DISTRICT

COOLING

BEST

PRACTICE

GUIDE

FIRST EDITION

Published to inform, connect

and advance the global

district cooling industry

INTERNATIONAL

DISTRICT ENERGY

ASSOCIATION

(2)

Dedicated

to

the growth and utilization

of

district cooling as a means to enhance energy

efficiency, provide more sustainable and

reliable energy infrastructure, and contribute

to

improving the global environment.

Proprietary Notice

Copyright©2008lnternational District Energy Association. ALL RIGHTS RESERVED. This publication contains proprietary content of International District Energy Association (IDEA) which is protected by copyright, trademark and other intellectual property rights.

No part of this publication or any "Information" (as defined below) contained herein may be reproduced (by photocopying or otherwise), transmitted, stored (in a database, retrieval system, or otherwise), or otherwise used through any meanswithoutthe express prior written permission of IDEA. "Information" means any and all

information, data, specific products, services, processes,

procedures, designs, techniques, technical data, editorial

material, advice, instructions, opinions or any other

content appearing or referenced in this publication.

No Professional Advice

IDEA has prepared this publication for informational purposes only. This publication is not intended to

provide anyprofessional advice, instruction or opinions

regarding any topic that appears in this publication and should not be relied upon as such. The Information contained in this publication is general in nature and may not apply to your particular circumstances or needs. Consult an appropriate professional for advice

tailored to your particular circumstances and needs.

Disclaimer of All Warranties

IDEA has exercised reasonable care in producing the Information contained in this publication. IDEAhas not investigated, and IDEA expressly disclaims any duty to

investigate, any specific product, service, process,

procedure, design, technique or the like that may be described herein. The appearance of any Information in this publication does not constitute endorsement,

warranty or guaranty by IDEA of any product, service, process, procedure, design or the like. IDEA does not

make any representation or warranties about the

suit-ability or accuracyof the Information in this publication or that the Information in this publication is error-free. All Information presented in this work is provided "as is" without warranty of any kind. IDEA disclaims all

warranties and conditions of any kind, express or

implied, including all implied warranties and conditions of merchantability, fitness for a particular purpose, title

and non-infringement. The Information contained in

this publication may be superseded, may contain

errors, and/or may include inaccuracies.

Disclaimer of Liability

IDEA shall not be liable for any special, indirect, incidental, consequential or any damages whatsoever

resulting from inconvenience. or loss of use, resources,

or profits, whether in an action of contract, negligence

orother tortious action, arising out of or in connection

with the use or performance of any of the Information available in this publication even if IDEA has been advised of the possibility of such damages or losses.

IDEA invites comments. criticisms and suggestions

regarding the subject matter in this publication,

including notice of errors or omissions.

INTERNATIONAL

DISTRICf ENERGY

ASSOCIATION

24 Lyman Street, Suite 230 Westborough, MA 01581 USA

508-366-9339 phone 508-366-0019 fax www.districtenergy.org

ISBN

978-0-615-25071-7

Library of Congress Control Number: 2008937624

(3)

Preface

When the National District Heating Association (NDHA) was founded in the United States in 1909, its mission was to be a collegial and vibrant resource of practical

engineering and operational information, to connect

people with technical resources and real-world

solutions, and to advance the district energy industry through education and advocacy on the economic and environmental benefits of district heating systems. The

cornerstone of the association wasthe open exchange of information on design, construction and safe

operation of district heating systems.

NDHA published the first edition Handbook of the

National District Heating Association in 1921, with subsequent revisions of the district heating handbook in 1932, 1951 and 1983. Over time, the association

would evolve to encompass district cooling, combined

heat and power and the world beyond North America, resulting in a name change from the National District Heating Association (NDHA) to the International District Heating Association (IDHA) in 1968 to the International District Heating and Cooling Association (IDHCA) in 1984 to the current International District EnergyAssociation (IDEA) in 1994. Throughout the first 100 years, IDEA hasremained true to its original mission by drawing from the collective experience of all membership segments - personnel from the operations,

engineering and distribution arenas as well asconsultants and manufacturers.

"'

In 2004, Dany Safi, founder and chief executive officer of Tabreed, suggested IDEA develop an industry guide-book to help transfer the deep technical and engineering experience resident within IDEA to support the nascent district cooling industry across the Middle East. Now, as IDEA begins its second century in 2009, there is

massive investment in new district cooling systems in

the Middle East, where the harsh climate and pace of real estate development demand a wide range of technical resources. It is this unique market segment that is the principal focus of this first edition of the

District Cooling Best Practice Guide.

The Best Practice Guide is a compilation of practical solutions and lessons learned by industry practitioners. It is not a compendium of standards, reference documents and design drawings and is not intended to displace long-standing reference sources for codes and ratings. The Best Practice Guide is intended to

support engineers, business developers, managers and

service providers in the business of district cooling. This first edition may not incorporate every detail of the

industry, but any omissions or oversights are

uninten-tional. IDEA welcomes suggestions and comments to

support improvements in future editions.

On behalf of the many contributors to this Best Practice

Guideand the IDEA Board of Directors, thank you for your interest in district cooling and for selecting the IDEAas your industry resource.

(4)

Acknowledgements

It may not be possible to properly acknowledge all of the contributors to IDEA's District Cooling Best Practice

Guide. By its very nature, a best practice guide reflects the collective experienceof industry participants, openly

sharing case studies, experiences and practical solutions

to the complex business of designing, constructing, operating and optimizing district cooling systems. Since IDEA's inception in 1909, generations of IDEA members

have made successive contributions to future colleagues. It

isour sincere hopethat publishing this District Cooling Best

Practice Guidewill continue and extend the IDEAtradi-tion of providing guidance to future industry participants in developing reliable, efficient and environmentally beneficial district energy systems. The world demands

our best efforts in this arena.

