Integrated Civil Engineering
Design Project
(Building Structure Design)
CIVL 395
HKUST
By : Ir. K.S. Kwan Date: 3/07
Content
1.
Building Control in Hong Kong
2.
Design Criteria
3.
Structural Form
(Residential Building)
4.
Hong Kong Wind Loading
5.
Computer Modeling
STRUCTURAL FORM
for Residential Building
•Tower
•Podium Structure
Lintel beam
To identify the wall as structural
element and link them together by lintel beam to provide sufficient lateral
stiffness
Slab
Slab Design
Slab Design
–
–
Concrete grade
Concrete grade
Grade 30 to 35 (too high concrete grade may lead to thermal cra
Grade 30 to 35 (too high concrete grade may lead to thermal cra
ck
ck
during large pour of concrete)
during large pour of concrete)
–
–
Steel reinforcement percentage
Steel reinforcement percentage
Design as HK
Design as HK
CoP
CoP
2004 for structural use of concrete
2004 for structural use of concrete
Average steel ratio is around 120~140 Kg/m
Average steel ratio is around 120~140 Kg/m
33–
–
Preliminary slab size estimation
Preliminary slab size estimation
About 100mm~400mm depending on the
About 100mm~400mm depending on the
span of slab
span of slab
( to minimize
( to minimize
the number of different slab thickness, say 2 ~3 types, at typic
the number of different slab thickness, say 2 ~3 types, at typic
al floor
al floor
for
for
buildability
buildability
consideration
consideration
To consider the following loading
To consider the following loading
–– Self weightSelf weight –
– Finishes (domestic area/toilet/kitchen) (25mm to 80mm thick)Finishes (domestic area/toilet/kitchen) (25mm to 80mm thick) –
Slab is designed as one-way or two ways slab
Wall Design
Wall Design
–
–
Concrete grade
Concrete grade
Grade 30, 40, 60 or more is commonly used. By using
Grade 30, 40, 60 or more is commonly used. By using
high strength
high strength
concrete
concrete
, it can optimize the wall thickness and increase the lateral
, it can optimize the wall thickness and increase the lateral
stiffness of wall. The concrete grade will also be
stiffness of wall. The concrete grade will also be
changed along the
changed along the
height of building
height of building
e.g. from Grade 60 at lower floor to Grade 30 at top
e.g. from Grade 60 at lower floor to Grade 30 at top
roof.
roof.
The
The
thickness
thickness
will be
will be
trimmed
trimmed
down along the height of building e.g.
down along the height of building e.g.
from 400 at 1/F and gradually changed to 200 at top floor. The
from 400 at 1/F and gradually changed to 200 at top floor. The
thickness will be changed every 10 ~20 storey to minimize the
thickness will be changed every 10 ~20 storey to minimize the
disturbance on construction.
disturbance on construction.
–
–
Steel reinforcement percentage
Steel reinforcement percentage
Design as HK
Design as HK
CoP
CoP
2004
2004
Average steel ratio is around 100~150Kg/m
Average steel ratio is around 100~150Kg/m
33–
–
Preliminary wall size estimation
Preliminary wall size estimation
Gravity Load
Gravity Load
–
–
by tributary method
by tributary method
Wind Load
3-D
Vertical Element Gravity Load Estimation by
Vertical Element Gravity Load Estimation by
Tributary Area Method
Tributary Area Method
Plan
W2 W1 W1 W3 C1 250 250 2625 200 2625 200 3900TRIBUTARY AREA METHOD
TRIBUTARY AREA METHOD
No. of storey = 20
Storey height = 2800
Slab thickness = 150
Beam size = 400x200 (ext.)
Beam size = 450x250 (int.)
Dead Load = 10KPa
Live Load = 3KPa
Assumption
Assumption
Plan
1266 W3 2568 W2 2264 W1 1686 C1 (KN) W2 W1 W1 W3 C1 250 250 2625 200 2625 200 3900TRIBUTARY AREA METHOD
TRIBUTARY AREA METHOD
Lintel Beam Design
Lintel Beam Design
(where linking shear (where linking shear wall together to transmit wind shear force)wall together to transmit wind shear force)
–
–
Size
Size
Width as wall thickness
Width as wall thickness
Depth controlled by headroom (min.
