DACS
SMPS Power plant division
DACS
SMPS POWER PLANT
Model: DACS 48-450
DACS
SMPS Power plant division
1. ABSTRACT
• DC power plant Commissioning.
• This document describes the procedure for commissioning of power plant.
2. MAIN SPECIFICATION FOR CABINET 2.1 MECHANICAL CHARACTERISTICS
Cabinet DACS 48-450
Width 573 mm
Depth 600 mm
Height 1500 mm
Max. Number of rectifiers (50A). 9 Max. Weight of one module 11 Kg Max. Total weight of fully
equipped cabinet
170 Kg
2.2 ENVIRONMENTAL CHARACTERISTICS ► Operation temperature : -5°C to 55°C ► Storage temperature : -5°C to +70°C
►Relative humidity : 10 to 95% non condensing ►Operating altitude : 0 - 3000 m
COMMISSIONING MANUAL
DACS 48-450
DACS
SMPS Power plant division
2.3 UPSTEAM CIRCUIT BREAKER TYPE AND CABLE DIAMETER
DACS 48-450
Size and tripping curve
Circuit breaker (three phase) 63A
Mains cable size
Minimum (mm²) 10
Maximum (mm²) 25
3. TOOLS AND DOCUMENTS NECESSARY FOR COMMISSIONING 3.1 Documents needed for commissioning:
• Electrical diagram of system.
3.2 Test equipments needed for commissioning: • 1 Load Bank
• Digital Multimeter (DMM) • Digital Ammeter
DACS
SMPS Power plant division
4. PRELIMINARY CHECKS 4.1 CONFORMITY WITH THE SPECIFICATION:
The installation and the connection of the equipment should be checked before all action.
4.2 INSTALLATION CHECK
• Installation general aspect
• Equipment aspect (no spot, stripe, wrapping, oxidation, edge smoothing).
• Painting aspect
• Minimum clearance between side and walls: 1 m
4.3 CABINET CHECK
1. Check wiring, whether any of the connectors are loose in transportation. Check especially the presence and cross-section of:
a. The link between 0V bus bar and earth.
b. The link between cabinet earth and site earth network. 2 Check fixing of cabinet.
3 In case of false floor, cabinets should be fixed on metallic support by 4 points. In case of concrete floor; cabinet is fixed directly on the ground by 4 points.
DACS
SMPS Power plant division
5. EARTHING GUIDELINES
1. Two numbers of Earth studs are provided on the topside of the power plant with crimping lugs.
2. Crimp the lugs with proper tools.
3. Connect the Earth cable to power plant on any or both Earth terminations.
4. Use at least 10 Sq. mm. Wires for the termination of earth to the power plant.
5. Measure the Earth resistance; it should be less than 0.5 Ohms.
6. Proper earth is required to communicate with the remote site through RS-485.
7. Connect earth to the foundation bolts.
8. Separate earth should be used for +Ve grounding.
9. Timely watering the earth pit is essential so that its resistance will be within limit.
10. Use only Copper/Lead Plates and bus bars for earth continuity.
11. Use at least four earth pits and short it with bus bar to achieve good results.
12. Improper earth to the power plant may cause failure to the power plant due to lightning.
6. ENERGIESING OF THE POWER PLANT
1 All disconnecting devices should be in the {{open}} position. Check that the mains voltage and frequency is as indicated in the name plate. 2 Do not install the modules before the mains and battery wirings are
completed.
3 For easy accessibility, remove the modules before operate the battery fuses or disconnecting switches.
4 Switch ON AC I/P MCB & DC O/P MCB off all the modules.
5 A healthy module will indicate DC voltage and current on DSCA by pressing UP key on front panel LCD.
6 Close all fuse – disconnecting switches and load protecting circuits of the power stations.
7 Check for proper operation of the system according to technical data sheets.
DACS
SMPS Power plant division
7. COMMISSIONNING TESTS 7.1 Check the measurements on System Display
• AC Voltage • Load Voltage • Load Current • Battery 1 Current • Battery 2 Current • Battery 3 Current • System Current • Battery Status 7.2 OPERATING CHECKS • Float Voltage 54.0V ±1% at 27°C • Charge Voltage 55.2V ±1% at 27°C
• Switch OFF mains, the system will change over from mains I/P to battery, which will generate alarm of “Mains Low” with audible alarm.
• The power cut – off or pre alarm when the battery voltage reaches the setting threshold “Load volt low” and “Bat disconnect” alarm displayed. To achieve this test, replace the battery by the DC power supply and disconnect all the rectifiers.
• Check “FR/FC XX NOT PRE” alarm by switching off the I/P O/P MCB of rectified module.
• Decrease system Float voltage till 44.0 V. Rectifier under voltage operates and on FR/FC as an alarm red LED DC Fail / DC UV glows. The same alarm is extended to DSA as “FR/FC XX FAIL”.
• Check “Battery X absent” by Dialing the non-zero AH capacity in menu without connecting batteries to the system.
