• No results found

Backing Up the System File

This topic describes how to back up the system file to prevent permanent data loss due to the system failure. At the first office deployment or when the upgrade is complete, you need to back up the database file and the configuration file to restore the system in the case of the system failure.

3.1 Checking the Settings of Jumpers and DIP Switches

This topic describes how to check the settings of the environment supervision circuit (ESC) board, fan EMU jumpers and dual-in-line package (DIP) switches so that the settings conform to the actual application.

3.1.1 Checking the Settings of DIP Switches and Jumpers of Environment Monitoring Boards

This topic describes how to check the settings of the jumpers on the ESC board and the dual-in-line package (DIP) switches. This ensures that the settings conform to the actual application.

Prerequisite

The UA5000 must be disconnected from the power supply.

Jumpers and DIP Switches of H303ESC

The H303ESC board is located on the right side of the environment monitoring unit (EMU).

The H303ESC board provides six jumpers, namely the S1, S2, S3, S8, S10, and S11, and two DIP switches S6 and S7. The S5 is the shielding switch of the board alarm buzzer, which is enabled by default, as shown in Figure 3-1.

Figure 3-1 Layout of jumpers on the H303ESC board and DIP switches

H303ESC

S11

D1 S5

ON OFF

S6

S1 S2 S10 S3 S81 2 3 12345678

ON OFF

S7

1234

Jumpers S1, S2, S3, S8 and S10 are used to set the type of the serial port. Table 3-1 provides their meanings and settings.

Table 3-1 Meanings and settings of the H303ESC S1, S2, S3, S8, and S10

Jumper Settings Meanings Default Settings

S1 1-2 connected The serial port SIO1 is

RS-232.

2-3 connected

Jumper Settings Meanings Default Settings 2-3 connected The serial port SIO1 is

RS-422.

S2 1-2 connected The serial port SIO2 is

RS-232.

2-3 connected

2-3 connected The serial port SIO2 is RS-422.

S3, S8, and S10

1-2 of S3, S8, and S10 connected

The serial port SIO3 is RS-232.

1-2 of all jumpers connected 2-3 of S2 connected; 1-2 of

S8 and S10 connected

The serial port SIO3 is RS-422.

2-3 of S8 and S10 connected, S3 connected unlimited

The serial port SIO3 is RS-485.

S11 is used to check whether the running LED on the front panel is valid. Table 3-2 provides the meanings and settings of S11.

Table 3-2 Meanings and settings of the H303ESC S11

Jumper Settings Meanings Default

Settings S11 1-2 connected The running LED on the board

is valid.

1-2 connected

2-3 connected The running LED on the board is invalid.

DIP switch S6 is used to set the type of external analog sensors. Table 3-3 provides the meanings and settings of S6.

Table 3-3 Meanings and settings of the H303ESC S6

DIP Switch Settings Meanings Default

Settings S6-1 to S6-6 ON The external analog sensor is of the

current type.

ON

OFF The external analog sensor is of the voltage type.

S6-7 to S6-8 Reserved -

-DIP switch S7 is used to set the reporting mode and ratio. Table 3-4 provides the meanings and settings of S7.

Table 3-4 Meanings and settings of the H303ESC S7

DIP Switch Settings Meanings Default

Settings

S7-1 ON The H303ESC board is used in the

access network.

ON

OFF The H303ESC board is used in the Local Exchange.

S7-2 ON The H303ESC board uses one serial

port for reporting.

ON

OFF The H303ESC board uses two serial ports for reporting.

S7-3 Reserved - ON

S7-4 ON The reporting ratio of the serial port is 19200 bit/s.

ON

OFF The reporting ratio of the serial port is 9600 bit/s.

Jumpers and DIP Switches of H304ESC

The H304ESC board provides two DIP switches, S2 and S3, and five jumpers S4-S8. The S9 is the shielding switch for the alarm buzzer of the board, which is enabled by default. Figure 3-2 shows the layout of the jumpers and DIP switches on the H304ESC board.

Figure 3-2 Layout of the jumpers and DIP switches on the H304ESC board

1 2 3 S 4S 5 S 6 S 8S 7

O N O F F S 2

1234

H3 0 4 E S C

D 6 S 9

O N S 3 O F F

12345678

Jumpers S4-S8 are used to set the serial port type. Table 3-5 provides the meanings and settings of S4-S8.

Table 3-5 Meanings and settings of the H304ESC S4-S8

Jumper Settings Meanings Default

Settings

S4 1-2 connected The serial port SIO1 is

RS-232.

1-2 connected

2-3 connected The serial port SIO1 is RS-422.

S5 1-2 connected The serial port SIO2 is

RS-232.

1-2 connected

2-3 connected The serial port SIO2 is RS-422.

S6-S8 2-3 of S7 connected; 1-2 of S6 and S8 connected

The serial port SIO3 is RS-232.

