Engineering Dependable Protection
Engineering Dependable Protection
Engineering Dependable Protection - Part I
Engineering Dependable Protection - Part I
"A Simple Approach to Short-Circuit Calculations"
"A Simple Approach to Short-Circuit Calculations"
T
Ta
ab
blle
e
o
of
f
C
Co
on
ntte
en
nttss
P
Pa
ag
ge
e
Basic C
Basic Consid
onsiderati
erations of Short-
ons of Short-Circ
Circuit Calc
uit Calculatio
ulations
ns ………
………
………3
…3
- Why
- Why Short-C
Short-Circu
ircuit Ca
it Calcula
lculations
tions ………
………
………3
………3
- Gener
- General Comm
al Comments on Shor
ents on Short-Cir
t-Circuit Ca
cuit Calcula
lculations
tions ………
………
………3
…3
-
- Asym
Asymmetri
metrical
cal Compon
Components
ents ………
………
………
………3
3
-
- Interr
Interrupting Rating, Interru
upting Rating, Interrupting Capacit
pting Capacity, Short-C
y, Short-Circu
ircuit Currents
it Currents ………
………4
…………4
3
3
ØØShort-C
Short-Circu
ircuit Current Calculati
it Current Calculations, Procedur
ons, Procedures and
es and Method
Methodss ………
………5
………5
-
- Ohmic
Ohmic Method
Method ………
………6
………6
-
- Per
Per-Un
-Unit
it Met
Method
hod …………
………
………
………
………
………
………
………1
………11
1
- TRON
- TRON
®®Comput
Computer Software Pro
er Software Procedur
ceduree ………
………
………16
………16
- Poin
- Point-to-Po
t-to-Point Me
int Method
thod ………
………
………
………17
……17
- Comparis
- Comparison of
on of Resul
Results
ts ………
………
………
………19
……19
1
1
ØØShort-Circuit Calculation on 1
Short-Circuit Calculation on 1
ØØT
Transfo
ransformer
rmer Syste
System, Pr
m, Procedu
ocedures a
res and Me
nd Methods
thods ………20
………20
- Per
- Per-Unit M
-Unit Method - Li
ethod - Line-to-
ne-to-Line F
Line Faults
aults ………
………
………21
…………21
- Per-Un
- Per-Unit Method - Line-to-
it Method - Line-to-Neutra
Neutral Faults
l Faults ………
………
………22
…………22
- Point-to-Po
- Point-to-Point Method - Line-to-Li
int Method - Line-to-Line Faults
ne Faults ………
………
………23
………23
- Point-to-Point
- Point-to-Point Method -
Method - Line-to-Neutral F
Line-to-Neutral Faults
aults ………
………24
……24
- Compariso
- Comparison of
n of Resu
Results
lts ………
………
………
………24
…24
Data Section………25
Data Section………25
- T
- Table 1
able 1 - T
- Transformer Impedance
ransformer Impedance Data
Data ………
………25
………25
- T
- Table 2
able 2 - Current
- Current Trans
Transformer Reacta
former Reactance Data
nce Data ………
………25
………25
- T
- Table 3 - D
able 3 - Disco
isconnecti
nnecting Switc
ng Switch Reac
h Reactance D
tance Data
ata ………
………
………25
…25
- Tab
- Table 4 - Circuit Bre
le 4 - Circuit Breaker Re
aker Reactan
actance Data
ce Data ………
………
………26
…………26
- Ta
- Table 5 - Insul
ble 5 - Insulated Con
ated Conductors I
ductors Impeda
mpedance Dat
nce Dataa ………
………
………26
…26
- Table
- Table 6 - “C” Values for PTP
6 - “C” Values for PTP Method Data
Method Data ………
………27
………27
- T
- Table 7 - Buswa
able 7 - Busway Impedance Da
y Impedance Data
ta ………
………28
………28
- T
- Table 8
able 8 - Asymmetric
- Asymmetrical Fac
al Factors
tors ………
………29
………29
Selec
Selective
tive Coordi
Coordination
nation -
- EDP
EDP II
II ………
………
………
………29
29
Selec
Part 1
Part 1
A Simple Approach
A Simple Approach
T
To
o
Short Circuit
Short Circuit
Calculations
Calculations
(2004-1)
(2004-1)
Protection
Protection
For An
For An
Electrical
Electrical
Distribution
Distribution
System
System
Basic Considerations of Short-Circuit Calculations
Basic Considerations of Short-Circuit Calculations
Sources of short circuit current that are
Sources of short circuit current that are normally taken
normally taken
under consideration include:
under consideration include:
-
- Utility
Utility Generation
Generation
-
- Local
Local Generation
Generation
-
- Synchronous
Synchronous Motors
Motors and
and
-
- Induction
Induction Motors
Motors
Capacitor discharge currents can normally be
Capacitor discharge currents can normally be
neglected due to
neglected due to their short time
their short time duration.
duration. Certain IEEE
Certain IEEE
(Institu
(Institute of
te of Electrical and Electronic Engineers
Electrical and Electronic Engineers)
) publications
publications
detail how
detail how to calculate these
to calculate these currents if they
currents if they are substantial.
are substantial.
Asymmetrical Components
Asymmetrical Components
Short circuit current normally takes on
Short circuit current normally takes on an asymmetrical
an asymmetrical
characteristic during the first few cycles of duration. That is,
characteristic during the first few cycles of duration. That is,
it is offset abou
it is offset about the zero axis, as indi
t the zero axis, as indicated
cated in Figure 1.
in Figure 1.
Figure 1
Figure 1
In Figure 2, note that the total short circuit current I
In Figure 2, note that the total short circuit current I
aais
is
the summation of two components - the
the summation of two components - the symmetrical RMS
symmetrical RMS
current I
current I
SS, and the DC component, I
, and the DC component, I
DCDC. The DC component
. The DC component
is a function of the stored energy within the system at the
is a function of the stored energy within the system at the
initiation of the short circuit. It decays to zero after a few
initiation of the short circuit. It decays to zero after a few
cycles due to I
cycles due to I
22R losses in the system, at which point
R losses in the system, at which point the
the
short circuit current is symmetrical about the zero axis. The
short circuit current is symmetrical about the zero axis. The
RMS value of the symmetrical co
RMS value of the symmetrical co mponent may be deter-
mponent may be
deter-mined using Ohm`s L
mined using Ohm`s L aw. T
aw. To determine
o determine the asymmetrical
the asymmetrical
component, it is necessar
component, it is necessar y to know the X/R ratio of the
y to know the X/R ratio of the
system. To obtain the X/R ratio, the total resistance and total
system. To obtain the X/R ratio, the total resistance and total
reactance of the circuit to the point of fault must be
reactance of the circuit to the point of fault must be
determined. Maximum thermal and mechanical stress on
determined. Maximum thermal and mechanical stress on
the equipment occurs during these first few cycles. It is
the equipment occurs during these first few cycles. It is
important to concentrate on what happens dur
important to concentrate on what happens dur ing the first
ing the first
half cycle after the initiation of
half cycle after the initiation of the fault.
the fault.
