Standards and Basic Equipment
Standards and Basic Equipment
Standards and Basic Equipment
Standards and Basic Equipment
Date : 15 November 2010
Date : 15 November 2010
1. Electrical Equipment
1. Electrical Equipment
2 Terminology
2 Terminology
2. Terminology
2. Terminology
1. Electrical Equipment
1. Electrical Equipment
A1) One Transformer and 11kV
A1) One Transformer and 11kV
S it h
i Hi h Ri
B ildi
S it h
i Hi h Ri
B ildi
Switchgear in High Rise Building
Switchgear in High Rise Building
A2) Three Transformers and 11kV
A2) Three Transformers and 11kV
S it h
i Hi h Ri
B ildi
S it h
i Hi h Ri
B ildi
Switchgear in High Rise Building
Switchgear in High Rise Building
A3) Minimum Requirements for the Customer’s Switchroom
A3) Minimum Requirements for the Customer’s Switchroom
Adj
t t S b t ti
f
M lti
Adj
t t S b t ti
f
M lti t
t
f
f
I
I
t ll ti
t ll ti
Adjacent to Substation for Multi
E) MCCB
D) Fuses Combination Unit (Switch Fuse)( )
B) Switch Board C) ACB
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
B) F t
B) F t
b ilt
b ilt
bl (S it hb
bl (S it hb
d)
d)
Typical forms of separation by
Typical forms of separation by
yp
yp
p
p
y
y
barriers of partition
barriers of partition
Form 1
Form 1 No separation
No separation
Form 2
Form 2 Separation of busbar from the functional
Separation of busbar from the functional
Form 2
Form 2 Separation of busbar from the functional
Separation of busbar from the functional
units
units
Form 3
Form 3 Separation of busbar from the functional
Separation of busbar from the functional
units and separation of all functional units
units and separation of all functional units
units and separation of all functional units
units and separation of all functional units
but not of their outgoing terminals, from one
but not of their outgoing terminals, from one
another
another
another.
another.
Form 4
Form 4 Separation of busbar from the functional
Separation of busbar from the functional
units and separation of all functional units,
units and separation of all functional units,
including their outgoing terminals, from one
including their outgoing terminals, from one
g
g
g
g
g
g
,
,
another.
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
C) Air Circuit Breakers (ACB)
C) Air Circuit Breakers (ACB)
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
D) F
C
bi ti
U it
d S it h
D) F
C
bi ti
U it
d S it h
D) Fuse Combination Units and Switch
D) Fuse Combination Units and
Switch--disconnections
disconnections
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
E) Moulded Case Circuit Breakers (MCCB)
E) Moulded Case Circuit Breakers (MCCB)
H) MCB F) Busbar Riser I) KWH Meter F) Busbar Riser G) MCB Distribution G) MCB Distribution Board
1
1 Electrical Eq ipment
Electrical Eq ipment
1
1. Electrical Equipment
. Electrical Equipment
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
G) MCB Di t ib ti
B
d
G) MCB Di t ib ti
B
d
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
H) Miniature Circuit Breakers (MCB)
H) Miniature Circuit Breakers (MCB) 11
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
H) Miniature Circuit Breakers (MCB)
H) Miniature Circuit Breakers (MCB) 22
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
I) KWH meter
I) KWH meter
I) KWH meter
I) KWH meter
L) Lighting Switch M) Lampholder N) Socket Outlet K) RCCB O) Connection Unit J) Consumer Unit
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
J) C
U it
J) C
U it
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
K) Residual Current Circuit Breakers (RCCB)
K) Residual Current Circuit Breakers (RCCB)
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
L) Li hti
S it h
L) Li hti
S it h
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
M) L
h ld
M) L
h ld
M) Lampholders
M) Lampholders
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
N) S k t
tl t
N) S k t
tl t
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
O) C
ti
U it
O) C
ti
U it
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
P) PVC C bl
P) PVC C bl
11
P) PVC Cable
P) PVC Cable -- 11
1 El
t i
l E
i
t
1 El
t i
l E
i
t
1. Electrical Equipment
1. Electrical Equipment
P) PVC C bl
P) PVC C bl
22
P) PVC Cable
P) PVC Cable -- 22
2 T
i
l
2 T
i
l
1
1
2. Terminology
2. Terminology -- 1
1
Live Part
Live Part
A conductor or conductive part intended to be A conductor or conductive part intended to be
A conductor or conductive part intended to be A conductor or conductive part intended to be
energized in normal use, including a neutral energized in normal use, including a neutral conductor
conductor conductor. conductor.
Electrical Installation
Electrical Installation
An assembly of associated electrical equipment An assembly of associated electrical equipment
supplied from a common origin to fulfill a specific supplied from a common origin to fulfill a specific purpose and having certain coordinated
purpose and having certain coordinated characteristics.
2 T
i
l
2 T
i
l
2
2
2. Terminology
2. Terminology -- 2
2
Electrical Equipment
Electrical Equipment
Any item for such purposes as generation conversion Any item for such purposes as generation conversion
Any item for such purposes as generation, conversion, Any item for such purposes as generation, conversion,
transmission, distribution or utilization of electrical transmission, distribution or utilization of electrical energy such as machines transformers protective energy such as machines transformers protective energy, such as machines, transformers, protective energy, such as machines, transformers, protective devices, wiring materials, measuring instruments, devices, wiring materials, measuring instruments, accessories appliances and luminaries
accessories appliances and luminaries accessories, appliances and luminaries. accessories, appliances and luminaries.
