Power Setup Group PW Trip Enable

This parameter allows the installer to enable or disable power based trip functions separately.

1 = Trip 0 = No TrIp

Parameter Number 225 Access Rule Get/Set Data Type UINT Object Mapping 0Fhex-E1-01 Group Power Setup

Units — Minimum Value — Maximum Value — Default Value — Bit Function: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X Under Real Pwr X Over Real Pwr X Under Con kVAR X Over Con kVAR X Under Gen kVAR X Over Gen kVAR X Under Power kVA

X Over Power kVA

X Under PF Lagging X Over PF Lagging X Under PF Leading X Over PF Leading X Power Overflow PW Warn Enable

This parameter allows the installer to enable or disable power based warning functions separately.

1 = Warning 0 = No Warning

Parameter Number 226 Access Rule Get/Set Data Type UINT Object Mapping 0Fhex-E2-01 Group Power Setup

Units — Minimum Value — Maximum Value — Default Value — Bit Function: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X Under Real Pwr X Over Real Pwr X Under Con kVAR X Over Con kVAR X Under Gen kVAR X Over Gen kVAR X Under Power kVA

X Over Power kVA

X Under PF Lagging

X Over PF Lagging

X Under PF Leading

X Over PF Leading

UW Inhibit Time

This parameter defines the amount of time for which an under real power (kW) detection is inhibited during a motor starting sequence.

Parameter Number 241 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-F1-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

UW Trip Delay

This parameter allows the installer to program a time duration for which an under real power (kW) condition must exist prior to the device tripping.

Parameter Number 242 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-F2-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

UW Trip Level

This parameter sets the under real power (kW) trip level.

Parameter Number 243 Access Rule Get/Set Data Type INT Object Mapping 0Fhex-F3-01 Group Power Setup

Units kW

Minimum Value 0 Maximum Value 32767 Default Value —

UV Warn Level

This parameter sets the under real power (kW) warning level.

Parameter Number 244 Access Rule Get/Set Data Type INT Object Mapping 0Fhex-F4-01 Group Power Setup

Units kW

Minimum Value 0 Maximum Value 32767 Default Value —

OW Inhibit Time

This parameter defines the amount of time for which an over real power (kW) detection is inhibited during a motor starting sequence.

Parameter Number 245 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-F5-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

OW Trip Delay

This parameter allows the installer to program a time duration for which an over real power (kW) condition must exist prior to the device tripping.

Parameter Number 246 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-F6-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

OW Trip Level

This parameter sets the over real power (kW) trip level.

Parameter Number 247 Access Rule Get/Set Data Type INT Object Mapping 0Fhex-F7-01 Group Power Setup

Units kW

Minimum Value 0 Maximum Value 32767 Default Value —

OW Warn Level

This parameter sets the over real power (kW) warning level.

Parameter Number 248 Access Rule Get/Set Data Type INT Object Mapping 0Fhex-F8-01 Group Power Setup

Units kW

Minimum Value 0 Maximum Value 32767 Default Value —

UVARC Inhibit Time

This parameter defines the amount of time for which an under reactive power (kVAR) consumed detection is inhibited during a motor starting sequence.

Parameter Number 249 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-F9-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

UVARC Trip Delay

This parameter allows the installer to program a time duration for which an under reactive power (kVAR) consumed condition must exist prior to the device tripping.

Parameter Number 250 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-FA-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

UVARC Trip Level

This parameter sets the under reactive power (kVAR) consumed trip level.

Parameter Number 251 Access Rule Get/Set Data Type INT Object Mapping 0Fhex-FB-01 Group Power Setup

Units kVAR

Minimum Value 0 Maximum Value 32767 Default Value —

UVARC Warn Level

This parameter sets the under reactive power (kVAR) consumed warning level.

Parameter Number 252 Access Rule Get/Set Data Type INT Object Mapping 0Fhex-FC-01 Group Power Setup

Units kVAR

Minimum Value 0 Maximum Value 32767 Default Value —

OVARC Inhibit Time

This parameter defines the amount of time for which an over reactive power (kVAR) consumed detection is inhibited during a motor starting sequence.

Parameter Number 253 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-FD-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

OVARC Trip Delay

This parameter allows the installer to program a time duration for which an over reactive power (kVAR) consumed condition must exist prior to the device tripping.