Why Short-Circuit Calculations
Why Short-Circuit Calculations
Several sections of the National Electrical Code relate
Several sections of the National Electrical Code relate
to
to proper overcurrent
proper overcurrent protection.
protection. Safe
Safe and
and reliable
reliable
application of overcurrent protective devices based on
application of overcurrent protective devices based on
these sections mandate that a short
these sections mandate that a short circuit study and a
circuit study and a
selective coordination study be conducted.
selective coordination study be conducted.
These sections include, among others:
These sections include, among others:
110-9
110-9 Interrupting
Interrupting Rating
Rating
110-10
110-10 Component
Component Protection
Protection
230-65
230-65 Service
Service Entrance Eq
Entrance Equipment
uipment
240-1
240-1 Conductor
Conductor Protection
Protection
250-95
250-95 Equipment Gr
Equipment Grounding Conductor P
ounding Conductor Protection
rotection
517-17
517-17 Health Car
Health Care Facilities - Selec
e Facilities - Selective Coordinat
tive Coordination
ion
Compliance with these code sections can best be
Compliance with these code sections can best be
accomplished by conducting a shor
accomplished by conducting a shor t circuit study and a
t circuit study and a
selective coordination study.
selective coordination study.
The protection for an electrical system should not only
The protection for an electrical system should not only
be safe under all service conditions but, to insure continuity
be safe under all service conditions but, to insure continuity
of service, it s
of service, it should be selectively coordinated as
hould be selectively coordinated as well.
well. A
A
coordinated system is one where only the faulted circuit is
coordinated system is one where only the faulted circuit is
isolated without disturbing any other part of the system.
isolated without disturbing any other part of the system.
Overcurrent protection devices should also provide
Overcurrent protection devices should also provide
short-circuit as well as overload protection for system
circuit as well as overload protection for system
components, such as bus, wire, motor controllers, etc.
components, such as bus, wire, motor controllers, etc.
T
To obtain reliable,
o obtain reliable, coordinated operation and assure
coordinated operation and assure
that system components are protected from damage, it is
that system components are protected from damage, it is
necessary to first calculate the available fault current at
necessary to first calculate the available fault current at
various critical points in the electrical
various critical points in the electrical system.
system.
Once the short-circuit levels are determined, the
Once the short-circuit levels are determined, the
engineer can specify proper interrupting rating
engineer can specify proper interrupting rating
require-ments, selectively coordinate the system and provide
ments, selectively coordinate the system and provide
component protection.
component protection.
General Comments on Short-Circuit Calculations
General Comments on Short-Circuit Calculations
Short Circuit Calculations should be done at all
Short Circuit Calculations should be done at all critical
critical
points in the system.
points in the system.
These would include:
These would include:
-
- Service
Service Entrance
Entrance
-
- Panel
Panel Boards
Boards
-
- Motor C
Motor Control
ontrol Centers
Centers
-
- Motor
Motor Starters
Starters
-
- Transfer
Transfer Switches
Switches
-
- Load
Load Centers
Centers
Normally
Normally, short
, short circuit studies involve calculating
circuit studies involve calculating a
a
bolted 3-phase fault
bolted 3-phase fault condition.
condition. This can be
This can be characterized
characterized
as all three phases “bolted” together to create a zero
as all three phases “bolted” together to create a zero
impedance connection.
impedance connection. This establishes
This establishes a “worst
a “worst case”
case”
condition, that results in maximum thermal and mechanical
condition, that results in maximum thermal and mechanical
stress in the
stress in the system.
system. From this calculation, other types
From this calculation, other types of
of
fault conditions can be obtained.
fault conditions can be obtained.
C C U U R R R R EE N N TT TIME TIME
T
To accomplish this,
o accomplish this, study Figure 2, and refer to T
study Figure 2, and refer to Table 8.
able 8.
Figure 2 illustrates a worst case waveform that 1 phase
Figure 2 illustrates a worst case waveform that 1 phase
of the 3 phase system will assume during the first few
of the 3 phase system will assume during the first few
cycles after the fault initiation.
cycles after the fault initiation.
For this example, assume an RMS
For this example, assume an RMS symmetrical short
symmetrical short
circuit value of 50,000 amperes, at a 15% short circuit
circuit value of 50,000 amperes, at a 15% short circuit
power factor.
power factor. Locate the 15% P
Locate the 15% P.F
.F. in T
. in Table 8.
able 8. Said another
Said another
way
way,
, the X/R short circuit ratio of t
the X/R short circuit ratio of this circuit is 6.5912.
his circuit is 6.5912.
The key portions are:
The key portions are:
- Symmetrical RMS Short Circuit Current =
- Symmetrical RMS Short Circuit Current = II
ss- Instantaneous Peak Current =
- Instantaneous Peak Current = II
pp- Asymmetrical RMS Short
- Asymmetrical RMS Short Circuit Current
Circuit Current
(worst case single phase) =
(worst case single phase) = II
aaFrom Table 8, note the following relationships.
From Table 8, note the following relationships.
II
ss= Symmetrical RMS Current
= Symmetrical RMS Current
II
pp=
= II
ssx
x M
M
pp(Column 3)
(Column 3)
II
aa=
= II
ssx
x M
M
mm(Column 4)
(Column 4)
For this example, Figure 2,
For this example, Figure 2,
II
ss= 50,000 Amperes RMS
= 50,000 Amperes RMS Symmetrical
Symmetrical
II
pp= 50,000 x 2.309 ( Column 3)
= 50,000 x 2.309 ( Column 3)
= 115,450 Amperes
= 115,450 Amperes
II
aa= 50,000 x 1.330 (Column 4)
= 50,000 x 1.330 (Column 4)
= 66,500
= 66,500 Amperes RMS Asymmetrical
Amperes RMS Asymmetrical
With this basic understanding, proceed in the systems
With this basic understanding, proceed in the systems
analysis.
analysis.
Basic Considerations of Short-Circuit Calculations
Basic Considerations of Short-Circuit Calculations
II
nterrupting Rating, Interrupting Capacity and Short-Circuit Currents
nterrupting Rating, Interrupting Capacity and Short-Circuit Currents
Interrupting Rating can
Interrupting Rating can be defined as
be defined as “the maximum
“the maximum
short-circuit current that a protective device can safely
short-circuit current that a protective device can safely
clear
clear, under
, under specified test conditions.”
specified test conditions.”
Interrupting Capacity can be defined as “the actual
Interrupting Capacity can be defined as “the actual
short circuit current that a protective device has been
short circuit current that a protective device has been
tested to interrupt.”
tested to interrupt.”
The National Electrical Code requires adequate
The National Electrical Code requires adequate
interrupting ratings in Sections 110-9 and 230-65.
interrupting ratings in Sections 110-9 and 230-65.
Section 110-9 Interrupting Rating.
