML250 40 – 3.5 3.5 3.5 3.5 8 8 8 8 20 20 30 30 30 36 63 – – 3.5 3.5 3.5 6 8 8 8 20 20 30 30 30 36 100 – – – 3.5 3.5 6 8 8 8 20 20 30 30 30 36 160 – – – – 3.5 – 8 8 8 20 20 30 30 30 36 250 – – – – – – – 6 6 20 20 30 30 30 36 Ma250E 40 – 0.63 1 1.6 2.5 8 8 8 8 20 20 T T T T 63 – – 1 1.6 2.5 6 6 6 6 20 20 T T T T 100 – – – 1.6 2.5 6 6 6 6 20 20 T T T T 160 – – – – 2.5 – 6 6 6 20 20 T T T T 250 – – – – – – – 6 6 20 20 T T T T MH/ML250E 40 – 0.63 1 1.6 2.5 8 8 8 8 20 20 30 30 30 36 63 – – 1 1.6 2.5 6 6 6 6 20 20 30 30 30 36 100 – – – 1 2.5 6 6 6 6 20 20 30 30 30 36 160 – – – – 2.5 – 6 6 6 20 20 30 30 30 36 250 – – – – – – – 6 6 20 20 30 30 30 36 Ma400–630MT 250-320 – – – – – – – 6 6 15 15 20 20 20 T 400 – – – – – – – – 6 15 15 20 20 20 T 500 – – – – – – – – – 10 10 20 20 20 T 630 – – – – – – – – – – 10 20 20 T MH/ML400 250-320 – – – – – – – 6 6 15 15 20 20 20 36 MH/ML630MT 400 – – – – – – – – 6 15 15 20 20 20 36 500 – – – – – – – – – 10 10 20 20 20 36 630 – – – – – – – – – – 10 20 20 36 Ma400E 160 – – – – – – 5 5 5 15 15 20 20 20 T Ma630E 250 – – – – – – – 5 5 15 15 20 20 20 T 400 – – – – – – – – 5 15 15 20 20 20 T 630 – – – – – – – – – – 15 – 20 20 T MH/ML400E 160 – – – – – – 5 5 5 15 15 15 15 30 36 MH/ML630E 250 – – – – – – – 5 5 15 15 15 15 30 36 400 – – – – – – – – 5 15 15 20 20 20 36 630 – – – – – – – – – – 15 – 20 30 36 Ma/MH/ML630 500 – – – – – – – – – 15 15 10 15 15 20 to 1250 630 – – – – – – – – – – 15 – 20 20 20 800-1000 – – – – – – – – – – – – – 20 20 1250 – – – – – – – – – – – – – – 20 Ma/MH630ES (E–S–T) 630 – – – – – – – – – – 15 – 15 15 20 Ma/MH800ES (E–S–T) 800 – – – – – – – – – – – – – 15 20 Ma/MH1250ES (E–S–T) 1250 – – – – – – – – – – – – – – 20

427

427

SELECTIVITY TaBLES

(24)

Selectivity: electronic MEGaTIKEr with SEL on Low

upstream and MEGaTIKEr downstream

500V a.c.

MEgaTIkEr MEgaTIkEr upstream

downstream Ma250E Ma400E Ma630E Ma630 to 800ES (E) Ma800ES (E–S–T) Ma1250ES (E–S–T) Ma1600ES (E–S–T) MH250E MH400E MH630E MH630 to 800ES (E) MH800ES (E–S–T) MH1250ES (E–S–T) MH1600ES (E–S–T) ML250E ML400E ML630E

In (A) 40 63 100 160 250 160 250 400 630 630 800 630 800 1250 1600 Ma125 16-25 3.5 3.5 3.5 3.5 3.5 T T T T T T T T T T 40 – 3.5 3.5 3.5 3.5 6 6 6 6 T T T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 T T T T T T 100-125 – – – 3.5 3.5 6 6 6 6 T T T T T T ME125B 16-25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 T T T T T T 40 – 3.5 3.5 3.5 3.5 6 6 6 6 T T T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 T T T T T T 100-125 – – – 3.5 3.5 6 6 6 6 T T T T T T ME125N 16-25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 12 12 T T T T 40 – 3.5 3.5 3.5 3.5 6 6 6 6 12 12 T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 12 12 T T T T 100-125 – – – 3.5 3.5 6 6 6 6 12 12 T T T T ME160B/N 25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 T T T T T T ME250B/N 40 – 3.5 3.5 3.5 3.5 8 8 8 8 T T T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 T T T T T T 100 – – – 3.5 3.5 6 6 6 6 T T T T T T 160 – – – – 3.5 – 6 6 6 T T T T T T 250 – – – – – – – 6 6 T T T T T T ME160H 25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 12 12 T T T T ME250H 40 – 3.5 3.5 3.5 3.5 8 8 8 8 12 12 T T T T 63 – – 3.5 3.5 3.5 6 6 6 6 12 12 T T T T 100 – – – 3.5 3.5 6 6 6 6 12 12 T T T T 160 – – – – 3.5 – 6 6 6 12 12 T T T T 250 – – – – – – – 6 6 12 12 T T T T Ma/MH160 25 3.5 3.5 3.5 3.5 3.5 8 8 8 8 12 12 T T T T Ma/MH/ML250 40 – 3.5 3.5 3.5 3.5 8 8 8 8 12 12 T T T T 63 – – 3.5 3.5 3.5 6 8 8 8 12 12 T T T T 100 – – – 3.5 3.5 6 8 8 8 12 12 T T T T 160 – – – – 3.5 – 8 8 8 12 12 T T T T 250 – – – – – – – 6 6 12 12 T T T T Ma/MH/ML250E 40 – 0.63 1 1.6 2.5 8 8 8 8 12 12 T T T T 63 – – 1 1.6 2.5 6 6 6 6 12 12 T T T T 100 – – – 1.6 2.5 6 6 6 6 12 12 T T T T 160 – – – – 2.5 – 6 6 6 12 12 T T T T 250 – – – – – – – 6 6 12 12 T T T T Ma/MH/ML400–630MT 250-320 – – – – – – – 6 6 12 10 T T T T 400 – – – – – – – – 6 12 10 T T T T 500 – – – – – – – – – – – – – – – 630 – – – – – – – – – – – – – – – Ma/MH/ML400E 160 – – – – – – 5 5 5 12 12 T T T T Ma/MH/ML630E 250 – – – – – – – 5 5 12 12 T T T T 400 – – – – – – – – 5 12 12 T T T T 630 – – – – – – – – – – 12 – T T T Ma/MH/ML630 500 – – – – – – – – – 12 12 T T T T to 1250 630 – – – – – – – – – – 12 – T T T 800-1000 – – – – – – – – – – – – – T T 1250 – – – – – – – – – – – – – – T Ma/MH630–800ES (E) 630 – – – – – – – – – – 12 – 20 20 20 800 – – – – – – – – – – – – – 20 20 Ma/MH630ES (E–S–T) 630 – – – – – – – – – – 20 – 20 20 20 Ma/MH800ES (E–S–T) 800 – – – – – – – – – – – – – 20 20 Ma/MH1250ES (E–S–T) 1250 – – – – – – – – – – – – – – 20