• Check “Batt X Isolated” by Dialing the 000 AH capacity in menu when all the batteries are connected to the system.
• Check “ONLY ONE BATT!!” by manually isolating the batteries one by one. This alarm appears when only one battery is connected and user wants to isolate it.
• Check “Temp X comp fail” alarm by shorting or disconnecting the external battery temperature-sensing device.
DACS
SMPS Power plant division
8. ALARM TERMINAL BLOCK • Connection is made on terminal block
• Loop ON/OFF characteristics: 100V max. – 0.5A Alarm on terminal block:
There are two number of NO, NC potential free contacts provided to extend all fault conditions. Contacts definition: • NO – Normally Open • NC – Normally Close • P - Pole
9. SYSTEM ASSIGNMENT
9.1 SYSTEM MENU PARAMETER To go into programming mode press Menu select key.
Press “UP arrow” key and “Down arrow” key for scrolling the parameters in menu.
The parameters in the Menu are as follows: 13. Mains High (480V to 470V). 14. Mains Low (320V to 340V).
15. System over load (100% to 105%) 16. System Float V (44.0V to 56.4V) 17. System Charge V (44.6V to 57.0V) 18. Load Voltage HI (56.0 V to 57.0V) 19. Load Voltage Low (45.5 V to 46.5V) 20. Bat 1 AH cap (000, 100, 200--- 2000) 21. Bat 2 AH cap (000, 100, 200--- 2000) 22. Bat 3 AH cap (000, 100, 200--- 2000) 23. Bat Disconnect V (44.4V to 45.5V) 24. Bat Reconnect V (51.6V to 55.2V) 25. No of FR/FC’s (1 to 9) 26. Edit FR/FC No (1 to 9)
a) Set Float Volt (44.0V to 56.4V) b) Set Charge Volt (44.6V to 57.0V) c) Set Over Volt (56.0V to 57.0V) d) Set under Volt (44.5V to 45.5V) e) Set over Load (40% to 110%)
DACS
SMPS Power plant division
27. Temp comp limit (50.4 to 52.8)
9.2 SYSTEM Menu Tree (Flow chart)
Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Press Menu
Set value Exit
Set value Exit
Mains high
Mains low
System over
load Set value Exit
System Float V Set value Exit
System Charge
V Set value Exit
Load voltage hi Set value Exit
Load voltage
low Set value Exit
Bat 1 AH cap Set value Exit
Bat 2 AH cap Set value Exit
Bat 3 AH cap Set value Exit Enter password
DACS
SMPS Power plant division
Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter Bat
Disconnect Set value Exit
Set value Exit
Set value Exit
Bat reconnect
No of FR/FC’s
Edit FR/FC No (Slot no)
Set Float Volt Set value Exit
Set Charge
Volt Set value Exit
Set Over Volt Set value Exit
Set under Volt Set value Exit
Set over Load Set value Exit
Temp comp
DACS
SMPS Power plant division
9.3 PARAMETER PROGRAMING PROCEDURE
While normal working of power plant on display the upper portion shows “System current” ,”Load current”, “ System voltage”, “Battery1 current”, “Battery2 current”, Battery 3 current”, “Mains voltage”.
The lower portion of LCD will display status of system and any alarm occurred during normal working condition.
To change settings of the parameters in the power plant go into menu. System will ask for a password.
Using UP & DOWN, arrow keys adjust number 203 on display and press ENTER key. Now the user can enter into menu.
Menu Alarm
Select Reset Enter
SYSTEM CURR 450
AUTO CHARGE
Menu Alarm
Select Reset Enter
DC VOLTS 54.0
PASSWORD 203
DACS
SMPS Power plant division
1. The first parameter in menu is “Mains HI”.
a. Press menu select key. Lower portion of LCD will display the parameter “Mains HI” and the Upper portion will display the present setting.
b. If “Mains HI” is not to be changed go to the next parameter using UP arrow key.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP arrow and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 470V to 480V and the default value is 480.
2. The next parameter in menu after “Mains HI” is “Mains Low”.
a. Press UP arrow key after “Mains HI” menu. Lower portion of LCD will display the parameter “Mains low” and the Upper portion will display the present setting.
b. If “Mains low” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 320V to 340V and the default value is 320.
Menu Alarm
Select Reset Enter
480
DACS
SMPS Power plant division
3. The next parameter in menu after “Mains low” is “System over load”.
a. Press UP arrow key after “Mains low” menu. Lower portion of LCD will display the parameter “system over load” and the Upper portion will display the present setting.
b. If “system over load” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 100 to 105% and the default value is 105%.
Menu Alarm
Select Reset Enter
320
MAINS LOW
Menu Alarm
Select Reset Enter
105
DACS
SMPS Power plant division
4. The next parameter in menu after “System overload” is “System float V”.
a. Press UP arrow key after “System over load” menu. Lower portion of LCD will display the parameter “System float V” and the Upper portion will display the present setting.
b. If “System float V” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 44.0V to 57.0V and the default value is 54.0V.
