Revision-A
Date : 02.01.2007
GRASIM CEMENTS - GRINDING UNIT AT PANIPAT
RECOMMENDED RELAY SETTING CHART
33/6.6 kV, 12/16 MVA
Prepared by : ABB
1
Differential
Protection
(Restrained)
ABB - RET
670
87T>
Stage 1
(T2D1 )
2
Differential
Protection
(Unrestrained)
,Stage 2
ABB - RET
670
87T>>
3
Restricted
Earth fault
Protection
ABB - RET
670
64R LV
( Low
impedance
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
SI. No.
Type of
Protection
Relay Make
/ No.
PROTECTION ANSI
CODE
64R HV
Restricted
Earth fault
Protection
ABB - RET
670
64R LV
(High
Impedence
64R HV
4
Stand -by
Earth fault
Protection
(HV Side)
ABB - RET
670
51s-EFR HV
( 4th-Stage- OFF)
RET-670 , TIME CO-ORDINATED SETTINGS OF
Stan-by-EFR ( HV & LV )
Stand -by Earth fault
Protection (LV Side)
ABB - RET
670
51s-EFR LV
I_base
I1>
t1>
I2>
t2>
I3>
t3>
I4>
t4>
Stand -by Earth fault
Protection (HV Side)
ABB - RET
670
51s-EFR HV
I_base
I1>
t1>
I2>
t2>
I3>
t3>
I4>
t4>
STAGE-3
STAGE-4
STAGE-1
STAGE-3
STAGE-4
600/1A (132KV side)
150/1A (132KV side)
STAGE-1
STAGE-2
STAGE-2
Parameter
Description
150/1A (132KV side)
Operation
on
2000/1A (11 kV Side)
IdMin
Setting of minimum
differential operating current
%Z = 12.5% ( TAKE
FROM Name plate of
trafo. )
End section 1
Cross-Over point b/w slope1
& Slope-2
Vector group = YNyn0
Slope section 2
Setting of slope 2
stabilisation, (Slope 1 has
fixed stabilization)
End section 2
Cross-Over point b/w slope2
& Slope-3
Slope section 3
Setting of slope 3
stabilisation,
150/1A (132KV side)
2000/1A (11 kV Side)
Idunre
Differential current, High set
(Unrestrained)
Cross blocking logic
OpCrossBlock
= on
I
d2f
/ I
d1f
> (%)
2nd Harmonic restraint
I
d5f
/ I
d1f
> (%)
5th Harmonic restraint
Set the operation of
Negative sequence
differential protection
OpNegSeqDiff =
= on
IMinNegSeq =
Setting of minimum negative
sequence differential current
level
NegSeqROA
Relay operate angle
2000/1A (11 kV Side)
Idmin (%)
ROA
Relay operate angle
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
CT Ratio / PT Ratio/
OTHER
Relay Setting
150/1A (132KV side)
Idmin (%)
ROA
Relay operate angle
2000/1A (11 kV Side)
U alarm
Operate voltage
t Alarm
Operate time
U trip
Operate voltage
t trip
Operate time
Rs
Series Resistor
150/1A (132KV side)
U alarm
Operate voltage
t Alarm
Operate time
U trip
Operate voltage
t trip
Operate time
Rs
Series Resistor
150/1A (132KV side)
I
N1
>/ Ib
Base Current Setting
Dir mode
Ibase
1st-stage
t11>
DT setting
NA
k11>
TMS
I
N2
>/ Ib
Base Current Setting
Dir mode
2nd-stage
t1 2>
DT setting
NA
k1 2>
TMS
I
N3
>/ Ib
Base Current Setting
Dir mode
3rd-stage
t1 3>
DT setting
NA
k1 3>
TMS
100%
80%
80% of Ibase
80% of Ibase
0.96 sec
0.0 sec
50% of Ibase
50% of Ibase
1.2 sec
0.40 sec
40% of Ibase
40% of Ibase
1.4sec
0.80 sec
30% of Ibase
30% of Ibase
1.6sec
1.20 sec
100%
80%
80% of Ibase
80% of Ibase
1.26 sec
0.3 sec
100% of Ibase
100% of Ibase
1.46 sec
0.15 sec
off
off
OFF
OFF
off
off
OFF
OFF
t= 0.96 sec. is the
Normal-EFR ( in incomer of
11KV-rex-521 ) Relay's time
setting. So, the same has
been maintained as trip-
time to SB-EFR-LV.
Assuming a time
descripation of 0.3 sec.
b/w 11KV & 132KV -trip
time , t1= 0.96 + 0.3sec. =
1.26 SEC.
600/1A (132KV side)
150/1A (132KV side)
Available range
PSM
TMS/DMT (sec)
----
----
----0.10-0.60
0.25 * Ibase.
Inst
0.2 - 1.5
1.25 * Ibase.
10.0 -50.0 %
40 * Ibias
1.0 -10
3 * Ibase.
30.0 -100.0 %
80 * Ibias
100- 5000 % of
Ibase
10 * Ibase.
Inst
---
---5-100 % of fn
15%
5-100 % of fn
25%
---
---(0.01 - 0.10 )* Iopr.
