Monitor and Control Settings

5 Management Function

7.4 Monitor and Control Settings

The monitor and control settings (in the submenu “Mon\Ctrl Settings”) are used to determine the parameters of the monitor and control function of this relay.

7.4.1 Closing Synchronism Check Settings

The closing synchronism check settings (in the submenu “Syn Settings”) are used to determine the settings of the closing synchronism check function.

All the settings of the closing synchronism check function are listed in the following table.

No. Menu text Explanation Range Step

1 25.U_Dd The voltage setting of the system dead check 2~120V 0.001V 2 25.U_Lv The voltage setting of the system live check 2~120V 0.001V

3 25.U_Comp The compensation coefficient setting of the

synchro-check voltage 0.2~5.0 0.001

4 25.phi_Comp The compensation phase angle setting of the

synchro-check voltage 0~360° 1°

5 25.Opt_Usyn The voltage type setting of the synchronism check

closing function 0~5 1

6 25.t_ClsCB The circuit breaker closing time setting of the

closing synchronism check function 0.02~1.00s 0.001s

7 25M.U_Diff The voltage difference setting of the manual

closing synchronism check function 2~120V 0.001V

8 25M.f_Diff The frequency difference setting of the manual

closing synchronism check function 0~2Hz 0.001Hz

9 25M.df/dt The frequency rate-of-change setting of the

manual closing synchronism check function 0~3Hz/s 0.001 Hz/s

10 25M.phi_Diff The phase angle difference setting of the manual

closing synchronism check function 0~60° 1°

11 25M.t_Wait The waiting time setting of the manual closing

synchronism check function 0.01~30s 0.001s

12 25M.Opt_DdChk The setting for selecting the dead check mode of

the manual closing function 1~7 1

13 25M.En_SynChk The logic setting of the synchronism check

function of the manual closing function 0~1 1

14 25M.En_DdChk The logic setting of the dead check function of the

manual closing function 0~1 1

15 25A.U_Diff The voltage difference setting of the auto-closing

synchronism check function 2~120V 0.001V

16 25A.f_Diff The frequency difference setting of the

auto-closing synchronism check function 0~2Hz 0.001Hz

17 25A.phi_Diff The phase angle difference setting of the

auto-closing synchronism check function 0~60° 1°

18 25A.t_Wait The waiting time setting of the auto-closing

synchronism check function 0.01~60s 0.001s

19 25A.Opt_DdChk The setting for selecting the dead check mode of

the auto-closing synchronism check function 1~7 1

20 25A.t_DdChk The time setting of the dead check function of the

auto-closer 0.01~25s 0.001s

21 25A.t_SynChk The time setting of the synchronism check

function of the auto-closer 0.01~25s 0.001s

NOTE!

1. The settings [25.U_Comp] and [25.phi_Comp] are used to compensate the synchro-check voltage, and make the compensated synchro-check voltage is equal to the corresponding protection voltage in normal operation situation.

The settings [25.U_Comp] and [25.phi_Comp] can be set according to following formula.

⎩ ⎨

In general application, the setting [25.U_Comp] is set as “1.000”, and the setting [25.phi_Comp] is set as “0°”.

For example, the synchro-check voltage and the protection are gotten from different sides of a power transformer respectively.

z Synchro-check VT: 400kV Primary, 110V Secondary z Protection VT: 200kV Primary, 100V Secondary z Power transformer: 400kV / 200kV, vector group Yd11

The synchro-check VT supplies 110V secondary rated voltage while the protection VT supplies 100V secondary rated voltage. Therefore, this difference must be balanced:

[25.U_Comp] = 100V / 110V = 0.91

The transformer vector group is defined from the high voltage side to the low voltage side. In this example, the synchro-check voltage is one of the voltages of the high voltage side, i.e. the compensation angle setting is 30° (according to the vector group):

[25.phi_Comp] = 30°

2. The setting [25.Opt_Usyn] is used to select the synchro-check voltage source of the synchronism check element, and this relay can use the corresponding protection voltage for the synchronism check element.

Setting Value 0 1 2 3 4 5

Voltage Type Ua Ub Uc Uab Ubc Uca

7.4.2 Manual Control Settings

The manual control settings (in the submenu “Control Settings”) are used to determine the parameters of the manual control function (local or remote closing and tripping).

All the settings of the manual control are listed in the following table.