2-3 of S7 connected; 1-2 of S6 and S8 connected 2-3 of S7 and S8 connected; 1-2

of S6 connected

The serial port SIO3 is RS-422.

DIP switch S2 is used to set the type of external analog sensors. Table 3-6 provides the meanings and settings of S2.

Table 3-6 Meanings and settings of the H304ESC S2 DIP

Switch Settings Meanings Default Settings

S2-1 ON The external sensor of JTA1 is of the current type.

OFF

OFF The external sensor of JTA1 is of the voltage type.

S2-2 ON The external sensor of JTA2 is of the current type.

OFF

OFF The external sensor of JTA2 is of the voltage type.

S2-3 ON The external sensor of JTA3 is of the current type.

OFF

OFF The external sensor of JTA3 is of the voltage type.

S2-4 Reserved -

-DIP switch S3 is used to set the reporting mode and ratio. Table 3-7 provides the meanings and settings of S3.

Table 3-7 Meanings and settings of the H304ESC S3

DIP Switch Settings Meanings Default

Settings S3-1 ON The H304ESC board is used in the access

network.

ON

OFF The H304ESC board is used on the Local Exchange.

S3-2 ON The H304ESC board uses one serial port for reporting.

OFF

OFF The H304ESC board uses two serial ports for reporting.

S3-3 Reserved -

-S3-4 ON The reporting rate of the serial port is 19200 bit/s.

OFF

OFF The reporting rate of the serial port is 9600 bit/s.

S3-5 to S3-8 Reserved -

-ESCM DIP Switch

The ESCM environment monitoring box provides a DIP switch S1. Figure 3-3 shows the layout of the DIP switch of the ESCM environment monitoring box.

Figure 3-3 Layout of DIP switch of ESCM environment monitoring box

ON

1 2 3 4 5 6 7 8

DIP switch Terminal block for environment parameter

COM1 COM2

Power socket LED

The available dialing digits of the DIP switch S1 are 8. Table 3-8 provides the meanings and settings of S1.

Table 3-8 Meanings and settings of the DIP switch S1 DIP

Switch Settings Meanings Default Settings

S1-1 to S1-5 unsupported - S1-1: ON

S1-2: ON S1-3: OFF S1-4: OFF S1-5: ON

S1-6 ON The reporting rate of

the serial port is 19200 bit/s

OFF

OFF The reporting rate of the serial port is 9600 bit/s.

S1-7 ON The external sensor

of JTA1 is of the current type.

ON

OFF The external sensor of JTA1 is of the voltage type.

S1-8 ON The external sensor

of JTA2 is of the current type.

ON

OFF The external sensor of JTA2 is of the voltage type.

Procedure

Step 1 Disconnect the cable connector if the ESC board is connected to the environment monitoring cable.

Step 2 Use the flathead screwdriver to unfasten the screws on the ESC board anticlockwise, as shown in (1) of Figure 3-4.

Figure 3-4 Removing and inserting the ESC board

Step 3 Hold the handlebar firmly on the front panel and pull out the ESC board from the PDU.

Step 4 Check whether the settings of the jumpers and DIP switches on the ESC board are practical in application. If not, proceed as follows:

l For H303ESC, refer to Table 3-1 and Table 3-2 to set the jumpers; refer to Table 3-3 and Table 3-4 to set the DIP switches.

l For H304ESC, refer to Table 3-5 to set the jumpers; refer to Table 3-6 and Table 3-7 to set the DIP switches.

l For ESCM, refer to Table 3-8 to set the DIP switches.

Step 5 Insert the ESC board into the PDU, as shown in (2) of Figure 3-4.

Step 6 Use the flathead screwdriver to fasten the screws clockwise on the ESC panel, insert the cable connector, and resume the monitoring cable connection of the ESC board.

----End

3.1.2 Checking the DIP Settings on the Monitoring Board of the Fan

This topic describes how to check the DIP settings on monitoring board of the fan. This ensures that the settings conform to the actual application.

Context

There are two types of fan monitoring boards: FCBA and FCBB, which are used as follows:

l The FCBA board is used in the rear access fan tray.

l The FCBB board is used in the front access fan tray.

DIP Switch Description

Figure 3-5 shows the layout of the DIP switches on the FCBA board. The DIP switches in the layout adopt the default settings.

Figure 3-5 Layout of the DIP switches on the FCBA board

1 2 3 4 5 6 7 8

ON OFF

SW101 ON

OFF1 2 3 4

SW102 H531FCBA

Figure 3-6 shows the layout of the DIP switches on the H801FCBB board, and Figure 3-6 shows the layout of the DIP switches on the H511FCBB board. The DIP switches in the layout adopt the default settings.