Fixed Appliance
Fixed Appliance
An appliance which is fastened to a support or An appliance which is fastened to a support or
otherwise secured at a specific location in normal use. otherwise secured at a specific location in normal use.
2 T
i
l
2 T
i
l
3
3
2. Terminology
2. Terminology -- 3
3
Portable Appliance
Portable Appliance
pp
pp
An appliance which is or can easily be moved from An appliance which is or can easily be moved from
one place to another when in normal use and while one place to another when in normal use and while pp connected to the supply.
connected to the supply.
Earthing
Earthing
The act of connecting the exposed conductive parts The act of connecting the exposed conductive parts
of an installation to an earth electrode. of an installation to an earth electrode.
2 T
i
l
2 T
i
l
4
4
2. Terminology
2. Terminology -- 4
4
Protective Conductor
Protective Conductor
A conductor used for some measure of protection A conductor used for some measure of protection
against electric shock and intended for connecting against electric shock and intended for connecting gg gg together any of the following parts:
together any of the following parts:
Exposed conductive parts,Exposed conductive parts,
Exposed conductive parts,Exposed conductive parts,
Extraneous conductive parts,Extraneous conductive parts,
Main
Main earthingearthing terminalterminal
Main Main earthingearthing terminal,terminal,
Earth electrodesEarth electrodes
2 T
i
l
2 T
i
l
5
5
2. Terminology
2. Terminology -- 5
5
Equipotential
Equipotential Bonding
q p
q p
Bonding
gg
Electrical connection maintaining various exposed Electrical connection maintaining various exposed
conductive pats and extraneous conductive parts at conductive pats and extraneous conductive parts at pp pp substantially the same potential
substantially the same potential
Exposed Conductive Part
Exposed Conductive Part
A conductive part of equipment which can be touched A conductive part of equipment which can be touched
and which is not a live part but which may become and which is not a live part but which may become live under fault conditions
2 T
i
l
2 T
i
l
6
6
2. Terminology
2. Terminology -- 6
6
Extraneous Conductive Part
Extraneous Conductive Part
A conductive part liable to introduce a potential, A conductive part liable to introduce a potential,
generally earth potential, and not forming part of the generally earth potential, and not forming part of the
g y p , g p
g y p , g p
electrical installation. electrical installation.
Circuit Protective Conductor (CPC)
Circuit Protective Conductor (CPC)
A i d i d
A i d i d
A protective conductor connecting exposed A protective conductor connecting exposed
conductive parts of equipment to the main
conductive parts of equipment to the main earthingearthing
t i l
t i l
terminal. terminal.
2 T
i
l
2 T
i
l
7
7
2. Terminology
2. Terminology -- 7
7
Earthing
Earthing Conductor
gg
Conductor
A protective conductor connecting a main A protective conductor connecting a main eathingeathing
terminal of an installation to an earth electrode or to terminal of an installation to an earth electrode or to other means of
other means of earthingearthing..
Direct Contact
Direct Contact
C f li k i h li hi h
C f li k i h li hi h
Contact of persons or livestock with live parts which Contact of persons or livestock with live parts which
may result in electric shock. may result in electric shock.
2 T
i
l
2 T
i
l
8
8
2. Terminology
2. Terminology -- 8
8
Indirect Contact
Indirect Contact
Contact of persons or livestock with exposed Contact of persons or livestock with exposed
conductive parts made live by a fault and which may conductive parts made live by a fault and which may pp yy yy result in electric shock.
result in electric shock.
Skilled Person
Skilled Person
A i h h i l k l d ffi i
A i h h i l k l d ffi i
A person with technical knowledge or sufficient A person with technical knowledge or sufficient
experience to enable him to avoid danger which experience to enable him to avoid danger which
l t i it t
l t i it t
electricity ay create. electricity ay create.
2 T
i
l
2 T
i
l
9
9
2. Terminology
2. Terminology -- 9
9
Instructed Person
Instructed Person
A person adequately advised or supervised by skilled A person adequately advised or supervised by skilled
persons to enable him to avoid dangers which persons to enable him to avoid dangers which
p g
p g
electricity may create. electricity may create.
Low Voltage (L.V.)
Low Voltage (L.V.)
V l ll di E L V l b
V l ll di E L V l b
Voltage normally exceeding Extra Low Voltage but not Voltage normally exceeding Extra Low Voltage but not
exceeding 1000V
exceeding 1000V a.ca.c. or 1500 . or 1500 d.cd.c. between . between
d t 600V
d t 600V 900V900V dd b tb t
conductors, or 600V
conductors, or 600V a.ca.c. or 900V . or 900V d.cd.c. between . between conductors and earth.
2 T
i
l
2 T
i
l
10
10
2. Terminology
2. Terminology -- 10
10
Extra Low Voltage
Extra Low Voltage
gg
Voltage normally not exceeding 50V Voltage normally not exceeding 50V a.ca.c. or 120 . or 120 d.cd.c., .,
whether between conductors or to earth. whether between conductors or to earth.