Section 110-9 Interrupting Rating. Equipment intended to
Equipment intended to
break current at fault levels shall have an
break current at fault levels shall have an interrupting rating
interrupting rating
sufficient for the system voltage and the current which is
sufficient for the system voltage and the current which is
available at the line terminals of
available at the line terminals of the equipment.
the equipment.
Section 230-65. Available Short-Circuit Current.
Section 230-65. Available Short-Circuit Current. Service
Service
Equipment shall be suitable for the short circuit current
Equipment shall be suitable for the short circuit current
available at its supply terminals.
available at its supply terminals.
Low voltage fuses have their interrupting rating
Low voltage fuses have their interrupting rating
expressed in terms of the symmetrical component of
expressed in terms of the symmetrical component of
short-circuit current, I
circuit current, I
SS. They are given an RMS symmetrical
. They are given an RMS symmetrical
interrupting rating at a
interrupting rating at a specific power factor
specific power factor. This means
. This means
that the fuse can interrupt any asymmetrical current
that the fuse can interrupt any asymmetrical current
associated with this rating. Thus only the symmetrical
associated with this rating. Thus only the symmetrical
component of short-circuit current need be considered to
component of short-circuit current need be considered to
determine the necessary interrupting rating of a low voltage
determine the necessary interrupting rating of a low voltage
fuse. For U.L. listed low
fuse. For U.L. listed low voltage fuses, interrupting rating
voltage fuses, interrupting rating
equals its interrupting capacity.
equals its interrupting capacity.
Low voltage molded case circuit breakers also have
Low voltage molded case circuit breakers also have
their interrupting rating expressed in terms of RMS
their interrupting rating expressed in terms of RMS
symmetrical amperes at a
symmetrical amperes at a specific power factor.
specific power factor. However,
However,
it is necessary to
it is necessary to determine a molded case
determine a molded case circuit breaker’
circuit breaker’s
s
interrupting capacity in order to
interrupting capacity in order to safely apply
safely apply it.
it. The reader
The reader
is directed to Buss bulletin PMCB II for an understanding of
is directed to Buss bulletin PMCB II for an understanding of
this concept.
this concept.
IIPP== 115,450A 115,450A IIaa== 66,500A 66,500A IIss== 50,000A 50,000AIIaa- Asymmetrical RMS Current- Asymmetrical RMS Current
IIDCDC- DC Component- DC Component
IIss- Symmetrical RMS Component- Symmetrical RMS Component
IIPP- Instantaneous Peak Current- Instantaneous Peak Current
Figure 2
Figure 2
C C U U R R R R EE N N TT IIaa IIDCDC TIME TIME IIssProcedures and Methods
Procedures and Methods
3Ø Short-Circuit Current Calculations,
3Ø Short-Circuit Current Calculations,
Procedures and Methods
Procedures and Methods
To determine the fault current at any point in the
To determine the fault current at any point in the
system, first draw a one-line diagram showing all of
system, first draw a one-line diagram showing all of the
the
sources of short-circuit current feeding into the
sources of short-circuit current feeding into the fault, as well
fault, as well
as the impedances of the
as the impedances of the circuit components.
circuit components.
To begin the study, the system components, including
To begin the study, the system components, including
those of the utility system, are represented as impedances
those of the utility system, are represented as impedances
in the diagram.
in the diagram.
The impedance tables given in the Data Section
The impedance tables given in the Data Section
include three phase and single phase transformers, current
include three phase and single phase transformers, current
transforme
transforme rs, safety
rs, safety switches, circuit
switches, circuit breakers, cable,
breakers, cable, and
and
busway
busway.
. These tables can be used if information from the
These tables can be used if information from the
manufacturers is not readily available.
manufacturers is not readily available.
It must be understood that short circuit calculations are
It must be understood that short circuit calculations are
performed without current limiting devices in
performed without current limiting devices in the system.
the system.
Calculations are done as though these devices are
Calculations are done as though these devices are
replaced with copper bars, to determine the maximum
replaced with copper bars, to determine the maximum
“available” short circuit
“available” short circuit current.
current. This is
This is necessary to
necessary to
project how the system and the current limiting devices will
project how the system and the current limiting devices will
perform.
perform.
Also, current limiting devices do not operate in
Also, current limiting devices do not operate in series
series
to produce a
to produce a “compounding” current lim
“compounding” current limiting effect.
iting effect. The
The
downstream, or load side, fuse will operate alone under a
downstream, or load side, fuse will operate alone under a
short circuit condition if properly coordinated.
short circuit condition if properly coordinated.
System A
System A
3Ø Single Transformer System
3Ø Single Transformer System
M M Available Utility Available Utility S.C. MVA 100,000 S.C. MVA 100,000 1500 KVA Transformer 1500 KVA Transformer 480Y/277V, 480Y/277V, 3.5%Z, 3.45%X, .56%R 3.5%Z, 3.45%X, .56%R IIf.l.f.l.= 1804A= 1804A 25’ - 500kcmil 25’ - 500kcmil 6 Per Phase 6 Per Phase
Service Entrance Conductors Service Entrance Conductors in Steel Conduit in Steel Conduit 2000A Switch 2000A Switch KRP-C-2000SP Fuse KRP-C-2000SP Fuse Main Swb’d. Main Swb’d. 400A Switch 400A Switch LPS-RK-400SP Fuse LPS-RK-400SP Fuse 50’ - 500 kcmil 50’ - 500 kcmil
Feeder Cable in Steel Conduit Feeder Cable in Steel Conduit Fault X Fault X22 MCC No. 1 MCC No. 1 Motor Motor Fault X Fault X11
System B
System B
33
Ø
Ø
Double Transformer System
Double Transformer System
1000 KVA Transformer, 1000 KVA Transformer, 480/277 Volts 3Ø 480/277 Volts 3Ø 3.45%X, .60%R 3.45%X, .60%R IIf.l.f.l.= 1203A= 1203A Available Utility Available Utility S.C. KVA 500,000 S.C. KVA 500,000 30’ - 500 kcmil 30’ - 500 kcmil 4 Per Phase 4 Per Phase Copper in PVC Conduit
Copper in PVC Conduit 1600A Switch1600A Switch KRP-C-1500SP Fuse KRP-C-1500SP Fuse LPS-RK-350SP Fuse LPS-RK-350SP Fuse 400A Switch 400A Switch 225 KVA 225 KVA 208/120 Volts 3Ø 208/120 Volts 3Ø .998%X, .666%R .998%X, .666%R 20’ - 2/0 20’ - 2/0 2 Per Phase 2 Per Phase Copper in PVC Conduit Copper in PVC Conduit
In this example, assume 0% motor load. In this example, assume 0% motor load.
22
T
To begin the
o begin the analysis, consider the following system,
analysis, consider the following system,
supplied by a 1500
supplied by a 1500 KV
KVA, three phase transformer
A, three phase transformer having a
having a
full load current of
full load current of 1804 amperes at 480
1804 amperes at 480 volts.
volts. (See System
(See System
A, below)
A, below) Also, System B
Also, System B, for a double transformation, wil
, for a double transformation, willl
be studied.
be studied.