The principal vision for IDEA's District Cooling Best

Practice Guidebegan with Dany Safi, CEO of Tabreed. In 2004, at the start of his first term on the IDEA Board of Directors, Safi proposed that IDEA assemble a guide book to help transfer the collective technical and business experience on district cooling that he had encountered over many years of attending IDEA conferences. The principal founder of the burgeoning

district cooling industry in the Middle East, Safi

foresaw the value and importance of technical

guid-ance and experience exchange to ensure that newly

developed systems are properly designed, constructed and operated for highest efficiency and reliability to pre-serve the positive reputation of the industry. Safi con-tributed personally, professionally and financially to this

guide and deserves special recognition for his

singular and sustaining commitment to a robust and

en-vironmentally progressive global district energy industry.

The principal authors of this guide are Mark Spurr and colleagues Bryan Kleist, Robert Miller and Eric Moe of FVB Energy Inc., with Mark Fisher of Thermo Systems LLC authoring the chapter on Controls, Instrumenta-tion and Metering. These gentlemen have dedicated hundreds of hours in organizing, writing, researching and editing this Best Practice Guide, drawing from decades of personal, professional experience in the

iv

design and engineering of numerous district cooling systems around the globe. Important contributions were also made by Bjorn Andersson, Peter Beckett, John Chin, Ehsan Dehbashi, Leif Eriksson, Leif Israelson, Ryan Johnson, Todd Sivertsson, Sieiman Shakkour and Bard Skagestad of FVB Energy; Trevor Blank, Stanislaus Hilton and Sai La of Thermo Systems LLC; and Peter

Tracey of CoolTech Gulf. Completing the guide

demanded the focused personal commitment of these fine industry professionals who have made a lasting and substantial professional contribution to IDEA and the entire global industry community.

From the outset and over the extended development process, the IDEA Board of Directors remained committed to the projectwith continuous support and leadership from Robert Smith, Juan Ontiveros, Tom Guglielmi and Dennis Fotinos. In addition, a core support team of IDEA leaders and volunteers chaired by Laxmi Raoand comprised of Cliff Braddock, Kevin Kuretich, Jamie Dillard and Steve Tredinnick contributed substantially by providing regular technical input and insight and participating in project

updates and review meetings.

Hundreds of pages of technical content were reviewed chapter by chapter by industry peers. These individuals volunteered to support IDEA's Best Practice Guide by reading, verifying and editing chapters in their areas of specialty to ensure editorial balance and the technical integrity of the final product. IDEA is indebted to peer reviewers John Andrepont, George Berbari, Bharat Bhola, Joseph Brillhart, Cliff Braddock, Jamie Dillard, Steve Harmon, Jean Laganiere, Bob Maffei, Gary Rugel, Ghassan Sahli, Sam Stone, Craig Thomas, Steve Tredinnick and Fouad Younan. We also appreciate the

assistance of the operation and maintenance team at

Tabreed, led by JamesKassim, who contributed insights

from their experience in operating a wide variety of

district cooling systems.

Important financial supportfor the Best Practice Guide was providedviaan award under the Market Development Cooperator Grant Program from the United States

(5)

Department of Commerce. IDEA acknowledges the important support of Department of Commerce staff including Brad Hess, Frank Caliva, Mark Wells, Sarah

Lapp and Patricia Gershanik for their multi-year

support of IDEA.

Tabreed provided substantial financial support during the early stage of the project, and Dany Safi, CEO of Tabreed, made a substantial personal financial

contri-bution to sponsor the completion of theBestPractice

Guide.IDEA thanks and gratefully acknowledges the leadership and unparalleled commitment demonstrated by Dany Safi and Tabreed, global leaders in the district cooling industry.

Monica Westerlund, executive editor of District Energy

magazine, provided timely editing of the guide and worked closely with Dick Garrison who designed the final layout of the book. This was a challenging task achieved under a tight timetable. Laxmi Rao provided management and stewardship throughout the project, and the printing and binding of the book was ably managed by Len Phillips. IDEA staff Dina Gadon and Tanya Kozel make regular contributions to the IDEA

community and therefore directly and indirectly

contributed to this effort. The sum of our IDEA parts is a much larger whole.

v

The IDEA community has grown with the recent addition of hundreds of members from the recently formed Middle East Chapter. The chapter would not be

in place without the commitment and resourcefulness

of Joel Greene, IDEA legal counsel from Jennings,

Strauss & Salmon. As former chair of IDEA, Joel has been committed to IDEA's growth in the Middle East region. Additionally, Rita Chahoud of Tabreed, the executive director of the IDEA Middle East Chapter, is a dedicated and energetic resource for the industry. Without her contributions and stewardship, the IDEA Middle East Chapter would not be where it is today.

Finally, the IDEA membership community is comprised of dedicated, committed and talented individuals who have made countless contributions to the success and growth of the district energy industry. As we celebrate IDEAs centennial and begin our second century, I wish to acknowledge the collective energy of our members in ad-vancingthe best practicesof our chosen field of endeavor.

Robert P. Thornton

President, International District Energy Association

Westborough, Massachusetts, USA

(6)

DISTRICT COOUNG BEST PRACTICE GUIDE e2008International DistrictEnetgyAssodatioo.Allrightsreserved.

Contents

Preface

Acknowledgements 1. Introduction

1.1Purpose

1.2

Overview and Structure of the Guide

2. Why District Cooling?

2.1 Customer Benefits

2.1.1

Comfort 2.1.2 Convenience 2.1.3 Flexibility

2.1.4

Reliability

2.1.5

Cost-effectiveness

Fundamental cost advantages Load diversity

Optimized operations Advanced technologies

Better staff economies Customer risk management Costcomparison

Capital costs Annual costs

2.2 Infrastructure Benefits

2.2.1

Peak power demand reduction

2.2.2

Reduction in government power sector costs Capital costs of power capacity

Power sector operating costs

Total costs of electricity

Power utility recognition of district cooling benefits

2.3

Environmental Benefits

2.3.1

Energy efficiency

2.3.2

Climate change

2.3.3

Ozone depletion 3. Business Development

3.1

District Cooling as a Utility Business

3.1.1

Engineering design

3.1.2

Organizational design

3.2

Marketing and Communications

3.2.1

Positioning

3.2.2

Customer value proposition Value proposition summary Building chiller system efficiency Structuring the cost comparison

Communicating with prospective customers

3.3

Risk Management

3.3.1

Nature of district cooling company

3.3.2

Capital-intensiveness

3.3.3

Will visions be

realized?

