• No results found

Transformer-Less Dynamic Voltage Restorer for Voltage Sag Compensation using PI Controller

N/A
N/A
Protected

Academic year: 2022

Share "Transformer-Less Dynamic Voltage Restorer for Voltage Sag Compensation using PI Controller"

Copied!
11
0
0

Loading.... (view fulltext now)

Full text

(1)

Transformer-Less Dynamic Voltage Restorer for Voltage Sag Compensation using PI Controller

M.Bharath1, M.Manikandan2

1PG Student, Department of Electrical and Electronics Engineering, Erode Sengunthar Engineering College, Tamilnadu, India

2AP, Department of Electrical and Electronics Engineering, Erode Sengunthar Engineering College, Tamilnadu, India

Abstract Power quality is one of major concerns in the present era. It has become important, especially, with the introduction of sophisticated devices, whose performance is very sensitive to the quality of power supply that results in a failure of end use equipment’s. One of the major problems dealt here is the voltage sag.To solve this problem, custom power devices are used. One of those devices is the Dynamic Voltage Restorer (DVR), which is the most efficient and effective modern custom power device used in power distribution networks. Its appeal includes lower cost, smaller size, and its fast dynamic response to the disturbance. It can provide the most commercial solution to mitigation voltage sag by injecting voltage as well as power into the system. This paper presents modeling, analysis and simulation of a Dynamic Voltage Restorer (DVR) using MATLAB. The efficiency of the DVR depends on the performance of the efficiency control technique involved in switching the inverters. In this model a PI controller and Discrete PWM pulse generator was used.

Keywords; Dynamic voltage restorer,voltage sag,power quality

1.INTRODUCTION

Modern electric power systems are complex networks with hundreds of generating stations and thousands of load centers are interconnected through long power transmission and distribution networks. Power quality is major concern in industries today because of enormous losses in energy and money. With the advent of myriad sophisticated electrical and electronic equipment, such as computers, programmable logic controllers and

variable speed drives which are very sensitive to disturbances and non-linear loads at distribution systems produces many power quality problems like voltage sags, swells and harmonics and the purity of sine waveform is lost. Voltage sags are considered to be one of the most severe disturbances to the industrial equipment’s.

2. PROPOSEDDVR 2.1 Ease of Use

Power distribution systems, ideally, should provide their customer with an uninterrupted power flow at smooth sinusoidal voltage at the contracted magnitude level and frequency .A momentary disturbance for sensitive electronic devices causes voltage reduction at load end leading to frequency deviations which results in interrupted power flow, scrambled data, unexpected plant shutdowns and equipment failure. Voltage lift up at a load can be achieved by reactive power injection at the load point of common coupling (PCC).

(2)

International Journal of Advanced Engineering Research and Science (IJAERS) [Vol-2, Issue-4, April- 2015]

ISSN: 2349-6495

Page | 65 Fig-1. Basic structure of DVR

(3)

The common method for this is to install mechanically switched shunt capacitors in the primary terminal of the distribution transformer. The mechanical switching may be on a schedule, via signals from a supervisory control and data acquisition (SCADA) system, with some timing schedule, or with no switching at all. The disadvantage is that, high speed transients cannot be compensated. Some sag is not corrected within the limited time frame of mechanical switching devices.

Transformer taps may be used, but tap changing under load is costly.

Fig-2. Location of DVR

Another power electronic solution to the voltage regulation is the use of a dynamic voltage restorer (DVR). DVR’s are a class of custom power devices for providing reliable distribution power quality. They employ a series of voltage boost technology using solid state switches for compensating voltage sags/swells. The DVR applications are mainly for sensitive loads that may be drastically affected by fluctuations in system voltage.

2.2 Solutions to Power Quality Problems:

There are two approaches to the mitigation of power quality problems. The solution to the power quality can be done from customer side or from utility side First approach is called load conditioning, which ensures that the equipment is less sensitive to power disturbances, allowing the operation even under significant voltage distortion. The other solution is to install line conditioning systems that

suppress or counteracts the power system disturbances.