0.04 * Iopr.
60 - 90 Degrees
60 °
4.0 -100.0
30%
Inst
60 - 90 Degrees
60 °
see ANNEXURE-01
This settings may not be
applicable - while we have
adopted High -Impedence
based REFR-Protection.
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Relay Setting
Remarks
4.0 -100.0
30%
Inst
60 - 90 Degrees
60 °
( 2 -500 ) V
N / A
0 - 60 sec
N / A
5.0 sec.
( 5 -900 ) V
109.5 V
---
----
Inst
10 -20000 Ohms.
396 ohms.
( 2 -500 ) V
N / A
0 - 60 sec
N / A
5.0 sec.
( 5 -900 ) V
63 V
---
----
Inst
10 -20000 Ohms.
250 ohms.
1.0 -2500.0 %
Ibase
20% * Ibase
---
Non directional
0 - 60 Secs
----
1.0 sec.
0.05 - 999
0.15 Secs
NI 0.15 Secs
1.0 -2500.0 %
Ibase
15% * Ibase
---
Non directional
0 - 60 Secs
----
1.5 sec.
0.05 - 999
0.15 Secs
NI 0.15 Secs
1.0 -2500.0 %
Ibase
10% * Ibase
---
Non directional
0 - 60 Secs
----
2.0 sec.
0.05 - 999
0.15 Secs
NI 0.15 Secs
This settings may not be
applicable - while we have
adopted High -Impedence
based REFR-Protection.
see ANNEXURE-01
see ANNEXURE-01
PACP
Recomended Relay Settings
Parameter
Description
Available range
PSM
TMS/DMT
(sec)
1
Differential Protection
(Restrained)
ABB - RET
670
87T>
150/1A (132KV side)
Operation
on
----
----
Stage 1
(T2D1 )
2000/1A (11 kV Side)
IdMin
Setting of minimum
differential operating
current
0.10-0.60
0.25 * Ibase.
Inst
%Z = 12.5% ( TAKE
FROM Name plate of
trafo. )
End section 1
Cross-Over point b/w
slope1 & Slope-2
0.2 - 1.5
1.25 * Ibase.
Vector group = YNyn0
Slope section 2
Setting of slope 2
stabilisation, (Slope 1
has fixed stabilization)
10.0 -50.0 %
40 * Ibias
End section 2
Cross-Over point b/w
slope2 & Slope-3
1.0 -10
3 * Ibase.
Slope section 3
Setting of slope 3
stabilisation,
30.0 -100.0 %
80 * Ibias
2
Differential Protection
(Unrestrained) ,Stage 2
ABB - RET
670
87T>>
150/1A (132KV side)
2000/1A (11 kV Side)
Idunre
Differential current,
High set (Unrestrained)
100- 5000 % of
Ibase
10 * Ibase.
Inst
Cross blocking logic
OpCrossBlock
= on
---
---I
d2f
/ I
d1f
> (%)
2nd Harmonic restraint
5-100 % of fn
15%
I
d5f
/ I
d1f
> (%)
5th Harmonic restraint
5-100 % of fn
25%
Set the operation of
Negative sequence
differential protection
OpNegSeqDiff =
= on
---
---IMinNegSeq =
Setting of minimum
negative sequence
differential current level
(0.01 - 0.10 )* Iopr.
0.04 * Iopr.
NegSeqROA
Relay operate angle
60 - 90 Degrees
60 °
3
Restricted Earth fault
Protection
ABB - RET
670
64R LV
2000/1A (11 kV Side)
Idmin (%)
4.0 -100.0
30%
Inst
( Low impedance bsed.)
ROA
Relay operate angle
60 - 90 Degrees
60 °
64R HV
150/1A (132KV side)
Idmin (%)
4.0 -100.0
30%
Inst
ROA
Relay operate angle
60 - 90 Degrees
60 °
Restricted Earth fault
Protection
ABB - RET
670
64R LV
2000/1A (11 kV Side)
U alarm
Operate voltage
( 2 -500 ) V
N / A
(High Impedence based.)
t Alarm
Operate time
0 - 60 sec
N / A
5.0 sec.
U trip
Operate voltage
( 5 -900 ) V
109.5 V
t trip
Operate time
---
----
Inst
Rs
Series Resistor
10 -20000 Ohms.
396 ohms.
64R HV
150/1A (132KV side)
U alarm
Operate voltage
( 2 -500 ) V
N / A
t Alarm
Operate time
0 - 60 sec
N / A
5.0 sec.
U trip
Operate voltage
( 5 -900 ) V
63 V
t trip
Operate time
---
----
Inst
Rs
Series Resistor
10 -20000 Ohms.
250 ohms.
see ANNEXURE-01
CT Ratio / PT Ratio/
OTHER
Relay Setting
This settings may not
be applicable - while
we have adopted High
-Impedence based
REFR-Protection.
see ANNEXURE-01
Available setting range
see ANNEXURE-01
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting
Remarks
SI.
No.
Type of Protection
Relay Make /
No.