3.3.4

District cooling company risks

Stranded capital Temporary chillers vi iii iv 1 1 2 2 2 2 2 2 2 2 2 2 2 3

3

3

3

3

3 3 3 4 4 4

5

5

7 7 7

8

9 9 9 9

9

9

10 10 10 10 11 11

11

11 11 12 12

12

(7)

DISTRICT COOLING BEST PRACTICE GUIDE

e2008!mem~tion,,!Di5tnct EnergyA5wd~ti(Jfl.Al!nghl:;reservro.

Construction risks

Underground congestion

Community relations General construction issues Revenue generation risks

Inadequate chilled-water delivery Delays in connecting buildings Metering

Reduced building occupancy 3.4 Rate Structures

3.4.1 Capacity, consumption and connection rates Capacity rates

Consumption rates

Connection charges Regional rate examples

3.4.2 Rate structure recommendations Capacity rates

Connection charges

Initial contract demand

Rate design to encourage optimal building design and operation 3.5 Performance Metrics

4. Design Process and Key Issues 4.1 Load Estimation

4.1.1 Peak demand

4.1.2 Peak-day hourly load profile 4.1.3 Annual cooling load profile 4.2 Design Temperatures and Delta T 4.2.1 Delta T is a key parameter

4.2.2 Limitations on lower chilled-water supply temperature Chiller efficiency

Evaporator freezeup Thermal energy storage

4.2.3 Limitations on higher chilled-water return temperature Dehumidification and coil performance

Heat exchanger approach temperature 4.2.4 Best practice recommendation 4.3 Master Planning

4.4 Permitting (Way Leaves)

4.5 Integration of District Cooling With Other Utility Infrastructure 4.5.1 Growth and infrastructure stresses

4.5.2 Paths for utility integration Heat rejection

Desalination

Natural gas

The challenge of utility integration 4.6 Designing for Operations

5. Building HVAC Design and Energy TransferStations(ETS) 5.1 Building System Compatibility

5.1.1 Cooling coil selection

5.1.2 Bypasses and three-way valves 5.1.3 Control-valve sizing and selection

vii

12

12

12

12

12

12

13 13 13 13 13 13 13 13 13 14 14 14 14 15 15

16

16 16 17 18 18 18 19 19

20

20

20

20

21

21

21

22

22 22 23 23 24 24 24 25 26

26

26

27 27

(8)

DISTRICT COOUNG BEST PRACTICE GUIDE

C2oo8Intemation<ll DiS/Iict EneIWAlsodanoo. Allrightsreserved.

5.1.4 Building pump control

5.1.5 Water treatment and heat-transfer effectiveness 5.1.6 Additional economic opportunities

5.2 System Performance Metrics at the ETS 5.3 Selecting Direct or Indirect ETS Connections

5.3.1 Direct connections 5.3.2 Indirect connections 5.4 Heat Exchanger Considerations

5.4.1 HEX temperature requirements 5.4.2 HEX pressure requirements 5.4.3 HEX redundancy requirements 5.4.4 HEX performance efficiency 5.4.5 Other HEX considerations 5.5 Control-Valve Considerations

5.5.1 Location and applications

5.5.2 Control-valve types and characteristics Pressure-dependent control

Pressure-independent control 5.5.3 Control-valve sizing

5.5.4 Actuator sizing and selection 5.5.5 Quality and construction 5.6 ETS and Building Control Strategies

5.6.1 Supply-water temperature and reset

5.6.2 Supply-air temperature and reset at cooling coils 5.6.3 Building pump and ETS control-valve control 5.6.4 Capacity control after night setback

5.6.5 Staging multiple heat exchangers 5.7 Metering and Submetering

5.7.1 Introduction 5.7.2 Meter types

Dynamic meters Static flow meters

5.7.3 Designing for meter installation and maintenance 5.7.4 Standards

5.7.5 Other equipment 5.7.6 Submetering

Meter reading

Conclusions about submetering

6. Chilled-Water Distribution Systems 6.1 Hydraulic Design

6.1.1 Hydraulic model

6.1.2 Customer loads and system diversity 6.1.3 Startup and growth

6.1.4 Piping layout 6.1.5 Delta T 6.1.6 Pipe sizing 6.2 Pumping Schemes

6.2.1 Variable primary flow

Special considerationsfor district cooling systems

Design considerations

When to use variable primary flow 6.2.2 Primary-secondary pumping 27

29

29

29

30 31

32

33 33 34 34 35 35 35

36

36

36

37

37

38 38 38 38

39

39

39

40

40

40

40

40

41 41 42 42 42 42 43 45 45 45 45

46

46

46

47

47

48

49

49

50

50

(9)

DISTRICT COOUNG BEST PRACnCEGUIDE e2008lnremarionalDi5frkt EnergyAllooiltion.Allrightste5ervro.