3. Power Distribution and Wiring
3. Power Distribution and Wiring
g
g
Design Consideration
Design Consideration -- 1
1
Installation Cost
Installation Cost
Purpose and planned duration of the installation
Purpose and planned duration of the installation
Purpose and planned duration of the installation
Purpose and planned duration of the installation
Environment factors and installation conditions
Environment factors and installation conditions
Type of building construction
Type of building construction
Flexibility of the system and circuit arrangement
Flexibility of the system and circuit arrangement
Flexibility of the system and circuit arrangement
Flexibility of the system and circuit arrangement
Appearance of the finished installation
Appearance of the finished installation
S f t
t
S f t
t
Safety aspect
Safety aspect
Nature of power supply and type of earthing
Nature of power supply and type of earthing
system
system
3
3 1
1 I
I
t ll ti
t ll ti
t Hi h H
t Hi h H
idit
idit
3
3..1
1 Installation at High Humidity
Installation at High Humidity
Environment
Environment
The wiring system should be selected and erected so The wiring system should be selected and erected so
that no damage is caused by high humidity or ingress of that no damage is caused by high humidity or ingress of
Environment
Environment
g y g y g
g y g y g
water during installation, use and maintenance. water during installation, use and maintenance.
All joint should be suitably insulated and protected All joint should be suitably insulated and protected
against the effects of moisture or water. Copperclad against the effects of moisture or water. Copperclad aluminum conductors should not be used.
aluminum conductors should not be used.
f h d d k h ld b
f h d d k h ld b
Every entry to finished ducts or trunking should be Every entry to finished ducts or trunking should be
placed so as to prevent the ingress of water or be placed so as to prevent the ingress of water or be
protected against such ingress Where water may collect protected against such ingress Where water may collect protected against such ingress. Where water may collect protected against such ingress. Where water may collect or condensation may form in a wiring system, provisions or condensation may form in a wiring system, provisions should be made to drain it away.
should be made to drain it away. should be made to drain it away. should be made to drain it away.
3.1 Installation at Adverse Ambient
3.1 Installation at Adverse Ambient
Temperature
Temperature
The wiring system including cables and wiring The wiring system including cables and wiring
accessories, should be suitable for the highest and lowest accessories, should be suitable for the highest and lowest accessories, should be suitable for the highest and lowest accessories, should be suitable for the highest and lowest ambient temperature that likely to encountered.
ambient temperature that likely to encountered.
The electrical insulation shall withstand the maximumThe electrical insulation shall withstand the maximum
The electrical insulation shall withstand the maximum The electrical insulation shall withstand the maximum
permissible operating temperature of the class of permissible operating temperature of the class of insulation to BS 2757 insulation to BS 2757 insulation to BS 2757. insulation to BS 2757. Class Class YY AA EE BB FF HH 200200 220220 250250 Temp( Temp(ooC)C) 9090 105105 120120 130130 155155 180180 200200 220220 250250
3.1 Installation at Adverse Ambient
3.1 Installation at Adverse Ambient
Temperature
Temperature -- 2
2
For general
For general--purpose PVC cable, the
purpose PVC cable, the
maximum permissible conductor of
maximum permissible conductor of
maximum permissible conductor of
maximum permissible conductor of
operating temperature is 70
operating temperature is 70
ooC and the
C and the
i
i ibl
bi t
i
i ibl
bi t
maximum permissible ambient
maximum permissible ambient
temperature is 65
temperature is 65
pp
ooC.
C.
In every vertical
In every vertical trunking
trunking or duct wiring
or duct wiring
installations suitable internal barriers
installations suitable internal barriers
installations, suitable internal barriers
installations, suitable internal barriers
sould
sould be provided between floors or at
be provided between floors or at
i t
l
f 5
hi h
i th l
i t
l
f 5
hi h
i th l
intervals of 5m whichever is the less.
intervals of 5m whichever is the less.
3.1 Installation at Adverse Ambient
3.1 Installation at Adverse Ambient
Temperature
Temperature -- 3
3
Suitable measures shall be provided to
Suitable measures shall be provided to
id th
ff t
f h t f
t
l
id th
ff t
f h t f
t
l
avoid the effects of heat from external
avoid the effects of heat from external
source including solar gain such as
source including solar gain such as
g
g
g
g
shielding or placing sufficiently far from
shielding or placing sufficiently far from
the source of heat or selecting insulation
the source of heat or selecting insulation
the source of heat or selecting insulation
the source of heat or selecting insulation
suitable for those temperature.
3 1 Inde of Protection
3 1 Inde of Protection
3.1 Index of Protection
3.1 Index of Protection
The code that specifies the protection of
The code that specifies the protection of
l
th t
b
d ithi
t i
l
th t
b
d ithi
t i
encloses that can be used within certain
encloses that can be used within certain
environment. The first numeral indicate
environment. The first numeral indicate
the protection against ingress of solid
the protection against ingress of solid
bodies The second number indicate the
bodies The second number indicate the
bodies. The second number indicate the
bodies. The second number indicate the
protection against the ingress of liquids.
protection against the ingress of liquids.