5. The next parameter in menu after “System float V” is “System charge V”. a. Press UP arrow key after “System float V” menu. Lower portion of LCD will
display the parameter “System charge V” and the Upper portion will display the present setting.
b. If “System charge V” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 44.0V to 57.0V and the default value is 55.2V.
Note: There is a lock (0.6V difference) between system float voltage and system charge voltage (always charge voltage > float voltage).
Menu Alarm
Select Reset Enter
54.0
DACS
SMPS Power plant division
6. The next parameter in menu after “System charge V” is “Load voltage HI”. a. Press UP arrow key after “System charge V” menu. Lower portion of LCD
will display the parameter “Load voltage HI” and the Upper portion will display the present setting.
b. If “Load voltage HI” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 56.0V to 57.0V and the default value is 56.1.
Menu Alarm
Select Reset Enter
55.2
SYSTEM CHARGE V
Menu Alarm
Select Reset Enter
56.1
DACS
SMPS Power plant division
7. The next parameter in menu after “Load voltage HI” is “Load voltage low”. a. Press UP arrow key after “Load voltage HI” menu. Lower portion of LCD
will display the parameter “Load voltage low” and the Upper portion will display the present setting.
b. If “Load voltage HI” is not to be changed, go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press, “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 45.5V to 46.5V and the default value is 45.7.
8. The next parameter in menu after “Load voltage low” is “Bat 1 AH CAP”.
a. Press UP arrow key after “Load voltage low” menu. Lower portion of LCD will display the parameter “Bat 1 AH CAP” and the Upper portion will display the present setting.
b. If “Bat 1 AH CAP” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. Menu Alarm
Select Reset Enter
45.7
DACS
SMPS Power plant division
f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 000 to 2000 and the default value is 200.
Note: To isolate battery 1 set “bat 1 AH cap” 000AH.
CAUTION: Enter the correct AH capacity of the battery after reconnecting to the power plant.
9. The next parameter in menu after “Bat 1 AH CAP” is “Bat 2 AH CAP”.
a. Press UP arrow key after “Bat 1 AH CAP” menu. Lower portion of LCD will display the parameter “Bat 2 AH CAP” and the Upper portion will display the present setting.
b. If “Bat 2 AH CAP” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 000 to 2000 and the default value is 200.
Note: To isolate battery 2 set “bat 2 AH cap” 000AH.
CAUTION: Enter the correct AH capacity of the battery after reconnecting to the power plant.
Menu Alarm
Select Reset Enter
200
DACS
SMPS Power plant division
10. The next parameter in menu after “Bat 2 AH CAP” is “Bat 3 AH CAP”.
a. Press UP arrow key after “Bat 2 AH CAP” menu. Lower portion of LCD will display the parameter “Bat 3 AH CAP” and the Upper portion will display the present setting.
b. If “Bat 3 AH CAP” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 000 to 2000 and the default value is 200.
Note: To isolate battery 3 set “bat 3 AH cap” 000AH.
CAUTION: Enter the correct AH capacity of the battery after reconnecting to the power plant.
Menu Alarm
Select Reset Enter
200
BAT 2 AH CAP
Menu Alarm
Select Reset Enter
200
DACS
SMPS Power plant division
11. The next parameter in menu after “Bat 3 AH CAP” is “Bat Disconnect V”. a. Press UP arrow key after “Bat 3 AH CAP” menu. Lower portion of LCD will
display the parameter “Bat Disconnect V” and the Upper portion will display the present setting.
b. If “Bat Disconnect V” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
g. Settable range for this parameter is 44.4V to 45.5V and the default value is 44.4V.
12. The next parameter in menu after “Bat Disconnect V” is “Bat Reconnect V”. a. Press UP arrow key after “Bat Disconnect V” menu. Lower portion of LCD
will display the parameter “Bat Reconnect V” and the Upper portion will display the present setting.
b. If “Bat Reconnect V” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
Menu Alarm
Select Reset Enter
44.4
DACS
SMPS Power plant division
g. Settable range for this parameter is 51.6V to 55.2V and the default value is 51.6V.
13. The next parameter in menu after “Bat Reconnect V” is “No of FR/FC’s”. a. Press UP arrow key after “Bat Reconnect V” menu. Lower portion of LCD
will display the parameter “No of FR/FC’s” and the Upper portion will display the present setting.
b. If “No of FR/FC’s” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To change the present setting press “ENTER” Key. d. Present setting will start blinking.
e. Using UP and DOWN arrow key set the new value. f. Press ENTER key to acknowledge the new setting.
NOTE: Always enter the number of FR/FC’s switched ON. Other wise there will be alarm of “Mod CONFIG Err” or “FR/FC?? NOT PRE”.