PROTECTION
ANSI CODE
PACP
Recomended Relay Settings
Parameter
Description
Available range
PSM
TMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
see ANNEXURE-01
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting
Remarks
SI.
No.
Type of Protection
Relay Make /
No.
PROTECTION
ANSI CODE
4
Stand -by Earth fault
Protection (HV Side)
ABB - RET
670
51s-EFR HV
150/1A (132KV side)
I
N1
>/ Ib
Base Current Setting
1.0 -2500.0 % Ibase
20% * Ibase
( 4th-Stage-
OFF)
Dir mode
---
Non directional
1st-stage
t11>
DT setting
0 - 60 Secs
----
1.0 sec.
NA
k11>
TMS
0.05 - 999
0.15 Secs
NI 0.15 Secs
I
N2
>/ Ib
Base Current Setting
1.0 -2500.0 % Ibase
15% * Ibase
Dir mode
---
Non directional
2nd-stage
t1 2>
DT setting
0 - 60 Secs
----
1.5 sec.
NA
k1 2>
TMS
0.05 - 999
0.15 Secs
NI 0.15 Secs
I
N3
>/ Ib
Base Current Setting
1.0 -2500.0 % Ibase
10% * Ibase
Dir mode
---
Non directional
3rd-stage
t1 3>
DT setting
0 - 60 Secs
----
2.0 sec.
NA
k1 3>
TMS
0.05 - 999
0.15 Secs
NI 0.15 Secs
see ANNEXURE-01 ---
PACP
Recomended Relay Settings
Parameter
Description
Available range
PSM
TMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
see ANNEXURE-01
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting
Remarks
SI.
No.
Type of Protection
Relay Make /
No.
PROTECTION
ANSI CODE
5
Stand -by Earth fault
Protection (LV Side)
ABB - RET
670
51s-EFR LV
600/1A ( in NGR )
I
N1
>/ Ib
Base Current Setting
1.0 -2500.0 % Ibase
15% * Ibase
( 4th-Stage-
OFF)
Dir mode
---
Non directional
1st-stage
t11>
DT setting
0 - 60 Secs
----
2.0 sec.
NA
k11>
TMS
0.05 - 999
0.15 Secs
NI 0.15 Secs
I
N2
>/ Ib
Base Current Setting
1.0 -2500.0 % Ibase
25% * Ibase
Dir mode
---
Non directional
2nd-stage
t1 2>
DT setting
0 - 60 Secs
----
1.5 sec.
NA
k1 2>
TMS
0.05 - 999
0.15 Secs
NI 0.15 Secs
I
N3
>/ Ib
Base Current Setting
1.0 -2500.0 % Ibase
30% * Ibase
Dir mode
---
Non directional
3rd-stage
t1 3>
DT setting
0 - 60 Secs
----
1.0 sec.
NA
k1 3>
TMS
0.05 - 999
0.15 Secs
NI 0.15 Secs
6
Under Frequency .
Protection.
ABB - RET
670
81.U
132KV / 110 Volts.
Operation mode
on /Off
on.
Ubase (KV)
Base voltage setting
0.05 - 2000 volts.
132 KV
f <
Start Freq.
Freq setting / start
value.
35 -75 Hz.
48.8 Hz.
Int_Bloc_Level
Internal_Blocking
_Level in % Of Ubase
0 -100 % Of UB
50%
Time delay operate
0 -60 sec.
0.2 sec.
Time delay Reset
0 -60 sec.
0.0 sec.
Time delay Restore
0 -60 sec.
0.0 sec.
Restore freq.
45 - 65 Hz.
50.10 Hz.
Timer Operation
DT/ Voltage based
DT
----Unom
50 -150 % Ub
100
N / A
Umin
50 -150 % Ub
90
N / A
Exponent .
0.0 - 5.0
1
N / A
Tmax.
0.01 -60 sec.
1
N / A
Tmin
0.01 -60 sec.
1
N / A
6
Over Frequency . Protection.
ABB - RET
670
81.O
132KV / 110 Volts.
Operation mode
on /Off
off
Ubase (KV)
Base voltage setting
0.05 - 2000 volts.
132 KV
f >
Start Freq.
Freq setting / start
value.
35 -75 Hz.
51.20 Hz.
Int_Bloc_Level
Internal_Blocking
_Level in % Of Ubase
0 -100 % Of UB
50%
Time delay operate
0 -60 sec.
0.0 sec.
Time delay Reset
0 -60 sec.
0.0 sec.
see ANNEXURE-01
see ANNEXURE-01
see ANNEXURE-01
PACP
Recomended Relay Settings
Parameter
Description
Available range
PSM
TMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
see ANNEXURE-01
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting
Remarks
SI.
No.
Type of Protection
Relay Make /
No.
PROTECTION
ANSI CODE
6
Rate of change of
Frequency . Protection.
ABB - RET
670
Df /dt
132KV / 110 Volts.
Operation mode
on /Off
off
Ubase (KV)
Base voltage setting
0.05 - 2000 volts.
132 KV
f >
Start Freq. Gradient.
Freq .Gradient.
-10 - 10 Hz/sec..