(25)

Selectivity: electronic MEGaTIKEr with SEL on high

upstream and MEGaTIKEr downstream

400V a.c.

MEgaTIkEr MEgaTIkEr upstream

downstream Ma400E Ma630E Ma630 to 800ES (E) Ma800ES (E–S–T) Ma1250ES (E–S–T) Ma1600ES (E–S–T) MH400E MH630E MH630 to 800ES (E) MH800ES (E–S–T) MH1250ES (E–S–T) MH1600ES (E–S–T) ML400E ML630E In (A) 160 250 400 630 630 800 630 800 1250 1600 ME125B 16 to 125 T T T T T T T T T T ME125N 16 to 125 T T T T T T T T T T ME160B/N/H* 25 to 160 T T T T T T T T T T ME250B/N/H* 250 – – T T T T T T T T Ma160 25 to 160 T T T T T T T T T T Ma250 250 – – T T T T T T T T MH/ML160 25 to 160 36 36 36 36 36 36 36 36 36 36 MH/ML250 250 – 36 36 36 36 36 36 36 36 36 Ma250E 40 to 160 T T T T T T T T T T 250 – T T T T T T T T T MH/ML250E 40 to 160 36 36 36 36 36 36 36 36 36 36 250 – 36 36 36 36 36 36 36 36 36 Ma400–630MT 250 – – 25 25 T T T T T T 320 to 500 – – – 25 T T T T T T 630 – – – – – T T T T MH/ML400 250 – – 25 25 36 36 36 36 36 36 MH/ML630MT 320 to 500 – – – 25 36 36 36 36 36 36 630 – – – – – 36 36 36 36 Ma400E 160-250 – 25 25 T T T T T T Ma630E 400 – – – 25 T T T T T T 630 – – – – – T – T T T MH/ML400E 160-250 – 25 25 36 36 36 36 36 36 MH/ML630E 400 – – – 25 36 36 36 36 36 36 630 – – – – – 36 – 36 36 36 Ma/MH/ML630 to 1250 500-630 – – – – – T – T T T 800-1000 – – – – – – – – T T 1250 – – – – – – – – – T Ma/MH630ES (E–S–T) 630 – – – – – 36 – 36 36 36 800 – – – – – – – – 36 36 Ma/MH800ES (E–S–T) 630 – – – – – 36 – 36 36 36 800 – – – – – – – – 36 36 Ma/MH1250ES (E–S–T) 1250 – – – – – – – – – 36 * For ME160H and ME250H, selectivity, with MEGATIKER upstream up to MA/MH/ML/630E, is equal to 36.

429

429

SELECTIVITY TaBLES

References

Related documents

1 illustrates, when the first screen test was negative, there would be no second and third tests, and these patients were counted as “missing.” By the additional two

27 MIDFIELD comprises whole population data for undergraduate, degree-seeking students—those who matriculate in engineering, those who switch into engineering from other

Response to the table addressing analysis shows that power method of addressing (the magnitude square of the source signal addressing) provides better output power spectrum than

 Canon imageRUNNER ADVANCE multi-function device with ColorPASS GX200 controller (EFI-based DFE)  Canon imagePRESS production color printer with imagePRESS Server A 1100

(1) We confirm and complements the findings by Anda [6], by extracting maintainability factors that are important from the software maintainer’s perspective, and (2) Based on

[r]

To derive a taxonomy from existing models, our research includes two steps: (1) the analysis of the generic process of reputation systems and (2) the identification of

Background: To compare serum uric acid levels in type 2 diabetes mellitus patients with no obvious complications and healthy controls.. Methods: 50 non-diabetics as controls and