Menu Alarm
Select Reset Enter
51.6
BAT RECONNECT V
Menu Alarm
Select Reset Enter
09
DACS
SMPS Power plant division
14. The next parameter in menu after “No of FR/FC’s” is “EDT FR/FC No”.
a. Press UP arrow key after “No of FR/FC’s” menu. Lower portion of LCD will display the parameter “EDT FR/FC No” and the Upper portion will display the present setting.
b. If “EDT FR/FC No” is not to be changed go to the next or previous parameter using UP and DOWN arrow keys.
c. To edit the parameters in required module press “ENTER” Key. d. Last edited module number will start blinking.
e. Using UP and DOWN arrow key set the new module is to be edited. f. Press ENTER key.
The parameters of module, which user can change from system level, are: a. SET FLOAT VOLT (44.0V to 57.0V) default is 54.0V.
b. SET CHARGE VOLT (44.0V to 57.0V) default is 55.2V. c. SET OVER VOLT (56.0V to 57.0V) default is 57.0V. d. SET UNDER VOLT (45.0V to 46.0V) default is 45.0V. e. SET OVER LOAD (40% to 110%) default is 110%.
Note: All the above FR/FC parameters are effective only when controller is not communicating with the module. Controller settings will over ride the locally generated module parameters.
a. Set float voltage:
I. Press menu select display appears “SET FLOAT VOLT” in lower portion of the LCD and value from 44.0 to 57.0 in the upper portion. II. Press, “ENTER” key. Value in upper portion starts blinking.
III. Using UP and DOWN arrow key set required float voltage. IV. Press Enter key to acknowledge the program.
Menu Alarm
Select Reset Enter
01
DACS
SMPS Power plant division
b. Set Charge voltage:
I. If float voltage is not to be set after “SET FLOAT VOLT” in lower portion of the LCD press up arrow key to get “SET CHARGE VOLT” in the lower portion.
II. Press ENTER Key. The upper portion will start blinking with current setting (from 44.0 to 57.0)
III. Press, “ENTER” key. Value in upper portion starts blinking. IV. Using UP and DOWN arrow key set required charge voltage. V. Press Enter key to acknowledge the program.
c. Set Over voltage:
I. If charge voltage is not to be set press UP arrow key after “SET CHARGE VOLT”, the next menu is “SET OVER VOLT”. Settable range is from 56.0 to 57.0 in the upper portion.
II. Press, “ENTER” key. Value in upper portion starts blinking. III. Using UP and DOWN arrow key set required over voltage. IV. Press Enter key to acknowledge the program.
Menu Alarm
Select Reset Enter
54.0
SET FLOAT VOLT
Menu Alarm
Select Reset Enter
55.2
DACS
SMPS Power plant division
d. Set Under voltage:
I. If over voltage is not to be set press UP arrow key after “SET OVER VOLT”, the next menu is “SET UNDER VOLT”. Settable range is from 45.0 to 46.0 in the upper portion.
II. Press, “ENTER” key. Value in upper portion starts blinking. III. Using UP and DOWN arrow key set required under voltage. IV. Press Enter key to acknowledge the program.
e. Set OVER LOAD:
I. If Under voltage is not to be set press UP arrow key after “SET UNDER VOLT”, the next menu is “SET OVER LOAD”. Settable range is from 40% to 110% in the upper portion.
II. Press, “ENTER” key. Value in upper portion starts blinking.
III. Using UP and DOWN arrow key set required overload in percentage.
IV. Press Enter key to acknowledge the program. V. Default value is 110%
Menu Alarm
Select Reset Enter
56.0
SET OVER VOLT
Menu Alarm
Select Reset Enter
45.0
DACS
SMPS Power plant division
15. The next parameter in menu after “No of FR/FC’s” is “EDT FR/FC No”.
a. Press UP arrow key after “No of FR/FC’s” menu. Lower portion of LCD will display the parameter “EDT FR/FC No” and the Upper portion will display the present setting.
b. If “EDT FR/FC No” is not to be changed, go to the next or previous parameter using UP and DOWN arrow keys.
c. To edit the parameters in required module press “ENTER” Key. d. Last edited module number will start blinking.
e. Using UP and DOWN arrow key set the new module to be edited. f. Press ENTER key.
Menu Alarm
Select Reset Enter
110%
DACS
SMPS Power plant division
9.4 SYSTEM IDENTIFICATION MENU (TO FACILITATE RS – 485) 9.4.1 SYSTEM Menu Tree (Flow chart)
Enter Enter Enter Enter Enter Enter Enter Enter Enter Enter
Enter Enter Enter
Enter Enter
Enter Enter Enter
Enter Enter
Enter Enter Enter
Press Enter & Down arrow
Set first byte Set second byte Set value Set third byte Hand shake byte
System make Exit Set fourth byte
Date of
commisning Set month Exit
Batt 1 make Exit
Exit
Date of
commisning Set month Set year Exit Set year
Set value
Batt 2 make Exit
Date of
commisning Set month Set year Exit Set value
Batt 2 make Exit
Date of
commissioning Set month Set year Exit Set value
DACS
SMPS Power plant division
8.4.2 SYSTEM IDENTITY PROGRAMMING
This programming is to be done while installing the power plant and batteries. To change settings in system identity programming menu press ENTER & DOWN arrow key at a time and while releasing first ENTER & then DOWN arrow keys.