0.5 Hz /sec.
Int_Bloc_Level
Internal_Blocking
_Level in % Of Ubase
0 -100 % Of UB
50%
Operate Time ( tTrip )
0 -60 sec.
0.2 sec.
Time delay Reset
0 -60 sec.
0.0 sec.
Time delay Restore
0 -60 sec.
0.0 sec.
Restore freq.
45 - 65 Hz.
49.90 Hz.
6
Over Fluxing (Over
excitation)
ABB - RET
670
99 (24)
220KV / 110 Volts.
V/Hz>
Voltage / Freq.
100 - 180% x U/f
110% x U/f
t alarm
oprtng. Time
0-9000 sec.
----
5sec.
T-alarm_level
Alarm operate level
50 -120%
100%
V/Hz>>
Voltage / Freq.
100 - 200% x U/f
140% x U/f
tmax.
max. trip delay for I
-curves
0 - 9000 sec.
1500
1800
tmin
min. trip delay for I
-curves
0 - 60 secs
4 sec
7
tr-pulse
length of Pulse for trip
0 - 60 secs
0.1
0.1
X-leakage
Leaakage reactance of
trafo. Winding.
0.00-200 ohms.
0
t-cooling
cooling time constant
for Trao.
0.1 -9000 sec
1200
1200 sec.
CurveType
curve selection.
INVERSE/ IEEE /
TAILOR MADE.
IEEE
see ANNEXURE-01
see ANNEXURE-01
PACP
Recomended Relay Settings
Parameter
Description
Available range
PSM
TMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
see ANNEXURE-01
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting
Remarks
SI.
No.
Type of Protection
Relay Make /
No.
PROTECTION
ANSI CODE
7
Local Breaker Back-up
ABB - RET
670
50 LBB
150 / 1A
(132KV side)
Operating mode
backup trip mode
1 out of 4/ 2 out of 4
/ 1 out of 3
1 out of 3
Retrip-mode
re-trip -Off
IP >
Operate Ph. Current in
% of Ibase
5-200%
10%
IN >
Operate Residual.
Current in % of Ibase
2-200%
10%
t1 >
time delay of re-trip
0-60sec.
0 sec.
0 sec.
8
Residual -Over voltage
Voltage Protection Protn.
ABB - RET
670
59N
132KV/√3 / 110V/√3
Operation Mode
----
0n , STAGE-1
UB =
Open-delta Voltage
CurveType
DT/C-A/C-B/C-C
DT
U1 >
START VOLTAGE
1- 200 % UB
30 % UB
t1 >
Definite Time Delay
0 - 6000 sec.
5 sec.
5 sec.
t1 min >
Operating Time for I
-curves
0 - 60 sec.
5 sec.
NA
k1 >
TMS
0.05 - 1.10
0.05
NA
HystAbs1
Absolute Hysteresis
in% of Ubase.
0 -100 % UB
0.5 % UB
Operation Mode
----
0n , STAGE-2
CurveType
DT/C-A/C-B/C-C
DT
U2 >
START VOLTAGE
1- 100 % UB
45 % UB
t2 >
Definite Time Delay
0 - 6000 sec.
5 sec.
5 sec.
t2 min >
Operating Time for I
-curves
0 - 60 sec.
5 sec.
NA
k2 >
TMS
0.05 - 1.10
0.05
NA
HystAbs2
Absolute Hysteresis
in% of Ubase.
0 -100 % UB
0.5 % UB
9
Back-up Overcurrent/ Earth
fualt protection ( Non-dir /
Dir )
REX 521
51 / 50 / 51N / 67
/ 67N
150/1A (132KV side)
Operation Mode
Not in use / DT/ NI/VI /
c-2 ETC. ( 1 to 15 )
DT =01
31>
H-02
NOC3Low (51)
31>
Current setting (I/ In)
0.10 - 5.00 xIn.
0.7
Operate time ( in DT)
0.05 - 300 Secs
0.05
time Multiplier ' K '( in
IDMT -mode )
0.05 - 1.00
0.05
IDMT
IEEE- time DAIL in
IDMT -mode
0.5 - 15
0.5
NOC3High ( 50 / 51 )
Operation Mode
Not in use / DT / inst..
Inst. = 02
31>>
31>>
Current setting (I/ In)
0.10 - 40 xIn.
2
Operate time ( in DT -
Mode)
0.05 - 300 Secs
0.05
DT- 0.05
SECS.
see ANNEXURE-01
see ANNEXURE-02
see ANNEXURE-02
Page 14 of 21
PACP
Recomended Relay Settings
Parameter
Description
Available range
PSM
TMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
see ANNEXURE-01
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting
Remarks
SI.
No.
Type of Protection
Relay Make /
No.
PROTECTION
ANSI CODE
REX 521
DEF2Low ( 67N / 51N )
Operation Mode
Not in use / DT/ NI/VI /
c-2 ETC.
DT =01
Io >->
Operation Criteria
67N,51N etc.., (1 to 05)
4 = Non-directional
Io>
---Operation direction
forward / Reverse
forward=0
N/A
Operation
Charecteristics.
