Experion HS

Quick Builder Patch 3

R410

Software Change Notice

(2)

Notices and Trademarks

© Honeywell International Inc. 2013. All Rights Reserved.

While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customer.

In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice. Honeywell PlantScape, Experion, and TotalPlant are US registered trademarks of Honeywell International Inc.

Other brand or product names are trademarks of their respective owners.

Honeywell Process Solutions 1860 West Rose Garden Lane

(3)

Support and Other Contacts

United States and Canada

Contact: Phone:

Facsimile Mail:

Honeywell Solution Support Center 1-800-822-7673

Calls are answered by dispatcher between 6:00 am and 4:00 pm Mountain Standard Time. Emergency calls outside normal working hours are received by an answering service and returned within one hour.

1-973-455-5000

Honeywell TAC, MS L17 1860 W. Rose Garden Lane Phoenix, AZ, 85027 USA Europe, Middle East, and Africa (EMEA)

Contact: Phone: Facsimile Mail:

Email:

Honeywell TAC – EMEA +32-2-728-2345 +32-2-728-2696 TAC-BE02 Hermes Plaza Hermeslaan, 1H B-1831 Diegem, Belgium [email protected] Pacific Contact: Phone: Facsimile Mail: Email:

Honeywell Global TAC – Pacific

1300-364-822 (toll free within Australia) +61-8-9362-9559 (outside Australia) +61-8-9362-9564

Honeywell Limited Australia 5 Kitchener Way

Burswood, WA, 6100, Australia [email protected]

(4)

Korea Contact: Phone: Facsimile Mail: Email:

Honeywell Global TAC – Korea

+82-80-782-2255 (toll free within Korea) +82-2-792-9015

Honeywell Co., Ltd

4F, Sangam IT Tower B4-4 Block 1590, DMC Sangam-dong, Mapo-gu Seoul, 121-835, Korea

[email protected] People’s Republic of China

Contact: Phone:

Mail:

Email:

Honeywell Global TAC – China +86- 21-2219-6888

800-820-0237 400-820-0386

Honeywell (China) Co., Ltd

33/F, Tower A, City Center, 100 Zunyi Rd. Shanghai 200051, People’s Republic of China [email protected] Singapore Contact: Phone: Facsimile Mail: Email:

Honeywell Global TAC – South East Asia +65-6823-2215

+65-6445-3033

Honeywell Private Limited Honeywell Building

17, Changi Business Park Central 1 Singapore 486073 [email protected] Japan Contact: Facsimile Mail: Email:

Honeywell Global TAC – Japan +81-3-6730-7228

Honeywell K.K

New Pier Takeshiba, South Tower Building 20th Floor, 1-16-1 Kaigan, Minato-ku Tokyo 105-0022, Japan

[email protected] World Wide Web

Honeywell Process Solutions website: https://www.honeywellprocess.com/ Training classes:

(5)

taught by experts in the field of process control systems. For more information about these classes, contact your Honeywell representative, or see

(6)

Symbol Definitions

The following table lists those symbols used in this document to denote certain conditions.

Symbol Definition

(7)

Revision history

Version Description

(8)

Table of Contents

1 Introduction...10

1.1 About the document ...10

1.2 About the patch ...10

1.2.1 Problems resolved ...10

1.2.2 Issues ...10

1.2.3 Limitations ...11

1.3 Before you begin ...11

1.3.1 Prerequisites ...11

1.3.2 Patch installation or migration checklist...11

1.3.3 Applicable nodes ...11

1.3.4 Applicable modules ...12

1.3.5 Supported controller migration paths ...12

1.3.6 Verify the present version on the node ...12

1.3.7 Copying and extracting the patch ...13

1.4 Change impact ...13

1.4.1 Control change impact ...13

1.4.2 Operational change impact ...13

1.4.3 Infrastructure change impact ...13

2 Patch installation ...14

2.1 Installing the patch on Non-Redundant Server and Console Station Systems ...14

2.1.1 To stop the services ...14

2.1.2 To install the patch ...14

2.1.3 To validate the patch installation ...14

2.1.4 Post-installation tasks ...15

2.2 Installing the patch on Redundant Server Systems ...15

2.2.1 To stop the services ...15

2.2.2 To install the patch ...15

2.2.3 To validate the patch installation ...15

2.2.4 Post-installation tasks ...15

2.3 Installing the patch on Flex Station or Console Extension Station ...16

(9)