2.2.1 Mechanical Switching Shunt Capacitors:

It is installed in primary terminal of distribution transformer. But some sag is not corrected within limited time frame of mechanical switching capacitors. Transformer taps may be used, but tap changing under load is costly.

2.2.2 Thyristor Based Static Switches:

The static switch is a versatile device for switching a new element into the circuit when the voltage support is needed. It has a dynamic response time of about one cycle.

Fig-3. Schematic diagram of DVR

To correct quickly for voltage spikes, sags or interruptions, the static switch can used to switch one or more of devices such as capacitor, filter, alternate power line, energy storage systems etc. The static switch can be used in the alternate power line applications.

2.2.3 Energy Storage Systems:

Storage systems can be used to protect sensitive production equipments from shutdowns caused by voltage sags or momentary interruptions.

These are usually DC storage systems such as UPS, batteries, superconducting magnet energy storage (SMES), storage capacitors or even fly wheels driving DC generators. The output of these devices can be supplied to the system through an inverter on a momentary basis by a fast acting electronic switch.

(4)

International Journal of Advanced Engineering Research and Science (IJAERS) [Vol-2, Issue-4, April- 2015]

ISSN: 2349-6495

Page | 67 Enough energy is fed to the system to compensate for

the energy that would be lost by the voltage sag or interruption.

.

Fig-4. RMS representation of voltage sag 3. REALIZATION OF COMPENSATION

TECHNIQUE 3.1. Discrete PWM scheme using PI controller

The test system for DVR is composed by a 13 kV, 50 Hz Generation system, feeding transmission line through a 2- winding transformer connected in Y/ Δ,13/115KV. Such transmission line feed distribution network through step down transformer connected in Δ/Y, 115/11 kV. To verify the working of DVR for voltage compensation a fault is applied at point X at resistance 0.66 U for time duration of 200 ms. The DVR is simulated to be in operation only for the duration of the fault.

Fig-5. Circuit diagram of DVR controller

Using the voltage divider model, where the voltage magnitude at the PCC is given by:

Usag= E [Zf /(Zs +Zf ) ]. . . equ(1)

Zs = the source impedance including the transformer impedance

Zf = the impedance between the PCC and the fault including fault and line impedances

Fig-6.Faults on parallel feeder causing voltage sag 3.2 Equations Related To DVR:

The system impedance Zth depends on the fault level of the load bus. When the system voltage (Vth) drops, the DVR injects a series voltage VDVR

through the injection transformer so that the desired load voltage magnitude VL can be maintained.

The series injected voltage of the DVR can be written as

VDVR=VL+ZthIL-Vth . . . equ(2)

Fig 3.3 Equivalent circuit diagram of DVR VL: The desired load voltage magnitude

Zth: The load impedance.

IL: The load current

Vth: The system voltage during fault condition.

The load current IL is given by

Il = (Pl +jQl)/Vl . . . . .equ(3)

(5)

When VL is considered as a reference equation

Θ= tan-1l / Pl ) . . .equ(4)

The complex power injection of the DVR can be written as,

Sdvr = Vdvr IL*. . . equ(5) It requires the injection of only reactive power and

the DVR itself is capable of generating the reactive power.

3.3 Operating Modes Of DVR:

The basic function of the DVR is to inject a dynamically controlled voltage VDVR generated by a forced commutated converter in series to the bus voltage by means of a booster transformer. The momentary amplitudes of the three injected phase voltages are controlled such as to eliminate any detrimental effects of a bus fault to the load voltage VL.

3.3.1 Protection Mode:

If the over current on the load side exceeds a permissible limit due to short circuit on the load or large inrush current, the DVR will be isolated from the systems by using the bypass switches (S2 and S3 will open) and supplying another path for current (S1 will be closed).

Fig-7. Protection mode 3.3.2 Standby Mode: (Vdvr= 0)

In the standby mode the booster transformer’s low voltage winding is shorted through the converter. No switching of semiconductors occurs in this mode of operation and the full load current will pass through the primary.

Fig-8.Standby mode 3.3.2 Injection/Boost Mode: (Vdvr>0)

In the Injection/Boost mode the DVR is injecting a compensating voltage through the booster transformer due to the detection of a disturbance in the supply voltage.