To start, obtain the available short-circuit KVA, MVA, or
To start, obtain the available short-circuit KVA, MVA, or
SCA from the local utility company.
SCA from the local utility company.
The utility estimates that System A can
The utility estimates that System A can deliver a short-
deliver a
short-circuit of 100,00
circuit of 100,00 0 MVA
0 MVA at the primar
at the primar y of the transforme
y of the transforme r.
r.
System B can deliver a
short-System B can deliver a short- circuit of 500,000 KVA at the
circuit of 500,000 KVA at the
primary of the first transformer
primary of the first transformer. Since the X
. Since the X /R ratio of t
/R ratio of t he
he
utility system is usually quite high, only the reactance need
utility system is usually quite high, only the reactance need
be considered.
be considered.
With this available short-circuit information, begin to
With this available short-circuit information, begin to
make the necessary calculations to determine the fault
make the necessary calculations to determine the fault
current at any point in
current at any point in the electrical system.
the electrical system.
Four basic methods will be presented in this text to
Four basic methods will be presented in this text to
instruct the reader on short
instruct the reader on short circuit calculations.
circuit calculations.
These include :
These include :
- the ohmic method
- the ohmic method
- the per unit method
- the per unit method
- the TRON
- the TRON
® ®Computer Software method
Computer Software method
- the point to point method
- the point to point method
11
22
Note: The above 1500KVA transformer serves 100% motor Note: The above 1500KVA transformer serves 100% motor load.load.
Fault X Fault X11
Fault X Fault X22
• •
Ohmic Method
Ohmic Method
33Ø
Ø Short Circuit Calculations,
Short Circuit Calculations,
Ohmic Method
Ohmic Method
Most circuit component impedances are given in ohms
Most circuit component impedances are given in ohms
except utility and transformer impedances which are found
except utility and transformer impedances which are found
by the following formulae* (Note that the transformer and
by the following formulae* (Note that the transformer and
utility ohms are referred to the secondary KV by squaring
utility ohms are referred to the secondary KV by squaring
the secondary voltage.)
the secondary voltage.)
Step 1.
Step 1.
††X
X
utilityutilityΩΩ==
1000 (KV
1000 (KV
secondarysecondary))
22S.C. KVA
S.C. KVA
utilityutilityS
Stteep
p 22..
X
X
transtransΩΩ==
(10)(%X**)(KV
(10)(%X**)(KV
secondarysecondary))
22KVA
KVA
transtransR
R
transtransΩΩ==
(10)(%R**)(KV
(10)(%R**)(KV
secondarysecondary))
22KVA
KVA
transtransStep 3.
Step 3.
The impedance (in ohms) given for
The impedance (in ohms) given for current
current
transformers, large switches and large circuit breakers is
transformers, large switches and large circuit breakers is
essentially all X.
essentially all X.
S
Stteep
p 44..
X
X
cable and buscable and busΩΩ..R
R
cable and buscable and busΩΩ..Step 5.
Step 5.
T
Total
otal all
all X
X and all
and all R
R in system to point of fault.
in system to point of fault.
Step 6.
Step 6.
Determine impedance (in ohms) of the
Determine impedance (in ohms) of the system by:
system by:
ZZ
TT==
√
√
(R
(R
TT))
22+ (X
+ (X
TT))
22Step 7.
Step 7.
Calculate short-circuit symmetrical RMS amperes
Calculate short-circuit symmetrical RMS amperes
at the point of fault.
at the point of fault.
II
S.CS.C. sym. sym RMSRMS==
EE
secondasecondaryry line-linline-linee√
√
3 (Z
3 (Z
TT))
Step 8.
Step 8.
Determine the motor
Determine the motor load.
load. Add up the
Add up the full load
full load
motor currents.
motor currents. The full load motor current in
The full load motor current in the system is
the system is
generally a percentage of the transformer full
generally a percentage of the transformer full load current,
load current,
depending upon the types of loads. The generally
depending upon the types of loads. The generally
accepted procedure assumes 50% motor load when both
accepted procedure assumes 50% motor load when both
motor and lighting loads are considered, such as supplied
motor and lighting loads are considered, such as supplied
by 4 wire, 208Y/120V and 480Y/277V volt 3-phase
by 4 wire, 208Y/120V and 480Y/277V volt 3-phase
systems.)
systems.)
*For simplicity of calculations all
*For simplicity of calculations all ohmic values are single phase ohmic values are single phase distance one way, later compensated for in distance one way, later compensated for in the three phase short-circuit formula the three phase short-circuit formula by the factor,by the factor,
√
√
3.3. (See Step 7.)(See Step 7.)
**UL Listed transformers 25 KVA and larger have a
**UL Listed transformers 25 KVA and larger have a ±±10% impedance tolera10% impedance tolerance. nce. Short circuit amperes can be affeShort circuit amperes can be affected by this tolerance.cted by this tolerance. †Only X is considered in this procedure since utility X/R ratios are usually quite high.
†Only X is considered in this procedure since utility X/R ratios are usually quite high. For more finite details obtain R of utility source.For more finite details obtain R of utility source. •
•AA more exact determinatimore exact determination depends upon the sub-transient reacton depends upon the sub-transient reactance of the motors in question and ance of the motors in question and associated circuit imassociated circuit impedances. pedances. A less conservativeA less conservative method would involve the total motor circuit
method would involve the total motor circuit impedance to a common bus (sometimes referred to as a “zero reactance bus”).impedance to a common bus (sometimes referred to as a “zero reactance bus”). ††Arithmeti
††Arithmetical addition results in conservative values of fault current. cal addition results in conservative values of fault current. More finite values involve vectorial addition of the currents.More finite values involve vectorial addition of the currents.
Step 9.
Step 9.
The symmetrical motor contribution can be
The symmetrical motor contribution can be
approximated by using an average multiplying factor
approximated by using an average multiplying factor
associated with the
associated with the motors in the sys
motors in the system.
tem. This factor varies
This factor varies
according to motor design and in this text may be chosen
according to motor design and in this text may be chosen
as 4 times motor full load current for approximate
as 4 times motor full load current for approximate
calculatio
calculatio n purposes.
n purposes. T
To solve
o solve for the
for the symmetrical motor
symmetrical motor
contribution:
contribution:
••
II
sym motor contrib
sym motor contrib
== (4)
(4) xx (I
(I
full load motorfull load motor))
Step 10.
Step 10.
The total symmetrical short-circuit RMS current is
The total symmetrical short-circuit RMS current is
calculated as:
calculated as:
†† ††II
total
total S.C. syS.C. symm RMSRMS
== (I
(I
S.C. sym RMSS.C. sym RMS)) ++ (I
(I
sym motor contribsym motor contrib))
Step 11.
Step 11.
Determine X/R ratio of the system to the point of
Determine X/R ratio of the system to the point of
fault.
fault.
X/R
X/R
ratioratio==
X
X
totaltotal Ω ΩR
R
totaltotalΩΩStep 12.
Step 12.
