For the procedure, please refer to chapter 4.3. The following section lists only the parameters you have to change with regard to the factory default settings for this application example. For the parameterization, please follow the order specified in the table below.
Parameter changes in the SINAMICS G110
Table 5-6 Parameter
No. Value Remark
Resetting to factory default settings
P0010 30 Commissioning parameter: Factory setting
P0970 1 Start of the reset of all parameters to default values
Quick commissioning
P0003 3 Access level: Expert
P0010 1 Commissioning parameter: Quick commissioning
P0305 1.34 Rated motor current (A) (for delta connection), see rating plate P0307 0.25 Rated motor power (kW), see rating plate
P0308 0.78 Rated power factor of the motor (cos φ), see rating plate
P0310 50 Rated motor frequency (Hz) for the specific motor data, see rating plate P0311 1350 Rated motor speed (min-1), see rating plate
P1082 100.00 Maximum frequency (Hz) (100Hz for 4-pole motor, 50Hz for 2-pole motor) P1120 0.00 Acceleration time (determined by the controller)
P1121 0.00 Deceleration time (determined by the controller)
P3900 1 End of quick commissioning (among other things, resets P0003 to 1)
Application-specific parameterizations
P0003 3 Access level: Expert
P0760 200.00 y2 value ADC scaling (%) (100% for 2-pole motors) P1240 0 Configuration of Vdc controller: Vdc controller disabled
Saving parameters to the inverter’s EEPROM
P0971 1 Transfer of values from RAM to EEPROM
Transferring parameter set to BOP for reuse
P0010 30 Commissioning parameter: Factory setting P0802 1 Parameter transfer from SINAMICS → BOP P0003 1 Access level: Standard
V2.0 16.07.2008 37/54 C opyr ight © Si em ens AG 2 008 Al l r ights r e se rv ed Set0 1_D ocT e ch_ 2d0 _en.d o c
NOTICE If you are using a motor type that differs from the ones listed in Table 3-1,
the following parameters have to be additionally considered during quick commissioning:
• P0304 rated motor voltage (V) (for delta connection), see rating plate
• P0335 rotor cooling: 1 = self-ventilated, 2 = separately ventilated
In this application example, the values of these parameters are already covered by the factory default settings and thus not listed in the above table.
Parameter transfer from BOP → SINAMICS G110
When you have transferred the inverter parameter set to the BOP as shown in Table 5-6, you can reload it from the BOP to the inverter very easily if required or distribute it to other inverters.
Table 5-7 Parameter
No. Value Remark
Transferring parameter set from the BOP to the frequency inverter
P0003 3 Access level: Expert
P0010 30 Commissioning parameter: Factory setting P0803 1 Parameter transfer from BOP → SINAMICS
Saving parameters to the inverter’s EEPROM
P0971 1 Transfer of values from RAM to EEPROM P0003 1 Access level: Standard
V2.0 16.07.2008 38/54 C opyr ight © Si em ens AG 2 008 Al l r ights r e se rv ed Set0 1_D ocT e ch_ 2d0 _en.d o c
6 Live Demo
OverviewTo facilitate understanding, the functions and features of Micro Automation Set 1 are shown in the form of a sample application.
If the components have been correctly configured as described in chapter 5, the program code can be tested.
Figure 6-1: Live demo overview
Optimizing the dynamic response Setting up the wire-wound coils Feeding in the wire
Producing 10 wire rods with a length of 2m (automatic mode)
Immediate stopping of the feed motion using the stop button of the TP 177micro Cutting wire rods of variable length (manual mode)
Immediate stopping of the feed motion using the hardware stop button (e.g. emergency stop) Data logging
Start
End
Basic information on operating the TP 177micro
Table 6-1
Definition Example
Input values:
Input or input/output fields are designated by a white background.
Output values:
Mere output fields are marked by a gray background.
Input/output field
V2.0 16.07.2008 39/54 C opyr ight © Si em ens AG 2 008 Al l r ights r e se rv ed Set0 1_D ocT e ch_ 2d0 _en.d o c Definition Example
Grayed out buttons:
Buttons with grayed out labeling indicate that the action associated with the button is locked for
programming reasons. For example, automatic mode can only be set after the wire has been fed in.
Not grayed out
Grayed out
Navigation buttons:
The navigation buttons for changing the screens/statuses are located on the bottom screen edge. The screens are structured as shown on the right. In case of voltage recovery or restart of the controller, the system
branches to the “feed in” screen. In the currently selected screen, the background of the navigation buttons is black and they cannot be
operated. settings recipe admin. feed in automatic manual production
Automatic mode selected
Graphic:
A graphic in the TP screens shows the wire cutting machine’s condition of motion.
Standstill
Cut Feed active
(the sectors within the coils rotate and the wire moves forward.)
Deleting old archive data
Delete any old logged data from the memory module and old csv log files before the live demo scenarios.
V2.0 16.07.2008 40/54 C opyr ight © Si em ens AG 2 008 Al l r ights r e se rv ed Set0 1_D ocT e ch_ 2d0 _en.d o c Table 6-2
No. Step Remark
1.
Double-click .
Ö Memory module is read out and deleted. 2.
Double-click .
Ö Directory of csv log files is opened. 3. Delete all csv files in the directory.
The logging was configured in such a way that the log data in the memory module is deleted when reading out the 256 KB memory module in a csv file.