Zero Sequence Overcurrent Protection Settings

List of Figures

3.2 Fault Detectors

3.5.5 Zero Sequence Overcurrent Protection Settings

For the information about the common explanation of the settings, see Section 7.3.

All the settings of the No.1 zero sequence overcurrent protection are listed in the following table.

No. Menu text Explanation Range Step

1 50/51G.RCA The relay characteristic angle for the No.1

directional zero sequence overcurrent protection -180°~179° 1°

2 50/51G.En_VTS_Blk

The logic setting of the function which blocks the 1ROC protection related voltage measurement when the voltage transformer is failed

0~1 1

3 50/51G.K_Hm2 The percent setting of the harmonic blocking

element for the No.1 ROC protection 0.05~1.00 0.001

4 50/51G.3I0_Rls_HmBlk The current setting for releasing the harmonic

blocking element of the No.1 ROC protection 0.05In~30In 0.001A

5 50/51G1.3I0_Set The current setting of the No.1 stage 1 zero

sequence overcurrent protection 0.05In~30In 0.001A

6 50/51G1.t_Op The time setting of the No.1 stage 1 zero

sequence overcurrent protection 0~100s 0.001s

7 50/51G1.Opt_Dir The setting is used to select the directional mode

for the No.1 ROC1 protection, see Section 3.5.3 0~2 1

8 50/51G1.En_Hm_Blk The logic setting of the harmonic blocking element

for the No.1 ROC1 protection 0~1 1

9 50/51G1.En The logic setting of the No.1 stage 1 zero

sequence overcurrent protection 0~1 1

10 50/51G1.OutMap The output matrix setting of the No.1 stage 1 zero sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1

11 50/51G2.3I0_Set The current setting of the No.1 stage 2 zero

sequence overcurrent protection 0.05In~30In 0.001A

12 50/51G2.t_Op The time setting of the No.1 stage 2 zero

sequence overcurrent protection 0~100s 0.001s

13 50/51G2.Opt_Dir The setting is used to select the directional mode

for the No.1 ROC2 protection, see Section 3.5.3 0~2 1

14 50/51G2.En_Hm_Blk The logic setting of the harmonic blocking element

for the No.1 ROC2 protection 0~1 1

15 50/51G2.En The logic setting of the No.1 stage 2 zero

sequence overcurrent protection 0~1 1

16 50/51G2.OutMap The output matrix setting of the No.1 stage 2 zero sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1

17 50/51G3.3I0_Set The current setting of the No.1 stage 3 zero

sequence overcurrent protection 0.05In~30In 0.001A

18 50/51G3.t_Op The time setting of the No.1 stage 3 zero

sequence overcurrent protection 0~100s 0.001s

19 50/51G3.Opt_Dir The setting is used to select the directional mode

for the No.1 ROC3 protection, see Section 3.5.3 0~2 1

20 50/51G3.En_Hm_Blk The logic setting of the harmonic blocking element

for the No.1 ROC3 protection 0~1 1

21 50/51G3.En The logic setting of the No.1 stage 3 zero

sequence overcurrent protection 0~1 1

22 50/51G3.OutMap The output matrix setting of the No.1 stage 3 zero sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1

23 50/51G4.3I0_Set The current setting of the No.1 stage 4 zero

sequence overcurrent protection 0.05In~30In 0.001A

24 50/51G4.t_Op The time setting of the No.1 stage 4 zero

sequence overcurrent protection 0~100s 0.001s

25 50/51G4.Opt_Dir The setting is used to select the directional mode

for the No.1 ROC4 protection, see Section 3.5.3 0~2 1

26 50/51G4.En_Hm_Blk The logic setting of the harmonic blocking element

for the No.1 ROC4 protection 0~1 1

27 50/51G4.En The logic setting of the No.1 stage 4 zero

sequence overcurrent protection 0~1 1

28 50/51G4.OutMap The output matrix setting of the No.1 stage 4 zero sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1

29 50/51G4.Opt_Curve The setting is for selecting the inverse time

characteristic curve for the No.1 ROC4 protection 0~13 1

30 50/51G4.TMS The time multiplier setting of the No.1 zero

sequence IDMT overcurrent protection 0.05~100.0 0.001

31 50/51G4.tmin The minimum operation time setting of the No.1

zero sequence IDMT overcurrent protection 0~100s 0.001s

32 50/51G4.K Constant “k” for the No.1 zero sequence IDMT

overcurrent protection, see Section 3.5.2 0.001~120.0 0.0001

33 50/51G4.C Constant “C” for the No.1 zero sequence IDMT

overcurrent protection, see Section 3.5.2 0.00~1.00 0.0001

34 50/51G4.Alpha Constant “α” for the No.1 zero sequence IDMT

overcurrent protection, see Section 3.5.2 0.01~3.00 0.0001

All the settings of the No.2 zero sequence overcurrent protection are listed in the following table.