The asymmetrical factor corresponding to the X/R
The asymmetrical factor corresponding to the X/R
ratio in Step 11 is found in Table 8, Column
ratio in Step 11 is found in Table 8, Column M
M
mm. This
. This
multiplier will provide the worst case asymmetry occurring
multiplier will provide the worst case asymmetry occurring
in the first 1/2 cycle. When the average 3-phase multiplier
in the first 1/2 cycle. When the average 3-phase multiplier
is desired use column
is desired use column M
M
aa..
Step 13
Step 13
.
. Calculate the
Calculate the asymmetrical RMS
asymmetrical RMS short-circu
short-circu it
it
current.
current.
II
S.C. asym RMSS.C. asym RMS= (I
= (I
S.C. sym RMSS.C. sym RMS) x (Asym Factor)
) x (Asym Factor)
Step 14.
Step 14.
The short-circuit current that the motor load can
The short-circuit current that the motor load can
contribute is an asymmetrical current usually approximated
contribute is an asymmetrical current usually approximated
as being equal to the
as being equal to the locked rotor current of
locked rotor current of the motor.
the motor.
As a close approximation with a margin of
As a close approximation with a margin of safety use:
safety use:
••
II
asym motor contribasym motor contrib= (5)
= (5) xx (I
(I
full load motorfull load motor))
Step 15.
Step 15.
The total asymmetrical short-circuit RMS current is
The total asymmetrical short-circuit RMS current is
calculated as:
calculated as:
M
M MM
Ohmic Method –
Ohmic Method –
To Fault X
To Fault X
1
1
– System A
– System A
Available Utility Available Utility S.C. MVA 100,000 S.C. MVA 100,000 1500 KVA Transformer, 1500 KVA Transformer, 480V, 3Ø, 480V, 3Ø, 3.5%Z, 3.4 3.5%Z, 3.45%X5%X , 0.56%R, 0.56%R IIf.f.l.l. transtrans= 1804A= 1804A
25’ - 500 kcmil 25’ - 500 kcmil 6 Per Phase 6 Per Phase Service Entrance Service Entrance
Conductors in Steel Conduit Conductors in Steel Conduit 2000A Switch 2000A Switch KRP-C-2000SP Fuse KRP-C-2000SP Fuse Fault X Fault X11 Motor Contribution Motor Contribution
R
R
X
X
X
X ==
1000(.48)
1000(.48)
22== 0.0000023
0.0000023
—
—
00..00000000002233
100,000,000
100,000,000
X
X ==
(10) (3.45) (.48)
(10) (3.45) (.48)
22== 0.0053
0.0053
—
—
0.0053
0.0053
1500
1500
R
R ==
(10) (.56) (.48)
(10) (.56) (.48)
22== 00..0000008866
00..0000008866
—
—
1500
1500
X
X ==
25'
25'
xx
0.0379
0.0379
== 00..000000115588
—
—
00..000000115588
1000
6
1000
6
R
R ==
25'
25'
xx
0.0244
0.0244
== 00..000000110022
00..00000011002
2
—
—
1000
6
1000
6
X
X == 0.000050
0.000050
—
—
0.000050
0.000050
Total R and X
Total R and X ==
00..000000996622
00..0000555511
ZZ
total pertotal per==
√
√
(0.000962)
(0.000962)
22++ (0.00551)
(0.00551)
22== 0.0056
0.0056
Ω
Ω
phasephase
II
S.C. sym RMSS.C. sym RMS==
480
480
= 49,489A
= 49,489A
√
√
3 (.0056)
3 (.0056)
II
sym motor contribsym motor contrib= 4
= 4 xx 1804
1804 == 7216A
7216A
(100% motor load)(100% motor load)
II
total S.C. sym RMStotal S.C. sym RMS== 49,489
49,489 ++ 7216
7216 == 56,705A
56,705A
(fault X (fault X11))X/R
X/R
ratioratio== .00551
.00551 = 5.73
= 5.73
.000962
.000962
Asym Factor
Asym Factor == 1.294 (Table 8)
1.294 (Table 8)
II
S.C. asym RMSS.C. asym RMS== 1.294
1.294 xx 49,489
49,489 == 64,039A
64,039A
II
asym motor contribasym motor contrib== 55 xx 1804
1804 == 9,020A
9,020A
(100% motor load)(100% motor load)
II
total S.C. asym RMStotal S.C. asym RMS== 64,039
64,039 ++ 9,020
9,020 == 73,059A
73,059A
(fault X(fault X11))
O
Onnee--LLiinne D ie D iaaggr ar amm IImmppeeddaanncce D ie D iaaggrraamm
1
1 11
Note:
Note: See Ohmic Method Procedure for Formulas.See Ohmic Method Procedure for Formulas.
(Table 1.2)
(Table 1.2)
(Table 3)
(Table 3)
(Table 5)
(Table 5)
R
R
X
X
X
X == 00..0000555511
—
—
00..0000555511
R
R == 00..000000996622
00..000000996622
—
—
X
X == ..0000000088
—
—
00..0000000088
X
X ==
50’
50’ xx .0379
.0379 == 00..0000118899
—
—
00..0000118899
1000
1000
R
R ==
50’
50’ xx .0244
.0244 == 00..0000112222
00..0000112222
—
—
1000
1000
Total R and X
Total R and X ==
00..000022118822
00..0000774488
ZZ
total pertotal per==
√
√
(0.002182)
(0.002182)
22++ (0.00748)
(0.00748)
22== 0.00778
0.00778
Ω
Ω
phasephase
II
S.C. sym RMSS.C. sym RMS==
480
480
== 35,621A
35,621A
√
√
3 (.00778)
3 (.00778)
II
sym motor contribsym motor contrib== 44 xx 1804
1804 == 7216A
7216A
(100% motor load)(100% motor load)
II
total S.C. sym RMStotal S.C. sym RMS== 35,621
35,621 ++ 7,216
7,216 == 42,837A
42,837A
(fault X (fault X22))X/R
X/R
ratioratio== .00748
.00748 == 3.43
3.43
.002182
.002182
Asym Factor
Asym Factor == 1.149 (Table 8)
1.149 (Table 8)
II
S.C. asym RMSS.C. asym RMS== 1.149
1.149 xx 35,621
35,621 == 40,929A
40,929A
II
asym motor contribasym motor contrib== 55 xx 1804
1804 == 9,020A
9,020A
(100% motor load)(100% motor load)
II
total S.C. asym RMStotal S.C. asym RMS== 40,929
40,929 ++ 9,020
9,020 == 49,949A
49,949A
(fault X(fault X22))
Note:
Note: See Ohmic Method Procedure for See Ohmic Method Procedure for Formulas. Actual motor contributionFormulas. Actual motor contribution will be somewhat smaller than calculated due to the impedance of the will be somewhat smaller than calculated due to the impedance of the feeder cable.
feeder cable.