p
g
g
q
p
g
g
q
IP XX
IP XX
3 1 Inde of Protection
3 1 Inde of Protection
3.1 Index of Protection
3.1 Index of Protection
General Use
General Use
Indoor Use: IP2X
Indoor Use: IP2X
Outdoor Use: IP54 (Weather
Outdoor Use: IP54 (Weather--proof)
proof)
3.1 Application of Wiring
3.1 Application of Wiring
pp
pp
g
g
System
System
Wiring System
Wiring System Cable TypeCable Type General UseGeneral Use Surface wiring
Surface wiring 1/C PVC/PVC cables with 1/C PVC/PVC cables with Temporary wiring;Temporary wiring; separate cpc; separate cpc; 2/C PVC/PVC cables with 2/C PVC/PVC cables with cpc; cpc; Low
Low--cost housingcost housing 4/C armored cables 4/C armored cables Conduit wiring Conduit wiring 11 ConcealedConcealed 1/C PVC insulated cables
1/C PVC insulated cables Office,Office,
Private hosing; Private hosing; 1. 1. ConcealedConcealed 2. 2. SurfaceSurface Private hosing; Private hosing; Factory; Factory; Plant room Plant room Wiring in trunking
Wiring in trunking 1/C PVC insulated cables1/C PVC insulated cables SubSub--main/laternal main main/laternal main distribution
distribution Risers in communal
Risers in communal Bare Cu/Al bars in trunkingBare Cu/Al bars in trunking Rising mains for internalRising mains for internal Risers in communal
Risers in communal installation
installation Bare Cu/Al bars in trunkingBare Cu/Al bars in trunkingArmored cables in cable Armored cables in cable duct
duct
Rising mains for internal Rising mains for internal power distribution system power distribution system Flameproof cable
Flameproof cable MineralMineral--insulated cablesinsulated cables Petrol station,Petrol station, Flammable areas Flammable areas
3.2 Typical Schematic Wiring Diagram for Internal
3.2 Typical Schematic Wiring Diagram for Internal
Power Distribution System
Power Distribution System
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
a) Basic Requirements
a) Basic Requirements
b) High Voltage Distribution
b) High Voltage Distribution
c) Mains
c) Mains
c) Mains
c) Mains
d) Sub
d) Sub -- Main
d) Sub
d) Sub
Main
aa
e) Lateral Main
e) Lateral Main
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
a) Basic Requirements
a) Basic Requirements 11
E i t ll ti h ll b di id d i t i it t E i t ll ti h ll b di id d i t i it t
Every installation shall be divided into circuits as necessary to Every installation shall be divided into circuits as necessary to
avoid danger in the event of a fault, and to facilitate safe avoid danger in the event of a fault, and to facilitate safe operation, inspection, testing and maintenance. Each circuit operation, inspection, testing and maintenance. Each circuit operation, inspection, testing and maintenance. Each circuit operation, inspection, testing and maintenance. Each circuit should be separately protected by an
should be separately protected by an overcurrentovercurrent protective protective device. Separate circuits shall be provided for parts of the device. Separate circuits shall be provided for parts of the i t ll ti hi h d t b t l t ll d i h i t ll ti hi h d t b t l t ll d i h
installation which need to be separately controlled in such a way installation which need to be separately controlled in such a way that these circuits are not affected by failure of other circuits.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
a) Basic Requirements 2
a) Basic Requirements 2
P t ti d i f h i it h ld b l l
P t ti d i f h i it h ld b l l l b ll dl b ll d
Protective devices of each circuit should be clearly Protective devices of each circuit should be clearly labelledlabelled or or
identified so that the rating of the devices and circuits they identified so that the rating of the devices and circuits they protect can be easily recognized.
protect can be easily recognized. protect can be easily recognized. protect can be easily recognized.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
B) High Voltage Distribution B) High Voltage Distribution--11
Although residential and the majority of commercial installations are Although residential and the majority of commercial installations are
adequately served from LV
adequately served from LV intake or HVintake or HV intakeintake LV distribution thereLV distribution there adequately served from LV
adequately served from LV--intake or HVintake or HV--intakeintake--LV distribution, there LV distribution, there are many industrial and some large commercial development
are many industrial and some large commercial development projects require HV intake with extensive HV distribution system projects require HV intake with extensive HV distribution system through the sites or buildings
through the sites or buildings through the sites or buildings. through the sites or buildings.
For example, a hospital or an university with a large campus, a For example, a hospital or an university with a large campus, a
cross harbor tunnel with high
cross harbor tunnel with high--tension motors for ventilation fans, a tension motors for ventilation fans, a very ;large commercial block and a large factory with several
very ;large commercial block and a large factory with several very ;large commercial block and a large factory with several very ;large commercial block and a large factory with several electrode boilers.
electrode boilers.
For these, the power company provides the main supply point For these, the power company provides the main supply point
through its own switchgear complete with bulk metering and the through its own switchgear complete with bulk metering and the through its own switchgear complete with bulk metering, and the through its own switchgear complete with bulk metering, and the customer is then responsible for the installation of suitable high customer is then responsible for the installation of suitable high voltage switchgear, all cabling and the required number of on
voltage switchgear, all cabling and the required number of on--site site substations
substations substations. substations.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
B) HV Ring Main Distribution system B) HV Ring Main Distribution system
Just similar to the ring main system which used by power company Just similar to the ring main system which used by power company gg yy y py p p yp y
in their 11kV network in their 11kV network
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
B) Advantage of HV Ring Main Distribution system B) Advantage of HV Ring Main Distribution system
Even in the event of a cable fault on the ring, it is still possible to Even in the event of a cable fault on the ring, it is still possible to
maintain or restore supply to all points by opening the switches on maintain or restore supply to all points by opening the switches on both sides of the fault.
both sides of the fault.
Additional outlets to the ring may be easily installed without shutAdditional outlets to the ring may be easily installed without shut
Additional outlets to the ring may be easily installed without shut Additional outlets to the ring may be easily installed without shut
downs. downs.
