CE 479: DESIGN OF BUILDING
COMPONENTS AND SYSTEMS
FALL 2012 – J. LIU
Shearwalls
The vertical elements in the lateral force-resisting system (LFRS)
Support the roof/floor diaphragms and transfer the lateral forces into the foundations
http://www.jlconline.com/Images/LateralForce%20Collectors%20for%20Seismic%20and%20 Wind-Resistant%20Framing_tcm96-1095375.pdf
Materials
Most typically used to develop shear wall action:
Wood structural panels (e.g. plywood and oriented strand board (OSB))
Lumber sheathing (diagonal or horizontal “strips”)
Materials
Might be adequate if design forces relatively small
Gypsum wallboard (drywall)
Interior and exterior plaster (stucco)
Fiberboard (including fiber-cement panels)
Note: generally, interior partition walls neglected in lateral force design
Design Considerations
Sheathing thickness Shear wall nailing
Chord design (tension and compression) Collector (strut) design
Anchorage requirements (hold-downs and shear) Shear panel proportions
Deflection
http://www.ehow.com/list_7192716_ubc-wood-shear-wall-spacing.html
Sheathing Thickness
Sheathing-type loads and spacing of wall studs may determine thickness
Unit shear often controls
May also be governed by the required fire rating of a wall
e.g., 1-hour fire rating for 2x4 wall studs @16”o.c.,
with 5/8” gypsum on the interior, and 5/8” Type X gypsum sheathing & minimum 3/8” plywood siding together on the outside.
Nailing, Chords, Collectors
Nailing
Function of unit shear in the wall and
materials
Chords
As with diaphragms, these are
designed to carry the moment
Required at both ends of a shear wall
Collector (strut)
Same collector we discussed with
Shearwall Proportions
Measured by height-to-width ratio, h/b
In buildings with two or more stories, the height, h, is the vertical clear distance between diaphragms
IBC sets upper limits on h/b for various wall sheathing materials used as shear walls
Shear walls satisfying h/b limits considered to be better with regards to deflection control
Height-to-Width Ratios
IBC sets h/b limit for wood structural panel shear walls to 3.5 for wind
(SDPWS uses this limit,
blocked shear walls; Table 4.3.4)
IBC sets h/b limit to 2.0 for seismic
Height-to-Width Ratios
For tables, may increase h/b for seismic up to 3.5 provided that tabulated allowable unit shears
reduced by multiplier 2bs/h (SDPWS 4.3.4.1)
Allowable Unit Shears
Tabulated values assume framing members are Douglas Fir-Larch or Southern Pine
Adjustment factors for other species given in footnote
Panels resisting wind loads are permitted to use unit shear capacities 40% higher than for seismic
Note that tables are for short-term forces (wind and seismic)
If panels used to support loads of longer duration,
Allowable Unit Shears
LRFD – use resistance factor D = 0.80
(SDPWS Section 4.3.3)
Tabulated values apply to panels installed vertically or horizontally
Assumed that all panel edges are supported by and are edge nailed to wall studs or blocking
Unit Shears
Can be obtained with more than one layer on other side of the wall
If same nail size and spacing is used, second layer can double shear capacity of the wall
Unit Shears
Generally wall covering (gypsum wallboard, plaster, stucco) capacity not additive to shear capacity of wood structural panel sheathing
One exception is gypsum wallboard under wood structural panel exterior (as in Table 4.3B)
Three Methods
Segmented shearwall (SDPWS 4.3.5.1)
Most common
Each segment designed separately
Design for force transfer around openings (SDPWS 4.3.5.2)
above and below openings designed as coupling beams Requires special detailing around openings
Perforated shear wall method (SDPWS 4.3.5.3)
Semi-empirical method, like 2nd method but less detailing
requirements and with capacity adjustment factor for openings (Table 4.3.3.5)
Shearwall Chord Members
Some designers will include overturning resistance due to dead load; others neglect
Force in compression chord can be underestimated when dead load neglected
Anchorage Considerations
Critical locations are where diaphragms connect to shearwalls and where shearwalls tie into the
foundation
Commonly use „tie-downs‟ or „hold-downs‟ (engineered prefabricated metal brackets) Must consider:
Vertical (gravity) loads
Lateral forces parallel to the wall
Shear Anchorage
Attachment of sheathing to bottom wall plate will transfer shear to base of the wall
Anchor bolts are designed to transfer shear to foundation
Anchorage for Perpendicular Force
Must rely on nail connection between stud and bottom wall plate, etc.
Deflection
Can also use SDPWS eq. 4.3-1 with Ga – apparent shear stiffness (including nail slip)