Ohmic Method –
Ohmic Method –
To Fault X
To Fault X
2
2
– System A
– System A
M M MM Adjusted Impedance Adjusted Impedance to Fault X to Fault X11 Fault X Fault X11 400A Switch 400A Switch LPS-RK-400SP Fuse LPS-RK-400SP Fuse 50’ - 500 kcmil 50’ - 500 kcmil Feeder Cable Feeder Cable in Steel Conduit in Steel Conduit Fault X Fault X22 Motor Contribution Motor Contribution One-Line Diagram
One-Line Diagram Impedance DiagramImpedance Diagram
22 22 11 11
(Table 3)
(Table 3)
(Table 5)
(Table 5)
To use the OHMIC Method through a second transformer,
To use the OHMIC Method through a second transformer,
the following steps apply:
the following steps apply:
Step 1a.
Step 1a.
Summarize X and R values of
Summarize X and R values of all components on
all components on
primary side
primary side of transformer.
of transformer.
O
Onene-L-Liine ne DDiaiagrgramam IImmpepedadannce ce DDiaiaggraramm
Step 1b.
Step 1b.
Reflect X and R values of
Reflect X and R values of all components to
all components to
secondary side of transformer
secondary side of transformer
X
X
ss== V
V
ss22(X
(X
pp))
R
R
ss== V
V
ss22(R
(R
pp))
V
V
pp22V
V
pp22and proceed with steps 2 thru 15 from page 6.
and proceed with steps 2 thru 15 from page 6.
Ohmic Method –
Ohmic Method –
To Fault X
To Fault X
1
1
– System
– System
B
B
R
R
X
X
X
X ==
100
10000 (.4
(.48)
8)
22== ..000000446611
—
—
..000000446611
500,000
500,000
X
X ==
(10) (3.45) (.48)
(10) (3.45) (.48)
22== ..0000779955
—
—
..0000779955
1000
1000
R
R ==
(10) (.60) (.48)
(10) (.60) (.48)
22== ..0000113388
..0000113388
—
—
1000
1000
X
X ==
11000000
30'
30'
xx
.0303 == .000227
.0303
44
.000227
—
—
..000227
000227
R
R ==
30'
30'
xx
.0220
.0220
== ..000000116655
..000000116655
—
—
11000000
44
X
X == ..000000005500
—
—
..0000000055
TToottaal
l R
R aannd
d X
X ==
..000011554455
..000088668888
ZZ
total pertotal per==
√
√
(.001545)
(.001545)
22++ (.008688)
(.008688)
22== .008824
.008824
Ω
Ω
phase phase
II
S.C. sym RMSS.C. sym RMS==
480
480
== 31,405A
31,405A
√
√
3 (.008824)
3 (.008824)
X/R
X/R
ratioratio== .008688
.008688 == 5.62
5.62
.001545
.001545
Asym Factor
Asym Factor == 1.285 (Table 8)
1.285 (Table 8)
II
S.C. asym RMSS.C. asym RMS== 31,405
31,405 xx 1.285
1.285 == 40,355A
40,355A
Available Utility Available Utility 500,000 S.C. KVA 500,000 S.C. KVA 1000KVA Transformer, 1000KVA Transformer, 480V, 3Ø, 480V, 3Ø, 3.45% X, .60% R 3.45% X, .60% R 30' - 500 kcmil 30' - 500 kcmil 4 Per Phase 4 Per Phase Copper in PVC Conduit Copper in PVC Conduit 1600A Switch 1600A Switch KRP-C-1500SP Fuse KRP-C-1500SP Fuse 11 11
(Table 1.2)
(Table 1.2)
(Table 3)
(Table 3)
(Table 5)
(Table 5)
Ohmic Method –
Ohmic Method –
To Fault X
To Fault X
2
2
– System B
– System B
Adjusted Impedance Adjusted Impedance to fault X to fault X11 400A Switch 400A Switch LPS-RK-350SP Fuse LPS-RK-350SP Fuse 20' - 2/0 20' - 2/0 2 Per Phase 2 Per Phase Copper in PVC Conduit Copper in PVC Conduit 225KVA Transformer, 225KVA Transformer, 208/120V, 208/120V, .998%X, .666%R .998%X, .666%R
R
R
X
X
X
X == ..000088668888
—
—
..000088668888
R
R == ..000011554455
..000011554455
—
—
X
X == ..0000000088
—
—
..0000000088
X
X ==
20'
20' xx .0327
.0327 == .000327
.000327
—
—
.000327
.000327
11000000
22
R
R ==
20'
20' xx .0812
.0812 == ..000000881122
..000000881122
—
—
11000000
22
TToottaal
l R
R aannd
d X
X ((448800V
V)
) ==
..000022335577
..000099009955
To Reflect X and R to secondary:
To Reflect X and R to secondary:
X
X
totaltotal==
(208)
(208)
22xx (.009095)
(.009095)
== ..000011770088
—
—
..000011770088
(208V) (208V)(480)
(480)
22R
R
totaltotal==
(208)
(208)
22xx (.002357)
(.002357)
== ..000000444422
..000000444422
—
—
(208V) (208V)(480)
(480)
22X
X ==
(10) (.998) (.208)
(10) (.998) (.208)
22== ..0000119922
—
—
..0000119922
225
225
R
R ==
(10) (.666) (.208)
(10) (.666) (.208)
22== ..0000112288
..0000112288
—
—
225
225
TToottaal
l R
R aannd
d X
X ((220088V
V)
) ==
..000011772222
..000033662288
ZZ
total pertotal per==
√
√
(.001722)
(.001722)
22+ (.003628)
+ (.003628)
22= .004015
= .004015
Ω
Ω
phasephase
II
S.C. sym RMSS.C. sym RMS==
208
208
== 29,911A
29,911A
√
√
3 (.004015)
3 (.004015)
X/R
X/R
ratioratio== .003628
.003628 == 2.10
2.10
.001722
.001722
Asym Factor = 1.0491 (Table 8)
Asym Factor = 1.0491 (Table 8)
II
S.C. asym RMSS.C. asym RMS= 29,911
= 29,911 xx 1.0491
1.0491 == 31,380A
31,380A
One-Line Diagram
One-Line Diagram Impedance DiagramImpedance Diagram
11 11 22 22
(Table 5)
(Table 5)
(Table 1.2)
(Table 1.2)
Per-Unit Method
Per-Unit Method
33
øø
Short Circuit
Short Circuit Calculation Per-Unit
Calculation Per-Unit Method*
Method*
The per-unit method is generally used for calculating
The per-unit method is generally used for calculating
short-circuit currents when the electrical system is more
short-circuit currents when the electrical system is more
complex.
complex.
After establishing a one-line diagram of the system,
After establishing a one-line diagram of the system,
proceed to the following calculations: **
proceed to the following calculations: **
Step 1.
Step 1.
††PUX
PUX
utilityutility==
KVA
KVA
basebaseS.C. KVA
S.C. KVA
utilityutilityS
Stteep
p 22..
P
PU
UX
X
transtrans==
(%X
(%X
••)(KVA
)(KVA
base base
))
(100)(KVA
(100)(KVA
transtrans))
PUR
PUR
transtrans==
(%R
(%R
••)(KVA
)(KVA
base base
))
(100)(KVA
(100)(KVA
transtrans))
S
Stteep
p 33..
