AC Failure Default: 0 Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter enables the output to activate when the control panel responds to an AC power failure as programmed in AC Fail Time. The output automatically resets when AC power is restored.
Connect a separate sounder to this output to create an audible annunciation from the keypads for all applications excluding commercial fire systems.
RPS Menu Location
Output Parameters > Panel Wide Outputs > AC Failure
Battery Trouble Default: 0 Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter enables the output to activate when battery voltage falls below 85%
of capacity (12.1 VDC) for a fully charged (13.8 VDC) battery, or when the battery is in a missing condition. The output automatically resets when battery power is restored.
Connect a separate sounder to this output to create an audible annunciation from the keypads for all applications excluding commercial fire systems.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Battery Trouble
Phone Fail Default: 0 Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter enables the output to activate when a telephone line failure alarm is generated. The output automatically resets when a valid passcode is entered at the keypad.
A time must be entered in Phone Supervision Time in order for this output to activate.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Phone Fail
Comm Fail Default: 0 Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter enables the output to activate when the control panel is unable to send a report after 10 attempts are made to each routing destination. This output automatically resets when a report is sent successfully. Use this parameter to report primary digital report failure to an alternate communication device.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Comm Fail
Log % Full (Outputs) Default: 0
Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter sets the number of the output that activates when the log has reached the programmed percentage of its capacity as programmed in Log % Full. A steady output is provided until the RPS pointer is set.
RPS Menu Location
Output Parameters > control panel Wide Outputs > Log % Full (Outputs) Additional resources
See Get History for more information.
Summary Fire Default: 0 Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter sets the number of the output that activates when any fire point in the system (Point type = Fire) goes into alarm. A steady output is provided until all fire points in the system are returned to normal.
IMPORTANT: This parameter only functions as described when Fire Summary Sustain ( >
Misc > Fire Summary Sustain) = No.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Fire
Summary Alarm Default: 0 Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter sets the number of the output that activates when a non-fire point goes into alarm. A steady output is provided until the alarm is acknowledged by a valid passcode then cleared from alarm memory with an acknowledgment at the keypad.
This output does not activate for silent alarms.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Alarm
Summary Fire Trouble Default: 0
Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter enables the output to activate when any fire point on the control panel is in trouble. A steady output is provided until all fire points have restored to a normal event.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Fire Trouble
Summary Supervisory Fire Default: 0
Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This output activates when any fire supervisory point on the control panel is in a supervisory event (off normal). A steady output is provided until all fire supervisory points are restored to a normal condition.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Supervisory Fire
Summary Trouble Default: 0
Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter output activates when any non-fire point on the control panel is in a trouble event. A steady output is provided until the trouble is acknowledged by the user at the keypad.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Trouble
Summary Supervisory Burg Default: 0
Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter enables the output to activate when any non-fire supervisory point on the control panel is in a supervisory condition. A steady output is provided until it is acknowledged at the keypad.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Supervisory Burg
Summary Gas Output Default: 0
Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter sets the number of the output that activates when any gas point in the system goes into alarm. A steady output is provided until all gas points in the system are returned to normal.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Gas Output
Summary Gas Supervisory Output Default: 0
Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter enables the output to activate when any gas supervisory point on the control panel is in a supervisory event (off normal). A steady output is provided until all gas supervisory points are restored to a normal condition.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Gas Supervisory Output
Summary Gas Trouble Output Default: 0
Selections:
B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58
B4512: A, B or C, 0, 11-18, 21-28, 31-38
This parameter sets the output to activate when any gas point on the control panel is in trouble. A steady output is provided until all gas points have restored to a normal condition.
RPS Menu Location
Output Parameters > Panel Wide Outputs > Summary Gas Trouble Output