When to use primary-secondary pumping 6.2.3 Distributed pumping

6.2.4 Booster pumps 6.3 Pump and Pressure Control

6.3.1 Distribution pumps 6.3.2 Variable-frequency drives 6.3.3 Differential pressure control 6.3.4 Pump dispatch

6.3.5 System pressure control and thermal storage 6.4 Distribution System Materials and Components

6.4.1 Pipe materials Welded-steel pipe HDPE pipe Ductile-iron pipe GRP pipe

Pipe material selection summary

Steel pipe HDPE pipe Ductile-iron pipe GRP pipe 6.4.2 Isolation valves Valve chambers

Direct-buried isolation valves Cost considerations

6.4.3 Branch connections/service line takeoffs 6.4.4 Insulation

Evaluating insulation requirements

Pre-insulated piping insulation considerations

6.4.5 Leak-detection systems Sensor-wire leak detection Acoustic leak detection Software-based leak detection 7. Chilled-Water Plants

7.1 Chilled-Water Production Technologies 7.1.1 Compression chillers

Reciprocating Rotary Centrifugal

Centrifugal-chiller capacity control Inlet guide vanes

Variable-speed drive (VSD) Hot-gas bypass

Meeting low loads 7.1.2 Natural gas chillers 7.1.3 Absorption chillers

Pros and cons

Efficiency Capacity derate Capital costs Equipment manufacturers Operating costs 7.1.4 Engine-driven chillers

ix

51 51 52 52 52 53 53 53 54 55 55 55 56 57

58

58

58

58

59

59

59

59

59

61 62 62 62 63 64 64 65 65 66 66 66 66 66 66 66 66 66 67 67 67

68

68

69

69

69

69

70

70

(10)

DISTRICTCOOUNG BESTPRACTICE GUIDE

C2008International Di5tn"d Energy A55odation. Allriglll5re~.

7.1.5 Combined heat and power (CHP) 70

7.1.6 Choosing chiller type in the Middle East 71

7.2 Thermal Energy Storage (TES) 71

7.2.1 Thermal energystorage (TES) types 72

Chilled-water thermal energy storage 72

Ice thermal energy storage 72

Low-temperature fluid thermal energy storage 72

7.2.2 Thermal energystorage benefits 72

Peak-load management 72

Energy efficiency 72

Capital avoidance 72

Operational flexibility 73

7.2.3 Thermal energy storage challenges 73

Sizing 73

Siting 73

Timing 74

7.3 Plant Configuration 74

7.3.1 Chiller sizing and configuration 74

7.3.2 Series-counterflow configuration 74

7.4 Major Chiller Components 75

7.4.1 Motors 75

Enclosure types 75

Standard motor enclosure costs 76

Inverter-duty premium 76

Motor efficiency 76

Motor physical size 76

Voltage options for chiller motors 76

7.4.2 Heat exchanger materials and design 77

7.5 Refrigerants 78

7.6 Heat Rejection 79

7.6.1 Overview of condenser cooling options 79

7.6.2 Optimum entering condenser-water temperature 80

7.6.3 Cooling tower considerations 80

Cooling tower sizing 81

Cooling tower basins 82

7.6.4 Condenser-water piping arrangement 83

7.7 Water Treatment 83

7.7.1 Water supply 83

Potable water 83

Treated sewage effluent 83

Seawater in a once-through arrangement 84

Seawater astower makeup 84

Seawater treated using reverse osmosis or other desalination technologies 85

7.7.2 Treatment approaches 85

Chilled water 85

Treatment approach 85

Dosing and control 86

Condenser water 86

Treatment approach 86

Dosing and control 86

Legionella control 87

7.7.3 Zero liquid discharge 87

7.7.4 Service standards 87

(11)

DISTRICT COOUNG BEST PRACfICE GUIDE

e2008Inremauonal Di,lIict EnergyAsm:i<!UOfl. All righ15teserved.

7.8 Balance of Plant

7.8.1 Piping design for condenser water 7.8.2 Sidestream filters

7.8.3 Cooling tower basin sweepers

7.8.4 Transformer room cooling

7.8.5 Equipment access 7.8.6 Noise and vibration 7.9 Electrical Systems

7.9.1 Short-circuit study

7.9.2 Protective device coordination study 7.9.3 Arc flash hazard study

8. Controls, Instrumentation and Metering 8.1 Introduction

8.2 Definitions

8.3 Overview

8.3.1 Typical DClCS functions 8.3.2 General design factors 8.3.3 DCICS evaluation performance 8.4 Physical Model

8.4.1 Sites 8.4.2 Plants

8.4.3 Local plant I&C system Local plant controllers Field devices

Local operator interface terminals Local workstations

8.4.4 Command centers

Data server Historical server

Command center workstations Terminal server

Other servers and workstations

8.5 Logical Model 8.5.1 Level

a

8.5.2 Levell 8.5.3 Level 2 8.5.4 Level 3 8.5.5 Level 4 8.5.6 Level 5 8.6 Sample DCICS

8.7 Level

a-

Best Practices

8.7.1 Point justification

8.7.2 Criteria for device selection

8.7.3 Redundant Level

a

equipment

8.7.4 Local instrumentation

8.7.5 Localized overrides for each controlled component 8.7.6 Good installation practices

8.8 Levell - Best Practices

8.8.1 Levell field instrumentation 8.8.2 I/O modules and racks 8.8.3 Onboard chiller controllers 8.8.4 Variable-frequency drives

xi

88 88 88 90 90 90 90 91 91 91 91

92

92 92 92 92 93 93 93 93 93 93 93 95 95 95 95 95 95

96

96

96 96 96 97 98 99 99 100 101 101 101 102 102 106 106 106 106 106 106 107 108

(12)

DlSTRIO COOUNG BEST PRAOICE GUIDE

C2008lntefmJUon~1District. fne.gyAssociaUon. Allrights reserved.

8.8.5 Energy monitoring equipment 8.8.6 Metering and submetering

8.8.7 Redundant Level 1 field instrumentation 8.8.8 Levell network best practice considerations 8.8.9 Levell data considerations

8.9 Levels 0 & 1 - Choosing Points to Monitor and Control 8.9.1 Example equipment segments

Primary-secondary systems Variable primary systems Chiller evaporators

Condenser-water systems

Cooling towers

Centrifugal chiller condensers Constant-speed pumps Variable-speed pumps Heat exchangers

8.9.2 Level 0 vs. Levell - field instrumentation 8.10 Level 2 - Best Practices

8.10.1 Types of controllers 8.10.2 Selection criteria 8.10.3 Distributing controllers 8.10.4 Controller redundancy 8.10.5 Critical data integrity