Parameter Number 254 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-FE-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

OVARC Trip Level

This parameter sets the over reactive power (kVAR) consumed trip level.

Parameter Number 255 Access Rule Get/Set Data Type INT Object Mapping 0Fhex-FF-01 Group Power Setup

Units kVAR

Minimum Value 0 Maximum Value 32767 Default Value —

OVARC Warn Level

This parameter sets the over reactive power (kVAR) consumed warning level.

Parameter Number 256 Access Rule Get/Set Data Type INT

Object Mapping 0Fhex-100-01 Group Power Setup

Units kVAR

Minimum Value 0 Maximum Value 32767 Default Value —

UVARG Inhibit Time

This parameter defines the amount of time for which an under reactive power (kVAR) generated detection is inhibited during a motor starting sequence.

Parameter Number 257 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-101-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

UVARG Trip Delay

This parameter allows the installer to program a time duration for which an under reactive power (kVAR) generated condition must exist prior to the device tripping.

Parameter Number 258 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-102-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

UVARG Trip Level

This parameter sets the under reactive power (kVAR) generated trip level.

Parameter Number 259 Access Rule Get/Set Data Type INT

Object Mapping 0Fhex-103-01 Group Power Setup

Units kVAR

Minimum Value -32768 Maximum Value 0 Default Value —

UVARG Warn Level

This parameter sets the under reactive power (kVAR) generated warning level.

Parameter Number 260 Access Rule Get/Set Data Type INT

Object Mapping 0Fhex-104-01 Group Power Setup

Units kVAR

Minimum Value -32768 Maximum Value 0 Default Value —

OVARG Inhibit Time

This parameter defines the amount of time for which an over reactive power (kVAR) generated detection is inhibited during a motor starting sequence.

Parameter Number 261 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-105-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

OVARG Trip Delay

This parameter allows the installer to program a time duration for which an over reactive power (kVAR) generated condition must exist prior to the device tripping.

Parameter Number 262 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-106-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

OVARG Trip Level

This parameter sets the over reactive power (kVAR) generated trip level.

Parameter Number 263 Access Rule Get/Set Data Type INT

Object Mapping 0Fhex-107-01 Group Power Setup

Units kVAR

Minimum Value -32768 Maximum Value 0 Default Value —

OVARG Warn Level

This parameter sets the over reactive power (kVAR) generated warning level.

Parameter Number 264 Access Rule Get/Set Data Type INT

Object Mapping 0Fhex-108-01 Group Power Setup

Units kVAR

Minimum Value -32768 Maximum Value 0 Default Value —

UVA Inhibit Time

This parameter defines the amount of time for which an under apparent power (kVA) detection is inhibited during a motor starting sequence.

Parameter Number 265 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-109-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

UVA Trip Delay

This parameter allows the installer to program a time duration for which an under apparent power (kVA) condition must exist prior to the device tripping.

Parameter Number 266 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-10A-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

UVA Trip Level

This parameter sets the under apparent power (kVA) trip level.

Parameter Number 267 Access Rule Get/Set Data Type INT

Object Mapping 0Fhex-10B-01 Group Power Setup

Units kVA

Minimum Value 0 Maximum Value 32767 Default Value —

UVA Warn Level

This parameter sets the under apparent power (kVA) warning level.

Parameter Number 268 Access Rule Get/Set Data Type INT

Object Mapping 0Fhex-10C-01 Group Power Setup

Units kVA

Minimum Value 0 Maximum Value 32767 Default Value —

OVA Inhibit Time

This parameter defines the amount of time for which an over apparent power (kVA) detection is inhibited during a motor starting sequence.

Parameter Number 269 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-10D-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

OVA Trip Delay

This parameter allows the installer to program a time duration for which an over apparent power (kVA) condition must exist prior to the device tripping.

Parameter Number 270 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-10E-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

OVA Trip Level

This parameter sets the over apparent power (kVA) trip level.

Parameter Number 271 Access Rule Get/Set Data Type INT

Object Mapping 0Fhex-10F-01 Group Power Setup

Units kVA

Minimum Value 0 Maximum Value 32767 Default Value —

OVA Warn Level

This parameter sets the over apparent power (kVA) warning level.