No. Menu text Explanation Range Step 1 A.50/51G.RCA The relay characteristic angle for the No.2

directional zero sequence overcurrent protection -180°~179° 1°

2 A.50/51G.En_VTS_Blk

The logic setting of the function which blocks the 2ROC protection related voltage measurement when the voltage transformer is failed

0~1 1

3 A.50/51G.K_Hm2 The percent setting of the harmonic blocking

element for the No.2 ROC protection 0.05~1.00 0.001

4 A.50/51G.3I0_Rls_HmBlk The current setting for releasing the harmonic

blocking element of the No.2 ROC protection 0.05In~30In 0.001A

5 A.50/51G1.3I0_Set The current setting of the No.2 stage 1 zero

sequence overcurrent protection 0.05In~30In 0.001A

6 A.50/51G1.t_Op The time setting of the No.2 stage 1 zero

sequence overcurrent protection 0~100s 0.001s

7 A.50/51G1.Opt_Dir The setting is used to select the directional mode

for the No.2 ROC1 protection 0~2 1

8 A.50/51G1.En_Hm_Blk The logic setting of the harmonic blocking element

for the No.2 ROC1 protection 0~1 1

9 A.50/51G1.En The logic setting of the No.2 stage 1 zero

sequence overcurrent protection 0~1 1

10 A.50/51G1.OutMap The output matrix setting of the No.2 stage 1 zero sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1

11 A.50/51G2.3I0_Set The current setting of the No.2 stage 2 zero

sequence overcurrent protection 0.05In~30In 0.001A

12 A.50/51G2.t_Op The time setting of the No.2 stage 2 zero

sequence overcurrent protection 0~100s 0.001s

13 A.50/51G2.Opt_Dir The setting is used to select the directional mode

for the No.2 ROC2 protection 0~2 1

14 A.50/51G2.En_Hm_Blk The logic setting of the harmonic blocking element

for the No.2 ROC2 protection 0~1 1

15 A.50/51G2.En The logic setting of the No.2 stage 2 zero

sequence overcurrent protection 0~1 1

16 A.50/51G2.OutMap The output matrix setting of the No.2 stage 2 zero sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1

17 A.50/51G3.3I0_Set The current setting of the No.2 stage 3 zero

sequence overcurrent protection 0.05In~30In 0.001A

18 A.50/51G3.t_Op The time setting of the No.2 stage 3 zero

sequence overcurrent protection 0~100s 0.001s

19 A.50/51G3.Opt_Dir The setting is used to select the directional mode

for the No.2 ROC3 protection 0~2 1

20 A.50/51G3.En_Hm_Blk The logic setting of the harmonic blocking element

for the No.2 ROC3 protection 0~1 1

21 A.50/51G3.En The logic setting of the No.2 stage 3 zero

sequence overcurrent protection 0~1 1

22 A.50/51G3.OutMap The output matrix setting of the No.2 stage 3 zero sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1

23 A.50/51G4.3I0_Set The current setting of the No.2 stage 4 zero

sequence overcurrent protection 0.05In~30In 0.001A

24 A.50/51G4.t_Op The time setting of the No.2 stage 4 zero

sequence overcurrent protection 0~100s 0.001s

25 A.50/51G4.Opt_Dir The setting is used to select the directional mode

for the No.2 ROC4 protection 0~2 1

26 A.50/51G4.En_Hm_Blk The logic setting of the harmonic blocking element

for the No.2 ROC4 protection 0~1 1

27 A.50/51G4.En The logic setting of the No.2 stage 4 zero

sequence overcurrent protection 0~1 1

28 A.50/51G4.OutMap The output matrix setting of the No.2 stage 4 zero sequence overcurrent protection

0x00000000 ~ 0x7FFFFFFF 1

29 A.50/51G4.Opt_Curve The setting is for selecting the inverse time

characteristic curve for the No.2 ROC4 protection 0~13 1

30 A.50/51G4.TMS The time multiplier setting of the No.2 zero

sequence IDMT overcurrent protection 0.05~100.0 0.001

31 A.50/51G4.tmin The minimum operation time setting of the No.2

zero sequence IDMT overcurrent protection 0~100s 0.001s

32 A.50/51G4.K Constant “k” for the No.2 zero sequence IDMT

overcurrent protection, see Section 3.5.2 0.001~120.0 0.0001

33 A.50/51G4.C Constant “C” for the No.2 zero sequence IDMT

overcurrent protection, see Section 3.5.2 0.00~1.00 0.0001

34 A.50/51G4.Alpha Constant “α” for the No.2 zero sequence IDMT

overcurrent protection, see Section 3.5.2 0.01~3.00 0.0001

3.6 Sensitive Earth Fault Protection