• No results found

Revise the WSP as necessary including updates to supporting programs.

In document 2012 WATER SAFETY PLAN (Page 58-67)

Maynilad Water Safety Plan Revision No.1/November 2012

59

ANNEX I: HAZARD IDENTIFICATION AND RISK ASSESSMENT

A. Source: Surface Water

Hazardous Event Hazard Likelihood Severity Score Risk Rating

1. Typhoon/Heavy Rains 2. Land slide, mud, debris

Physical (High Turbidity) Chemical

Microbial

2.5 5 12.5 High

3. Illegal Logging (denudation of watershed)

Physical (High Turbidity) 3 3 9 Medium

4. Human Access (Dumagat & Illegal Settlers)

Microbial (Fecal/e-coli) 2 5 10 Medium

5. Breakdown of NPC Auxiliary Turbines and Bypass leading to the use of Low Level Outlet (LLO) or spillway

Physical (High Turbidity) & Chemical (Manganese)

2 3 6 Medium

6. Malfunction of turbidimeter

7. (Wrong turbidity measurement leading to erroneous information can be relayed to water production for treatment)

Physical 2 3 6 Medium

8. La Nina (turbidity) Physical (High Turbidity) 1 4 4 Low

9. Malfunction of silt ejector Physical (High Turbidity) 1 3 3 Low

10. El Nino leading to the use of Low Level Outlet (LLO)

Physical (High Turbidity) & Chemical (Manganese)

1 3 3 Low

11. Disturbance of Manganese deposit within the watershed & sediments (Earthquake, landslide, human activity, terrorist act, project construction etc.)

Chemical 1 4 4 Low

12. Forest Fire Physical (High Turbidity) 2 2 4 Low

13. Terrorist Act Chemical toxic substance & Physical (High Turbidity)

Maynilad Water Safety Plan Revision No.1/November 2012

60

14. Oil spill Physical & Chemical 1 1 1 Low

15. Earthquake Physical (High turbidity) 1 3 3 Low

16. Theft/Vandalism of facilities (BNAQ’s) Physical (High turbidity) & Microbial (fecal/e-coli)

1 5 5 Low

Maynilad Water Safety Plan Revision No.1/November 2012

61

B. Water Treatment: La Mesa Water Treatment Plant 1&2

Process Step Hazardous Event Hazard Likelihood Severity Score Risk Rating

Caustic Soda Application Overdosing and under dosing of chemicals Chemical 2 2 4 Low

Potassium Permanganate application

Overdosing/ under dosing of chemical Physical Chemical

2 3 6 Medium

Screening

(Primary and Secondary)

1. Intrusion of garbage and floatables during normal & stormy weather due to

ineffectiveness of screen

Physical Chemical

3 3 9 Medium

Microbial 3 5 15 High

2. Uncontrolled raw water quality due to natural calamities like El Nino, La Nina & flash flooding in far off provinces like Quezon