Parameter Number 272 Access Rule Get/Set Data Type INT

Object Mapping 0Fhex-110-01 Group Power Setup

Units kVA

Minimum Value 0 Maximum Value 32767 Default Value —

UPFLG Inhibit Time

This parameter defines the amount of time for which an under power factor lagging detection is inhibited during a motor starting sequence.

Parameter Number 273 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-111-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

UPFLG Trip Delay

This parameter allows the installer to program a time duration for which an under power factor lagging condition must exist prior to the device tripping.

Parameter Number 274 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-112-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

UPFLG Trip Level

This parameter sets the under power factor lagging trip level.

Parameter Number 275 Access Rule Get/Set Data Type SINT Object Mapping 0Fhex-113-01 Group Power Setup

Units %

Minimum Value -100 Maximum Value 0 Default Value -90

UPFLG Warn Level

This parameter sets the under power factor lagging warning level.

Parameter Number 276 Access Rule Get/Set Data Type SINT Object Mapping 0Fhex-114-01 Group Power Setup

Units %

Minimum Value -100 Maximum Value 0 Default Value -95

OPFLG Inhibit Time

This parameter defines the amount of time for which an over power factor lagging detection is inhibited during a motor starting sequence.

Parameter Number 277 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-115-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

OPFLG Trip Delay

This parameter allows the installer to program a time duration for which an over power factor lagging condition must exist prior to the device tripping.

Parameter Number 278 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-116-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

OPFLG Trip Level

This parameter sets the over power factor lagging trip level.

Parameter Number 279 Access Rule Get/Set Data Type SINT Object Mapping 0Fhex-117-01 Group Power Setup

Units %

Minimum Value -100 Maximum Value 0 Default Value -95

OPFLG Warn Level

This parameter sets the over power factor lagging warning level.

Parameter Number 280 Access Rule Get/Set Data Type SINT Object Mapping 0Fhex-118-01 Group Power Setup

Units %

Minimum Value -100 Maximum Value 0 Default Value -90

UPFLD Inhibit Time

This parameter defines the amount of time for which an under power factor leading detection is inhibited during a motor starting sequence.

Parameter Number 281 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-119-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

UPFLD Trip Delay

This parameter allows the installer to program a time duration for which an under power factor leading condition must exist prior to the device tripping.

Parameter Number 282 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-11A-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

UPFLD Trip Level

This parameter sets the under power factor leading trip level.

Parameter Number 283 Access Rule Get/Set Data Type SINT Object Mapping 0Fhex-11B-01 Group Power Setup

Units %

Minimum Value 0 Maximum Value 100 Default Value 90

UPFLD Warn Level

This parameter sets the under power factor leading warning level.

Parameter Number 284 Access Rule Get/Set Data Type SINT Object Mapping 0Fhex-11C-01 Group Power Setup

Units %

Minimum Value 0 Maximum Value 100 Default Value 95

OPFLD Inhibit Time

This parameter defines the amount of time for which an over power factor leading detection is inhibited during a motor starting sequence.

Parameter Number 285 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-11D-01 Group Power Setup

Units Seconds

Minimum Value 0 Maximum Value 250 Default Value 10

OPFLD Trip Delay

This parameter allows the installer to program a time duration for which an over power factor leading condition must exist prior to the device tripping.

Parameter Number 286 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-11E-01 Group Power Setup

Units Seconds

Minimum Value 0.1 Maximum Value 25.0 Default Value 1.0

OPFLD Trip Level

This parameter sets the over power factor leading trip level.

Parameter Number 287 Access Rule Get/Set Data Type SINT Object Mapping 0Fhex-11F-01 Group Power Setup

Units %

Minimum Value 0 Maximum Value 100 Default Value 95

OPFLD Warn Level

This parameter sets the over power factor leading warning level.

Parameter Number 288 Access Rule Get/Set Data Type SINT Object Mapping 0Fhex-120-01 Group Power Setup

Units %

Minimum Value 0 Maximum Value 100 Default Value 90

Demand Period

This parameter sets the time period in minutes for which the demand calculation averages energy usage.

Parameter Number 291 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-123-01 Group Power Setup

Units Minutes

Minimum Value 1 Maximum Value 255 Default Value 15

Num of Periods

This parameter sets the number of periods to average for the demand calculation.

Parameter Number 292 Access Rule Get/Set Data Type USINT Object Mapping 0Fhex-124-01 Group Power Setup

Units —

Minimum Value 1 Maximum Value 15 Default Value 1