3.4 Voltage Injection Methods of DVR:

Voltage injection or compensation methods by means of a DVR depend upon the limiting factors such as; DVR power ratings, various conditions of load, and different types of voltage sags. Some loads are sensitive towards phase angel jump and some are sensitive towards change in magnitude and others are tolerant to these. Therefore the control strategies depend upon the type of load characteristics.

3.4.1 Pre-Sag Compensation Method:

The pre-sag method tracks the supply voltage continuously and if it detects any disturbances in supply voltage it will inject the difference voltage between the sag or voltage at PCC and pre-fault condition, so that the load voltage can be restored back to the pre-fault condition.

VDVR = Vprefault – Vsag. . . . (6) Θdvr = tan-1 [ Vl sin θl / (Vl cosθl – Vs

cosθs )] . . . (7)

(6)

International Journal of Advanced Engineering Research and Science (IJAERS)

Fig-9.pre-sag compensation method 3.4.2 In-Phase Compensation Method:

This is the most straight forward method. In this method the injected voltage is in phase with the supply side voltage irrespective of the load current and pre-fault voltage. The phase angles of the pre and load voltage are different but the most impor criteria for power quality that is the constant magnitude of load voltage are satisfied. One of the advantages of this method is that the amplitude of DVR injection voltage is minimum for certain voltage sag in comparison with other strategies.

|VL|=|Vprefault| . . . (8)

Fig-10.In-phase compensation method 3.5 Voltage tolerance method with minimum energy injection:

A small drop in voltage and small jump in phase angle can be tolerated by the load itself. If the voltage magnitude lies between 90%

nominal voltage and 5%-10% of nominal state that will not disturb the operation characteristics of loads.

International Journal of Advanced Engineering Research and Science (IJAERS) April- 2015]

sag compensation method Phase Compensation Method:

This is the most straight forward method. In this method the injected voltage is in phase with the supply side voltage irrespective of the load current fault voltage. The phase angles of the pre-sag and load voltage are different but the most important criteria for power quality that is the constant magnitude of load voltage are satisfied. One of the advantages of this method is that the amplitude of DVR injection voltage is minimum for certain voltage sag in comparison with other strategies.

. . . (8)

phase compensation method

Voltage tolerance method with minimum

A small drop in voltage and small jump in phase angle can be tolerated by the load itself. If the voltage magnitude lies between 90%-110% of 10% of nominal state that will not disturb the operation characteristics of loads.

Both magnitude and phase are the control parameter for this method which can be achieved by small energy injection.

Fig-11.Voltage tolerance method with minimum energy injection

4.SIMULATION AND RESULTS

The first simulation was done with no DVR and results are obtained as shown in figure

International Journal of Advanced Engineering Research and Science (IJAERS) [Vol-2, Issue-4, ISSN: 2349-6495

Page | 69 itude and phase are the control parameter for this method which can be achieved by small

Voltage tolerance method with minimum energy injection

.SIMULATION AND RESULTS

simulation was done with no DVR btained as shown in figure

(7)

Fig-12.System without DVR and fault After the MATLAB Simulation of faults in transmission line, it was observed that the voltage and current waveforms are transient. During the initial part of the short circuit, the short-circuit current was limited by sub- transient reactance of synchronous machine & impedance of the transmission line between the machine and the point of fault. After that it was limited by transient reactance of synchronous machine and impedance of line.

Fig-13. Vabc, Iabc for single L-G fault Finally, the short-circuit current settled down to steady state limited by synchronous reactance of the machine and line impedance. The negative and zeo sequence components were present initially only and disappeared after the circuit breaker cleared the fault.

Fig-14. Vabc, Iabc for double L-G fault Next simulation was done with no fault and a three phase fault, double line fault and single L-G fault is applied to the system at point with fault resistance of 0.66 U for time duration of 200 ms with voltage sag magnitude of 0.1, 0.5 and 0.9 p.u.

respectively.