1. The first parameter in this menu is “HAND SHAKE BYTE”.
a. Press Enter & Down arrow keys simultaneously. Lower portion of LCD will display the parameter “HAND SHAKE BYTE” and the Upper portion will display the present setting.
b. If “Mains HI” is not to be changed, go to the next parameter using UP arrow key.
c. To change the present setting press, “ENTER” Key. d. First byte will start blinking.
e. Using UP arrow and DOWN arrow key set first byte and press Enter key. f. Second byte will start blinking.
g. Using UP arrow and DOWN arrow key set second byte and press Enter key.
h. Third byte will start blinking.
i. Using UP arrow and DOWN arrow key set third byte and press Enter key. j. Fourth byte will start blinking.
k. Using UP arrow and DOWN arrow key set fourth byte. l. Press ENTER key to acknowledge the new setting. m. Settable range for every byte is 00 to FF.
Note: First four bytes of RS 485 remote monitoring system data and power plant should be always same otherwise there will be communication error.
Menu Alarm
Select Reset Enter
FF FF FF FF
DACS
SMPS Power plant division
2. The next parameter in this menu after “HAND SHAKE BYTE” is “System MAKE”. In this menu user has to give the identity number to identify the power plant make from remote computer.
a. Press UP arrow keys after “HAND SHAKE BYTE” Lower portion of LCD will display the parameter “SYSTEM MAKE” and the Upper portion will display the present setting.
b. If “SYSTEM MAKE” is not to be changed, go to the next parameter using UP arrow key.
c. To change the present setting press, “ENTER” Key. d. The present value will start blinking.
e. Using UP arrow and DOWN arrow key set new setting. f. Press ENTER key to acknowledge the new setting. g. Settable range for every byte is 00 to FF.
3. The next parameter in this menu after “SYSTEM MAKE” is “DATE OF COMMISIONN”. In this menu user has to set the month and year of commissioning of power plant.
a. Press UP arrow keys after “SYSTEM MAKE” Lower portion of LCD will display the parameter “DATE OF COMMISIONN” and the Upper portion will display the present setting.
b. If “DATE OF COMMISIONN” is not to be changed, go to the next parameter using UP arrow key.
c. To change the present setting press, “ENTER” Key. d. The last month setting entered will start blinking.
e. Using UP arrow and DOWN arrow key set new setting. Press ENTER key. f. The last year-entered setting will start blinking.
g. Using UP arrow and DOWN arrow key set new setting. (MM YY) h. Press ENTER key to acknowledge the new setting.
Menu Alarm
Select Reset Enter
FF
DACS
SMPS Power plant division
4. The next parameter in this menu after power plant “DATE OF COMMISIONN” is “BATT 1 MAKE”. In this menu user has to give the identity number to identify the Battery 1 make connected to power plant from remote computer.
a. Press UP arrow keys after “DATE OF COMMISIONN” Lower portion of LCD will display the parameter “BATT 1 MAKE” and the Upper portion will display the present setting.
b. If “BATT 1 MAKE” is not to be changed, go to the next parameter using UP arrow key.
c. To change the present setting press, “ENTER” Key. d. The present value will start blinking.
e. Using UP arrow and DOWN arrow key set new setting. f. Press ENTER key to acknowledge the new setting. g. Settable range for every byte is 00 to FF.
Menu Alarm
Select Reset Enter
05 06
DATE OF COMMISIONN
Menu Alarm
Select Reset Enter
FF
DACS
SMPS Power plant division
5. The next parameter in this menu after “BATT 1 MAKE” is “DATE OF COMMISIONN” of battery 1. In this menu user has to set the month and year of commissioning of Battery1 connected to power plant.
a. Press UP arrow keys after “BATT 1 MAKE” Lower portion of LCD will display the parameter “DATE OF COMMISIONN” and the Upper portion will display the present setting.
b. If “DATE OF COMMISIONN” is not to be changed, go to the next parameter using UP arrow key.
c. To change the present setting press, “ENTER” Key. d. The last month setting entered will start blinking.
e. Using UP arrow and DOWN arrow key set new setting. Press ENTER key. f. The last year-entered setting will start blinking.
g. Using UP arrow and DOWN arrow key set new setting. (MM YY) h. Press ENTER key to acknowledge the new setting.
6. The next parameter in this menu after Battery1 “DATE OF COMMISIONN” is “BATT 2 MAKE”. In this menu user has to give the identity number to identify the Battery 2 make connected to power plant from remote computer.
a. Press UP arrow keys after “DATE OF COMMISIONN” Lower portion of LCD will display the parameter “BATT 2 MAKE” and the Upper portion will display the present setting.
Menu Alarm
Select Reset Enter
12 06
DACS
SMPS Power plant division
b. If “BATT 2 MAKE” is not to be changed, go to the next parameter using UP arrow key.
c. To change the present setting press, “ENTER” Key. d. The present value will start blinking.
e. Using UP arrow and DOWN arrow key set new setting. f. Press ENTER key to acknowledge the new setting. g. Settable range for every byte is 00 to FF.
