Liquid-Liquid separators
Roberto Bubbico PhD, Chem. Eng.
Department of Chemical Engineering “Sapienza” University of Rome
INTRODUCTION
It is commonly encountered in different
phases:
• in the unit operation of liquid-liquid extraction
• in the separation of small quantities of
entrained water from process streams (oil)
• in the separation of water polluted by
INTRODUCTION
• The simplest form of equipment used to
separate liquid phases is the gravity settling
tank (decanter)
• they are designed for continuous operation,
but batch operation is also possible
• the feed to the decanter is a mixture of a
dispersed and a continuous liquid phase
(they can be more or less stable)
INTRODUCTION
The aim of the separator is to provide a
sufficiently large volume to allow:
• sufficient residence time for the
dispersed-phase drops to separate and reach (rise or
drop) the liquid-liquid interface, and
• sufficient residence time for the droplets to
coalesce.
• Thus, the residence time has two
INTRODUCTION
In an operating decanter three zones can be identified: • clear heavy liquid;
• separating dispersed liquid (the dispersion zone); • clear light liquid.
The separating zone can be further subdivided in two zones: • a settling out dispersion zone, where dispersed drops rise
or settle out through the continuous phase
• a zone of densely packed dispersed drops that coalesce more or less quickly
DECANTERS SIZING
Even though settling and coalescing occur
simultaneously, it will be assumed that first
the drops flow to the interface, and then the
drops coalesce with the appropriate phase
DECANTERS SIZING
• There is no universally accepted procedure
for decanters sizing.
• Accurate sizing must be supplemented by
testing
DECANTERS SIZING
• The first step in developing a sizing procedure is to
determine which phase is dispersed
• the parameter θ, can be used as a guide to
determine the dispersed phase
Heavy phase dispersed >3.3
Heavy phase probably dispersed
2-3.3
Design for the worst case
0.5-2
Light phase probably dispersed
0.3-0.5
Light phase dispersed <0.3 Result θ 3 . 0
⎟⎟
⎠
⎞
⎜⎜
⎝
⎛
=
L H H L H LQ
Q
µ
ρ
µ
ρ
θ
Q= volumetric flow rateL= light phase H= heavy phase
VERTICAL DECANTERS
• The decanter size is based on the settling velocity of the droplets of the dispersed phase (e.g. Stokes’ equation):
where µc is the viscosity of the continuous phase.
• The calculation of UT requires the knowledge of the droplets diameter (reference Dp= 150 µm)
• A maximum of 4 mm/s is usually assumed
c L H p T gD U
µ
ρ
ρ
18 ) ( 2 − =VERTICAL DECANTERS
• The velocity of the continuous phase must be less than the settling velocity (plug flow is assumed)
• The velocity of the continuous phase is calculated using the area of the interface
• Then, a hold-up time of 5 to 10 min is usually
assumed (sufficient where emulsions are not likely to form) T I c c
U
A
Q
v
=
<
INTERFACE
• The position of the interface can be
controlled, with or without the use of
instruments, by use of a siphon take-off for
the heavy liquid
• The height of the take-off can be determined
by making a pressure balance:
(
)
3 3 1 2z
z
z
z
H L+
−
=
ρ
ρ
INTERFACE
• An alternative approach for the automatic control of the interface:
• The height of the liquid interface should be controlled
accurately when the liquid densities are close, when one component is present only in small quantities, or when the throughput is very small
INTERFACE
• Where one phase is present only in small amounts it is often recycled to the decanter feed to give
more stable operation
• Drain valves should be fitted at the interface so that any tendency for an emulsion to form can be checked; and the emulsion accumulating at the interface drained off periodically as necessary
HORIZONTAL DECANTERS
• Liquid-liquid separation is markedly influenced (hindered) by turbulence Probable poor separation >50000 Major problem 20000-50000 Some hindrance 5000-20000 Negligible effect <5000 Effect Re • The separator diameter is calculated to minimize turbulence • The Reynolds numbers must be
calculated for both the light and heavy
HORIZONTAL DECANTERS
The Reynolds number must be calculated with the equivalent diameter:
where i = L, H the light and heavy phases. It is generally assumed that the liquid-liquid
interface is at the center of the vessel.
i i i i eq i
v
D
µ
ρ
,Re
=
π
π
+
=
2
, i i eqD
D
HORIZONTAL DECANTERS
• Assuming a limiting value of Re for each
phase, two values of D are obtained.