Fig-15.Phase –phase, three-phase and p.u.

voltages at load point for a-b-c fault

(8)

International Journal of Advanced Engineering Research and Science (IJAERS) [Vol-2, Issue-4, April- 2015]

ISSN: 2349-6495

Page | 71 Fig-16. Phase –phase, three-phase and p.u.

voltages at load point for a-g fault

Each mosfet conducts for 180 degree. Three mosfets remain on at any instant of time. There are six modes of operation in a cycle and the duration of each mode is 60 degree. The gating signals are shifted from each other by 60 degree to obtain three- phase balanced (fundamental) voltages.Fig 5.4.1 is simulated in MATLAB and sinusoidal phase-ground

voltages are obtained.

Fig-17.Sine wave inverter

Next simulation is carried out at the same scenario as above but a DVR is now introduced at the load side to compensate the voltage sag occurred due to the three phase fault applied.

(9)

Fig-18 Phase-phase voltage across inveter and load.

Fig-19. System with DVR and fault When the DVR is in operation the voltage interruption is compensated almost completely and

the rms voltage at the sensitive load point is maintained at normal condition.

Fig-20. Phase –phase voltages at load point for a- b-c fault

Fig-21.Phase –phase and three-phase voltages at load point for a-b-c fault

5.CONCLUSION

`In order to show the performance of DVR in mitigation of voltage sags, s simple distribution network is simulated using MATLAB. A DVR is connected to a system through a series transformer with a capability to insert a maximum voltage of 50%

of phase to ground system voltage. In-phase compensation method is used. DVR handles both balanced and unbalanced situations without any difficulties and injects the appropriate voltage component to correct rapidly any deviation in the supply voltage to keep the load voltage constant at the nominal value. The main advantages of the proposed DVR are simple control, fast response and low cost. The proposed PWM control scheme using

(10)

International Journal of Advanced Engineering Research and Science (IJAERS) [Vol-2, Issue-4, April- 2015]

ISSN: 2349-6495

Page | 73 PI controller is efficient in providing the voltage sag

compensation. As opposed to fundamental frequency switching schemes already available in the MATLAB/SIMULINK, this PWM control scheme only requires voltage measurements. This characteristic makes it ideally suitable for low- voltage custom power applications. DVR works independently of the type of fault as tested for the system as based on the analysis of test system DVR mitigates voltage sags due to three phase, single L-G and double line faults. The main shortcoming of the DVR, being a series device, is its inability to mitigate complete interruptions.

REFERENCES 1. H.P. Tiwari, Sunil Kumar Gupta, “Dynamic

Voltage Restorer Based on Load Condition”, International Journal of Innovation, Management and Technology, Vol. 1, No. 1, April 2010.

2. Tarek I. El-Shennawy, Abdel-Mon’em Moussa, Mahmoud A. El-Gammal and Amr Y. Abou-Ghazala, “A Dynamic Voltage Restorer for Voltage Sag Mitigation in a Refinery with Induction Motors Loads”, American J. of Engineering and Applied Sciences 3 (1): 144-151, 2010.

3. Mohan, T. M. Undeland, andW. P. Robbins, Power Electronics: Converters,Applications and Design . New York: Wiley, 1995.

4. Narain G. Hingorani, Laszlo Gyugyi,”Understanding FACTS: Concepts and Technology of Flexible AC

Transmission Systems”,452

pages,December 1999, Wiley-IEEE Press 5. Paisan Boonchiam and Nadarajah

Mithulananthan, “Understandingo f Dynamic Voltage Restorers Through MATLAB Simulation”, ThammasatI nt. J.

Sc.Tech.,Vol. 11,N o. 3, July-September 2006.

6. H. Ezoji, A. Sheikholeslami, M. Tabasi and M.M. Saeednia,” Simulation of Dynamic Voltage Restorer Using Hysteresis Voltage

Control”, European Journal of Scientific ResearchISSN 1450-216X Vol.27 No.1 (2009), pp.152-166

7. Changjian Zhan,V.K. Ramachandrara murthy, A. Arulampalam,M.Barnes and G.Strbac N.Jekin, “Dynamic Voltage Restorer Based on Voltage Space Vector PWM Control”, Applied Power Electronics Conference and Exposition, 2001. APEC 2001. Sixteenth Annual IEEE Volume 2, 4-8 March 2001Vol.2, Page(s):1301 - 1307.

