Control accessories
The manifold functions of the central controls GB-50ADA and AG-150A can be extended with the input and output modules PAC-YG. The modules are integrated into the M-Net bus sys- tem and require at least one M-Net indoor unit address per module.
During planning, it must be taken into account that the total of indoor units, Lossnay heat exchangers and PAC-YG mod- ules in one M-Net system may not exceed 50. Every PAC-YG module requires an uninterruptible 24 V DC power supply to be provided by the customer. For installation in dry surroundings (inside buildings).
• Recording of different counter types like current, gas, water or heat quantities is possible
• Recording of the counter readings of the impulse counters
• Recording of energy consumption and individual cost ac- counting in connection with a central control and the operat- ing software TG2000
• Counter readings are displayed in the web display of the GB-50A
PAC-YG60 MCA-J Pulse input module
• Automatic sending of e-mails containing the recorded data in connection with AG-150 or GB-50PRO possible (if applicable router as per ME specifications required).
• When leaving the target range, an alarm is activated in form of a potential-free contact
• In connection with a central control, there is the additional possibility to send an alarm e-mail when leaving the target
range (if applicable router as per ME specifications required) • Recording of temperature and humidity sensors
• 2 inputs per module, one is suitable for the direct connection of a PT100 temperature sensor.
• Possible signal inputs: 0 –10 V, 4 – 20 mA, 1– 5 V
• Recording of measured values for temperature and/or humidity
PAC-YG63 MCA-J Analogue input module
• Same functions as PAC-YG63MCA-J
• When leaving the target range, countermeasures will be initi- ated, e.g. switching on another indoor unit in the M-Net bus system
• M-Net interlock function, e.g. setting the temperature target value for the indoor unit depending on the external sensor (e.g. outside temperature)
PAC-YG63 MCA-J PRO
• Control of external systems such as lighting systems, jalou- sies, ventilation systems, external fans, pumps etc.
• Up to 6 outputs and 6 inputs per module
• External systems can be controlled (On/Off)
• The operating status of the external systems is recorded (on/ off, operation/alarm)
PAC-YG66 DCA-J Digital input/output module
• Same functions as PAC-YG66MCA-J • M-Net interlock function, e.g. starting of certain indoor units
by means of an external contact
PAC-YG66 DCA-J PRO
PAC-YG66MCA-J PAC-YG63MCA-J
PAC-YG60MCA-J
Module designation PAC-YG60MCA-J PAC-YG63MCA-J PAC-YG63 Pro PAC-YG66DCA-J PAC-YG66 Pro
Dimensions (mm) Height x Width x Length
120/200/45 120/200/45 120/200/45 120/200/45 120/200/45
CONTROL ACCESSORIES
Control accessories
LonWorks® interface
• Easy connection of City Multi systems to building control
technology via LonWorks® interface L-MAP02-E.
• One LonWorks® interface is required for 50 indoor units.
• For more detailed information on our LonWorks® interface,
please refer to the brochure „Controls and remotes“.
L-MAP02-E BACnet™ interface
• For control of up to 50 indoor units (up to 150 indoor units with PAY-YG50ECA expansion controllers). All functions of the indoor units can be controlled via the BACnet™ protocol.
All relevant system parameters such as operating status and mode are displayed.
BAC-HD150
Maintenance tool
• The easiest and most cost-effective way to monitor, maintain and operate City Multi systems is the maintenance tool by Mitsubishi Electric.
• All relevant system parameters and error messages can be displayed, saved or changed using the computer*.
• In combination with a modem, a remote data transmission is possible.
• The maintenance tool consists of an interface box, adapter and software programme; an USB cable is additionally re- quired. Plug form PC: USB type A. Plug form CMS-MNG-E: USB type B
* for Windows 2000 or Windows XP, minimum Celeron 1 GHz, minimum 512 MB RAM, available disk space 1 GB, USB port, serial port CMS-MNG-E*
Drainpump
ACCESSORIES
Designation Description
PCFY-P VKM-E Ceiling suspended units
Filter
Stopper Knob
Intake grille High-efficiency filter element
High-efficiency filter element as replacement for the standard air filter. High-efficiency and standard filters cannot be operated simultaneously.