Figure 3-6 Layout of the DIP switches on the H801FCBB board

H801FCBB

ON

5 6 7 81 2 3 4

SW2

Figure 3-7 Layout of the DIP switches on the H511FCBB board

H511FCBB

ON OFF SW101

12345678 SW201

1234 ON

OFF

NOTE

The following table considers the H801FCBB board as an example to describe the meanings of the DIP switches, and the relation between the DIP switch, sub-node, fan quantity, and fan speed adjustment mode.

Table 3-9 lists the DIP switches on the H801FCBB board.

Table 3-9 Description of the DIP switches on the H801FCBB board

DIP Description Defaults

SW2-1 Set the mapping sub-node addresses of data configuration.

l ON corresponds to address bit 0.

l OFF corresponds to address bit 1.

ON

SW2-2 OFF

SW2-3 OFF

SW2-4 ON indicates that the baud rate of the communication between the fan tray and the control board is 19200 bit/s.

OFF

OFF indicates that the baud rate of the communication between the fan tray and the control board is 9600 bit/s.

OFF

SW2-5 Set the number of fans. OFF

SW2-6 ON

SW2-7 Set the speed adjustment modes of fans. OFF

SW2-8 ON

Table 3-10 provides the relation between the DIP switches and the sub-node addresses.

Table 3-10 Relation between the DIP switches and the sub-node addresses

SW2-3 SW2-2 SW2-1 Sub-Node Addresses

ON ON ON 000 (0)

ON ON OFF 001 (1)

ON OFF ON 002 (2)

ON OFF OFF 003 (3)

OFF ON ON 004 (4)

OFF ON OFF 005 (5)

OFF OFF ON 006 (6)

OFF OFF OFF 007 (7)

Table 3-11 provides the relation between the settings of the DIP switches and the number of fans.

Table 3-11 Relation between the DIP switch settings and the fan quantity

SW2-6 SW2-5 Fan Quantity

ON ON 6

ON OFF 8

OFF ON 4

OFF OFF 10

Table 3-12 provides the relation between the settings of the DIP switches and the speed adjustment mode of the fans.

Table 3-12 Relation between the DIP switch settings and the speed adjustment mode

SW2-8 SW2-7 Speed Adjustment Mode Speed Adjustment

Scheme

ON ON Measure the temperature on the

air intake vent

Scheme 1

ON OFF Measure the temperature on the

air exhaust vent

Scheme 2

OFF ON Reserved Scheme 3

OFF OFF Stop the fan and measure the

temperature on the air intake vent

Scheme 4

Prerequisites

The device must be powered off.

Procedure

Step 1 Use a screwdriver to unfasten the screws anticlockwise on the front panel of the fan tray, as shown in (1) of Figure 3-8.

Figure 3-8 Removing/Inserting the fan tray

Step 2 Remove the fan tray from the service shelf, as shown in (2) of Figure 3-8.

Step 3 Check whether the DIP switch settings on the fan monitoring and control board are consistent with the actual application. If not, configure the DIP switches again according to Table 3-9.

Step 4 Insert the fan tray into the corresponding slot, as shown in (3) of Figure 3-8.

Step 5 Use the screwdriver to fasten the screws clockwise on the front panel of the fan tray, as shown in (4) of Figure 3-8.

----End

3.2 Powering On the Indoor Device

This topic describes how to power on the indoor device to ensure that each board is supplied with power in the normal state.

Prerequisite

l The installation check and the power-on check must be performed on the device.

l All the input power and the output control switches of the DC PDU must be turned off.

Procedure

Step 1 Turn on the input power of the DC PDU.

Step 2 Turn on the output control switches of the DC PDU.

----End

Result

The LED of the control board blinks 1s on and 1s off repeatedly.

3.3 Powering On the Outdoor Device

This topic describes how to power on the outdoor device to ensure that each board is supplied with power in the normal state.

Prerequisite

l The installation check and the power-on check must be performed on the device.

l The power switch of the lightning arrester, the input/output switches of the GEPS4860, and the power switch of the heating panel must be turned off.

Procedure

Step 1 Turn off the AC power input switch to power on the lightning arrester.

Step 2 Turn off the MCB "AC POWER" to power on the GEPS4860.

Step 3 When the device temperature is lower than -25°C, turn on the miniature circuit breaker (MCB) of the heating panel to heat the device components until the device temperature is higher than -25°C. When the device temperature is higher than -25°C, skip this step.

NOTE

When the device starts at the temperature lower than -25°C, use the heating panel to heat all the components to -25°C above, and then the device can be powered on.

Step 4 Turn on the AC input MCB on the GEPS4860 (set the MCB upward). In the normal state, after a short delay, the RUN LEDs on the front panels of all the rectifier units are green after the rectifiers units are started. The RUN LED on the monitoring unit blinks slowly in green, and the ALM LED is on.

Step 5 Turn on all the load MCBs on the GEPS4860 (set the MCBs upward). In the normal state, the ALM LED on the front panel of the monitoring unit is off.

