Intelligent/Addressable Devices

The NBG-12LX

Addressable Manual Pull Station

6 6 4 3 c o v 1 .jp g ‘General

The Notifier NBG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface for any Notifier intelligent control panel except FireWarden series panels, and the NSP- 25 panel. Because the NBG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm.

Features

• Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of

the station, flashes in normal operation and latches steady red when in alarm.

• Handle latches in down position and the word “ACTIVATED” appears to clearly indicate the station has been operated. • Captive screw terminals wire-ready for easy connection to

SLC loop (accepts up to 12 AWG/3.25 mm² wire).

• Can be surface mounted (with SB-10 or SB-I/O) or semi- flush mounted. Semi-flush mount to a standard single- gang, double-gang, or 4" (10.16 cm) square electrical box. • Smooth dual-action design.

• Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force.

• Highly visible.

• Attractive shape and textured finish. • Key reset.

• Includes Braille text on station handle. • Optional trim ring (BG12TR).

• Meets UL 38, Standard for Manually Actuated Signaling Boxes.

• Up to 99 NBG-12LX stations per loop on CLIP protocol loops.

• Up to 159 NBG-12LX stations per loop on FlashScan® pro- tocol loops.

• Dual-color LED blinks green to indicate normal on FlashScan® systems.

Construction

Shell, door, and handle are molded of durable polycarbonate material with a textured finish.

Specifications

Shipping Weight: 9.6 oz. (272.15 g) • Normal operating voltage: 24 VDC. • Maximum SLC loop voltage: 28.0 VDC. • Maximum SLC standby current: 375 A. • Maximum SLC alarm current: 5 mA.

Temperature Range: 32°F to 120°F (0°C to 49°C) • Relative Humidity: 10% to 93% (noncondensing) • For use indoors in a dry location

Installation

The NBG-12LX will mount semi-flush into a single-gang, dou- ble-gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the model SB-10 or SB-I/O sur- face backbox. If the NBG-12LX is being semi-flush mounted, then the optional trim ring (BG12TR) may be used. The BG12TR is usually needed for semi-flush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes).

Operation

Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word “ACTI- VATED” (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos- ing the door automatically resets the switch.

Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 – 159 on FlashScan® systems, 1 – 99 on CLIP systems).

Architectural/Engineering Specifications

Manual Fire Alarm Stations shall be non-coded, with a key- operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red-colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-10 or SB-I/O; or semi-flush mounting on a standard single-gang, double-gang, or

Page 2 of 2 — DN-6726:D • 4/13/2012

NOTIFIER® and FlashScan® are registered trademarks of Honeywell International Inc.

©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com

Made in the U.S. A.

shall be Underwriters Laboratories listed.

Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches.

The loop poll LED shall be clearly visible through the front of the station. The LED shall flash while in the normal condition, and stay steadily illuminated when in alarm.

Product Line Information

NBG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli- cations.)

NBG-12LXSP: Spanish/English labelled version.

NBG-12LXP: Portuguese labelled version.

SB-10: Surface backbox; metal.

SB-I/O: Surface backbox; plastic.

BG12TR: Optional trim ring.

17021: Keys, set of two.

NY-Plate: New York City trim plate.

Agency Listings and Approvals

In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status.

UL/ULC Listed: S692 (listed for Canadian and non-Cana- dian applications).

MEA: 67-02-E.

CSFM: 7150-0028:0199.

• FDNY: COA #6085 (NFS2-640), COA #6098 (NFS2-3030). • BSMI: CI313066760047.

• U.S. Coast Guard. • Lloyd’s Register. • FM Approved.

Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108.

Operates on either 12V or 24V Widest range of candela options: 12V: 15 and 15/75 candela

24V: 15, 15/75, 30, 75, 110 candela Easy candela selection

Lower current draw

Easy DIP switch selection for horn options

Easy mounting with QuickClick™ Synchronizable with MDL Sync•Circuit™ module

Meets UL1971, NFPA72, and ADA signaling requirements

All strobe and horn/strobe models incorporate a new patented voltage booster design that has a more consistent flash bulb voltage over the range of candela selections. The benefit to the customer is a high quality strobe device.

Models Available Strobes Red White S1224MC S1224MCW S1224MCP S1224MCPW S1224MCK S1224MCSP Horn/Strobes Red White P1224MC P1224MCW P1224MCP P1224MCPW P1224MCK P1224MCSP Horns Red White H12/24 H12/24W H12/24K Product Overview

SpectrAlert® Selectable Output Horns, Strobes, and Horn/Strobes offer enhanced fea-

tures that include the widest range of candela options available and the capability to recognize and self-adjust for either 12 or 24 volt operation. With an overall feature set that combines performance, installation ease, flexibility, and a consistent, aesthetically pleasing appearance, the SpectrAlert Selectable Output devices provide both the innovation and efficiency synonymous with the SpectrAlert name. Performance.SpectrAlert selectable output wall-mount horns, strobes, and horn/strobes offer key performance features long associated with the SpectrAlert name. The select- able candela strobes and horn/strobes offer average current draws that are not only lower than conventional fixed-candela SpectrAlert products, but also lower than similar selectable candela products. By consuming less current, the ability to connect even more devices per loop is possible, resulting in a lower installed cost.

Installation.SpectrAlert selectable output horns, strobes, and horn/strobes offer the same installation-friendly features synonymous with the SpectrAlert name, such as the option of 2- and 4-wire operation; the ability to use standard size backboxes with no encroachment into the box; and universal mounting incorporating the labor-saving QuickClick™ feature. Such labor-savings features make wire connections simple and fast,

further reducing installed cost.

Flexibility.SpectrAlert selectable output strobes and horn/strobes offer the broadest range of candela options. In addition, the selectable output strobes and horn/strobes can operate on either 12V or 24V, with no setting required; the device recognizes and self-adjusts to the correct current automatically. Temporal 3 or Continuous tone options continue to be available, in either an Electromechanical or 3kHz pattern.

Aesthetics.SpectrAlert selectable output horns, strobes, and horn/strobes incorporate the same stylish, low profile design of the conventional SpectrAlert products, for a con- sistent and aesthetically pleasing appearance across the entire product line.

S1224MC Strobe

P1224MC Horn/Strobe

Selectable Output Strobe