P
PU
UX
X
component (cable,component (cable,==
(X
(X
ΩΩ
)(KVA
)(KVA
basebase))
switches, CT, bus)switches, CT, bus)
(1000)(KV)
(1000)(KV)
22S
Stteep
p 44..
P
PU
UR
R
component (cable,component (cable,==
(R
(R
ΩΩ
)( KVA
)( KVA
basebase))
switches, CT, bus)switches, CT, bus)
(1000)(KV)
(1000)(KV)
22Step 5.
Step 5.
Next, total all per-unit
Next, total all per-unit X
X and all per-unit
and all per-unit R
R in system
in system
to point of fault.
to point of fault.
Step 6.
Step 6.
Determine the per-unit impedance of the system by:
Determine the per-unit impedance of the system by:
PUZ
PUZ
totaltotal==
√
√
(PUR
(PUR
totaltotal))
22++ (PUX
(PUX
totaltotal))
22Step 7.
Step 7.
Calculate the symmetrical RMS short-circuit current
Calculate the symmetrical RMS short-circuit current
at the point of fault.
at the point of fault.
II
S.CS.C. sym. sym RMSRMS==
KVA
KVA
basebase√
√
3 (KV)(PUZ
3 (KV)(PUZ
totaltotal))
Step 8
Step 8
. Determine the
. Determine the motor load.
motor load. Add up
Add up the full load
the full load
motor currents.(Whenever motor and lighting loads are
motor currents.(Whenever motor and lighting loads are
considered, such as supplied by 4 wire, 208Y/120 and
considered, such as supplied by 4 wire, 208Y/120 and
480Y/277 volt
480Y/277 volt 3
3 phase systems,
phase systems, the generally
the generally accepted
accepted
procedure is to assume 50% motor load based on the full
procedure is to assume 50% motor load based on the full
load current rating
load current rating of the
of the transformer
transformer.)
.)
Step 9.
Step 9.
The symmetrical motor contribution can be
The symmetrical motor contribution can be
approximated by using an average multiplying factor
approximated by using an average multiplying factor
associated with the motors in the system. This factor varies
associated with the motors in the system. This factor varies
according to motor design and in this text may be chosen
according to motor design and in this text may be chosen
as 4 tim
as 4 times motor f
es motor full load current
ull load current for
for approximate
approximate
calculation purposes. To solve for the symmetrical motor
calculation purposes. To solve for the symmetrical motor
contribution:
contribution:
*** ***
II
sym motor contrib
sym motor contrib
== (4)
(4) xx (I
(I
full load motorfull load motor))
Step 10.
Step 10.
The total symmetrical short-circuit rms current is
The total symmetrical short-circuit rms current is
calculated as:
calculated as:
•• ••
II
tota
total l S.C. symS.C. sym RMSRMS
== (I
(I
S.C. sym RMSS.C. sym RMS)) ++ (I
(I
sym motor contribsym motor contrib))
Step 11.
Step 11.
Determine X/R ratio of the system to the point of
Determine X/R ratio of the system to the point of
fault.
fault.
X/R
X/R
ratioratio==
PUX
PUX
totaltotalPUR
PUR
totaltotalStep 12.
Step 12.
From Table 8, Column
From Table 8, Column M
M
mm, obtain the
, obtain the asymmetrical
asymmetrical
factor corresponding to the X/R ratio determined in Step
factor corresponding to the X/R ratio determined in Step
11. This multiplier will provide the worst case asymmetry
11. This multiplier will provide the worst case asymmetry
occurring in the first
occurring in the first 1/2 cycle.
1/2 cycle. When the average 3-ph
When the average 3-phase
ase
multiplier is desired use column
multiplier is desired use column M
M
aa..
Step 13.
Step 13. The asymmetrical RMS short-circuit current can
The asymmetrical RMS short-circuit current can
be calculated as:
be calculated as:
II
S.C. asym RMSS.C. asym RMS= (I
= (I
S.C. sym RMSS.C. sym RMS) x (Asym Factor)
) x (Asym Factor)
Step 14.
Step 14. The short-circuit current that the motor load can
The short-circuit current that the motor load can
contribute is an
contribute is an asymmetrical current usually approximated
asymmetrical current usually approximated
as being equal to the locked rotor current of the motor.***
as being equal to the locked rotor current of the motor.***
As a close approximation with a margin of
As a close approximation with a margin of safety use:
safety use:
*** ***
II
asym motor contrib
asym motor contrib
== (5)
(5) xx (I
(I
full load motorfull load motor))
Step 15.
Step 15. The total asymmetrical short-circuit RMS current
The total asymmetrical short-circuit RMS current
is calculated as:
is calculated as:
•• ••
II
totalS.C. asym RMS
totalS.C. asym RMS
== (I
(I
S.C. asym RMSS.C. asym RMS)) ++ (I
(I
asym motor contribasym motor contrib))
** The base KVA used throughout this text will be 10,000 KVA.The base KVA used throughout this text will be 10,000 KVA. **
**
10,000 KVA Base
10,000 KVA Base
PUR
PUX
PUR
PUX
PUX
PUX ==
10,000
10,000
== 00..00000011
—
—
00..00000011
100,000,000
100,000,000
PUX
PUX ==
(3.45) (10,000)
(3.45) (10,000)
== 00..22330000
—
—
00..22330000
(100) (1500)
(100) (1500)
PUR
PUR ==
(.56) (10,000)
(.56) (10,000)
== 00..00337733
00..00337733
—
—
(100) (1500)
(100) (1500)
(25')
(25')
xx
(.0379)
(.0379)
x (10,000)
x (10,000)
PUX
PUX ==
((11000000))
((66))
== 0.00685
0.00685 —
—
00..0000668855
(1000) (.480)
(1000) (.480)
22(25')
(25')
xx
(.0244)
(.0244)
x (10,000)
x (10,000)
((11000000))
((66))
PUR
PUR ==
(1000) (.480)
(1000) (.480)
22== 00..00004444
00..00004444
—
—
PUX =
PUX =
(.00005) (10,000)
(.00005) (10,000)
=
=
00..0000221177
—
—
00..0000221177
(1000) (.480)
(1000) (.480)
22Total PUR and PUX
Total PUR and PUX ==
0.0417
0.0417
0.2391
0.2391
PUZ
PUZ
totaltotal==
√
√
(0.0417)
(0.0417)
22++ (0.2391)
(0.2391)
22== .2430
.2430
II
S.C. sym RMSS.C. sym RMS==
10,000
10,000
== 49,489A
49,489A
√
√
3 (.480)(.2430)
3 (.480)(.2430)
II
sym motor contribsym motor contrib== 44 xx 1804
1804 == 7,216A
7,216A
II
total S.C. sym RMStotal S.C. sym RMS== 49,489
49,489 ++ 7,216
7,216 == 56,705A
56,705A
(fault X (fault X11))X/R
X/R
ratioratio== .2391
.2391 == 5.73
5.73
.0417
.0417
Asym Factor = 1.294 (Table 8)
Asym Factor = 1.294 (Table 8)
II
S.C. asym RMSS.C. asym RMS== 49,489 x 1.294
49,489 x 1.294 == 64,039A
64,039A
II
asym motor contribasym motor contrib== 55 xx 1804
1804 == 9,020A
9,020A
(100% motor load)(100% motor load)
II
total total S.C. asS.C. asymym RMSRMS== 64,039
64,039 ++ 9,020
9,020 == 73,059A
73,059A
(fault X(fault X11))
Per-Unit Method –
Per-Unit Method –
To Fault X
To Fault X
1
1
– System A
– System A
Available Utility Available Utility S.C. MVA 100,000 S.C. MVA 100,000 1500 KVA Transformer, 1500 KVA Transformer, 480V, 3Ø, 480V, 3Ø, 3.5%Z, 3.45%X, .56%R 3.5%Z, 3.45%X, .56%R IIf.l. transf.l. trans= 1804A= 1804A
25’ - 500kcmil 25’ - 500kcmil 6 Per Phase 6 Per Phase Service Entrance Service Entrance
Conductors in Steel Conduit Conductors in Steel Conduit
2000A Switch 2000A Switch KRP-C-2000SP Fuse KRP-C-2000SP Fuse M M M M Impedance Diagram Impedance Diagram One-Line Diagram One-Line Diagram Note:
Note: See Per Unit Method Procedure for Formulas.See Per Unit Method Procedure for Formulas. Actual motor contribution will be somewhat smaller than
Actual motor contribution will be somewhat smaller than calculatedcalculated due to impedance of the feeder cable.