Greater maintenance facilities are available both on the ring feeder Greater maintenance facilities are available both on the ring feeder
i it b k d th RMU i it b k d th RMU circuit breakers and the RMUs. circuit breakers and the RMUs.
In additional, if the main HV switchboard is sectionalized and fed In additional, if the main HV switchboard is sectionalized and fed
from more than one supplier
from more than one supplier’’s substations, a ring main may bes substations, a ring main may be
from more than one supplier
from more than one supplier s substations, a ring main may be s substations, a ring main may be supplied from two different sections, thus improving security. supplied from two different sections, thus improving security.
Apart from fault conditions, it is also possible to operate a ring main Apart from fault conditions, it is also possible to operate a ring main
in open mode as the preferred arrangement but for whatever in open mode as the preferred arrangement but for whatever in open mode as the preferred arrangement but, for whatever in open mode as the preferred arrangement but, for whatever
purpose it must be ensured that neither of the section is overload. purpose it must be ensured that neither of the section is overload.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) Mains
c) Mains -- 11
Consumer main switch shall be installed and Consumer main switch shall be installed and
Consumer main switch shall be installed and Consumer main switch shall be installed and
connected immediately before the supply co.
connected immediately before the supply co.’’s meter.s meter.
A i it h h ll b i t ll d t t l ll
A i it h h ll b i t ll d t t l ll
A common main switch shall be installed to control all A common main switch shall be installed to control all
the communal installation of the same consumer. the communal installation of the same consumer.
The consumer main switch should incorporate:The consumer main switch should incorporate:
Means of isolation and switchingMeans of isolation and switching
Means of protection against Means of protection against overcurrentovercurrent, and , and
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) Mains
c) Mains -- 22
The main switch or circuit breaker shall have a short The main switch or circuit breaker shall have a short
The main switch or circuit breaker shall have a shortThe main switch or circuit breaker shall have a
short--circuit breaking capacity of 40kA at low voltage. circuit breaking capacity of 40kA at low voltage.
Th h t i ti f th i it h h ll di t
Th h t i ti f th i it h h ll di t
The characteristic of the main switch shall disconnect The characteristic of the main switch shall disconnect
within 5 seconds during an earth fault. within 5 seconds during an earth fault.
The switchboard shall incorporate The switchboard shall incorporate CastellCastell key key
interlock or other means to prevent the supply interlock or other means to prevent the supply
f d i ll l All i i
f d i ll l All i i
transformers operated in parallel. All interconnecting transformers operated in parallel. All interconnecting devices including the bus
devices including the bus--section switch shall be of 4section switch shall be of
4--l t ith l t i l d h i l i t l k
l t ith l t i l d h i l i t l k
pole type with electrical and mechanical interlock. pole type with electrical and mechanical interlock.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) Mains
c) Mains -- 33
Where standby generator is installed mechanically Where standby generator is installed mechanically
Where standby generator is installed, mechanically Where standby generator is installed, mechanically
interlocked
interlocked 44--pole changeover device shall be used pole changeover device shall be used for interconnection between the normal and standby for interconnection between the normal and standby for interconnection between the normal and standby for interconnection between the normal and standby source. A local switch shall be installed after a
source. A local switch shall be installed after a changeover device
changeover device changeover device. changeover device.
Single phase consumer main switch shall be of double Single phase consumer main switch shall be of double
pole type pole type pole type. pole type.
A schematic wiring diagram showing the main A schematic wiring diagram showing the main
di t ib ti t h ld b di l d th i
di t ib ti t h ld b di l d th i
distribution system should be displayed near the main distribution system should be displayed near the main switch with rating
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) Mains
c) Mains -- 44
Each consumer installation shall provided his ownEach consumer installation shall provided his own
Each consumer installation shall provided his own Each consumer installation shall provided his own
earthing
earthing systemsystem
For 3 phase installation with main switch rating ofFor 3 phase installation with main switch rating of
For 3 phase installation with main switch rating of For 3 phase installation with main switch rating of
160A and above, C.T. operated meter shall be 160A and above, C.T. operated meter shall be installed.
installed.
Warning Notice: Warning Notice: ‘‘DANGERDANGER--ELECTRICITY, ELECTRICITY,
UNAUTHORISED ENTRY PROHIBITED
UNAUTHORISED ENTRY PROHIBITED’’ with Chinese with Chinese
translation shall be painted or engraved on plastic translation shall be painted or engraved on plastic boards permanently fixed outside the door of
boards permanently fixed outside the door of switchrooms
switchrooms Each character shall not less thanEach character shall not less than switchrooms
switchrooms. Each character shall not less than . Each character shall not less than 50mm high.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) Mains
c) Mains -- 55
The mina
The mina earthing
earthing terminal of the installation
terminal of the installation
should be bonded by a conductor of not less
should be bonded by a conductor of not less
yy
than 150mm
than 150mm
2 2copper
copper to the electricity
to the electricity
supplier’s transformer earth or metallic
supplier’s transformer earth or metallic
supplier s transformer earth or metallic
supplier s transformer earth or metallic
sheaths of service cable.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) LV Distribution c) LV Distribution--11
LV distribution exist in nearly all electrical installations.LV distribution exist in nearly all electrical installations.
Nearly all LV distribution are in radial from.Nearly all LV distribution are in radial from.
