E3 is Reset from Trip

After an E3 Overload Relay is returned to normal following a trip reset, operation of Out A and Out B is determined by the state of the firmware latch. The output state matrix below details this.

Table 64 - Output State Matrix for Output Setup Parameters

Out X Output State

Commanded Output State

Prior to Trip PR FltState Setting PR FltValueSetting with Active Trip Last Commanded During Trip

Following Trip Reset (before any new command) Series A Series B & Later Open 0 = Go to FltValue 0 = Open Open Open Open Open

Close Closed Open -none - Open Open 1 = Closed Closed Open Open Closed

Close Closed Closed -none - Open Closed 1 = Ignore Fault — As Commanded

Close 0 = Go to FltValue 0 = Open Open Open Open Open

Close Closed Open -none - Closed Open 1 = Closed Closed Open Open Closed

Close Closed Closed -none - Closed Closed 1 = Ignore Fault — As Commanded

Table 65 - Output A Parameters Detail

OUTA PR FLTSTATE

This parameter, in conjunction with Parameter 66, defines how Output A will respond when a trip occurs. When set to “1”, Output A will continue to operate as commanded via the network. When set to “0”, Output A will open or close as determined by the setting of Parameter 66.

Parameter Number 65

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-1-113

Group DeviceNet I/O

Units —

Minimum Value 0 = Go to FltValue (#66) Maximum Value 1 = Ignore Fault

Default Value 0

OUTA PR FLTVALUE

This parameter determines the state that Output A assumes when a trip occurs and Parameter 65 is set to “0”.

Parameter Number 66

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-1-114

Group DeviceNet I/O

Units —

Minimum Value 0 = Open

Maximum Value 1 = Closed

Default Value 0

OUTA DN FLTSTATE

This parameter, in conjunction with Parameter 68, defines how Output A will respond when a DeviceNet network fault occurs. When set to “1”, Output A will hold the state prior to trip occurrence. When set to “0”, Output A will open or close as determined by the setting of Parameter 68.

Output A can be configured to go to a desired state in the event of a DeviceNet network fault independent from enabling CommFault in Parameter 24, Trip Enable.

Parameter Number 67

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-1-5

Group DeviceNet I/O

Units —

Minimum Value 0 = Go to FltValue (#68) Maximum Value 1 = Hold Last State

Default Value 0

OUTA DN FLTVALUE

This parameter determines the state that Output A assumes when a DeviceNet network fault occurs and Parameter 67 is set to “0”.

Parameter Number 68

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-1-6

Group DeviceNet I/O

Units —

Minimum Value 0 = Open

Maximum Value 1 = Closed

Default Value 0

OUTA DN IDLSTATE

This parameter, in conjunction with Parameter 70, defines how Output A will respond when the DeviceNet network is idle. When set to “1”, Output A will hold the state prior to trip occurrence. When set to “0”, Output A will open or close as determined by the setting in Parameter 70.

The Dn Flt parameters supersede the Dn Idl parameters.

Parameter Number 69

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-1-7

Group DeviceNet I/O

Units —

Minimum Value 0 = Go to IdlValue (#70) Maximum Value 1 = Hold Last State

Table 66 - Output B Parameters Detail — E3 Plus

OUTA DN IDLVALUE

This parameter determines the state that Output A assumes when the network is idle and Parameter 69 is set to “0”.

Parameter Number 70

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-1-8

Group Advanced Setup

Units —

Minimum Value 0 = Open

Maximum Value 1 = Closed

Default Value 0

OUTB PR FLTSTATE

This parameter, in conjunction with Parameter 72, defines how Output B will respond when a trip occurs. When set to “1”, Output B will continue to operate as commanded via the network. When set to “0”, Output B will open or close as determined by the setting in Parameter 72.

Parameter Number 71

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-2-113

Group DeviceNet I/O

Units —

Minimum Value 0 = Go to FltValue (#72) Maximum Value 1 = Ignore Fault

Default Value 0

OUTB PR FLTVALUE

This parameter determines the state that Output B assumes when a trip occurs and Parameter 71 is set to “0”.

Parameter Number 72

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-2-114

Group DeviceNet I/O

Units —

Minimum Value 0 = Open

Maximum Value 1 = Closed

Default Value 0

OUTB DN FLTSTATE

This parameter, in conjunction with Parameter 74, defines how Output B will respond when a DeviceNet network fault occurs. When set to “1”, Output B will hold the state prior to trip occurrence. When set to “0”, Output B will open or close as determined by the setting in Parameter 74.

Output B can be configured to go to a desired state in the event of a DeviceNet network fault independent from enabling CommFault in Parameter 24, Trip Enable.

Parameter Number 73

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-2-5

Group DeviceNet I/O

Units —

Minimum Value 0 = Go to FltValue (#74) Maximum Value 1 = Hold Last State

Default Value 0

OUTB DN FLTVALUE

This parameter determines the state that Output B assumes when a comm fault occurs and Parameter 73 is set to “0”.

Parameter Number 74

Access Rule Get/Set

Data Type BOOL

Object Mapping 0x09-2-6

Group DeviceNet I/O

Units —

Minimum Value 0 = Open

Maximum Value 1 = Closed

DeviceLogix Group — E3 Plus