IoSin(phi) / IoCos(phi)
( 0,1)
0
N/A
Basic Angle
-90 deg to 60 deg.
-90 deg
N/A
Io >
Current setting (Io/ In)
0.01 - 5.00 xIn.
0.075
Uo>
Start voltage
2.0 - 100 % of Un.
75%
N/A
Operate time ( in DT)
0.10 - 300 Secs
0.1
REX 521
DEF2High ( 67N )
Operation Mode
Not in use / DT/ NI/VI /
c-2 ETC.
DT =01
Io >>->
Operation Criteria
67N, etc.., (1 to 05)
0 = Basic angle &
Uo
---Operation direction
forward / Reverse
forward=0
---Operation
Charecteristics.
IoSin(phi) / IoCos(phi)
( 0,1)
0=Io*sin(phi)
----Basic Angle
-90 deg to 60 deg.
-90 deg
---Io >
Current setting (Io/ In)
0.01 - 5.00 xIn.
0.075
Uo>
Start voltage
2.0 - 100 % of Un.
5%
Operate time ( in DT)
0.1 - 300 Secs
0.1
intermittent EFR
Active / Not-active (0,1)
0
---REX 521
DOC6Low ( 67 )
Operation Mode
Not in use / DT/ NI/VI /
c-2 ETC.
DT =01
3I >_>
3I >>_>
Operation direction
forward / Reverse
forward=0
---Operation
Charecteristics.
IoSin(phi) / IoCos(phi)
( 0,1)
0=Io*sin(phi)
---Basic Angle
0 deg to 90 deg.
60 deg
---Io >
Current setting (Io/ In)
0.05 - 40 xIn.
0.75
time Multiplier ' K '( in
IDMT -mode )
0.05 - 1.00
0.05
IDMT
Operate time ( in DT)
0.05 - 300 Secs
0.05
see ANNEXURE-02
PACP
Recomended Relay Settings
Parameter
Description
Available range
PSM
TMS/DMT
(sec)
CT Ratio / PT Ratio/
OTHER
Relay Setting
Available setting range
see ANNEXURE-01
RECOMMENDED RELAY SETTING CHART FOR 132/11.5kV, 20/25 MVA TRANSFORMER
Recommended setting
Remarks
SI.
No.
Type of Protection
Relay Make /
No.
PROTECTION
ANSI CODE
intermittent EFR
-protection
Disabled / Enabled(0,1)
0
---REX 521
DOC6High ( 67 )
Operation Mode
Not in use / DT/ Inst.
Inst. = 02
3I >>_>
3I >>_>
Operation direction
forward / Reverse
forward=0
---Operation
Charecteristics.
IoSin(phi) / IoCos(phi)
( 0,1)
0=Io*sin(phi)
---Basic Angle
0 deg to 90 deg.
60 deg
---Io >
Current setting (Io/ In)
0.05 - 40 xIn.
0.05
Non directional
Operation
when the dir. Cannot be
determined ( 0, 1 )
0
----Operate time ( in DT)
0.05 - 300 Secs
0.05
intermittent EFR
-protection
Disabled / Enabled(0,1)
0
---10
Under-Voltage Relay.
RXEG 21
27
132000V/√3 / 110V/√3
Operation Mode
DT -ALARM / trip
stage
U<
-U< Alarm
Under voltage setting.
40 -120 V
85 volts.
t > alarm
time setting.(DT)
0 - 99 hrs.
3.0 sec.
U< Trip
Under voltage setting.
40 -120 V
77 volts.
t > Trip
time setting.(DT)
0 - 99 hrs.
1.0 sec.
11
Over-Voltage Relay.
RXEG 21
59
132000V/√3 / 110V/√3
Operation Mode
DT -ALARM / TRIP
stage
U>
-U> Alarm
Under voltage setting.
60 -160 V
115 volts.
t > alarm
time setting.(DT)
0 - 99 hrs.
3.0 sec.
U> Trip
Under voltage setting.
40 -120 V
121 volts.
t > Trip
time setting.(DT)
0 - 99 hrs.
1.0 sec.
see ANNEXURE-01
APPM-MDP Recomended Relay Settings
1)
a) Initial setting:( Idmin) ; --- This setting covers the un-balance created in the differential operating current by the On load Tap changer. In our case the the Tap changer limits are +10% to -15% , and hence the mean tap value : [ 10 +(-15) ] / 2 = - 2.5% and so, the Hv -amps @ mean tap value =[109.35 / (1-0.0250 ] = 112.154 Amps, which corresponds to 2.56% variation in the HV-currents when mean value is considered. Also,in practice typically the initial minimum differentialpick up value for power trafos with OLTC is set between 30% - 40% . However, RET-670 is in-built with OLTC compensation factor and it is possible to set the Id(min) to more sensitive pick up value between ( 15% to 20% ) .Thus we preferred to se the Idmin = 0.25 of Ibase.
b) Endsection-1 setting: ; --- This is the most sensitive part of the charecteristic.Uncompensated OLTC currents are the reason for the existing of false diff currents in this region. so, the slope in this section is always zero.The end lit of this section is set at 1.25 after ensuring the risk of higher false differential currents relatively low.Also,this is the defualt setting set in the RET-670.