The greater the impedance of the cable from the secondary of the The greater the impedance of the cable from the secondary of the
transformer to the LV switchboard the less be the potential transformer to the LV switchboard the less be the potential transformer to the LV switchboard, the less be the potential transformer to the LV switchboard, the less be the potential short
short--circuit current, and therefore these cables should not be circuit current, and therefore these cables should not be larger than necessary.
larger than necessary.
If two 1500kVA transformer were connected in parallel, then the If two 1500kVA transformer were connected in parallel, then the
potential fault current could be as much as 60MVA. As this potential fault current could be as much as 60MVA. As this
exceeds the breaking capacity of most standard LV switchboards exceeds the breaking capacity of most standard LV switchboards exceeds the breaking capacity of most standard LV switchboards exceeds the breaking capacity of most standard LV switchboards ( which is usually only 31 MVA, it would entail the installation of ( which is usually only 31 MVA, it would entail the installation of much more expensive switchboard or special high
much more expensive switchboard or special high--reactance reactance
transformers or split the LV main switchboards into two or more transformers or split the LV main switchboards into two or more transformers, or split the LV main switchboards into two or more transformers, or split the LV main switchboards into two or more separate sections, each section being fed from a transformer not separate sections, each section being fed from a transformer not exceeding 1500kVA.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) LV Distribution c) LV Distribution--22
The greater the impedance of the cable from the secondary of the The greater the impedance of the cable from the secondary of the gg pp yy
transformer to the LV switchboard, the less be the potential transformer to the LV switchboard, the less be the potential short
short--circuit current, and therefore these cables should not be circuit current, and therefore these cables should not be larger than necessary
larger than necessary larger than necessary. larger than necessary.
If two 1500kVA transformer were connected in parallel, then the If two 1500kVA transformer were connected in parallel, then the
potential fault current could be as much as 60MVA As this potential fault current could be as much as 60MVA As this potential fault current could be as much as 60MVA. As this potential fault current could be as much as 60MVA. As this
exceeds the breaking capacity of most standard LV switchboards exceeds the breaking capacity of most standard LV switchboards ( which is usually only 31 MVA, it would entail the installation of ( which is usually only 31 MVA, it would entail the installation of much more expensive switchboard or special high
much more expensive switchboard or special high--reactance reactance
transformers, or split the LV main switchboards into two or more transformers, or split the LV main switchboards into two or more separate sections each section being fed from a transformer not separate sections each section being fed from a transformer not separate sections, each section being fed from a transformer not separate sections, each section being fed from a transformer not exceeding 1500kVA.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) LV Distribution c) LV Distribution--33
If If sectionisedsectionised is used in switchboard interlocked busis used in switchboard interlocked bus--section section
switches should be provided switches should be provided
Radial distribution diagram for typical small commercial building – meters on
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
C) Rising Mains C) Rising Mains--11
1) Cable, including prefabricated tee
1) Cable, including prefabricated tee--off cable.off cable.
The selection of cable as rising mains is usually limited by its The selection of cable as rising mains is usually limited by its gg yy yy
current carrying capacity (CCC) current carrying capacity (CCC)
The cable may be singleThe cable may be single--core insulted cable, or multicore insulted cable, or multi--core core
dd blbl armoured
armoured cable.cable.
For singleFor single--core, core, p.v.c.p.v.c.--insulated. Noninsulated. Non--armouredarmoured cable, the largest cable, the largest
cross sectional area is 1000mm2 giving a CCC of 1200A cross sectional area is 1000mm2 giving a CCC of 1200A cross sectional area is 1000mm2 giving a CCC of 1200A. cross sectional area is 1000mm2 giving a CCC of 1200A.
As a rule of thumb, when the demand exceeds 800A, As a rule of thumb, when the demand exceeds 800A, busductbusduct is is
preferred. preferred. pp
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) Rising Mains c) Rising Mains--22 2) Insulated
2) Insulated busductbusduct (or (or busbarbusbar) system, including feeder type ) system, including feeder type and plug
and plug--in type in type busductbusduct..
The rating of The rating of busductbusduct could be up to 5000A or even higher. The could be up to 5000A or even higher. The
provision of plug
provision of plug--in unit provide flexibility for teein unit provide flexibility for tee--off at any location/ off at any location/ floor at anytime when demand required
floor at anytime when demand required floor at anytime when demand required. floor at anytime when demand required.
The bus may be insulated conductor or bare conductors totally The bus may be insulated conductor or bare conductors totally
enclosed in continuous steel
enclosed in continuous steel trunkingtrunking.. enclosed in continuous steel
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
c) Rising Mains c) Rising Mains--33
The following factors affect the selection of the type of rising main: The following factors affect the selection of the type of rising main:
L d L d
Load assessmentLoad assessment
Load distributionLoad distribution
Environmental conditions such as ambient temperature and humidityEnvironmental conditions such as ambient temperature and humidityEnvironmental conditions such as ambient temperature and humidityEnvironmental conditions such as ambient temperature and humidity
Heights of riserHeights of riser
Maximum allowable voltage dropMaximum allowable voltage drop
F lt l l F lt l l
Fault levelFault level
Likelihood of alternation and future extension/ expansion being frequently Likelihood of alternation and future extension/ expansion being frequently
required required
form, types and usage of the buildingform, types and usage of the building
whether the wiring is to be installed during the construction of a building, in whether the wiring is to be installed during the construction of a building, in
a completed building, or as and extension system. a completed building, or as and extension system. a completed building, or as and extension system. a completed building, or as and extension system.