7. The next parameter in this menu after “BATT 2 MAKE” is “DATE OF COMMISIONN” of battery 2. In this menu user has to set the month and year of commissioning of Battery1 connected to power plant.
a. Press UP arrow keys after “BATT 2 MAKE” Lower portion of LCD will display the parameter “DATE OF COMMISIONN” and the Upper portion will display the present setting.
b. If “DATE OF COMMISIONN” is not to be changed, go to the next parameter using UP arrow key.
c. To change the present setting press, “ENTER” Key. d. The last month setting entered will start blinking.
e. Using UP arrow and DOWN arrow key set new setting. Press ENTER key. f. The last year-entered setting will start blinking.
g. Using UP arrow and DOWN arrow key set new setting. h. Press ENTER key to acknowledge the new setting.
Menu Alarm
Select Reset Enter
FF
DACS
SMPS Power plant division
8. The next parameter in this menu after Battery2 “DATE OF COMMISIONN” is “BATT 3 MAKE”. In this menu user has to give the identity number to identify the Battery 3 make connected to power plant from remote computer.
a. Press UP arrow keys after “DATE OF COMMISIONN” Lower portion of LCD will display the parameter “BATT 3 MAKE” and the Upper portion will display the present setting.
b. If “BATT 3 MAKE” is not to be changed, go to the next parameter using UP arrow key.
c. To change the present setting press, “ENTER” Key. d. The present value will start blinking.
e. Using UP arrow and DOWN arrow key set new setting. f. Press ENTER key to acknowledge the new setting. g. Settable range for every byte is 00 to FF.
Menu Alarm
Select Reset Enter
12 06
DATE OF COMMISIONN
Menu Alarm
Select Reset Enter
FF
DACS
SMPS Power plant division
9. The next parameter in this menu after “BATT 3 MAKE” is “DATE OF COMMISIONN” of battery 3. In this menu user has to set the month and year of commissioning of Battery3 connected to power plant.
a. Press UP arrow keys after “BATT 3 MAKE” Lower portion of LCD will display the parameter “DATE OF COMMISIONN” and the Upper portion will display the present setting.
b. If “DATE OF COMMISIONN” is not to be changed, go to the next parameter using UP arrow key.
c. To change the present setting press, “ENTER” Key. d. The last month setting entered will start blinking.
e. Using UP arrow and DOWN arrow key set new setting. Press ENTER key. f. The last year-entered setting will start blinking.
g. Using UP arrow and DOWN arrow key set new setting. h. Press ENTER key to acknowledge the new setting.
Menu Alarm
Select Reset Enter
12 06
DACS
SMPS Power plant division
10. SYSTEM STATUS AND ALARM INDICATIONS
The upper portion of the LCD always keeps on scrolling system voltages and currents i.e. “MAINS VOLT XXX “, “SYSTEM VOLT XX.X “, “SYSTEM CURR XXX “, “BATT 1 CURR XXX “, “BATT 2 CURR XXX “, “BATT 3 CURR XXX “, and “LOAD CURR XXX” (XXX is the actual value).
In normal working condition, scrolling of parameters may be stopped to observe continuously any one parameter by pressing “ENTER” key. When scrolling is stopped, there is “*” sign after the parameter.
Again to put into scrolling mode press, “ENTER” key. Scrolling will start and “*” sign will disappear.
The status and any alarm occurred in system is displayed on the lower portion of the LCD. If there is any fault occurred in the system then it will go on scrolling the massages.
10.1 SYSTEM STATUS
1. When individual battery current is less than 3% of the AH capacity i.e. fully charged then the system will be in Auto float mode
Menu Alarm
Select Reset Enter
SYSTEM CURR 450 *
AUTO CHARGE
Menu Alarm
Select Reset Enter
BATT 1 CURR 003
AUTO FLOAT
DACS
SMPS Power plant division
2. When any battery current is more than 5% of the AH capacity i.e. Battery in discharged condition then the system will be in Auto charge mode.
3. When Mains AC is in specified limits and system is working on Mains AC voltage then there is a status of “POWER MAINS”.
4. When Mains AC is in out of specified limits and system is working on stand by Generator AC source then there is a status of “POWER STAND BY”.
Menu Alarm
Select Reset Enter
BATT 1 CURR 020
AUTO CHARGE
Menu Alarm
Select Reset Enter
BATT 1 CURR 040
POWER MAINS
Menu Alarm
Select Reset Enter
BATT 1 CURR 040
POWER STAND BY
DACS
SMPS Power plant division
5. When Mains ac is out of specified limits then system will change over to battery. At this time, there is an alarm of “LOAD ON BATT”.
6. To monitor the individual module Voltage and current press UP Arrow key. One by one it will display FR/FC Voltage and current of the number of modules present in the system in scrolling manner and will restore to the system display after releasing the Key. Also it will show the version No and software Check sum value of the individual FR/FC module.
