Typical Low Wall Return
4 HVAC APPLICATIONS BY PROCESS AND CLASSIFICATION
4.9 ASEPTIC PROCESSING FACILITY
3474 3475
4.9.1 System Schematic (Sample) 3476
3477
3478 3479
4.9.2 System Design Considerations 3480
3481
Considerable background on the design of HVAC systems is covered in 3482
the ISPE Baseline Guide for Sterile Manufacturing Facilities.
3483
Eliminate contamination introduced through the air conditioning 3484
supply system by utilizing properly installed and integrity tested 3485
ceiling mounted terminal HEPA filters.
3486
Minimize infiltration of contamination from uncontrolled areas by 3487
the use of room pressure differentials and airlocks between air 3488
classes.
3489
Continuous room pressure monitoring with alarms and recording 3490
devices that indicate out of spec conditions are recommended.
3491
Consider automatic pressure controls to keep the spaces within 3492
specified pressure limits where process exhausts change, or where 3493
door and hatch are frequently opened or door seal integrity varies.
3494
Dehumidification and post cooling coils should be considered for low 3495
humidity room control.
3496
A dedicated air handling system is recommended, serving only the 3497
aseptic area and remaining operational for required pressure control 3498
redundancy (parallel fans or fan walls) Consider utilizing standby 3504
electric power generating systems to maintain fans and design 3505
pressure differentials in the event of local power failures.
3506
The air handling system should be of the constant volume terminal 3507
reheat type utilizing industrial grade equipment.
3508
Ductwork should be designed per SMACNA standards but in no case 3509
should it be constructed for less than 4" water gauge duct static 3510
pressure and seal Class "A".
3511
Ductwork should be galvanized steel except where exposed (to a 3512
minimum extent) in production areas or subject to moisture, in which 3513
case it should be a minimum 304 stainless steel with cleanable 3514
finish. Cleaning materials used in the room should be considered.
3515
monitor PAO (aerosol) challenge materials upstream on the non-3527
aseptic side of the HEPA diffusers are suggested for filter 3528
integrity testing.
3529
Air supplied through ceiling mounted terminal HEPA filters should be 3530
life. Recirculation HEPA/fan units mounted below the ceiling are not 3534
recommended as they require service within the aseptic area, do not 3535
normally utilize low returns, and lack adequate pre-filtration.
3536
The return air openings in the aseptic area should be located near 3537
the floor, preferably on at least two (2) walls and along the long 3538
dimensions of the room to ensure maximum uniformity of airflow. More 3539
return openings are better than too few.
3540
Differential air pressure should be employed to minimize 3541
infiltration of contaminants from outside the controlled area. The 3542
aseptic area should be designed for a positive pressure with all 3543
doors closed in relation to less clean adjacent areas outside the 3544
controlled area (refer to latest issue of Federal Standard 209).
positive pressure relative to the outside and uncontrolled areas.
3548
Differential pressures are measured ACROSS airlocks (see the ISPE 3549
Baseline Guides for Sterile and Biopharm Facilities.) 3550
leading to this room are to be maintained successively less positive 3555
down to the zero reference level of uncontrolled areas (the general 3556
building). Only high-pressure Grade 7airlocks that have HEPA 3557
filtered supply air may have pressures higher than the aseptic 3558
filling room. A control range should be established for each room 3559
pressure level such that the pressure can float within the range and 3560
still satisfy the specified differentials.
3561
A remotely operated or automatic damper may be provided in the 3562
return air duct from each room as a means of obtaining and setting 3563
the established pressure differentials. Simple facilities may be 3564
successfully balanced using only manual dampers, especially if 3565
terminal HEPA filters do not load quickly.
3566
If manual / remotely operated dampers are used, the remote damper 3567
controls should be tamper-proof or concealed in a lockable cabinet 3568
accessible to authorized personnel only. A differential pressure 3569
gauge should be provided for each room adjacent to the remote damper 3570
controls.
3571
The manual/remote gauges and controls or automatic controls should 3572
be mounted in a common panel outside the controlled area. An audible 3573
alarm may be provided to indicate loss of area pressure control.
3574
This alarm may be manual reset type and equipped with a hard copy 3575
printout that indicates the out-of-range alarm.
3576
Unidirectional airflow serves as a barrier between product and 3577
microbial and particulate contamination generated by the equipment 3578
and personnel within the aseptic area. Where possible, terminal HEPA 3579
filters should be located directly over the exposed product, 3580
components and equipment that are not protected by UFH.
3581
When the central system air conditioning air quantity required to 3582
maintain room conditions is not sufficient to provide protection 3583
temperature. The engineer should consider the heat generated from 3589
the local recirculating system fan motor. This particular oversight 3590
is quite common and can lead to serious temperature stratification 3591
and overheating in the aseptic area.
3592
Airflow patterns within the work space may be uniform with minimum 3593
turbulence. Ambient air may not aspirate into the work areas along 3594
the perimeter of the unidirectional airflow barrier. The heights and 3595
filter area should deliver Class 100 air at a velocity of 90 feet 3596
(27.5 meters) per minute, with uniformity within plus or minus 20%, 3597
measured at the filter face. Velocity at the work height should also 3598
be measured. The optimal filter face velocity should be determined 3599
during qualification of the UFH using airflow visualization (―smoke 3600
testing‖). See the ISPE Sterile Baseline Guide.
3601
Room temperatures should be controlled by maintaining constant 3602
airflow and modulating a heating coil. Systems in which varying flow 3603
is used as a means of controlling room temperatures are unacceptable 3604
because of their adverse effects on room pressures.
3605
Where low relative humidity is required, special attention may be 3606
given to sealing the return duct systems to prevent inward air 3607
leakage from uncontrolled areas and resultant high humidity.
3608 3609
4.9.3 Aseptic Potent Compounds:
3610 3611
Processes should be contained in isolators, with dedicated HVAC for 3612
the containment enclosure.
3613
Where the process leaks into the room, protect the HVAC system and 3614
other rooms on the system from hazardous compounds by utilizing non-3615
recirculating primary air conditioning systems.
3616
The exhaust or return air ducts must be fitted with HEPA filters 3617
protected from physical damage with a pre-filter or equivalent.
3618
These filters should be located within the room where they can be 3619
serviced by properly gowned and protected personnel.
3620
If filters are located remote from the room where open processing 3621
occurs, they should be housed in a high containment bag-in/bag-out 3622
filter housing and identified as such. These filters contain the 3623
potentially hazardous compounds and minimize particulate "fall back"
3624
during fan failure.
3625
Gowning areas shall be supplied with air and maintained at a 3626
negative pressure relative to the controlled aseptic area and at a 3627
positive pressure relative to the uncontrolled areas. The gowning 3628
area should be separated from the aseptic filling room by a high 3629
pressure airlock.
3630
The de-gowning area must be separated from the aseptic filling room 3631
by a low pressure airlock. The de-gowning room shall be maintained 3632
negative relative to adjacent spaces on the uncontrolled side.
3633
Material entering the aseptic filling room must be transferred via a 3634
HEPA filtered, high pressure tunnel, box or sterilizer. Material 3635
leaving the aseptic filling room must be transferred via a low 3636
pressure tunnel or box.
3637 3638