Step 6 Turn on (set the switch upward) the power switch on the GEPS4860 to supply power for the heat exchanger.

Step 7 Turn on (set the MCB upward) the MCB "BATT" on the GEPS4860 to supply power for batteries.

----End

Result

The RUN LED on the control board blinks 1s on and 1s off repeatedly.

3.4 Commissioning the Power System

This topic describes how to commission the reliability of the power supply system so that the system can supply the power to the device in the normal state.

3.4.1 Checking the Power Supply of DC PDU

This topic describes how to check whether each power input which supports mutual backup can supply power to the cabinet independently through the two or four power inputs.

Prerequisite

The two or four power inputs of the DC PDU supply power to the cabinet at the same time

Procedure

l Please implement the following steps when the two independent power supplies works in the normal state for the cabinet:

1. Disconnect power input A of the DC PDU and check the power supply of the cabinet.

2. Restore the power supply of power input A to the cabinet.

3. Disconnect power input B of the DC PDU and check the power supply of the cabinet.

4. Restore the power supply of power input B to the cabinet.

l When the four power inputs supply power to the cabinet in the normal state, usually adopt the mutual backup. That is, A and B mutually backup for each other, C and D mutually backup for each other, please implement the following steps:

1. Disconnect the power supply of power input A and C of the DC PDU and check the power supply of the cabinet.

2. Restore the power supply of power input A and C to the cabinet.

3. Disconnect power input B and D of the DC PDU and check the power supply of the cabinet.

4. Restore the power supply of power input B and D to the cabinet.

----End

Result

After disconnecting the backup power supply of any power input, the power supply and the service of the device board stay unaffected.

3.4.2 Checking the Power Supply of AC Power Module

This topic describes how to check whether other rectifier units can supply power to the cabinet in the normal state when the rectifier unit of the AC power is configured redundantly and one rectifier unit is faulty.

Prerequisite

The AC mode is used in the cabinet for power supply.

Procedure

Step 1 Remove a rectifier unit and check the power supply of the cabinet.

Step 2 Insert the rectifier unit back into the cabinet.

NOTE

Repeat step 1 and step 2 to verify one by one whether other redundant rectifier units are normal.

----End

Result

After removing any rectifier unit, the power supply and the service of the device board stay unaffected.

3.4.3 Configuring the Battery and Checking the Power Supply of the Battery

This topic describes how to configure the battery and verify whether the backup power supplied by the battery to the AC power system is in the normal state.

Prerequisite

The cabinet must adopt the AC power supply and must be configured with the battery.

Context

l Currently, the encapsulated valve regulated lead acid (VRLA) batteries used in the communication industry are all produced in full loading state, that is, the battery has been charged with electricity fully.

l Based on the battery features, automatic discharge will occur due to chemical reaction during the delivery and storage process. In this case, the battery capacity and the open circuit voltage decrease. We refer to this phenomenon as the automatic charge of the battery.

In a certain period, if you use appropriate methods, the voltage and the capacity of the battery can be restored completely.

l To make up the automatic discharge during the idle period, you need to perform the supplementary charge for the battery in long idleness periodically. For this type of situation, refer to "Operation Guide on Battery Supplementary Charge" to complete the

supplementary charge of the battery first, and then perform the following commissioning procedures.

Procedure

Step 1 In global config mode, run the emu add command to add the EMU of the power system.

Step 2 In global config mode, run the display emu command to query whether the status of the power system shows normal.

Step 3 Run the interface emu command to enter the EMU mode to configure the battery parameters.

CAUTION

The battery capacity parameters corresponding with different cabinets are different. You need to configure in correct way. Otherwise, you may damage the battery.

Step 4 In the corresponding power mode, run the power battery command to configure the battery parameters.

Table 3-13 lists the battery capacity of the different cabinets in the UA5000.

Table 3-13 Battery capacity of different cabinets

Cabinet Type Battery Capacity

ONU-F01E200 (Outdoor) 50 AH

ONU-F01E400 (Outdoor) 75 AH

ONU-F01D200 (Outdoor) 80 AH

ONU-F01D500 (Outdoor) 150 AH/184 AH

ONU-F01D1000 (Outdoor) 184 AH

ONU-F02A (Indoor) 100 AH

Step 5 In the corresponding power mode, run the power battery-test command to configure the battery discharging parameters.

Step 6 In privilege mode, run the save command to save the related configuration. When the monitoring module and the UA5000 device communicate with each other in the normal state, the configured data take effect automatically.

Step 7 Disconnect the mains supply, and check whether the cabinet power system can switch to the battery supply mode.

Step 8 Restore the mains supply, and check whether the cabinet power system can switch to the mains

Step 8 Restore the mains supply, and check whether the cabinet power system can switch to the mains

Related documents