Capital outlay requiredCapital outlay required
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
d) Sub
d) Sub--main
main -- 11
Any building of more than four floors including the Any building of more than four floors including the
Any building of more than four floors including the Any building of more than four floors including the
ground floor and designed for occupation of more ground floor and designed for occupation of more than one consumer shall be provided with 3 phase than one consumer shall be provided with 3 phase than one consumer shall be provided with 3 phase than one consumer shall be provided with 3 phase electrical rising mains with 3 phase and neutral tee electrical rising mains with 3 phase and neutral tee--off at each floor
off at each floor off at each floor off at each floor
Type of rising mains could be one of the followings:Type of rising mains could be one of the followings:
I l t d d t i
I l t d d t i tt kiki // d itd it
Insulated conductors in Insulated conductors in trunkingtrunking/ conduit;/ conduit;
ArmouredArmoured cables suitably supported;cables suitably supported;
Bare conductors in
Bare conductors in trunkingtrunking
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
d) Sub
d) Sub--main
main -- 22
Each riding mains installation shall be protected Each riding mains installation shall be protected
Each riding mains installation shall be protected Each riding mains installation shall be protected
against
against overcurrentovercurrent and earth leakage and shall be and earth leakage and shall be equipped with suitable means of isolation
equipped with suitable means of isolation equipped with suitable means of isolation. equipped with suitable means of isolation.
For For busbarbusbar installation having a rated capacity not installation having a rated capacity not
di 400A i h h f 3 h 4 i
di 400A i h h f 3 h 4 i
exceeding 400A in each phase of a 3 phase 4 wire exceeding 400A in each phase of a 3 phase 4 wire system, the associated neutral
system, the associated neutral busbarbusbar should have a should have a cross
cross sectional area not less than the crosssectional area not less than the cross sectionalsectional cross
cross--sectional area not less than the crosssectional area not less than the cross--sectional sectional area of the phase
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
d) Sub
d) Sub--main
main -- 33
Rise
Rise ea thing
ea thing cond cto fo m lti
cond cto fo m lti tenant
tenant
Riser
Riser earthing
earthing conductor for multi
conductor for multi--tenant
tenant
installations shall be installed and the
installations shall be installed and the
i i
i
f i
i i
i
f i
thi
thi
d t
d t
i
i
minimum size of riser
minimum size of riser earthing
earthing conductor is
conductor is
70mm
70mm
22copper.
copper.
The loadings on 3 phase rising mains should
The loadings on 3 phase rising mains should
be properly balanced. The neutral conductor
be properly balanced. The neutral conductor
should have a suitable current carrying
should have a suitable current carrying
capacity to cater for any imbalance or
capacity to cater for any imbalance or
harmonic current.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
d) Sub
d) Sub--main
main -- 44
The design of rising mains installation should
The design of rising mains installation should
be agreed by the electricity supplier.
be agreed by the electricity supplier.
g
g
y
y
y
y
pp
pp
No part of the communal installation should
No part of the communal installation should
pass through any individual consumers unit
pass through any individual consumers unit
pass through any individual consumers unit
pass through any individual consumers unit
within the multi
within the multi--consumer building.
consumer building.
No cable, other than that for lift installation
No cable, other than that for lift installation
governed by BS5655, shall be run in lift shaft.
governed by BS5655, shall be run in lift shaft.
g
y
,
3
3..2
2 Internal Power Distribution
Internal Power Distribution
System
System
e) Lateral Mains
e) Lateral Mains -- 11
Adequate space for lateral mains and meter board Adequate space for lateral mains and meter board
Adequate space for lateral mains and meter board Adequate space for lateral mains and meter board
wiring shall be provided in meter room. wiring shall be provided in meter room.
Th l di 3 h l t l i h ld b
Th l di 3 h l t l i h ld b
The loading on 3 phase lateral mains should be The loading on 3 phase lateral mains should be
balanced as far as practicable. balanced as far as practicable.
An installation requiring more than 60A is required to An installation requiring more than 60A is required to
be arranged to service a 3
be arranged to service a 3--phase supply.phase supply.
Appropriate correction factors shall be applied for Appropriate correction factors shall be applied for
determining the current carrying capacity of cables. determining the current carrying capacity of cables.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
e) Lateral Mains
e) Lateral Mains -- 22
Distribution board switchgear and
Distribution board switchgear and busbarbusbar chamberchamber
Distribution board, switchgear and Distribution board, switchgear and busbarbusbar chamber chamber
should have phase identification. should have phase identification.
Wh bl d t d t th h
Wh bl d t d t th h
Where cables, conducts, ducts pass through Where cables, conducts, ducts pass through
structural element such as floors and walls, the structural element such as floors and walls, the
i h ll b l d b i t fi i t t
i h ll b l d b i t fi i t t
openings shall be sealed by appropriate fire resistant openings shall be sealed by appropriate fire resistant materials. In addition, internal fire
materials. In addition, internal fire--resistant barriers resistant barriers shall be provided to prevent the spread of fire
shall be provided to prevent the spread of fire shall be provided to prevent the spread of fire. shall be provided to prevent the spread of fire.