c) Slopesection-2 , End section-2 ,Slopesection-3 ; --- These settings are typically adopted to form the Differntial -curve as shown above. The curve with these setting is suitable for various applications as per the Technical -reference manual-rev-b (p-116) .Also, the basis for these settings are as descibed in the technical reference manuals.
d) Unrestrain -high set ,Idunre ; --- This setting by defualt set at 10.This setting ensures the operation instantaneously, as without any doubt this big differential current occurs only due to internal fualts. Also, this by-passes the harmonic test in its operation and so, called unstabilised operation.( Technical -reference manual-rev-b (p-115)
2)
It is a common known fact that ( compared to Low impedence based REFR protection) , High impedence based protections are highly sensitive, accurate & fast operating. Since, high impedence based protections are current / voltage based , and hence makes use of METROSIL & STABILIZING RESISTOR in it's circuit is evident due to high-impedence occurance. The settings for Metrosil and Stablising resistor are as under : CTR -HV = 150 / 1A . R nct = ( as per the field test data ) 2.0 ohms. Rct= 2.0 ohms.
RET-670 & REX-521 RELAY - DETAILED DESCRIPTION FOR SETTING BASIS.
87T -TRAFO. DIFFERENTIAL PROTECTION: The charecteristic for this protection function as adopted in the relay is as shown below.64R-HV & 64R-LV -TRAFO.HIGH IMPEDENCE BASED RESTRICTED EARTH FUALT PROTECTION :
APPM-MDP Recomended Relay Settings
Rs = Us / Ir --- 1
Rs = The resistance of the stabilizing circuit. Ir = The setting value of the Relay.. Us = The stabilizing voltage of the Relay..
Ir = The setting value of the Relay..
Us = If / CTR [ Rct + Rlead ] --- 2 If = Max. expected Through fault current. CTR = phase & nuetral common CT Ratio. Rct = Internal CT secondary resistance of the Circuit. Rl = R of Longest loop of secondary circuit.
Uk > = 2 * Us --- 3 , where Uk = Knee point voltage of the Relay. And factor 2 is used when no operate delay permitted for protection.
I prim = CTR* [ Ir + Inr + m x Ie ] --- 4
Iprim = prim. Operating Current of the relay. Ir = setting value of the Relay.
Inr = Current through the Non-Linear Resistance m = no of CT's in the circuit. / no of CT's in parallel. Ie = Excitation current of the CT @ Us.
Ie = 0.5 * I0 --- 5
Io = Excitation current of the relay @ Uk
Ir recommended > = m x Ie = m x 0.5 x Io ( as per the technical manual )
Also, as per the Relay manuals and pratice , If ( max. thro fualt current ) = 16 x IfL ---- for small Transformers. = 12 x IfL ---- for Big Transformers. = 6 x IfL ---- for Generators. IfL ---- > Full load current of the Transformer /Generator.
Also, the sensitivity requirements for the protection are jeopardize if the magnetizing current of the CT's at Vk is too high. The Iprim Vaue at which the Relay operates at certain settings can be calculated using the formula. As in the eqn --- 4.
TRANSFORMER DATA : MVA = 20 /25 ONAN /ONAF KV -Rating. : 132 /11.5 KV % Z = 12.5 P.u ON 20 MVA BASE. Vector group : YNyn.
Tap Change Limit : +10 % to -15% @ 1.25% Nct -Ratio = 150 /1A
Uk -Nct = 150 Volts. ( as phase CT's are designed for Uk> 400volts,Hence the chances getting saturated is minimum.) Excitation current for NCT < 30 mA @ Vk / 2.
APPM-MDP Recomended Relay Settings
Calculations for REFR -HV :
Rnct = 2.0 ohms , Rlead = 2.0 ohms. & Rct(ph) = 4.0 ohms. ( for calculations Rct(ph) shall be taken or which ever is Higher.) Nct -Ratio = 150 /1A
Uk -Nct = 150 Volts. ( as phase CT's are designed for Uk> 400volts,Hence the chances getting saturated is minimum.) Excitation current for NCT < 30 mA @ Vk /2 ( considering the worst case ).
IfL -HV = 109.35A , CTR= 150
If = ( %Z ) x IfL = 12.5 x 109.35 = 1367 A ( Max. expected through fault current expected. )
Uk = (required) = 2 x Us. = 2 x If / CTR [ Rct + Rlead ] = 2 x (1367 / 150) [4 +2 ] = 109.36 volts.=110 V (approx.)
As Uk is >>> than 150 V as per the Trafo. Name plate data for NCT.The operation of protection would be ensured perfectly. And is not a case dependent. Us =Uk /2 = 54.68 volts.=55 V (approx.)
Now, since the RET-670 adopts High-Impedence scheme with voltage as operand.
Hence, the Stabilizing Resistor , Rs= 250 ohms. & Us>= 63volts.
