Parameterizing the G110 frequency inverter

In document Micro Application Example (Page 36-40)

For the procedure, please refer to chapter 4.3. The following section lists only the parameters you have to change with regard to the factory default settings for this application example. For the parameterization, please follow the order specified in the table below.

Parameter changes in the SINAMICS G110

Table 5-6 Parameter

No. Value Remark

Resetting to factory default settings

P0010 30 Commissioning parameter: Factory setting

P0970 1 Start of the reset of all parameters to default values

Quick commissioning

P0003 3 Access level: Expert

P0010 1 Commissioning parameter: Quick commissioning

P0305 1.34 Rated motor current (A) (for delta connection), see rating plate P0307 0.25 Rated motor power (kW), see rating plate

P0308 0.78 Rated power factor of the motor (cos φ), see rating plate

P0310 50 Rated motor frequency (Hz) for the specific motor data, see rating plate P0311 1350 Rated motor speed (min-1), see rating plate

P1082 100.00 Maximum frequency (Hz) (100Hz for 4-pole motor, 50Hz for 2-pole motor) P1120 0.00 Acceleration time (determined by the controller)

P1121 0.00 Deceleration time (determined by the controller)

P3900 1 End of quick commissioning (among other things, resets P0003 to 1)

Application-specific parameterizations

P0003 3 Access level: Expert

P0760 200.00 y2 value ADC scaling (%) (100% for 2-pole motors) P1240 0 Configuration of Vdc controller: Vdc controller disabled

Saving parameters to the inverter’s EEPROM

P0971 1 Transfer of values from RAM to EEPROM

Transferring parameter set to BOP for reuse

P0010 30 Commissioning parameter: Factory setting P0802 1 Parameter transfer from SINAMICS → BOP P0003 1 Access level: Standard

V2.0 16.07.2008 37/54 C opyr ight © Si em ens AG 2 008 Al l r ights r e se rv ed Set0 1_D ocT e ch_ 2d0 _en.d o c

NOTICE If you are using a motor type that differs from the ones listed in Table 3-1,

the following parameters have to be additionally considered during quick commissioning:

• P0304 rated motor voltage (V) (for delta connection), see rating plate

• P0335 rotor cooling: 1 = self-ventilated, 2 = separately ventilated

In this application example, the values of these parameters are already covered by the factory default settings and thus not listed in the above table.

Parameter transfer from BOP SINAMICS G110

When you have transferred the inverter parameter set to the BOP as shown in Table 5-6, you can reload it from the BOP to the inverter very easily if required or distribute it to other inverters.

Table 5-7 Parameter

No. Value Remark

Transferring parameter set from the BOP to the frequency inverter

P0003 3 Access level: Expert

P0010 30 Commissioning parameter: Factory setting P0803 1 Parameter transfer from BOP → SINAMICS

Saving parameters to the inverter’s EEPROM

P0971 1 Transfer of values from RAM to EEPROM P0003 1 Access level: Standard

V2.0 16.07.2008 38/54 C opyr ight © Si em ens AG 2 008 Al l r ights r e se rv ed Set0 1_D ocT e ch_ 2d0 _en.d o c

6 Live Demo

Overview

To facilitate understanding, the functions and features of Micro Automation Set 1 are shown in the form of a sample application.

If the components have been correctly configured as described in chapter 5, the program code can be tested.

Figure 6-1: Live demo overview

Optimizing the dynamic response Setting up the wire-wound coils Feeding in the wire

Producing 10 wire rods with a length of 2m (automatic mode)

Immediate stopping of the feed motion using the stop button of the TP 177micro Cutting wire rods of variable length (manual mode)

Immediate stopping of the feed motion using the hardware stop button (e.g. emergency stop) Data logging

Start

End

Basic information on operating the TP 177micro

Table 6-1

Definition Example

Input values:

Input or input/output fields are designated by a white background.

Output values:

Mere output fields are marked by a gray background.

Input/output field

V2.0 16.07.2008 39/54 C opyr ight © Si em ens AG 2 008 Al l r ights r e se rv ed Set0 1_D ocT e ch_ 2d0 _en.d o c Definition Example

Grayed out buttons:

Buttons with grayed out labeling indicate that the action associated with the button is locked for

programming reasons. For example, automatic mode can only be set after the wire has been fed in.

Not grayed out

Grayed out

Navigation buttons:

The navigation buttons for changing the screens/statuses are located on the bottom screen edge. The screens are structured as shown on the right. In case of voltage recovery or restart of the controller, the system

branches to the “feed in” screen. In the currently selected screen, the background of the navigation buttons is black and they cannot be

operated. settings recipe admin. feed in automatic manual production

Automatic mode selected

Graphic:

A graphic in the TP screens shows the wire cutting machine’s condition of motion.

Standstill

Cut Feed active

(the sectors within the coils rotate and the wire moves forward.)

Deleting old archive data

Delete any old logged data from the memory module and old csv log files before the live demo scenarios.

V2.0 16.07.2008 40/54 C opyr ight © Si em ens AG 2 008 Al l r ights r e se rv ed Set0 1_D ocT e ch_ 2d0 _en.d o c Table 6-2

No. Step Remark

1.

Double-click .

Ö Memory module is read out and deleted. 2.

Double-click .

Ö Directory of csv log files is opened. 3. Delete all csv files in the directory.

The logging was configured in such a way that the log data in the memory module is deleted when reading out the 256 KB memory module in a csv file.