Segregation of lowSegregation of low--voltage circuits, fire alarm circuits voltage circuits, fire alarm circuits
d t l h / t l i ti i it h ll b
d t l h / t l i ti i it h ll b
and telephone/ telecommunication circuits shall be and telephone/ telecommunication circuits shall be made when they run together.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
e) Lateral Mains
e) Lateral Mains -- 33
Connection between the electricity supplier
Connection between the electricity supplier’’s meters meter
Connection between the electricity supplierConnection between the electricity supplier’’s meter s meter
and the consumer
and the consumer’’s main switch should be not less s main switch should be not less
than 4mm
than 4mm22 stranded copper conductorstranded copper conductor
than 4mm
than 4mm2 2 stranded copper conductor.stranded copper conductor.
The insulation and/ or sheath of the cables shall be The insulation and/ or sheath of the cables shall be
d f di t f 150 f th
d f di t f 150 f th
removed for a distance of 150mm from the removed for a distance of 150mm from the
connection, and replaced if necessary by suitable connection, and replaced if necessary by suitable heat
heat resisting insulation when connecting the cable toresisting insulation when connecting the cable to heat
heat--resisting insulation when connecting the cable to resisting insulation when connecting the cable to bare conductors/
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
e) Lateral Mains
e) Lateral Mains -- 44
Warning notice
Warning notice ““DANGERDANGER”” in red legible letter within red legible letter with
Warning notice Warning notice –– ““DANGERDANGER”” in red legible letter with in red legible letter with
Chinese translation shall be displayed near each Chinese translation shall be displayed near each
distribution board Each character shall not less than distribution board Each character shall not less than distribution board, Each character shall not less than distribution board, Each character shall not less than 10mm high.
10mm high.
Wh i t ll ti i t d t i i i
Wh i t ll ti i t d t i i i
Where an installation is connected to rising mains, Where an installation is connected to rising mains,
agreement should be obtained from the owner of agreement should be obtained from the owner of rising mains if new current demand exceed that rising mains if new current demand exceed that rising mains if new current demand exceed that rising mains if new current demand exceed that before. Moreover, prior approval from the power before. Moreover, prior approval from the power company should be obtained before any alteration company should be obtained before any alteration company should be obtained before any alteration company should be obtained before any alteration work is carried out.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
f) Installation methods of cables
f) Installation methods of cables
According to he CP for WP or IEE Wiring Regulations According to he CP for WP or IEE Wiring Regulations
According to he CP for WP or IEE Wiring Regulations, According to he CP for WP or IEE Wiring Regulations,
cables can be in the following ways: cables can be in the following ways:
O li d di t
O li d di t
Open or clipped directOpen or clipped direct
Embedded direct in building ,materialsEmbedded direct in building ,materials
In conduit In conduit
In truckingIn truckingIn truckingIn trucking
In free air, on cleats, brackets or ladderIn free air, on cleats, brackets or ladder
In building voidsIn building voids
In building voidsIn building voids
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
Definition of Final Circuit
Definition of Final Circuit
A circuit connected directly to current
A circuit connected directly to current
using equipment or to a socket outlet or
using equipment or to a socket outlet or
using equipment, or to a socket outlet or
using equipment, or to a socket outlet or
other outlet points for the connection of
other outlet points for the connection of
h
i
h
i
such equipment.
such equipment.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
Final Circuit
Final Circuit
–
–
Typical Arrangement 1
Typical Arrangement 1
yp
yp
g
g
IEE Reg. 314
IEE Reg. 314--01
01--04 states that an installation
04 states that an installation
comprises more than one final circuit each
comprises more than one final circuit each
comprises more than one final circuit, each
comprises more than one final circuit, each
shall be connected to a separate way in a
shall be connected to a separate way in a
d
b
b
d
d h
h
h
d
b
b
d
d h
h
h
distribution board and that the wiring to each
distribution board and that the wiring to each
final circuit shall be electrically separate from
final circuit shall be electrically separate from
each other.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
Final Circuit
Final Circuit
–
–
Typical Arrangement 2
Typical Arrangement 2
yp
yp
g
g
Typical Arrangement shall be :
Typical Arrangement shall be :
T
li hti
i
it t
th
h l
it ill
T
li hti
i
it t
th
h l
it ill
Two lighting circuits to ensure the whole unit will
Two lighting circuits to ensure the whole unit will
not be in darkness if a fault occurs on one lighting
not be in darkness if a fault occurs on one lighting
circuit
circuit
circuit.
circuit.
Circuit for 5A or 15A socket outlet to be fed by an
Circuit for 5A or 15A socket outlet to be fed by an
l i
di l fi l i
it Th
i
l di
l i
di l fi l i
it Th
i
l di
exclusive radial final circuit. The maximum loading
exclusive radial final circuit. The maximum loading
of each socket outlet shall be 5A or 15A
of each socket outlet shall be 5A or 15A
ti l
ti l
respectively.
respectively.
3.2 Internal Power Distribution
3.2 Internal Power Distribution
System
System
Final Circuit
Final Circuit
–
–
Typical Arrangement 3
Typical Arrangement 3
yp
yp
g
g
Circuit for 13A socket outlets complying with
Circuit for 13A socket outlets complying with
BS1363
BS1363
BS1363.
BS1363.
Separate circuit for each large current
Separate circuit for each large current--using
using
appliance such as room cooler
appliance such as room cooler cookre
cookre or kitchen
or kitchen
appliance such as room cooler,
appliance such as room cooler, cookre
cookre or kitchen
or kitchen
appliance.
appliance.
Lighting circuits should be electrically separate
Lighting circuits should be electrically separate