• The largest of the diameters is adopted.
(D
min=10 cm due to wall effects)
• The velocity of the phases is calculated
as:
where i i iA
Q
v
=
8
2D
A
i=
π
HORIZONTAL DECANTERS
• The total length of the decanter is the sum of the lengths required for settling and coalescence
• The settling velocity for the dispersed liquid drops is calculated using the Stokes' Law (with Dp=150 µm)
• The time taken for the dispersed phase to reach the interface and the length of the settling zone are:
and
where vd is the velocity of the dispersed phase
T s
U
D
t
2
=
L
s=
v
dt
sHORIZONTAL DECANTERS
• The dispersed phase drops finally
accumulate near the interface to form a
coalescing zone
• The length of the coalescing zone of the
decanter is determined by the time required
for the dispersed phase to coalesce.
HORIZONTAL DECANTERS
• No relationship can predict the time required
for coalescence (from seconds to many
hours, by experiments)
• Coalescence is enhanced by:
– low viscosity of the continuous phase,
– large density difference between the phases, – large interfacial tension,
HORIZONTAL DECANTERS
• It is usually recommended that the thickness of the coalescing zone be Hc≤ 10% of the decanter
diameter
• It is also assumed that the drops occupy about half of the volume of the coalescing zone volume.
• If the liquid-liquid interface is at the center of the separator, the dispersion zone volume is
approximately equal to:
where AI is the area of the interface.
I c
c
H
A
INTRODUCTION
• The residence time, t
c, of the drops in the
coalescing zone is given by:
where QD is the
volumetric flow rate
of the dispersed phase
• tc is specified by experience, and the interfacial area required for coalescence (AI) is calculated.
D I c D c c
Q
A
H
Q
V
t
2
1
2
1
=
=
HORIZONTAL DECANTERS
• The length of the coalescing zone, L
c, is
calculated from (neglecting the actual shape
of the shell):
and thus the total length of the separator is
calculated:
D
A
L
c=
I/
c sL
L
L
=
+
SUMMARY OF THE SIZING
PROCEDURE
1.
Calculate θ to determine the dispersed phase 2. Calculate the inside diameter of the decanter,assuming that the light phase determines the diameter.
3. Calculate the inside diameter of the decanter, assuming that the heavy phase determines the diameter.
4. The decanter diameter is the larger of the diameters calculated in Steps 2 and 3.
SUMMARY OF THE SIZING
PROCEDURE
6.
Calculate ts, the dispersed-phase settling time 7. Calculate Ls, the decanter length required forsettling of the dispersed phase
8. Determine Hc, the coalescing-zone height
9. Calculate AI, the interfacial area required for coalescing the dispersed phase
10. Calculate Lc, the decanter length required for coalescing the dispersed phase
PIPING ARRANGEMENT
To prevent generating turbulence and entraining in the vessel, both the inlet and outlet liquid streams velocities should be kept relatively low:
• the inlet velocity should be below 1 m/s
• the liquid velocity in each outlet nozzle should not be greater than 10 times the average velocity of each phase in the decanter
SPECIAL CONFIGURATIONS
When separation is a problem, different arrangements are used:
– proprietary equipment (baffles, parallel plates, etc.) – centrifugal separation (centrifuges, hydrocyclones)
1/3 Ddrum ≥1500 500 1000-1500 ½ Ddrum ≤1000 Dpot (mm) Ddrum (mm)
When a small amount of
heavy phase is present, it is preferable to use a
settling pot on the bottom of the drum to save