2.3.2 To install the patch ...16

2.3.3 To validate the patch installation ...16

2.3.4 2.3.3 Post-installation tasks ...17

2.4 Migrating controllers ...17

2.5 Troubleshooting issues during installation ...17

3 Patch removal ...18

3.1 Removing the patch from Non-Redundant Server and Console Station Systems...18

3.1.1 To stop the services ...18

3.1.2 To remove the patch ...18

3.1.3 To validate the patch removal ...18

3.1.4 Post-removal tasks ...19

3.2 Removing the patch from Redundant Server Systems ...19

3.2.1 To stop the services ...19

3.2.2 To remove the patch ...19

3.2.3 To validate the patch removal ...19

3.2.4 Post-removal tasks ...19

3.3 Removing the patch from Flex Station or Console Extension Station ...20

3.3.1 To stop the services ...20

3.3.2 To remove the patch ...20

3.3.3 To validate the patch removal ...20

3.3.4 Post-removal tasks ...21

4 Additional information ...22

4.1 Additional information to validate patch installation ...22

4.1.1 Files added or replaced ...22

(10)

1 Introduction

1.1 About the document

The Software Change Notice describes the prerequisites, resolved PARs, applicable nodes, and steps to install/uninstall the patch. Additionally, the SCN contains information about the change impact and additional information for this patch. The latest version of this SCN is always

available on the Honeywell Process Solutions website.

1.2 About the patch

This patch addresses problems and offers improvements requested since the release of Experion R410.1. It can be installed on Experion HS R410.1 systems.

1.2.1 Problems resolved

This patch resolves the following issues.

Applicable only if required for systems needing the enhancement

PAR Subsystem Description of problem

1-YX831K Download/Export When requested to present user credential for downloading, user can cancel log on dialog and still download successfully. 1-WQCHIL Download/Export Default download option should be

"Download Modified Items" instead of "Download All".

1-PCIVB9 Property Sheets Enhancement to the addressing range for the HC900 Universal Modbus Interface to allow access to 32k addresses using a single virtual controller.

1-URNA7T Property Sheets Need to be able to configure Control Inhibit and Journal Only flags for a point from Quick Builder.

1.2.2 Issues

(11)

1.2.3 Limitations

1.2.3.1 Patch removal

[] Automatic

[ ] Can be done manually during next upgrade

[ ] Must be done manually before next upgrade 1.2.3.2 Patch distribution

[ ] Not Limited [ ] Limited for:

1.2.3.3 Localization

[ ] Not impacted [ ] Patch may contain strings in English. A Localization version to be included in the next release. [] Needs additional localization support 1.2.3.4 Cumulative patch [ ] Yes. See Prerequisites [ ] No

1.3 Before you begin

1.3.1 Prerequisites

The patch must be installed on a node on which the following updates are installed:

 Experion HS R410.1

1.3.2 Patch installation or migration checklist

Task order Task Reference

1 Prerequisites See section Prerequisites

2 Applicable nodes See section Applicable nodes

(12)

Node Is the patch applicable?

Experion Server (ESV) Yes

Flex Station (ES-F) Yes

1.3.4

Applicable modules

This patch is applicable for the following modules.

Node Is the patch applicable?

C200 controller No

C200E controller No

C300 controller No

Fieldbus Interface Module No

Fieldbus Interface Module 4 No

Fieldbus Interface Module 8 No

Fault Tolerant Ethernet Bridge Module (FTEB) No

Serial I/O Module (IOM) No

Legacy I/O Module (LIOM) No

PROFIBUS Gateway Module (PGM) No

SeriesC IO Module No

1.3.5 Supported controller migration paths

N/A

1.3.6 Verify the present version on the node

To verify the present version on the node, perform the following steps. 1. Start Quick Builder

(13)

1.3.7 Copying and extracting the patch

Copy the software patch package to a temporary directory on the node where install is applicable. There are 3 files in the patch package:

 ApplyUpdate.bat

 ApplyUpdate.vbs

 Experion_R410_QBP_Patch3.msp

1.4 Change impact

After the installation of this patch the following changes are expected.

1.4.1 Control change impact

No impact.

1.4.2 Operational change impact

No impact.

1.4.3 Infrastructure change impact

(14)

2 Patch installation

Patch Installation will require the user to log on to the system using an account with membership in the Windows administrators group.

2.1 Installing the patch on Non-Redundant Server

2.1.1 To stop the services

1. Ensure no instances of Quick Builder are running and qckbld folder is closed.

2. If you are running in the node of Remote Engineering and Station Server, you may need to open Task Manager and check there is no instance of qckbld.exe running for all users.

