A REA W IDE O UTPUTS

These output functions need to be manually reset with Change Output function:

Fail To Close Force Armed

Duress Log % Full

9.1 Area Wide Outputs

Alarm Bell Default: A Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

This parameter activates and provides 12 VDC output when an intrusion point assigned to this area goes into alarm.

IMPORTANT: To comply with SIA CP-01 False Alarm Reduction, set this parameter to a value other than 0 for each enabled area. Refer to SIA CP-01 Verification for more information.

Burg Time and Burg Pat must be programmed. This output activates according to the bell pattern and remains active until the bell time expires or is manually silenced.

Silent Bell must be set to No in order for the bell to ring upon alarm.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide Outputs > Alarm Bell

Fire Bell Default: A Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

This parameter activates and provides 12 DC output when a fire point assigned to this area goes into alarm.

Fire Time and Fire Pat must be programmed in Bell Parameters. This output activates according to the bell pattern and remains active until the bell time expires or is manually silenced. Silent Bell must be set to No in order for the bell to ring upon alarm.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide Outputs > Fire Bell

Reset Sensors Default: C Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

This parameter (output C) output de-activates for five seconds when the RESET SENSORS? function is initiated from the keypad or during a FIRE WALK? test.

The Reset Sensor time converts from the five second default time to the time programmed in Verify Time (Area parameters section) when a point programmed for Alarm Verify (Point Index Section) goes into an alarm event.

When sharing one output to reset sensors in two or more areas you must program the following. Failure to do so can cause TROUBLE PT ### for all point types

programmed as Resettable:

 Scope must include all the areas that are sharing the output.

 Reset Sensors for the user initiating the sensor reset must be enabled in all the areas that are sharing the output.

 Verify Time must be the same number of seconds for all the areas that are sharing the output.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide outputs > Reset Sensors

Fail To Close/Part On Default: 0

Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

To change between the Fail To Close and Part On output functions described below, configure the Part On Output parameter.

for Fail To Close Operation

This output activates when the closing window expires for the specified area. It remains activated until midnight, or until another closing window starts, or the control panel is reset, whichever occurs first.

Each area can be assigned a unique output number for each of the events listed in this section.

This output activates when all areas assigned to the same output are armed Part On Instant or Part On Delayed.

RPS Menu Location

Output Parameters > Area Wide Outputs > Fail to Close/Part On

Force Armed Default: 0 Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

This output activates when this area is force armed. It remains activated until the area is disarmed or the control panel is reset. This output does not activate when Part On force arming.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide Outputs > Force Armed

Watch Mode Default: 0 Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

This output activates when a controlled point programmed for Watch Point is tripped in the specified area while the area is in Watch Mode and the point is not armed. It remains activated for two seconds after each point is faulted.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide Outputs > Watch Mode

Area Armed Default: 0 Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

The output activates when the specified area becomes All On (exit delay must expire before the output activates). The output remains activated until the area is disarmed, it does not deactivate during the entry delay time.

If multiple areas use the same output, the output activates when all areas are armed.

It deactivates when the first area disarms.

 Keyswitch area armed status with LED's. Use an module and connect an LED to display the armed state.

 Alternate communication trigger: This output can be used to trigger the input zone of a device being used as a slave to report control panel arming status.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide Outputs > Area Armed

Area Off Default: 0 Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

When an area's arming state switches from All On (either delay or instant) to Part On or Disarmed, the output number configured here activates.

When an area's arming state switches from Part On or Disarmed to All On (either delay or instant), the output number configured here de-activates.

If the same output number is configured in more than one area's Area Off Output, the output will only activate when the first area is no longer armed All On. If the same output number is configured in more than one area's Area Off Output, the output will only de-activate if all area's using that same output number are armed All On.

The Area Off Output is also affected by the Early Area Armed Output. When the Early Area Armed Output is set to No,the Area Off Output does not activate until the end of exit delay. When the Early Area Armed Output is set to Yes, the Area Off Output de-activates as soon as exit delay starts and the area is armed All On.

Note: if the Error! Hyperlink reference not valid. option is set to Yes and the area switches to Part On at the end of exit delay, the Area Off Output will activate at that time.

Simply starting entry delay does not affect the state of the output configured in Area Off.

RPS Menu Location

Output Parameters > Area Wide Outputs > Area Off

Area Fault Default: 0 Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

The output activates whenever a Part On, Interior or Interior Follower point is faulted.

The output remains activated until all perimeter and interior points in the area are normal.

Keyswitch area armed status with LED's: Use a B308 module and connect an LED to illuminate when this output is activated indicating that the area is not ready to arm.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide Outputs > Area Fault

Duress Output Default: 0 Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

The output activates when a duress alarm is generated from a assigned to the specified area.

Burg Time must have a bell period programmed and Duress Enable must be set to Yes. This output activates "steady" regardless of bell pattern and remains active until the bell time expires.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide Outputs > Duress Output

Part On Fault Default: 0 Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

The output activates when a controlled perimeter point (Type 1) assigned to the specified area is faulted. This output activates regardless of the areas armed state.

This output provides a steady output until all perimeter points in the area return to normal.

This output does not activate on interior faults. To detect all area point faults, program all points as perimeter points in the area to which this output is assigned.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide Outputs > Part On Fault

Silent Alarm Default: 0 Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

This output activates when a point assigned to the specified area and programmed for Silent Bell goes into alarm.

Use this output for invisible/silent bell 24-hour panic/hold up applications.

RPS Menu Location

Output Parameters > Area Wide Outputs > Silent Alarm

Gas Bell Default: A Selections:

 B5512: A, B or C, 0, 11-18, 21-28, 31-38, 41-48, 51-58

 B4512: A, B or C, 0, 11-18, 21-28, 31-38

This voltage output activates and provides 12 VDC output when a gas point assigned to this area goes into alarm.

IMPORTANT: To comply with SIA CP-01 False Alarm Reduction, set this parameter to a value other than 0 for each enabled area. Refer to SIA CP-01 Verification for more information.

The area-wide Gas alarm bell uses the time in Fire Bell Time and output cadence defined in Gas Pattern. This output activates according to the bell pattern and remains active until the bell time expires or is manually silenced.

Each area can be assigned a unique output number for each of the events listed in this section.

RPS Menu Location

Output Parameters > Area Wide Outputs > Gas Bell