The setting to adopted is = 115% of Us> = 1.15 x 55 = 63 (Approx.) volts. Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }
Ir = Current through the Relay @ voltage Us> = 63/250 = 252 mA . Inlr = Current through the Non- Linear Resistor = (from the graph.) = 5 mA.
nxIe = no. of CT's and their average Excitation currents. = (0.0504+3x0.0252) = 126mA.(approx.) Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }= 150{ 252+5+126 } = 57.45 A. This is well below the value minimum fualt current, and only constitute 38.3 % of Rated CT current. Also,
As, per the above description , The Ir >= m x 0.5 x Io = 4 x 0.5 x ( 0.030 x 2 ) = 0.12 A so, the setting is safe.
Hence, the Stabilizing Resistor , Rs= 250 ohms. & Us>= 63volts.
Calculations for REFR -LV :
Rnct = 4.0 ohms , Rct (ph) = 10.0 ohms. & Rlead = 2.0 ohms.( for calculations Rct(ph) shall be taken or which ever is Higher. ) IfL -LV = 1255.15A , CTR= 2000/1A
Nct -Ratio = 2000 /1A
Uk -Nct = >300 Volts. ( as phase CT's are also,designed for Uk> 300volts,Hence the chances getting saturated is minimum.) Excitation current for NCT < 30 mA @ Vk / 4.
If = ( %Z ) x IfL = 12.5 x 1255.15 = 15690 A ( Max. expected through fault current expected. )
Uk = (required) = 2 x Us. = 2 x If / CTR [ Rct + Rlead ] = 2 x (15690 / 2000) [ 10 +2 ] = 188.3 volts.=189 V (approx.)
As Uk is >>> than 300 V as per the NGR. Name plate data for NCT.The operation of protection would be ensured perfectly. And is not a case dependent. Us =Uk /2 = 94.14 volts.=95 V (approx.)
Hence, the Stabilizing Resistor , Rs= Us/Ir. = 95 / 0.24 =395.83 = 396 Ohms (approx.)
Now, since the RET-670 adopts High-Impedence scheme with voltage as operand. The setting to adopted is = 115% of Us> = 1.15 x 95 = 109.5 (Approx.) volts. Calculation of Stabilizing Resistor : As per manuals of RET ,
This can be directly selected to a value Rs=396 ohms . Now , this value of resistor should satisfy the below eqn.
Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }
Ir = Current through the Relay @ voltage Us> = 109.5/396 = 276.5 mA . Inlr = Current through the Non- Linear Resistor = (from the graph.) = 5 mA.
nxIe = no. of CT's and their average Excitation currents. = (0.0544+3x0.0544) = 218mA.(approx.) Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }= 2000{ 276.5+5+218 } = 999.0 A. This is well below the value minimum fualt current, and only constitute 49.95 % of Rated CT current. Also,
As, per the above description , The Ir >= m x 0.5 x Io = 4 x 0.5 x ( 0.030 x 4 ) = 0.24 A so, the setting is safe.
Hence, the Stabilizing Resistor , Rs= 396 ohms. & Us>= 109.5 volts.
APPM-MDP Recomended Relay Settings
3) 51Ns -HV & LV :
The stand by earth-fualt protection , is mainly to Protect the NGR from over heating due to Fualt current exceeding the rated current rating of the NGR. .So, the settings adopted have to be set in Definite time mode depending upon it's thermal current rating of the Transformer. The rated duty of the NGR is our case is 600A for 30 secs. And hence , the settings should be planned such that the HV - S/b EFR should trip HV-Breaker , and LV - S/b EFR should trip LV -Breaker , compeletely isolating the Transformer from the circuit. However , as discussed in the prior meeting held with Mr.B.D.Shaw,if the Lower rating -NGR that are existing in the System , then it's setting should be minimised to the value of Lower -rating NGR or 90% of that. We have attached a document on S/B EFR Protection with this for your reference. Hence, the setting should be adopted for
HV S/B EFR : CTR= 150 /1A ,
Io > setting= approx.( 15 % - considering the Lowest rating NGR ,rating = 100A ,Else 85% - considering the rated ampacity of the NGR.) Time setting: definite time , and should be with in the Rated duty of NGR i.e 3.0 secs.
LV S/B EFR : CTR= 600 /1A ,
Io > setting= approx.( 15 % - considering the Lowest rating NGR ,rating = 100A .)
4) 99 (24) : Over fluxing Protection.
Actual set limits for this protection should be in accordance with the data submitted by the ' Trafo. Manufacturer. " . However , the default settings
of as in the relay , suits for most of the applications. These default settings programmed at ABB Factory , after a detailed study of Most -common and most versatile applications. As pe the TRAFo. " Permissible Over-excitation Curve " ( attached with mail.) .
Some Important Factors / Notes for Over fluxing Protection:
1) Over excitaion occurs from the excessive applied voltage, possibly in combination with below normal Frequency. Such conditions are very often , when Transformers are directly connected to the Generators.
2) Bmax is directly proportional to the Induced voltage., as E = 4.44 x f x n x Bmax . A 3) The calculation of the relative ( M ) ,is based on the V/Hz ratio..