3. Start the Experion PKS Services Control Panel program (from <install_drive>\Program Files (x86)\Honeywell\Experion PKS\Utilities\SSServices\SSServices.exe). Once started, select “Stop All services” and click OK to stop all Experion services.

2.1.2 To install the patch

1. Navigate to the software patch package in Windows Explorer and right-click

“ApplyUpdate.bat” and select “Run as administrator”. The software patch installer will start and installation wizard appears.

2. If User Account Control dialog box appears, click Yes

3. Choose “OK” button after apply update ‘QBP Patch3’ dialog appears.

4. Follow the prompts and complete the wizard. The install may take a few minutes. 5. Click OK to close the dialog.

Notes:

If the software patch installer reports that some programs must be closed before installing, click “OK” to accept this and let the installer to terminate these programs. Otherwise, click “Cancel” to abort installation.

2.1.3 To validate the patch installation

To verify the successful installation of the patch:

1. Using Notepad, open the ProductVersion.txt file located in the following path: C:\Program Files (x86)\Honeywell\Experion PKS\ProductVersion.txt

(15)

“++ Patch Experion PKS R410 QBP patch3 installed on <install date & time>”

2.1.4 Post-installation tasks

1. Start all Experion services.

2. Run Quick Builder from Configuration Studio and the migration wizard will appear. Follow the wizard instructions and the database will be migrated to the latest version.

2.2 Installing the patch on Redundant Server Systems

2.2.1 To stop the services

1. Ensure the Primary and Backup Server databases are synchronized before proceeding 2. Ensure Quick Builder is not running on any nodes and ensure not to run Quick Builder

on any nodes before finishing the patch installation on both primary and backup servers.

2.2.2 To install the patch

1. On the backup server, run the software patch installation procedure for a non-redundant server system

2. Synchronize primary and backup server databases

3. Fail over the primary server to the backup server. The backup server will become primary and the primary server become backup

4. Run the software patch installation procedure for a non-redundant server system on the new backup server

5. Synchronize primary and backup server databases.

2.2.3 To validate the patch installation

To verify the successful installation of the patch:

(16)

2.3 Installing the patch on Flex Station

2.3.1 To stop the services

1. Ensure no instances of Quick Builder are running and qckbld folder is closed. 2. If you are running in the node of Remote Engineering and Station Server, you may

need to open Task Manager and check there is no instance of qckbld.exe running for all users.

3. Start the Experion PKS Services Control Panel program (from <install_drive>\Program Files (x86)\Honeywell\Experion

PKS\Utilities\SSServices\SSServices.exe). Once started, select “Stop All services” and click OK to stop all Experion services.

2.3.2 To install the patch

1. Navigate to the software patch package in Windows Explorer and right-click “ApplyUpdate.bat” and select “Run as administrator”. The software patch installer will start and installation wizard appears.

2. If User Account Control dialog box appears, click Yes

3. Choose “OK” button after apply update QBP Patch3 dialog appears.

4. Follow the prompts and complete the wizard. The install may take a few minutes. 5. Click OK to close the dialog.

Notes:

If the software patch installer reports that some programs must be closed before installing, click “OK” to accept this and let the installer to terminate these programs. Otherwise, click “Cancel” to abort installation.

2.3.3 To validate the patch installation

To verify the successful installation of the patch:

1. Using Notepad, open the ProductVersion.txt file located in the following path: C:\Program Files (x86)\Honeywell\Experion PKS\ProductVersion.txt

2. Verify that the file contains an entry starting with:

(17)

2.3.4 2.3.3 Post-installation tasks

1. Start all Experion services.

2. Run Quick Builder from Configuration Studio and the migration wizard will appear. Follow the wizard instructions and the database will be migrated to the latest version.

2.4 Migrating controllers

N/A

2.5 Troubleshooting issues during installation

(18)

3 Patch removal

3.1 Removing the patch from Non-Redundant Server

3.1.1 To stop the services

1. Ensure no instances of Quick Builder are running and qckbld folder is closed. 2. If you are running in the node of Remote Engineering and Station Server, you may

need to open Task Manager and check there is no instance of qckbld.exe running for all users.

3. Start the Experion PKS Services Control Panel program (from <install_drive>\Program Files (x86)\Honeywell\Experion

PKS\Utilities\SSServices\SSServices.exe). Once started, select “Stop All services” and click OK to stop all Experion services.