due to impedance of the feeder cable. 1
M
M MM
Per-Unit Method –
Per-Unit Method –
To Fault X
To Fault X
2
2
– System A
– System A
Fault X Fault X11 400A Switch 400A Switch LPS-RK400SP Fuse LPS-RK400SP Fuse 50’ - 500kcmil 50’ - 500kcmil Feeder Cable in Feeder Cable in Steel Conduit Steel Conduit Motor Contribution Motor Contribution O
Onnee- L- Liinne De Diiaaggrraamm IImmppeeddaanncce De Diiaaggrraamm
10,000 KVA Base
10,000 KVA Base
PUR
PUX
PUR
PUX
PUX
PUX == ..22339911
—
—
..22339911
PUR
PUR == ..0044117
7
..00441177
—
—
PUX
PUX ==
(.00008) (10,000)
(.00008) (10,000)
== ..00003344
—
—
..00003344
(1000) (.480)
(1000) (.480)
2250’
50’ xx (.0379)
(.0379) xx (10,000)
(10,000)
PUX
PUX ==
1000
1000
== ..0088222
2
—
—
..00882222
(1000) (.480)
(1000) (.480)
2250’
50’ xx (.024
(.0244) x (10,000)
4) x (10,000)
PUR
PUR ==
1000
1000
== ..00552299
..00552299
—
—
(1000) (.480)
(1000) (.480)
22Total PUR and PUX
Total PUR and PUX ==
..00994466
..33224477
PUZ
PUZ
totaltotal==
√
√
(.0946)
(.0946)
22++ (.3247)
(.3247)
22== 0.3380
0.3380
II
S.C. sym RMSS.C. sym RMS==
10,000
10,000
== 35,621A
35,621A
√
√
3 (.480)(.3380)
3 (.480)(.3380)
II
sym motor contribsym motor contrib== 44 xx 1804
1804 == 7,216A
7,216A
II
total total S.C. symS.C. sym RMSRMS== 35,621
35,621 ++ 7,216
7,216 == 42,837A
42,837A
(fault X (fault X22))X/R
X/R
ratioratio==
.32477
.32477
== 3.43
3.43
.09465
.09465
Asym Factor
Asym Factor == 1.149 (Table 8)
1.149 (Table 8)
II
S.C. asym RMSS.C. asym RMS== 1.149
1.149 xx 35,621
35,621 == 40,929A
40,929A
II
asym motor contribasym motor contrib== 55 xx 1804
1804 == 9,020A
9,020A
(100%motor load)(100%motor load)
II
total S.C. asym RMStotal S.C. asym RMS== 40,929
40,929 ++ 9,020
9,020 == 49,949A
49,949A
(fault X (fault X22)) Adjusted Impedance Adjusted Impedance to Fault X to Fault X11 1 1 11 22 2210,000KVA Base
10,000KVA Base
P
PU
UR
R
P
PU
UX
X
PUX
PUX ==
10,000 == ..0022
10,000
—
—
..0022
500,000
500,000
PUX
PUX ==
(3.45) (10,000)
(3.45) (10,000)
== ..334455
—
—
..334455
(100) (1000)
(100) (1000)
PUR
PUR ==
(.6) (10,000)
(.6) (10,000)
== ..0066
..0066
—
—
(100) (1000)
(100) (1000)
(30')
(30')
xx
(.0303)
(.0303)
PUX
PUX ==
((11000000))
((44))
x (
x (10,000)
10,000)
== ..00009999
—
—
..00009999
(1000) (.48)
(1000) (.48)
22(30')
(30')
xx
(.0220)
(.0220)
PUR
PUR ==
((11000000))
((44))
xx (10
(10,00
,000)
0)
== ..00007722
..00007722
—
—
(1000) (.48)
(1000) (.48)
22PUX
PUX ==
(.00005) (10,000)
(.00005) (10,000)
== ..00002222
—
—
..00002222
(1000) (.48)
(1000) (.48)
22TToottaal
l P
PU
UR
R aannd
d P
PU
UX
X ==
..00667722
..33777711
PUZ
PUZ
totaltotal==
√
√
(.0672)
(.0672)
22++ (.3771)
(.3771)
22== .383
.383
II
S.C. sym RMSS.C. sym RMS==
10,000
10,000
== 31,405A
31,405A
√
√
3 (.48)(.383)
3 (.48)(.383)
X/R
X/R
ratioratio== .3771
.3771 = 5.62
= 5.62
.0672
.0672
Asym Factor = 1.285 (Table 8)
Asym Factor = 1.285 (Table 8)
II
S.C.asym RMSS.C.asym RMS== 31,405
31,405 xx 1.285
1.285 == 40,355A
40,355A
Per-Unit Method –
Per-Unit Method –
To Fault X
To Fault X
1
1
– System B
– System B
Available Utility Available Utility S.C. KVA 500,000 S.C. KVA 500,000 1000 KVA Transformer, 1000 KVA Transformer, 480V, 3Ø 480V, 3Ø 3.45%X, .60%R 3.45%X, .60%R 30' - 500kcmil 30' - 500kcmil 4 Per 4 Per PhaPhasese
Copper in PVC Conduit Copper in PVC Conduit 1600A Switch 1600A Switch KRP-C-1500SP Fuse KRP-C-1500SP Fuse One-Line Diagram
One-Line Diagram Impedance DiagramImpedance Diagram