Menu Alarm
Select Reset Enter
BATT 1 CURR 040
LOAD ON BATTERY
Menu Alarm
Select Reset Enter
54.0 V 50.1A
FR/FC 1 1-DOE9
DACS
SMPS Power plant division
7. To monitor the Version No and Check sum value of the system press Alarm reset and Down arrow Key simultaneously.
8. To observe the temperature of the battery temperature compensation sensors press down arrow key in normal working condition. First temperature is of battery1 second is of battery2 and third is of battery3.
9. To observe the ID of system press alarm reset and ENTER key simultaneously. The ID of the system is settable from 00 to 0F. To change ID inset Jumper on the DSA mother board on different position to achieve the required ID(Useful in RS-485 communications.)
Menu Alarm
Select Reset Enter
BATT 1 CURR 020
28° 27°C 25°C 28°C
Menu Alarm
Select Reset Enter
CHECK SUM 2FDA
VERSION NO. 001
DACS
SMPS Power plant division
Mother Board view
10. To observe that whether modules are communicating to the system or not press “ENTER” and “UP arrow” Key. The COM STATUS will be a 01FF If all nine modules are working and communicating with DSCA. Here 1 is for 9th module (“1” if ON and “0” if OFF). Next “F” in COM status stands for
Menu Alarm
Select Reset Enter
BATT 1 CURR 020
PWR PLANT ID 0F
DSA MOTHER BOARD
Jumper to change ID
Batt Monitor card slot AC DC Card slot
PFC BTC Board
cable
Control connector
Ac connector Curr sense Con
Communication
DACS
SMPS Power plant division
module no 5 to 8. This value will change from 0 to F as per the module condition (ON or OFF). Next “F” in COM status stands for module no 1 to 4. This value will change from 0 to F as per the module condition (ON or OFF). The details to identify which module is not communicating with DSCA is given in the table below.
Mod
8
Mod
7
Mod
6
Mod
5
HEX
CODE
Mod
4
Mod
3
Mod
2
Mod
1
HEX
CODE
OFF OFF OFF OFF
0
OFF OFF OFF OFF
0
OFF OFF OFF
ON
1
OFF OFF OFF
ON
1
OFF OFF
ON
OFF
2
OFF OFF
ON
OFF
2
OFF OFF
ON ON
3
OFF OFF
ON ON
3
OFF
ON
OFF OFF
4
OFF
ON
OFF OFF
4
OFF
ON
OFF
ON
5
OFF
ON
OFF
ON
5
OFF
ON ON
OFF
6
OFF
ON ON
OFF
6
OFF
ON ON ON
7
OFF
ON ON ON
7
ON
OFF OFF OFF
8
ON
OFF OFF OFF
8
ON
OFF OFF
ON
9
ON
OFF OFF
ON
9
ON
OFF
ON
OFF
A
ON
OFF
ON
OFF
A
ON
OFF
ON ON
B
ON
OFF
ON ON
B
ON ON
OFF OFF
C
ON ON
OFF OFF
C
ON ON
OFF
ON
D
ON ON
OFF
ON
D
ON ON ON
OFF
E
ON ON ON
OFF
E
ON ON ON ON
F
ON ON ON ON
F
Menu Alarm
Select Reset Enter
SYSTEM CURR 107
COM STATUS 01FF
DACS
SMPS Power plant division
When all 9 modules are working and communicating with the DSCA then there is 01FF in COM status.
11. To load the default setting (Factory settings) press, “ENTER” and “Menu Select” Key there will be a message of “DEFAULT LOADED” and system will follow factory settings.
10.2 SYSTEM ALARMS
1. When Mains AC is within the specified limits and still battery is discharging then there is an alarm of “AC OK BATT DISC”.
Menu Alarm
Select Reset Enter
BATT 1 CURR 040
AC OK BATT DISC
Menu Alarm
Select Reset Enter
SYSTEM CURR 107
DEFAULT LOADED
DACS
SMPS Power plant division
2. When Stage 2 surge arrestor fails due to lightning then there is an alarm of “STAGE II FAIL”.
3. When the system current more than the preset percentage entered in the menu then there is an alarm of “SYSTEM OVER LOAD”. This alarm appears as per the total number of working modules in the system. The settable range in the menu is 100% to 105% of the system working capacity.
Menu Alarm
Select Reset Enter
BATT 1 CURR 040
STAGE II FAIL
Menu Alarm
Select Reset Enter
SYSTEM CURR 472
SYSTEM OVER LOAD
DACS
SMPS Power plant division
4. When the number of working module preset in the system more than the number of module entered in the Menu then there is an alarm of “FR/FC CONFIG ERR”. This alarm will disappear only when correct number of working modules entered in Menu.
5. Due to any reason, if module is failed and on module, there is an alarm of “FR/FC FAIL” then there is an alarm of “FR/FC XX FAIL” on system (XX stands for number of module).