3.1.2 To remove the patch

1. Navigate to “Start -> All Programs -> Honeywell Experion PKS, select the Maintenance Tool and run same with Administrator privilege.

2. Click on “View\Uninstall Experion Updates”

3. Locate the patch to uninstall and click on the “Remove” button. 4. Follow the prompts on screen to uninstall the patch.

5. Once the uninstallation completed, an uninstallation successfully completed dialog box will popup.

6. If prompted, restart the machine.

3.1.3 To validate the patch removal

To verify the successful un-installation of the patch:

1. Using Notepad, open the ProductVersion.txt file located in the following path: C:\Program Files (x86)\Honeywell\Experion PKS\ProductVersion.txt

2. Verify that the file contains an entry starting with:

(19)

3.1.4 Post-removal tasks

None

3.2 Removing the patch from Redundant Server Systems

3.2.1 To stop the services

1. Ensure the Primary and Backup Server databases are synchronized before proceeding.

2. Ensure Quick Builder is not running on any nodes and ensure not to run Quick Builder on any nodes before finishing the patch installation on both primary and backup servers.

3.2.2 To remove the patch

1. On the backup server, run the software patch un-installation procedure for a non-redundant server system.

2. Synchronize primary and backup server databases.

3. Fail over the primary server to the backup server. The backup server will become primary and the primary server become backup.

4. Run the software patch un-installation procedure for a non-redundant server system on the new backup server.

5. Synchronize primary and backup server databases.

3.2.3 To validate the patch removal

To verify the successful un-installation of the patch:

1. Using Notepad, open the ProductVersion.txt file located in the following path: C:\Program Files (x86)\Honeywell\Experion PKS\ProductVersion.txt

(20)

3.3 Removing the patch from Flex Station

3.3.1 To stop the services

1. Ensure no instances of Quick Builder are running and qckbld folder is closed. 2. If you are running in the node of Remote Engineering and Station Server, you may

need to open Task Manager and check there is no instance of qckbld.exe running for all users.

3. Start the Experion PKS Services Control Panel program (from <install_drive>\Program Files (x86)\Honeywell\Experion

PKS\Utilities\SSServices\SSServices.exe). Once started, select “Stop All services” and click OK to stop all Experion services.

3.3.2 To remove the patch

1. Navigate to “Start -> All Programs -> Honeywell Experion PKS, select the Maintenance Tool and run same with Administrator privilege.

2. Click on “View\Uninstall Experion Updates”.

3. Locate the patch to uninstall and click on the “Remove” button.

4. Follow the prompts on screen to uninstall the patch.

5. Once the uninstallation completed, an uninstallation successfully completed dialog box will popup.

6. If prompted, restart the machine.

3.3.3 To validate the patch removal

To verify the successful un-installation of the patch:

1. Using Notepad, open the ProductVersion.txt file located in the following path: C:\Program Files (x86)\Honeywell\Experion PKS\ProductVersion.txt

2. Verify that the file contains an entry starting with:

(21)

3.3.4 Post-removal tasks

(22)

4 Additional information

4.1 Additional information to validate patch installation

4.1.1 Files added or replaced

All files in C:\Program Files(x86)\Honeywell\Experion PKS\client\qckbld are replaced by this patch.

4.1.2 Firmware revision

(23)

References

Related documents

Oblique view of the stifle in a foal aged 6 months, showing a wide dip in the bone surface in the proximal third of the lateral Trochlear ridge of the distal femora ( white

The present study examined the effects of an intake of five grams per day of Arthrospira platensis focusing on the antiretroviral effect, immune function, antioxidative potential

The magnetic properties of all four compounds have been measured and show that compounds 2 and 4 containing Dy III ions exhibit slow relaxation of magnetization characteristic of

If it is the key that is stored in the online, then the systems permit delivery of encrypted data to recipients’ desktops, with a required multi-step recipient

We proposed ReLEx, a set of loss terms that provide regularisation for the behaviour of a ReLU network, such that it produces linear extrapolations beyond the range of the training

Section 2(1) of the 1987 Constitution government- owned or controlled corporations organized under the Corporation Code are not covered by the Civil Service Law

The P&amp;H shovel line is combining its solid reputation of reliability with the proven Centurion ® Electrical Control System, time-tested DC systems, rugged structures and

Identifying Orion Console components 12 Unpacking the Experion Orion Console 13 Placing the Experion Orion Console into position 18 Attaching the work surface to the Experion