4) As per IEC 60076-1 , All transformers shall be capable of operating continuously at 10% above rated voltage. On that basis the setting range is 100 - 150%. & if the User does not know what exactly to be set , then th e standard IEC-60076 -1 section-4.4 suggests defualt value V/Hz > = 1.10 p.u.
5) As long as the E/f or V/F did not cross the relative value (M) set of the relay, the Trafo. Is not overexcited. The relative over excitation is thus defined as Over excitaion = M - V/Hz >
6) Operatin Time of the Overexcitation Protection :
The most famous Law ,so called IEEE Law approximates a square Law and has been choosen based on the analysis of the various transformers over excitation capability charecteristics. They can match a well a transformer core capability.
t op = 0.18 x k [ M - V/Hz>)2 ….= 0.18 x k / ( Overexcitaton ) .
Where: M -- is the , Mean value in the interval from t=0 to t=top .
V/Hz > ---- is the Max. continously allowed voltage at no -Load and rated Frequency , in p.u . &
K --- is the time multiplier setting for the inverse time functions as usual & selects one curve frim the family of Curves.
Since , from - " Trfo. Data curves " over Excitation of beyond 110% is not allowed so, for Our setting of V/Hz > 110 % of Vr /fr is set and is same as default. Also, the Alarm setting in the relay is in-built and is 2% less than the set value , with a definite time delay of set limit - Tmin. And all other settings are as in the setting chart. We have attached a " over -Excitation Protection basis for your reference along with the Trafo. Over-Excitaion Curve.
APPM-MDP Recomended Relay Settings
5) 81.O & 81.U - or df/dt Protection. : ( RET-670 )
The basis for this settings when derived from the over excitation limits ( V/Hz - ratio limits) along with the Under & Over voltage set limits , The values found to be extremely high or extremely low , such as ( f > becomes 55 Hz. & f < becomes 36 Hz.) ,Hence, these limits are set in accordance with the ELECTRICITY Regulatory Rules bound to that region. We request M/s Customer to do this setting at site.However, we maintained the same defualt settings for this application.
6) 27 & 59 - Protection. : ( REXEG-21 )
These settings are based on the common practice adopted at most of the installations. Also, the same values are acceptable to most of the Electricity Boards across India. The values adopted are --- 110% of the 110V = 121 volts. ( PT -secondary Rated-value ) --- for Over voltage Limits &
---- 70% of the 110V = 77 Volts ( PT -secondary Rated-value ) --- for Under voltage Limits
7) 50/51, 50N/51N, 67 & 67N - Protection. : ( Rex-521)
These settings are based on the relay co-ordination study , and direction is also based on the study whre in if the non-directional Overcurrent grading is set to follow relay cordination timings , then the Directional - OCR shall be graded fastly to look towards that direction where the former gives graded timing with a substantial time delay. Also, the current settings for these Relays are the full-load current of the Equipment / Feeder.So, we have achieved in this settings, whreas the setting of TMS , needs a DETAILED STUDY.
Calculations for REFR -LV :
Rnct = 4.0 ohms , Rct (ph) = 10.0 ohms. & Rlead = 2.0 ohms.( for calculations Rct(ph) shall be taken or which ever is Higher. ) IfL -LV = 15690 A , CTR= 2000/1 A
Nct -Ratio = 2000 /1A
Uk -Nct = >300 Volts. ( as phase CT's are also,designed for Uk> 300volts,Hence the chances getting saturated is minimum.) Excitation current for NCT < 30 mA @ Vk / 4.
If = ( %Z ) x IfL = 12.5 x 1255.15 = 15690 A ( Max. expected through fault current expected. )
Uk = (required) = 2 x Us. = 2 x If / CTR [ Rct + Rlead ] = 2 x (15690 / 2000) [ 10 +2 ] = 188.3 volts.=190 V (approx.)
As Uk is >>> than 300 V as per the NGR. Name plate data for NCT.The operation of protection would be ensured perfectly. And is not a case dependent. Us =Uk /2 = 95 volts.=95 V (approx.)
Now, since the RET-670 adopts High-Impedence scheme with voltage as operand. The setting to adopted is = 115% of Us> = 1.15 x 101 = 117 (Approx.) volts. Calculation of Stabilizing Resistor : As per manuals of RET ,
This can be directly selected to a value Rs=450 ohms . Now , this value of resistor should satisfy the below eqn.
Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }
Ir = Current through the Relay @ voltage Us> = 117/450 = 260 mA . Inlr = Current through the Non- Linear Resistor = (from the graph.) = 5 mA.
nxIe = no. of CT's and their average Excitation currents. = (0.0544+3x0.0544) = 218mA.(approx.) Ip(prim) = (Sentivity current measured) = CTR { Ir + I_nlr + n x Ie }= 3000{ 260+5+218 } = 1449.0 A. This is well below the value minimum fualt current, and only constitute 48.3 % of Rated CT current. Also,
As, per the above description , The Ir >= m x 0.5 x Io = 4 x 0.5 x ( 0.030 x 4 ) = 0.24 A so, the setting is safe.
Hence, the Stabilizing Resistor , Rs= 450 ohms. & Us>= 117 volts.