No. Menu text Explanation Range Step

1 Ctrl1.t_PW_Opn The output pulse width of the No.1 manual

tripping element 0.1~99.0s 0.001s

2 Ctrl1.t_PW_Cls The output pulse width of the No.1 manual closing

element 0.1~99.0s 0.001s

3 Ctrl1.OutMap_Opn The output matrix setting of the No.1 manual tripping element

0x00000000 ~ 0x7FFFFFFF 1

4 Ctrl1.OutMap_Cls The output matrix setting of the No.1 manual closing element

0x00000000 ~ 0x7FFFFFFF 1

5 Ctrl2.t_PW_Opn The output pulse width of the No.2 manual

tripping element 0.1~99.0s 0.001s

6 Ctrl2.t_PW_Cls The output pulse width of the No.2 manual closing

element 0.1~99.0s 0.001s

7 Ctrl2.OutMap_Opn The output matrix setting of the No.2 manual tripping element

0x00000000 ~ 0x7FFFFFFF 1

8 Ctrl2.OutMap_Cls The output matrix setting of the No.2 manual closing element

0x00000000 ~ 0x7FFFFFFF 1

9 Ctrl3.t_PW_Opn The output pulse width of the No.3 manual

tripping element 0.1~99.0s 0.001s

10 Ctrl3.t_PW_Cls The output pulse width of the No.3 manual closing

element 0.1~99.0s 0.001s

11 Ctrl3.OutMap_Opn The output matrix setting of the No.3 manual tripping element

0x00000000 ~ 0x7FFFFFFF 1

12 Ctrl3.OutMap_Cls The output matrix setting of the No.3 manual closing element

0x00000000 ~ 0x7FFFFFFF 1

13 Ctrl4.t_PW_Opn The output pulse width of the No.4 manual

tripping element 0.1~99.0s 0.001s

14 Ctrl4.t_PW_Cls The output pulse width of the No.4 manual closing

element 0.1~99.0s 0.001s

15 Ctrl4.OutMap_Opn The output matrix setting of the No.4 manual tripping element

0x00000000 ~ 0x7FFFFFFF 1

16 Ctrl4.OutMap_Cls The output matrix setting of the No.4 manual closing element

0x00000000 ~ 0x7FFFFFFF 1

17 Ctrl5.t_PW_Opn The output pulse width of the No.5 manual

tripping element 0.1~99.0s 0.001s

18 Ctrl5.t_PW_Cls The output pulse width of the No.5 manual closing

element 0.1~99.0s 0.001s

19 Ctrl5.OutMap_Opn The output matrix setting of the No.5 manual tripping element

0x00000000 ~ 0x7FFFFFFF 1

20 Ctrl5.OutMap_Cls The output matrix setting of the No.5 manual closing element

0x00000000 ~ 0x7FFFFFFF 1

7.4.3 Interlock Settings

The interlock settings (in the submenu “Interlock Settings”) are used to determine whether the interlock check of the manual control function (local or remote closing and tripping) is enabled.

All the settings of the interlock check function are listed in the following table.

No. Menu text Explanation Range Step

1 Interlock1.En_BlkOpn The logic setting of the interlock check of the No.1

manual tripping element 0~1 1

2 Interlock1.En_BlkCls The logic setting of the interlock check of the No.1

manual closing element 0~1 1

3 Interlock2.En_BlkOpn The logic setting of the interlock check of the No.2

manual tripping element 0~1 1

4 Interlock2.En_BlkCls The logic setting of the interlock check of the No.2

manual closing element 0~1 1

5 Interlock3.En_BlkOpn The logic setting of the interlock check of the No.3

manual tripping element 0~1 1

6 Interlock3.En_BlkCls The logic setting of the interlock check of the No.3

manual closing element 0~1 1

7 Interlock4.En_BlkOpn The logic setting of the interlock check of the No.4

manual tripping element 0~1 1

8 Interlock4.En_BlkCls The logic setting of the interlock check of the No.4

manual closing element 0~1 1

9 Interlock5.En_BlkOpn The logic setting of the interlock check of the No.5

manual tripping element 0~1 1

10 Interlock5.En_BlkCls The logic setting of the interlock check of the No.5

manual closing element 0~1 1

NOTE!

1. The interlock check function can be programmed through the PCS-Explorer configuration tool auxiliary software.