Use Program 10-03 : ETU Setup to setup and confirm the Basic Configuration data for each ETU. When changing a defined terminal type, first set the type to 0 and then plug the new device in to have the system automatically define it or you may have to reseat the ETU.
The items highlighted in gray are read only and cannot be changed.
The item numbers indicated below are different when using PCPro/WebPro due to the window layout of the applications. Refer to the program in the PCPro/WebPro application to determine the correct item number.
Input Data
For CNF PKG Setup
For CCISoIP PKG Setup
Program 10 : System Configuration Setup
10-03 : ETU Setup
Level: IN
Physical Port Number 01~16
Item
No. Item Input Data Default
01 Logical Port Number 0~256 0
Physical Port Number 01~24
Item
No. Item Input Data Default
01 Logical Port Number
The start port number of a T1 line is displayed, and 24 logic ports are automatically assigned to a DTI (T1) line.
0~200 0
02 T1 Signal Format Selection 0 = D4 (12 Multi Frame) 1 = ESF (24 Multi Frame)
For MG 16 PKG Setup
04 Line Length Selection 0 = 0 feet ~ 133 feet
1 = 134 feet ~ 266 feet 2 = 267 feet ~ 399 feet 3 = 400 feet ~ 533 feet 4 = 534 feet ~ 655 feet
0
Physical Port Number 0
Item
No. Item Input Data Default
01 Logical Port Number 0~256 0
For ESI PKG Setup
Physical Port Number 01~16
Item
No. Item Input Data Default
01 Terminal Type (B1) 0 = Not set
1 = Multiline Terminal 2 = SLT Adapter 3 = -- Not Used -- 4 = -- Not Used -- 5 = -- Not Used -- 6 = PGD (Paging) 7 = PGD (Tone Ringer) 8 = PGD (Doorbox) 9 = PGD (ACI) 10 = DSS Console 11 = -- Not Used -- 0
02 Logical Port Number (B1) 0 = Not set
1 = Multiline Terminal 2 = SLT Adapter 3 = Not Used 4 = Not Used 5 = 2DCI Adapter 1~32 6 = PGD (Paging)
7 = PGD (for Tone Ringer) 1~4 or 1~8 8 = PGD (for Door Box) 1~4 or 1~8 9 = PGD (for Analog I/F) 1~8 or 1~96 10 = DSS
0
Item
For SLI PKG Setup
03 --- Not Used ---
04 Optional Installed Unit 1 0 = None 1 = APR Module 2 = APA Module 3 = ADA Module 4 = CTA/CTU Module
0
05 Optional Installed Unit 2 0 = None 1 = APR Module 2 = APA Module 3 = ADA Module 4 = CTA/CTU Module 0 B-Channel 2 Item
No. Item Input Data Default
06 Terminal Type (B2) 0 = Not set
6 = PGD (Paging) 7 = PGD (Tone Ringer) 8 = PGD (Door Box) 9 = PGD (ACI) 12 = APR 0
07 Logical Port Number (B2) PGD (Paging/Tone Ringer) = 1-PGmax PGD (for Door Box) = 1-DBmax PGD (Analog I/F) = 1-ACImax APR (for B2 mode) 193~256
Physical Port Number 01~08
Item
No. Item Input Data Default
01 Logical Port Number 0~256 0
02 --- Not Used --- Item
For COIU Unit Setup
For TLI PKG Setup
For DID PKG Setup
For OPX PKG Setup
Physical Port Number 01~08
Item
No. Item Input Data Default
01 Logical Port Number 0~200 0
Physical Port Number 01~02
Item
No. Item Input Data Default
01 Logical Port Number 0~200 0
Physical Port Number 01~04
Item
No. Item Input Data Default
01 Logical Port Number 0~200 0
Physical Port Number 01~08
Item
No. Item Input Data Default
For BRI PKG Setup
ISDN Line Number 01~08
Item
No Item Input Data Default
01 --- Not Used ---
02 Logical Port Number
The starting port number of a BRI line is displayed. Two logic ports are automatically assigned to a BRI line.
0 = Net Set
1 = For T-Bus (1~200) 2 = For S-Bus (1~256)
0
03 Connection Type 0 = Point-to-Multipoint (not
available for Networking) 1 = Point-to-Point
0
04 Layer 3 Timer Type
Each timer value of Layer 3 is set up for every type using Program 81-06 (T-Bus)
1~5 1
05 CLIP Information Announcement
Based on this setting, the system includes a Presentation Allowed (1) or Presentation Restricted (0) in the Setup message to allow or deny the Calling Party Number. Program 15-01-04 must also be set to 1 if this option is enabled.
0 = Disable 1 = Enable
1
06 --- Not Used ---
07 --- Not Used ---
08 Dial Sending Mode 0 = Enblock Sending
1 = Overlap Sending
1 09 Dial Information Element
(Only when Dialing Sending Mode (10-03-08) is set for 1 (Overlap Sending)
0 = Keypad Facility 1 = Called Party Number
10 --- Not Used ---
11 --- Not Used ---
12 --- Not Used ---
13 --- Not Used ---
For PRI PKG Setup
ISDN Line Number 01~24
Item
No. Item Input Data Default
01 --- Not Used ---
02 Logical Port Number
The start port number of a PRI line is displayed, and 24 logic ports are automatically assigned to a PRI line.
1 = for T-Bus 1~200 1
03 --- Not Used ---
04 Layer 3 Timer Type
Each timer value of Layer 3 is set up for each type in
Program 81-06 (T-Bus)
1~5 1
05 CLIP Information
Based on this setting, the system includes a Presentation Allowed (1) or Presentation Restricted (0) in the Setup message to allow or deny the Calling Party Number. Program 15-01-04 must also be set to 1 if this option is enabled. 0 = Disable 1 = Enable 1 06 Length of Cable 0 = 0 ~ 40m 1 = 41~ 80m 2 = 81~ 121m 3 = 122 ~ 162m 4 = 163 ~ 200m 0 07 --- Not Used ---
08 Dial Sending Mode 0 = Enblock Sending
1 = Overlap Sending
1 09 Dial Information Element
(Only when Dialing Sending Mode (10-03-08) is set for 1 (Overlap Sending)
0 = Keypad Facility 1 = Called Party Number
10 --- Not Used ---
11 --- Not Used ---
12 Short / Long-Haul 0 = Short-Haul
1 = Long-Haul
For DTI (T1) PKG Setup
13 Loss-Of-Signal Detection Limit In Short-Haul Mode: 0 = 0.91V 1 = 0.74V 2 = 0.59V 3 = 0.42V 4 = 0.32V 5 = 0.21V 6 = 0.16V 7 = 0.10V In Long-Haul Mode: 0 = 1.70V 1 = 0.84V 2 = 0.84V 3 = 0.45V 4 = 0.45V 5 = 0.20V 6 = 0.10V 7 = Not Defined 0 14 --- Not Used --- 21 Number of Ports
RequiresVersion 1500 or higher
0: Auto 1: 4 Ports 2: 8 Ports 3: 12 Ports 4: 16 Ports 5: 20 Ports 0
Physical Port Number 01~24
Item
No. Item Input Data Default
01 Logical Port Number
The start port number of a T1 line is displayed, and 24 logic ports are automatically assigned to a DTI (T1) line.
0~200 0
02 T1 Signal Format Selection 0 = D4 (12 Multi Frame) 1 = ESF (24 Multi Frame)
1
Item
For VMS/FMS PKG Setup
Conditions
When changing a defined terminal type, first set the type to 0 and then plug the new device in to have the system automatically define it or redefine the type manually.
The system must have an ETU installed to view/change the options for that type of ETU.