8.10.6 Time-of-day synchronization between controllers 8.10.7 Controller power requirements

8.11 Level 3 - Best Practices

8.11.1 Connecting local OITs to local controllers 8.11.2 Displaying metering data on local OITs 8.11.3 Environment

8.11.4 Local OIT power requirements 8.12 Level 4 - Best Practices

8.13 Networking Best Practice Considerations 8.13.1 DCICS network categories 8.13.2 Level 2+ network infrastructure

Fiber optics Wireless Internet

8.13.3 Remote control vs. manning individual plants 8.13.4 Sophistication

8.13.5 Performance 8.13.6 Security

8.13.7 Physical network topologies 8.13.8 Network monitoring via OPC

8.13.9 Network bridging and controller pass-through 8.13.10 DCICS network and Level 4 equipment ownership 8.13.11 DCICS Level 2+ network component power requirements 8.14 Control Functions

8.15 Human-Machine Interface Functionality 8.16 Standardization

8.17 Standard Design Documents 8.18 Standard Testing Documents

xii

108 108 110 110

110

110

111

111 113 115 116 117 118 119 120 121 122 122 122 123 123 123 124 124 124 125 125 125 125 125 125 125 125 129 129 129 130 130 130 130 130 131 131 131 132 132 133 133 133 134 135

__

(13)

DISTRICT COOLING BEST PRACTICE GUIDE C2008lnremaliooalDirtrktEnergyA550darion,Allri9hl'.ireserved.

9. Procurement and Project Delivery 9.1 Design/Bid/Build (DBB)

9.2 Engineer/Procure/Construct (EPC) 9.3 Packaged Plants

10. Commissioning Appendix

A - Abbreviations and Definitions B - Conversion Factors C - Arc Flash 136 136 137 137 140 A-1 B-1 C-1 Tables Table 2-1 Table 2-2 Table 3-1 Table 5-1 Table 5-2 Table 5-3 Table 5-4 Table 5-5 Table 6-1 Table 6-2 Table 7-1 Table 7-2 Table 7-3 Table 7-4 Table 7-5 Table 7-6 Table 7-7 Table 7-8 Table 7-9 Table 7-10 Table 7-11 Table 7-12 Table 8-1 Table 8-2 Table 8-3 Table 8-4 Table 8-5 Table 8-6 Table 8-7 Table 8-8 Table 9-1 Figures Figure 2-1 Figure 2-2 Figure 2-3. Figure 2-4 Figure 2-5

Combined-cycle power plant operation cost factors

Conversion of fuel prices in US$ per barrel oil equivalent (BOE) to US$ per MMBtu Summary of customer value

Typical coil (and delta T) performance as entering-water temperature varies

Sample heat exchanger differences with coldersupply-watertemperature and common building-side conditions

Tonnage capacity per heat exchanger

Recommended maximum chloride content (ppm) Control-valve applications and control points Impact of delta T on 990 mm (36") pipe capacity Impact of delta T on capacity of 1000 hp pump set

Summary of packaged chiller types and capacities (ARI conditions) Impact of delta T in operation on chilled-water storage capacity Inputs to series-counterflow example

Performance results for series-counterflow example Example dimensions and weights of motor types

Corrosion resistance and performance of condenser tube material options

Refrigerant phaseout schedule (Montreal Protocol, Copenhagen Amendment, MOP-19 adjustment) Inputs to low condenser flow example

Performance results for low condenser flow example (3 gpm/ton vs. 2.3 gpm/ton) Recommended monthly tests

Corrosion-coupon standards

Performance characteristics of sand filters vs. cyclone separators PLC vs. DCS - pros and cons

Level 0 best practice specifications Energy meter best practice specifications Keyto instrument tagging symbols Function identifier key

Level 0 vs. Level 1 field instrumentation - selection criteria Level 4 componentry best practicetips

DClCS network categories

Example detailed outline of Owner's Requirements Documents (ORDs) for engineer/procure/construct (EPC) procurement

Peak power demand reductions with district cooling World oil prices during the past 10 years

Oil prices in US$ per MMBtu

Projected impact of oil price on price of delivered liquefied natural gas

Long-run marginal costs of delivered electricity from new combined-cycle plantat a range of fuel prices

xiii

(14)

Figure2-6 Figure2-7 Figure3-1 Figure4-1 Figure 4-2 Figure4-3 Figure4-4 Figure4-5 Figure4-6 Figure4-7 Figure5-1 Figure5-2 Figure5-3 Figure5-4 Figure5-5 Figure5-6 Figure5-7 Figure

5-8

Figure5-9 Figure5-10 Figure5-11 Figure5-12 Figure5-13 Figure5-14 Figure

6-1

Figure6-2 Figure6-3 Figure6-4 Figure6-5 Figure6-6 Figure6-7 Figure

6-8

Figure 6-9 Figure

6-10

Figure6-11 Figure6-12 Figure6-13 Figure7-1 Figure7-2 Figure

7-3

Figure7-4 Figure7-5 Figure7-6 Figure7-7 Figure 7-8 Figure

7-9

Figure7-10 Figure7-11 Figure7-12 Figure7-13

DISlRlcr COOUNG BEST PRAcrlCE GUIDE

1:12008 inlemaliOfliJiDi.lridEnergyA>soda/i·Ofl. All right>re>erWd.

Example of time-of-day power rates compared with power demand, per New England Hourly Electricity Price Index

Annual electric energy consumption savings with district cooling Examples of Middle East district cooling rates

Design dry-bulb and mean-coincidentwet-bulb temperatures for selected Middle East cities (ASHRAE 0.4% design point)

Design wet-bulb and mean-coincidentdry-bulb temperatures for selected Middle East cities (ASHRAE 0.4% design point)

Example peak-day load profilesfor various building types

Illustrative peak-day load profile for district coolingservinq mixed building types Illustrative district coolingannual load-durationcurve

Effect of increased delta T on LMTD of cooling coils Paths for potential utility integration

Expected coil performance over the design flow range for typical coil Decoupled direct ETS connection

Simplified direct ETS connection

Indirect ETS connection (with combined HEX control valves) Indirect ETS configuration (with dedicated HEX control valves) Plate-and-frame heat exchanger installation