6. Due to any reason, if module is not communicating with system or switching OFF any module, creates an alarm of “FR/FC XX NOT PRE” (XX stands for number of module). If the module is identified then it will show the respective number or it will show “FR/FC ?? NOT PRE”. If the module number is unknown, check number of FR/FC entered in menu.
Menu Alarm
Select Reset Enter
SYSTEM CURR 100
FR/FC CONFIG ERR
Menu Alarm
Select Reset Enter
SYSTEM CURR
100
FR/FC XX FAIL
DACS
SMPS Power plant division
7. To disconnect the battery from the system, select 000AH capacity for each battery. As soon as user selects 000AH, the DC contactor of the respective battery turns OFF. There is an interlock in the system that at least one battery will always be connected to the system. When user goes for selection of 000AH capacity of the last battery connected to the power plant as soon as he acknowledges it with “ENTER” key there is a massage “ONLY ONE BATT!!”. This last command is not accepted by the system, the previous AH capacity remains unchanged and also the respective DC contactor does not turns OFF.
8. When Mains AC voltage is more than the Mains high cut OFF voltage set in the menu then there is an alarm of “MAINS HIGH”. During the alarm the mains supply of the modules are isolated due to which modules are in OFF condition. When Mains AC voltage restores back with in the specified limit (Hysterisis of 10V is given to operate and release levels) there is a delay of 10sec(approx) to turn ON the modules.
Menu Alarm
Select Reset Enter
000AH
ONLY ONE BATT!!
Menu Alarm
Select Reset Enter
SYSTEM CURR 100
FR/FC XX NOT PRE
DACS
SMPS Power plant division
9. When Mains AC voltage is less than the Mains low cut OFF voltage set in the menu then there is an alarm of “MAINS LOW”. During the alarm the mains supply of the modules are isolated due to which modules are in OFF condition. When Mains AC voltage restores back with in the specified limit (Hysterisis of 10V is given operate and release levels) there is a delay of 10sec (approx) to turn ON the modules.
10. If some how the system voltage increases beyond the LOAD VOLT HI value then there is an alarm of “LOAD VOLT HIGH”. This alarm is PRE WARN alarm for battery disconnection.
Menu Alarm
Select Reset Enter
MAINS VOLT 490
MAINS HIGH
Menu Alarm
Select Reset Enter
MAINS VOLT 310
MAINS LOW
DACS
SMPS Power plant division
11. If Mains AC voltage is out of specified limit then the system works on battery and battery starts discharging. When the battery voltage reaches below the LOAD VOLT LOW value set in the menu then there is an alarm of “LOAD VOLT LOW”. This alarm is PRE WARN indication before battery disconnection voltage.
12. When battery is discharged below LOAD VOLT LOW condition and when the battery voltage reaches below the BAT DISCONNECT V value set in the menu then there is an alarm of “BATT DISCONNECT”. This alarm disconnects all the batteries (through DC contactors) connected to the system. Now battery will reconnect only when the system voltage rises above the BAT RECONNECT V set in Menu.
Menu Alarm
Select Reset Enter
SYSTEM VOLT 45.5
LOAD VOLT LOW
Menu Alarm
Select Reset Enter
SYSTEM VOLT 56.1
LOAD VOLT HIGH
DACS
SMPS Power plant division
13. The system is having facility to monitor Battery room temperature. The system corrects the DC voltage in 72mV per degree centigrade law. At 27°C there is no correction but as temperature increases system voltage decreases and wise versa. 55.8V is the lock where further decrease in temperature will not cause any correction. Menu contains Settable range for lock in lower side where there is decrease in temperature. When the sensor is short or is open then there is an alarm of “TEMP. X COMP. FAIL” (X stands for battery number i.e. 1 or 2 or 3).
NOTE: The system has provision to monitor temperature of each battery with separate probes. When any of the sensors is open or short creates, an Alarm. Among all three temperatures, correction in system voltage is made according to highest temperature.
14. When programming 000AH isolates battery then the respective battery gets isolated and an alarm of “BATT X ISOLATED” (X stands for battery number i.e. 1 or 2 or 3) generated.
Menu Alarm
Select Reset Enter
SYSTEM VOLT 44.4
BATT DISCONNECT
Menu Alarm
Select Reset Enter
SYSTEM VOLT 55.8
TEMP. X COMP. FAIL
DACS
SMPS Power plant division
15. If any battery does not connected to battery terminal and user has selected other than 000AH for same battery then there is an alarm of “BATTERY X ABSENT” (X stands for battery number i.e. 1 or 2 or 3).
NOTE: Whenever any of the above alarm operates there is an audible as well as visual alarm. Buzzer is used as audio alarm whereas alarm is visualized on LCD display. To cut OFF audio alarm press alarm reset key. Whenever audio alarm is cut OFF visual alarm remains continuously until the alarm is rectified.
Menu Alarm
Select Reset Enter
SYSTEM VOLT 54.0
BATT X ISOLATED
Menu Alarm
Select Reset Enter
SYSTEM VOLT 54.0
BATTERY X ABSENT
DACS
SMPS Power plant division