8. H. Hingorani “Introducing custom power”

IEEE spectrum, vol.32 no.6 June 1995 p 41- 48.

9. Ray Arnold “Solutions to Power Quality Problems” power engineering journal 2001 pages: 65-73.

10. John Stones and Alan Collinsion

“Introduction to Power Quality” power engineering journal 2001 pages: 58 -64.

11. C. Zhan, M. Barnes, V.K.

Ramachandaramurthy, and N.

Jenkis,“DynamicVoltage Restorer with Battery Energy Storage for Voltage Dip Mitigation” Power Electronics and Variable Speed Drives, 18-19, Conference Publication No. 475, IEE September 2000.

12. Norbert EDOMAH, “Effects of voltage sags, swell and other disturbances on electrical

equipment and their economic implications”, Paper 0018, 20th International Conference on Electricity Distribution, Prague, 8-11 June 2009 13. Mehmet Tumay, Ahmet Teke, K. Cağatay

Bayındır, M. Uğras Cuma, “Simulation and modeling of a dynamic voltage restorer” . 14. O. Anaya-Lara, E. Acha, “Modeling and

Analysis of Custom Power Systems by PSCAD/EMTDC,” IEEE Trans., Power Delivery, PWDR vol-17 (1), pp. 266-272, 2002.

15. Bingsen Wang, Giri Venkataramanan and Mahesh Illindala, “Operation and Control of

(11)

a Dynamic Voltage Restorer Using Transformer Coupled H-Bridge Converters”, IEEE transactions on power electronics, VOL. 21, NO. 4, JULY 2006.

16. John Stones and Alan Collinsion

“Introduction to Power Quality” power engineering journal 2001 pages: 58 -64.

17. Gregory F. Reed, Masatoshi Takeda,

"Improved power quality solutions using advanced solid-state switching and static compensation technologies," Power Engineering Society 1999 Winter Meeting, IEEE

18. G. Venkataramanan and B. Johnson, “A pulse width modulated power line conditioner for sensitive load centers,” IEEE Trans. Power Delivery, vol. 12, pp. 844–

849, Apr. 1997.

19. M.H.Haque “Compensation of distribution system voltage sag by DVR and DSTATCOM” Power Tech Proceedings, 2001 IEEE Porto , Volume: 1 , 10-13 Sept.

2001 Pages:5 pp. vol.1

20. S. S. Choi, B. H. Li, and D.

D.Vilathgamuwa, “Dynamic voltage restoration with minimum energy injection,”

IEEE Trans. Power Syst., vol. 15,pp. 51–57, Feb. 2000

References

Related documents

Vol 12, Issue 2, 2019 Online 2455 3891 Print 0974 2441 CHRONIC INTERACTION BETWEEN METFORMIN AND MELOXICAM IN MICE FALAH MUOSA KADHIM AL REKABI* Department of Physiology, Biochemistry

I think this view is mistaken since Feyerabend disagrees with Popper’s understanding of quantum theory (what he would later call “pompous declarations and sophomore

Yu, S., et al., Surface modification of thin-film composite polyamide reverse osmosis membranes by coating n-isopropylacrylamide-co-acrylic acid copolymers for

The results in table 7 depicted the major HR Challenges faced by Manufacturing companies for training the personnel are Schedule, Cost, Rapid changes, Trained Trainer,

To propose a weighted Genetic Algorithm and PCA (Principle Component Analysis) [5] based feature selection approach and compare the performance of existing and the proposed

In this thesis, the design, fabrication and a scheme for mounting and actuation o f a novel double stator axial flux bio-mechanically driven MEMS power generator

These results show that the equilibrium frequency of a defective repair allele with recessive fitness effects can be elevated up to an order of magnitude if the heterozygous

Statistical significance was determined using Student t-Test, and one-way ANOVA to compare tramadol treated groups and controls groups as well as tramadol Oral