Physical 2.5 3 7.5 Medium

Chemical 1 3 3 Low

Microbial

1 5 5 Low

Pre-chlorination 1. Formation of disinfection by-products

due to high raw water turbidity

Chemical

(LMTP 1) 1 4 4 Low

Chemical

(LMTP 2) 2 5 10 High

2. Under dosing / no pre-chlorination Microbial 2 5 10 High

3. Less effective disinfection due to high

turbidity - LMTP 2 Microbial 2 5 10 High

4. Insufficient Chlorine Supply Microbial 2 5 10 High

5. Chlorine Supply Quality (Non- Compliance)

Chemical 2 4 8 Medium

Microbial 2 5 10 High

Coagulation (LMTP 1 & 2) 1. Incorrect dispersal of coagulant due to

rapid mixer trouble

Physical 3 3 9 Medium

Chemical 3 3 9 Medium

2. Overdosing / under dosing Physical 3 2 6 Medium

Chemical 3 3 9 Medium

Maynilad Water Safety Plan Revision No.1/November 2012

62

Process Step Hazardous Event Hazard Likelihood Severity Score Risk Rating

of feed lines b) dosing pump / transfer

pump trouble Chemical 4 2 8 Medium

4. Insufficient Coagulant Supply Physical 2 2 4 Low

Chemical 2 3 6 Medium

5. Coagulant Supply Quality (Non- Compliance)

Physical 2 2 4 Low

Chemical 2 2 4 Low

Flocculation (LMTP 1) 1. Incorrect setting of variators /

flocculators Physical 3 1 3 Low

Chemical 3 2 6 Medium

2. Overdosing/Underdosing of coagulant aid Physical 3 2 6 Medium

Chemical 3 3 9 Medium

Sedimentation (LMTP 1) 1. Sludge blanket formation exceeds 10

meters length from entry into sedimentation basis

Physical 3 2 6 Medium

Chemical 3 2 6 Medium

Microbial 3 5 15 High

2. Sludge bulking Physical 1 3 3 Low

Chemical 1 3 3 Low

Microbial 1 3 3 Low

3. Floating leaves and other floatables Physical 5 1 5 Low

Chemical 5 1 5 Low

Microbial 5 1 5 Low

4. Formation of algae in Sedimentation

Basin (Launders) Microbial 2 3 6 Medium

Pulsation (LMTP 2) 1. Sludge blanket blowdown Physical 2.5 3 7.5 Medium

Maynilad Water Safety Plan Revision No.1/November 2012

63

Process Step Hazardous Event Hazard Likelihood Severity Score Risk Rating

Microbial 1 5 5 Low

2. Overdosing/Under dosing of primary

coagulant and coagulant aid Physical 2.5 3 7.5 Medium

Chemical 2.5 3 7.5 Medium

Microbial 1 5 5 Low

3. Vacuum pumps and compressor failure Physical 2.5 3 7.5 Medium

Chemical 2.5 3 7.5 Medium

Microbial 1 5 5 Low

Intermediate Chlorination

(LMTP 1) 1. Under dosing Microbial 3 4 12 High

2. Leak in Chlorine Pipes Microbial 2 5 10 High

3. Less effective disinfection due to high

turbidity Microbial 1 4 4 Low

4. Insufficient Chlorine Supply Microbial 2 5 10 High

5. Chlorine Supply Quality (Non-

Compliance) Chemical 2 4 8 Medium

Microbial 2 5 10 High

Filtration (LMTP 1 and LMTP 2)

1. Poor performance of filters as surface wash (LMTP 1), scour air blower (LMTP 2) are not operating well

2. Depleted filter media

3. Electro-mechanical and electro- pneumatic system failure

4. Excessive algal formation due to irregular and inefficient backwashing

Physical 1 3 3 Low

Chemical 1 4 4 Low

Microbial 1 5 5 Low

Maynilad Water Safety Plan Revision No.1/November 2012

64

Process Step Hazardous Event Hazard Likelihood Severity Score Risk Rating

Microbial 2 5 10 High

Recovery Highly Turbid Recovered Water Physical 5 3 15 Very High

Chemical 5 2 10 High

Microbial 1 5 5 Low

Post chlorination 1. Residual Chlorine greater than 1.50 ppm Chemical 1 4 4 Low

2. Under dosing Microbial 2 5 10 High

3. Leak in Chlorine Pipes Microbial 2 5 10 High

4. Insufficient Chlorine Supply Microbial 1 5 5 Low

5. Chlorine Supply Quality (Non- Compliance)

Chemical 2 4 8 Medium

Microbial 2 5 10 High

All process steps Power outage / unbalanced power supply

which stop the entire treatment process

Physical 2 3 6 Medium

Chemical 2 4 8 Medium

Microbial 2 5 10 High

Gen set breakdown Physical 1 3 3 Low

Chemical 1 4 4 Low

Microbial 2 5 5 High

Internal/external sabotage & illegal tampering of plant facilities like opening of alum tank drain, unauthorized resetting of dosing pumps or dumping of large volume of sand upstream

Physical 1 3 3 Low

Chemical 1 4 4 Low

Maynilad Water Safety Plan Revision No.1/November 2012

65

C. Putatan Water Treatment Plant

Process Step Hazardous Event Hazard Likelihood Severity Score Risk rating

INTAKE Elevated levels of manganese, chlorides, ammonia, turbidity, total dissolved solids and algal count during El Nino

Physical Chemical Microbial

1 5 5 Low

Human Access Physical

Chemical Microbial

2 5 10 High

Algal Bloom Physical

Chemical Microbial

2 5 10 high

Proliferation of Fish pens Physical Chemical Microbial

3 5 15 High

Heavy rains and typhoon lake water disturbance

Physical Chemical

3 4 12 high

Intrusion of garbage and others Physical Chemical Microbial

3 5 15 High

Discharges of domestic and industrial wastes nearby the intake

Physical Chemical Microbial

5 5 25 Very high

FOREBAY Siltation at the twin box culvert Physical Chemical Microbial

1 5 5 Low

Intrusion of drainage and sewage from the cracks along twin box culvert

Physical Chemical Microbial

Maynilad Water Safety Plan Revision No.1/November 2012

66

Algal Bloom Physical

Chemical Microbial

2 5 10 High

Solid Waste Intrusion (e.i.garbage and twigs)

Physical Chemical Microbial

4 5 10 high

Intrusion of MF backwash water from the water recovery system

Physical Chemical Microbial

5 5 25 Very high

Siltation at the bottom of forebay Physical Chemical Microbial

2 5 10 High

Siltation at the bottom of forebay Physical Chemical Microbial

2 5 10 High

DISSOLVED AIR FLOTATION COAGULATION/FLOCCULATI

ON/FLOTATION

Improper dosing of coagulant and potassium permanganate

Physical Chemical Microbial

2 5 10 high

Flash mixer not working (ACH addition) Physical Chemical Microbial

2 5 10 high

Rapid and slow mixers not working Physical Chemical Microbial

2 5 10 high

Non-compliance of chemicals Physical Chemical Microbial

2 5 10 high

Malfunction of surface and bottom scrapers

Physical Chemical

Maynilad Water Safety Plan Revision No.1/November 2012

67

In document 2012 WATER SAFETY PLAN (Page 58-67)

Related documents