Depth controlled by headroom (min.
under side of beam i.e. 2100 at door
under side of beam i.e. 2100 at door
and 2300 under beam
and 2300 under beam
Concrete grade same as floor slab
Concrete grade same as floor slab
for easy concrete pour with slab or
for easy concrete pour with slab or
more if required
more if required
–
–
Steel reinforcement percentage
Steel reinforcement percentage
Design as HK
Design as HK CoPCoP2004 2004
Average steel ratio is around 120
Average steel ratio is around 120
~160 Kg/m
~160 Kg/m33
–
–
Preliminary lintel size estimation
Preliminary lintel size estimation
Wind Load
Wind Load –– by simple computer by simple computer model; the size is always controlled
model; the size is always controlled
by wind shear transmission (in some
by wind shear transmission (in some
critical case, steel plate will be used
critical case, steel plate will be used
to replace
to replace r.cr.c. design to enhance the . design to enhance the wind shear transmission)
wind shear transmission)
Gravity Load
Gravity Load –– by tributary method by tributary method (not the controlled case)
(not the controlled case)
Lintel Beam
Steel plate at lintel beam
Transfer
Structure
Podium
(Plate Structure)
Tower
(Shear Wall system)
Supporting Column (Rigid Frame)
Transfer Girder Structure
The behavior is similar to deep beam when the wall extending to columns such as case a, b & c.
Transfer Plate Structure
Shear Wall Structure at Tower above Transfer Plate Column Structure below Transfer PlateThick plate structure to support all wall
Transfer Structure Design (Plate or Girder)
Transfer Structure Design (Plate or Girder)
–
–
Design similar to
Design similar to
pilecap
pilecap
or beam
or beam
–
–
Closed column spacing under the transfer structure to allow trus
Closed column spacing under the transfer structure to allow trus
s effect
s effect
at transfer structure to minimize the deformation of transfer st
at transfer structure to minimize the deformation of transfer st
ructure
ructure
(
(
Prestressed
Prestressed
transfer structure is required for large span )
transfer structure is required for large span )
–
–
Steel reinforcement percentage
Steel reinforcement percentage
Design as HK
Design as HK CoPCoP2004 2004
Average steel ratio is around 240~280 Kg/m
Average steel ratio is around 240~280 Kg/m33
–
–
Preliminary size estimation (1.5m ~5m)
Preliminary size estimation (1.5m ~5m)
Depend on the spacing of columns and tower loading
Depend on the spacing of columns and tower loading
Gravity load
Gravity load –– as the wall load transmitted tower load to plate level as the wall load transmitted tower load to plate level Wind load
Wind load –– the plate the plate behaviourbehaviour as frame structure integrated with columns as frame structure integrated with columns below
below
Normally, the thickness is controlled by shear stress
Loading from tower including:
(P) Axial Load (M) Moment (V) Shear
Transfer Plate Design
To cater for gravity load and
wind load from tower
structure including axial load, moment and shear
The transfer plate with
column below to form a rigid frame structure
All loadings are transmitted
to foundation by shear, moment and axial force. Podium
Structure Behavior
Transfer Plate with Prestressed Tendon
Building Development
Adjacent to Slope
Retaining structure is
required for building
near the slope
The extent of
excavation will
depend on the subsoil
condition of slope i.e.
Rock / Soil
????
????? ??
Building Development near Slope Column under transfer structure Transfer Plate Walls at Tower Large Diameter
Retaining Wall Structure
Retaining structure for semi-basement
Retaining Wall Structure with deep excavation
Two levels basement to reduce the deep
HONG KONG
WIND LOAD
Wind Load
Wind Responses of a Building
• Static
• Dynamic
No movement Wind direction
- Along wind response - Cross wind response - Torsional wind response • Equivalent Static Load • WC 2004 • Gust Factor Method • WC 2004
• Literature/ Wind Tunnel Test • WC 2004
Wind Load Assessment Procedure
(1)
(i) Open frame with significant resonant dynamic response, or (ii) fnatural < 0.2Hz, or
(iii) Significant cross wind / torsional resonant response (i) fnatural <= 1Hz; and
(ii) H > 5 x Min (B, D); or H > 100m
(i) fnatural > 1Hz; or
(ii) H <= 5 x Min (B, D); and H <= 100m
Signpost in Wind Code 2004
• Susceptible to dynamic
excitation
• Recommendation from
literature/ Dynamic wind tunnel test [App. A, p.7] III
• Susceptible to along wind
resonant response
• Gust Factor Method
[Cl. 7, p.4] II
• No significant resonant
dynamic response
• Equivalent Static Load
Method [Cl. 5, p.3] I
Characteristic Method
Step 1 – Determine Method of Calculation
• Determine method of calculation according to the signpost in Cl. 3.3 (p.2) and Cl. 7.6 (p.5).