PAC-SH88KF-E for PCFY-P40VKM-E
PAC-SH89KF-E for PCFY-P63VKM-E
PAC-SH90KF-E for PCFY-P100/125VKM-E
Drain pump
The drain pump is integrated in the unit and drains the condensate in an upwards direction. The delivery height is 600 mm.
PAC-SH83DM-E for PCFY-P40VKM-E
PAC-SH85DM-E for PCFY-P63-125VKM-E
Signal sender Signal receiver
Infrared remote control
The infrared remote control set consists of the infra- red remote control (transmitter), a wall holder and the receiving part which is inserted into the label on the bottom side of the housing.
PAR-SL94B-E for PCFY-P40-125VKM-E
PEFY-P VMH(S)-E/VMH-E-F Ceiling concealed ducted units
Drainpump
Drain pump
Drain pump for installation in the units.
PAC-KE04DM-F PEFY-P 40-250VMH(S)-E, PEFY-P80/140VMH-E-F
Long life filter
Long-life filter element
The filter frame PAC-KE TB-F is required when using the filter elements.
PAC-KE86LAF for PEFY-P40-63VMH-E
PAC-KE88LAF for PEFY-P71/80VMH-E, PEFY-P80VMH-E-F
PAC-KE89LAF for PEFY-P100-140VHM-E, PEFY-P140VMH-E-F
PAC-KE85LAF for PEFY-P200/250VMH(S)-E
Filter frame
Filter frame
The filter frame is required when using the long-life filters.
PAC-KE63TB-F for PEFY-P40-63VMH-E
PAC-KE80TB-F for PEFY-P71/80VMH-E, PEFY-P80VMH-E-F
PAC-KE140TB-F for PEFY-P100-140VHM-E, PEFY-P140VMH-E-F
PAC-KE250TB-F for PEFY-P200/250VMH(S)-E
PEFY-P VMA-E Ceiling concealed ducted units
Filter Box
Filter boxes
The filter boxes allow for removing the filters from the side or below even if a channel is connected to the suction side. The air filter included in the scope of delivery of the indoor unit is inserted into the filter box.
PAC-KE91TB-E for PEFY-P20-32VMA
PAC-KE92TB-E for PEFY-P40/50VMA
PAC-KE93TB-E for PEFY-P63-80VMA
PAC-KE94TB-E for PEFY-P100/125VMA
PAC-KE95TB-E for PEFY-P140VMA
Designation Description
PLFY-P-VBM-E 4-way ceiling cassettes
Panel Space Panel
Base grille
Allows for installation when only little free space is available in the ceiling. The required installation height is reduced by 40 mm.
PAC-SH48AS-E for PLFY-P32-140VBM-E
Indoor unit body Multi-functional casement
Outside air box incl. filter housing
Used to supply ceiling cassettes with outside air. The outside air volume can be up to 20 % of the nominal air volume. For installation between unit and grille, installation height 135 mm.
PAC-SH53TM-E for PLFY-P32-140VBM-E
High-efficiency filter element
Plug (for directing airflow)
*for 4-way cassette units
High-efficiency filter element
High-efficiency filter element for use in outside air box PAC-SH53TM-E. The high-efficiency filter has a filter efficiency of 65 %, service life approx. 2,500 operating hours.
PAC-SH59KF-E for PLFY-P32-140VBM-E with outside air box
PAC-SH53TM-E
Shuttle Plate
Shutter plate
The shutter plates are installed in the air outlet opening of the indoor units, in order to close a maximum of 2 air outlets.
PAC-SH51SP-E for PLFY-P32-140VBM-E
*for 4-way cassette units
i-see sensor
corner panel i-see sensor
The i-see sensor measures the temperature in the floor area and, in connection with the automatic fan control, minimises temperature stratifications. Due to the better temperature distribution, the compres- sor running time and the energy consumption are reduced.
PAC-SA1ME-E for PLFY-P32-140VBM-E
Infrared receiver for integration into the grille The infrared receiver can be integrated into the grille. The PAR-LS97A remote control is required for operation.
PAR-SA9FA-E for PLFY-P32-140VBM-E
Filter lift panel
The filter can be lowered by up to 4 m by means of the remote control. Especially in high rooms, this enables an easy cleaning of the filter.
PLP-6BAJ for PLFY-P32-140VBM-E