Plate-and-frame heat exchanger (courtesy Alfa Laval) HEX surface area vs. "approach"

Importance of critical customer design Pressure-dependent "globe" valve Common control-valve characteristics

Pressure-independent control valve (courtesy Flow Control Industries) Submetering system via fixed wireless

Submetering system with an RF handheld terminal Impact of delta T on hydraulic profile

Variable primary flow

Traditional primary-secondary system All variable primary-secondary system Distributed primary-secondary system

Thermal storage tank used for maintaining static pressure in system Weld-end ball valve

Weld-end butterfly valve

Direct-buried valve with mechanical actuation Direct-buried valve with hydraulicactuator Sluice plate hot tap

Example of estimated average ground temperatures at various depths

Distribution system supply-water temperature rise for example system at part load Single-effect absorption cycle (courtesy York/Johnson Controls)

Engine-based CHP with electric and absorption chillers (courtesy York/Johnson Controls) Turbine-based CHP with electric and steam-turbine-drive chillers

Load-leveling potential with thermal energy storage Lift in single and series-counterflowchillers Enclosure premiums above open drip-proof Inverter-duty motorcost premium

Motor efficiency

Refrigerant environmental impact comparison Counterflow cooling tower

Crossflow cooling tower

Chiller and tower kW/ton vs. ECWT

(15)

DISTRICT COOLINGBEST PRACTICE GUIDE

C2008 International Di5trid EnergyA'isociation. Alln9h~resevea.

Figure 7-14 Figure 7-15 Figure 8-1 Figure 8-2 Figure 8-3 Figure 8-4 Figure 8-5 Figure 8-6 Figure 8-7 Figure 8-8 Figure 8-9 Figure 8-10 Figure 8-11 Figure 8-12

Pumps dedicated to specific condensers Condenser pumps with header

DClCS physical model . DClCS logical model

Sample DClCS system Primary-secondary systems

Variable primary system instrumentation

Chiller evaporator supply and return instrumentation

Condenser-water system instrumentation Cooling tower instrumentation

Chiller condenser supply and return instrumentation Constant-speed pump instrumentation

Variable-speed pump instrumentation

Heat exchanger instrumentation

(16)
(17)

DISTRICT COOUNG BEST PRACTICE GUIDE C2008lnremab'onal Di5rrid EnergyA55OOalion.Allnghtste5erved.

1. Introduction

1.1. Purpose

The purpose of the International District Energy

Association's

District Cooling Best Practice Guide

is to

facilitate the design of district cooling businesses and systems that are reliable, efficient and profitable. The guide is focused on a key district cooling growth market - the Middle East - that has some specific challenges due to climate, the nature of the loads and the pace of development.

The guide is not a set of standards, nor isit an encyclopedia covering every detail of district cooling systems or a detailed design and specification guide. Rather, it is intended to share insights into key design issues and "lessons learned" from the recent development and operation of district cooling systems, particularly in the Middle East.

It is important to emphasize that "best practices" will vary depending on a wide variety of case-specific

conditions, including

.seasonal and daily load characteristics;

.type of cooling load and any special reliability requirements(e.g., hospitals, computer servers, etc.);

• size of plant site and anyconditions or constraints

relating to the site (height restriction, air emissions,

noise sensitivities of neighbors, etc.);

.availability and prices of electricity, water and natural gas;

• local codes and regulations;

• underground conditions affecting pipe installation;

• organizational resources; and

.financial criteria and strategic goals of the district cooling company.

The intention of theDistrict CoolingBestPractice Guide

is to address the advantages and disadvantages of

design options, discuss the circumstances under which

a given option may be the best approach and suggest approaches to determining the optimal approach once key factors affecting a specific case are known.

The International District Energy Association envisions

this guide will be updated periodically as technologies and the district cooling industry evolve.

1.2. Overview and Structure

of the Guide

The next chapter, Chapter 2 - Why District Cooling?, is a review of the rationale for district cooling, including

its benefits for customers, governments and the environment. It is useful to review the drivers behind

the establishment of district cooling systems so that discussion of business and technology best practices relate to the key reasons such systems are developed.

Chapter 3 - Business Development presents key topics on the business side of district cooling, including the

fundamental importance of approaching district

cooling as a utility business. This viewpoint has implications for designing all aspects - technology, business and operating structure - of the district cooling company. Other critical business considerations,

including marketing and communications, risk management and rate structures are also covered.

Chapter 4 - Design Process and Key Issues covers

essential pre-design tasks with enormous cost and risk

implications, suchas load estimationand the fundamental design parameters that have significant technical and cost implications for all elements of a district cooling system, such as design supply and return temperatures. It also suggests approaches to master planning complex district cooling systems and the critical and often-difficult topic of obtaining permits to develop the district cooling system. The challengesand opportunities of integrating district cooling system planning and design with other infrastructure are discussed. This chapter closes with an emphasis on the importance of designingwith long-term

operation and maintenance in mind, consistent with

the philosophy that successful district cooling systems must be approached as a utility business.

Chapter 5 focuses on building cooling system design

and energy transfer stations or ETS (interface

between the distribution system and the building). Chapters 6 and 7 address district cooling distribution systems and plants.

Although these discussions may appear to be presented out of order, this structure was deliberately chosen for

several reasons. First, satisfaction of comfort

require-ments is the ultimate business and technical purpose

of district cooling systems, so success is not possible

without good design on this end. Second, the

economic performance of district cooling systems is

dependent on sound performance of building systems, particularly delta T (temperature difference between supply and return). The economic implications of delta T are large and pervasive.

Chapter 8 - Controls, Instrumentation and Metering ties the ETS, distribution and plant systems together. The guide concludes in Chapters 9 and 10 with discussions of options for project procurement,

deliv-ery and commissioning.

A summary of abbreviations and definitions and a list of conversion factors are provided as appendices. A vari-ety of units are used in this document, consistent with

(18)

DISTRICTCOOLING BEST PRACTICE GUIDE

e2008InremaliooalDi5ln'dEnergyk:5ociarioo. Ai!nghl5 reserved.