Building height (H) Building least horizontal dimension (B,D) B Building on plan To determine building height (H) and width (B,D)
h
B H
b To define the height
and least dimension of building
Sec A-A
Sec B-B A-A
Wind Load Assessment Procedure (2)
• Calculate Force Coefficients (Cf)
– Height Aspect Factor, Ch – Shape Factor, Cs
[Appendix D, p.14~15]
• Calculate Force Coefficients (Cf)
– Height Aspect Factor, Ch – Shape Factor, Cs
– Reduction Factor, RA
[Appendix D, p.14~16]
4
• Calculate Gust Response Factor (G)
[Appendix F, p.19~21]
2b
• Calculate Total Along-Wind Force
F = G. Cf .Σ qz .Az
[Eqn (3), p. 4]
• Calculate Topography Factor
[Appendix C, p.10~13]
• Calculate Design Hourly Mean Wind Pressure
[Table 2, p.5]
Method 2 – Slightly Dynamic Building
• Calculate Total Wind Force
F = Cf. Σ qz .Az
[Eqn (1), p. 3]
5
• Calculate Topography Factor
[Appendix C, p.10~13]
3
• Calculate Design Wind Pressure
(3-sec. gust pressure)
[Table 1, p.3]
2a
Method 1 – Static Building Step
Steps 2 - 5
• Wind Code 2004
– Only One Terrain
• Open Sea Terrain
Step 2a – Design Wind Pressure/ Design
Hourly Mean Wind Pressure
Wind Profiles Below 200m
Wind Pressure Profile Under 200m
0 50 100 150 200 250 0.00 1.00 2.00 3.00 4.00 5.00 Pressure (KPa) He ig h t ( m ) 1983 1983 (Stepwise) PNAP150 2004
• The original method was developed by Davenport
(1967) and Vickery (1966 and 1971)
• In Wind Code 2004, the equation is simplified to:
(Refer to Wind Code 2004 Appendix F for
description of the other variables)
Step 2b - Along Wind Dynamic
Resonant Response by Gust Factor
Method (1)
ς
SE
g
B
g
I
G
h v f 2 22
1
+
+
=
• Dynamic resonant response is dependant on the
magnitude of the fluctuating load as well as its size
(or scale) in relation to the size of the structure
• The size reduction factor, S, accounts for the
correlation of pressures over a building and is equal
to
• The reduction factor, R
A, in Table D3 (p.16) does
not apply to the Gust Factor Method in
Appendix F
⎥
⎦
⎤
⎢
⎣
⎡
+
⎥
⎦
⎤
⎢
⎣
⎡
+
h a h aV
b
n
V
h
n
4
1
5
.
3
1
1
Step 2b - Along Wind Dynamic Resonant
Response by Gust Factor Method (2)
h/λ
b/λ
λ represents
the size of the
wind gust
Step 3 – Topography Factor (1)
• Wind Code 2004
– Speed up ratio adopted from BS6399-2:1995
except that the altitude factor in BS6399-2 was
excluded
(In BS6399-2, altitude factor is used to adjust
the basic wind speed for the altitude of the site
above seal level.)
These examples are taken from British reference book based on British Code. Due to the different requirements in British Code and Hong Kong Code regarding the idealization of the hill/slope, the actual
hill/slope shall be differently idealized under the two Codes. These examples from British were for illustration only and the method of idealizing the hill/slope should not be copied for application to Hong Kong Code.
Comment: Idealized slope (a) may be more appropriate for Hong Kong Code.
Topography Factor
Forces on Buildings
1.
Total Force on a Building
F = C
fΣ q
zA
z
where C
f= force coefficient
q
z= design wind pressure at height z
A
z= effective projected area of that part of the
building corresponding to qz
2.
The effective projected area of an enclosed building shall
be the frontal projected area
3.
The effect projected area of an open framework building
shall be the aggregate projected area of all members on a
plane normal to the direction of the wind
4.
Each building shall be designed for the effects of wind
pressures acting
along each of the critical directions
Force Coefficeints
A.
For Enclosed Building
a) C
f= C
hx C
sb) From
other international codes
accetped by
BA
c) For building with isolated blocks projecting
above a general roof level, individual force
coefficients corresponding to the height
and shape of each block shall be applied.
d)
For building composed of similar contiguous
structures separated by expansion joints,
the force coefficients shall be applied to
the entire building.
