This menu contains the parameters for the configuration of the analog inputs of the MSLC-2.

Remote Load Reference Input / Process Reference Input

This analog input can be used for two functionalities:

1. Remote load reference input. The input becomes active, if the DI “Setpoint Raise” / “Setpoint Lower” (remote) are closed and the DI “Base Load” or “Imp/Exp Control” is closed.

Figure 3-26: ToolKit – relevant fields for remote load reference input

The load control interacts with the percentage input value shown in field Reference input (parameter 10177). The setting on the right side is the scaling for a minimum and maximum load value while displaying the actual kW setting, which is shown in the field Remote load reference input (parameter 7738).

2. Process reference input. The input becomes active, if the DI “Setpoint Raise” / “Setpoint Lower” (re- mote) are closed and the DI “Process Control” is closed.

Figure 3-27: ToolKit – relevant fields for remote process reference input

The process control interacts with the percentage input value shown in field Remote reference input (parameter 10117). The setting on the right side will display the actual Process reference (parameter 7726). The process en- gineering unit will allow you to display a 4 to 20 mA input as a kW value (Example, there are many engineering units to select). The process signal input and the process reference (remote) will both display the engineering units selected.

Linear

ID Parameter CL Setting range Default Description

4311 User defined

min display value

2 -100.0 to 100.0 %

0.0 % Remote load reference input / process reference input. Linear scaling: This is the percentage value according to the lowest hardware signal. 4312 User defined max display value 2 -100.0 to 100.0 %

100.0 % Remote load reference input / process reference input. Linear scaling: This is the percentage value according to the highest hardware signal.

10117 Remote

reference input

- Info - This is the resulting percentage value calculated out of the mini- mum and maximum scaling as to what the remote input actually has connected. 7735 Remote load ref min value 2 -999999.9 to 999999.9 kW

0.0 kW This setting is only in use, if the remote load reference input is in use (see description above). This value is the according kW value to the percentage value according to the lowest hardware signal (parameter 4311).This setting is used to display the analog input reference in kW. 7736 Remote load ref max value 2 -999999.9 to 999999.9 kW

500.0 kW This setting is only in use, if the remote load reference input is in use (see description above). This value is the according kW value to the percentage value according to the highest hardware signal (parameter 4312). This setting is used to display the analog input reference in kW.

7738 Remote load

reference input

- Info - This is the resulting kW value calculated out of the minimum and maximum scaling.

7726 Process

reference

- Info - This is the resulting Process reference value calculated out of the minimum and maximum scaling, adjusted in parameter 7733 and parameter 7734. 7732 Process engineering unit 2 kW / °C / kPA / bar / V / mA

kW The process control engineering units are selected here. With this input the reference and the real value can be defined in engineer- ing units for easier customer use.

Process Signal Input

This analog input stands for the process control real signal. The input comes as a hardware signal but the engi- neering values can be selected here. The process engineering units are adjustable and used for visualizing purpos- es. The regulation of the process is done with the percentage value.

Figure 3-28: ToolKit – process signal input

ID Parameter CL Setting range Default Description

7674 HW signal 2 0 to 20 mA./ 4 to 20 mA./ 0 to 10 V./

0 to 5 V./

Linear

ID Parameter CL Setting range Default Description

4322 User defined

min display value

2 -100.0 to 100.0 %

0.0 % Process signal input (real value). Linear scaling: This is the per- centage value according to the lowest hardware signal.

4323 User defined

max display value

2 0.0 to 100.0 % 100.0 % Process signal input (real value). Linear scaling: This is the per- centage value according to the lowest hardware signal.

10151 Process

signal input

- Info - This is the resulting percentage value calculated out of the mini- mum and maximum scaling.

7732 Process

engineering unit

2 kW / °C / kPA / bar / V / mA

kW The process control engineering units can be determined here. With this input the reference and the real value can be defined in engineering units.

7733 Process min

value

2 -999999.9 to 999999.9

-500.0 This value is the engineering unit value to the percentage value according to the lowest hardware signal (parameter 4322). 7734 Process max

value

2 -999999.9 to 999999.9

500.0 This value is the engineering unit value to the percentage value according to the highest hardware signal (parameter 4323). 7727 Process

signal Input

- Info - This is the resulting process signal input value calculated out of the minimum and maximum scaling, adjusted in parameter 7733 and parameter 7734.

Reactive Load Input

This analog input stands for the power factor reference signal. Remote var reference control is not available at this time. To activate the remote reactive load input, the discret inputs “Voltage raise” and “Voltage lower” must be closed.

Figure 3-29: ToolKit – reactive load input

ID Parameter CL Setting range Default Description

7675 HW signal 2 0 to 20 mA./ 4 to 20 mA./ 0 to 10 V./

0 to 5 V./ 1 to 5 V

Linear

ID Parameter CL Setting range Default Description

4333 User defined

min display value

2 -0.999 to 0.999 PF

-0.990 PF Power factor reference signal input. Linear scaling: This is the power factor value according to the lowest hardware signal.

4334 User defined

max display value

2 -0.999 to 0.999 PF

0.710 PF Power factor reference signal input. Linear scaling: This is the power factor value according to the highest hardware signal.

7718 Reactive

load input

- Info - This is the resulting power factor reference calculated out of the minimum and maximum scaling, adjusted in parameter 4333 and parameter 4334.