2. Why District Cooling?

District cooling is being implemented worldwide by

many different kinds of organizations, including

investor-owned power utilities, government-owned

utilities, privately owned district energy companies,

universities, airports and military bases. District cooling

systems serve a wide variety of types of buildings, including commercial offices, residential, hotels, sports arenas, retail stores, schools and hospitals.

District cooling is growing rapidly for many reasons, including

• increasing demand for comfort cooling, due to

construction of many new buildings that are "tighter" than older buildings and contain more

heat-generating equipment such as computers; • a growing trend toward "outsourcing" certain

op-erations to specialist companies that can provide these services more efficiently;

• reductions in peak electricity demand provided by

district cooling;

• environmental policies to reduce emissions of air

pollution, greenhouse gases and ozone-depleting refrigerants; and

• most important, the customer value provided by

district cooling service in comparison with

conven-tional approaches to building cooling.

2.1 Customer Benefits

When properly designed and operated, district cooling systems cost-effectively deliver a variety of benefits to

customers, including superior comfort, convenience,

flexibility and reliability.

2.1.1 Comfort

Comfort is the ultimate purpose of air conditioning. District cooling systems can help keep people more comfortable because industrial-grade equipment is used to provide a consistent and high-quality source of cooling. In addition, specialist attention is focused on optimal operation and maintenance of cooling systems - providing better temperature and humidity control than packaged cooling equipment and, therefore, a healthier indoor environment Buildings are quieter because there isno heavyequipment generating vibration and noise, making tenants happier and allowing them

to be more productive.

2.1.2 Convenience

District cooling is a far more convenient way to cool a

building than the conventional approach to air condi-tioning because cooling is always available in the pipeline, thus avoidingthe needto start and stop building cooling units. Fromthe building manager'sstandpoint,

it is attractive to be able to provide reliable comfort without worrying about managing the equipment, labor and materials required for operating and main-taining chiller and cooling tower systems. This allows

the manager to focus resources on more critical

bottom-line tasks, suchasattracting and retainingtenants.

2.1.3 Flexibility

The pattern and timing of cooling requirements in a building vary depending on building use and weather. With building chiller systems, meeting air-conditioning requirements at night or on weekends can be difficult and costly, particularly when the load issmall. With district cooling, these needs can be met easily and cost-effec-tively whenever they occur. Each building can use as much or as little cooling as needed, whenever needed, without worrying about chiller size or capacity.

2.1.4 Reliability

The building manager has a critical interest in reliability becausehe or she wants to keep the occupants happy and to avoid dealing with problems relating to main-taining comfort. District cooling is more reliable than the conventional approach to cooling because district cooling systems use highly reliable industrial equipment and can cost-effectively provide equipment redundancy. Staffed with professional operators around-the-clock,

district cooling companies are specialists with expert operations and preventive maintenance programs. A

survey conducted by the International District Energy Association (IDEA) shows that district cooling systems have a documented reliability exceeding 99.94%, which issignificantly more reliable than individual building

cooling systems.

2.1.5 Cost-effectiveness

Fundamental cost advantages

District cooling has numerous fundamental cost

advantages:

Load diversity

Not all buildings have their peak demand at the same time. This "load diversity" means that when cooling loads are combined in the district cooling system, more buildings can be reliably served at lower cost

Optimized operations

With district cooling, equipment can be operated at the most efficient levels, whereas with building cooling equipment, the units operate for most hours each year at less-than-optimallevels.

(19)

DISTRlcr COOUNGBEST PRACTICE GUIDE

02008Inh?mational Diwid EnergyAAoda~On.Allrigh~fe5erved.

Advanced technologies

District cooling also offers economies of scale to

implement more efficient and advanced technologies,

such as

• thermal energy storage (TES), which can further reduce peak power demand, save energy, enhance reliability and reduce capital expenses for both the

utility and its customers;

• natural gas-driven chillers;

• integration with wastewater treatment infrastructure

through use of treated sewage effluent (TSE) for

condenser cooling; and

• use of seawater for condenser cooling, either for

makeup water in cooling towers or for direct

condenser cooling.

Better staff economies

District cooling cost-effectively provides around-the-clock specialized expertise to operate and maintain the equipment required to reliably deliver building comfort. Customer risk management

For the real estate developer, district cooling systems reduce capital risk because no capital is tied up in the building for cooling equipment. Operating risks associated with operation and maintenance of building cooling equipment are eliminated, with more predictable costs. ln a competitive real estate market, buildings that consistently.provide superior comfort will attract and keep tenants and maintain a higher market value. Poor

indoor comfort is a primary reason for tenants to leave

a building or not renew a lease. District cooling providestechnical benefits that mitigate [ass of tenants.

Cost comparison

The costs of the conventional approach to cooling involve far more than the cost of electricity, as described below.

Capital costs

By choosing district cooling service, a building avoids a large capital investment for the total installed capital costs of a building chiller system, including

• construction cost of space for equipment;

• chiller and condenser cooling equipment; • pumps and controls;

.power utility connection fees and/or substation construction, asrequired;

• transformers and cables; • engineering services; and

• replacement capital costs.

Capital costsfor a building to connect to a district cooling

3

system are generally very low, encompassing piping,

valves, controls and, in many cases, a heat exchanger.

Some district cooling utilities require the customer to pay for the cost of extending pipe from the nearest pipe main to the building, while other utilities cover this cost so that the customer pays only for the piping, valves and ancillary equipment inside the building wall, With district cooling systems that distribute water at a lower-than-normal temperature (such as is possible with ice thermal energy storage or freeze-point depressant chemicals), it is possible to further reduce building costs. This is because such systems enable reductions in the size of fans and ducts due to the reduced temperature of air produced in air-handling

systems.