Height Aspect Ratio C
h
Height Aspect Factor Ch
1.2
1.2
10.0
1.4
-20.0 and over
1.1
1.1
6.0
1.05
1.05
4.0
1.0
1.0
2.0
0.95
0.95
1.0 or less
2004
1983
Height
Breadth
Shape Factors Cs for Enclosed Building
1.3
3.0
and over
1.1
2.0
1.0
1.0
or less
C
sb/d
Plan Shape
d b windRemark: Interpolate linearly Rectangular b d Cs for buildings with closed spacing
Shape Factors Cs for Enclosed Building
wind
Cs for the Respective enclosing
rectangular shape in the direction of
the wind
Other Shapes
0.75
Circular
Cs
Plan Shape
Note:When the actual shape of a building renders it to become sensitive to wind acting not perpendicular to its face, the diagonal wind
Reduction Factor RA
• Gusts are the results of eddies and vortices
• The speed of gust is a function of its duration
• The smaller the size of the gust, the shorter will be its duration and the higher will be the gust speed
• The larger the size of gust, the longer will be its duration and the lower the average gust speed
• A small gust can only create high wind loading on a small local area of the structure
• The whole structure should be designed with the speed of a gust which is just big enough to affect the whole structure simultaneously
• A 3 second gust can normally engulf a building with frontal area of 300 to 800m2, a longer duration gust is required to be effective on the whole of the structure
• A reduction factor is therefore applied when designing buildings of larger dimensions
(E.C.C.Choi – Commentary on 1983 wind codes)
• Not applicable for buildings with significant resonant dynamic response designed by using hourly mean wind pressure
Reduction Factor RA for Enclosed
Buildings
0.80
15000 and over
0.84
10000
0.86
8000
0.89
5000
0.92
3000
0.96
1000
0.97
800
1.00
500 or less
2004
Reduction Factor RA
Frontal Projected Area m2
• Wind Load Case
– X & Y directions are commonly accepted
– Additional wind direction (e.g. diagonal wind
for Y-shape building) is required
– For large frontal area building (say >50m),
additional torsional wind load (10% of long
face dimension) is required
Wind Load Distribution
at Building
Wind Load Calculation as HK CoP
Wind load
calculation at each floor for a building with 40 storey (with 3 floors above domestic floor) and the building width is 40.23m Building structure as significant resonant dynamic structure \ Sa=topography factor
Wind Load Calculation as HK CoP
Wind load
calculation at each floor for a building with 40 storey (with 3 floors above
domestic floor) and the building width is 40.23m
Building structure not considered as significant resonant dynamic structure (Note: Total wind shear is larger based on static wind load approach for building aspect ratio just
greater than 5) Sa = topography factor
Common Structural Analysis
Common Structural Analysis
Software used in Hong Kong
Software used in Hong Kong
ETABS
ETABS
SAP2000
SAP2000
SAFE
SAFE
SADS
SADS
GSA
GSA
STARIII
STARIII
GTSTRUDL
GTSTRUDL
PAFEC
PAFEC
STAN
STAN
Tall Building Modelling Assumptions
Tall Building Modelling Assumptions
1.
1.
Material
Material
–
–
All structural
All structural
components behave
components behave
linearly elastically.
linearly elastically.
2.
2.
Participating
Participating
Components
Components
–
–
only the
only the
primary structural
primary structural
components
components
participate
participate
in the overall behaviour
in the overall behaviour
3.
3.
Floor slabs
Floor slabs
–
–
Floor slab
Floor slab
are assumed to be
are assumed to be
rigid
rigid
in plane
in plane
unless they
unless they
contain large openings
contain large openings
or are long and narrow
or are long and narrow
in plan
in plan
Only the primary structural components are
put in model
Tall Building Modelling Assumptions
Tall Building Modelling Assumptions
4.
4.
Negligible stiffness
Negligible stiffness
–
–
component stiffness of
component stiffness of
relatively small magnitude
relatively small magnitude
are assumed negligible
are assumed negligible
5.
5.
Negligible deformations
Negligible deformations
–
–
deformations that are
deformations that are
relatively small and of little
relatively small and of little
influence are neglected.
influence are neglected.
6.
6.
Cracking
Cracking
–
–
the effects of
the effects of
cracking in reinforced
cracking in reinforced
concrete members to
concrete members to
flexural tensile stresses may
flexural tensile stresses may
be represented by a
be represented by a
reduced stiffness
reduced stiffness
This line should be a straight line in assumption due to the
How to apply wind loading in
How to apply wind loading in
computer model?
computer model?
V
In common building shape with the rigid diaphragm assumption, the wind load should be applied at the
geometry centre of each floor
Wind load applied at floor
Wind load applied at centre of frontal area
What can you find in
What can you find in
computer modeling?
computer modeling?
–
–
Seismic, wind and gravity
Seismic, wind and gravity
analysis
analysis
–
–
Deformation of building
Deformation of building
under different loading
under different loading
conditions
conditions
–
–
Member force under
Member force under
different loading conditions
Deflection of building at top floor including the X & Y
displacement and Z direction rotation
Q
&
A
If you have any questions about the structural design, please forward email (with your Name and Student ID no.)