Annual costs

District cooling service allows the building manager to eliminate the annual costs of operating and maintaining a building chiller system, including

• electricity,

• scheduled annual maintenance, • periodic major maintenance,

• unscheduled repairs,

• refrigerant management, • spare parts,

• labor and

• management oversight.

lt is also appropriate to account for the opportunity cost of the income or amenity value of the building area or rooftop used for equipment. For example, if building chillerswould be located within the building, this space might othervvise be rentable (even for storage space), thereby generating revenue. Space used for roof-mounted chillers or cooling towers could instead be

used for tenant amenities such as a swimming pool.

Chillers located on the ground take up space that could be used for parking.

Further discussion and guidance regarding presentation of cost comparisons is provided in Chapter 3.

2.2 Infrastructure Benefits

2.2.1 Peak power demand reduction

The benefits that district cooling offers relative to power demand and annual energy are key advantages of the technology. Chiller equipment in the Middle East is typically subject to a difficult operating environment, including extreme heat, windborne sand and saline humidity. Equipment performance will degrade as the system ages, particularly if there is not an aggressive

maintenance program. Over time, the performance,

efficiencyand reliability of this equipment suffers, leading to high electricity demand, maintenance costs and, ultimately, to the need for equipment replacement.

(20)

DISTRICT COOUNG BEST PRACTICE GUIDE

02008lnrematiOl1al Dis!nCtEnergyAssociation.AllrightsreselW'd.

proper accounting of the total cost of power must include not only fuel and other operating costs, but also the cost of amortizing the capital to build power plants and deliver the power to customers.

Figure 2-1 summarizes representative peak electric

demand efficiencies of several major types of district cooling systems and compares them with representative peak demand of conventional air-cooled systems. District cooling reduces power demand in new

devel-opment by 50% to 87% depending on the type of

district

cooling technology used.

Capital

costs

of power

capacity

Figure 2-1. Peak power demand reductions with district cooling.

2.2.2 Reduction in government

power sector costs

District cooiing reduces the capital investment required

for additional power generation, transmission and

distribution infrastructure. District cooling also reduces

power sector operating costs. Because power costs are

typically subsidized in the Middle East, district cooling saves governments substantially both in capital invest-ment and in operating subsidies. In the long run, a A straight centrifugal chiller plant will cut peak demand (comparedwith the conventional air-cooled approach)by about 50%. The impact of thermal energy storage (TES) depends on the peak day load profile of the aggregate customer base. The graph illustrates a representative situation in a mixed-use development in the Middle East, in which TES reduced the peak power demand of the

district system by about 20%. Natural gas

district

cooling

can provide even more dramatic reductions in power

demand.Asdiscussed in Chapter 7, engine-driven chillers

are the most cost-effective gas-driven approach. Figure 2.1 shows the peak power demand of two gas-driven options: 100% gas-driven without TES and a hybrid in which 50% of the capacity is gas-driven, 40% is

electric-driven and 10% is TES. Power plant heat rate 7050 Btu/kWh

Generation efficiency 48.4%

Transmission/distribution losses 7.0%

Net efficiency 45.0%

Variable O&M 2.13 US$/MWh

Fixed O&M 12.93 US$/kW

Capacity factor 0.60

Average non-fuel O&M cost 4.59 US$/MWh

New power generation capacity in the Middle East is typically large [more than 250 megawatts (MW)] combustion turbine combined-cycle plants that use byproduct steam for desalination. Capital costs for power plants have increased dramatically since 2005 for

a variety of reasons, including significant increases in

materials costs and a very tight international market for qualified contractors, Through 2009, the estimated unit cost of power generation capacity is US$1,067 per kilowatt (kW). In addition, substantial investment must be made in transmission and distribution (T&D)facilities including substations. The estimated average costs of T&D infrastructure is US$296/kW, for a total generation and T&D cost of US$1 ,363/kW.

With variable operation and maintenance (O&M) costs of US$2.13/megawatt-hour (MWh), fixed O&M costs of US$12.93/kW and a capacity factor of 0.60, the average non-fuel O&M cost is US$4.59/MWh.

Table 2-1 summarizes operating cost factors for a new

combined-cycle power plant. New combined-cycle

power plants can reach maximum operating efficiencies

of more than 55% under ISO conditions (16 C or 60 F) outdoor air, 60% relative humidity and 1 atmosphere barometric pressure (14.7 psi). However, combustion turbine power output drops significantly as the ambient

air temperature increases. For Middle East conditions, combined-cycle generation efficiency is projected to be

48.4% [heat rate 7050 Btu/kilowatt-hour (kWh)]. With estimated T&D losses of 7.0%, the net (delivered)

efficiency is 45.0%.

Power sector operating costs

Table 2-1. Combined-cycle power plant operation cost factors. District cooling (50% gas-fired with TES) District cool1ng (100% gas-fired) District cooling (electricwilh TES) District cooling (electric) 2.00 '2 1.75

s

1.50 ~

~

1.25· 0 c

E 1.00

0

~

0.75 0 ~

0.50

c, 0.25 0 Air-cooled building systems

(21)

DISTRlcr (OOUNG BESTPRAcrlCE GUIDE

e2008 lt1remaUonal DiS!fiaEt1f!i9y Am'(;aUon.All right>re5efVed,

Fuel for power generation may be natural gas or oil depending on available resources. Although a state-owned power utility may buy fuel very cheaply from a state-owned company, it is worthwhile to reflect on the opportunity cost of using that fuel to produce power to run inefficient chillers. Certainly, oil could instead be sold at the increasingly high international price. (See Figure 2-2.) Figure 2-3 illustrates the conversion of oil prices from u.S. dollars per barrel to u.S. dollars per million Btu. The same data is shown in tabular form in Table 2-2.

160

140

120

·0 ~

100

0 ~

I~

:;

80

.0

IJ

J

c,

60

I,P

'J.{

..

'"

::>

40

,.I'

f i

~

'"

v\

20

rw-

IY

0

eo 0> 0 ~

'" '"

..,

"' '"

....

eo

% %

~

'I

~ ~ ~ ~

0 'I 0 0>

in

0>

in

,

,j!

,

,

, , , ,

, ,

,j!

«

« «

-c

« « « «

-c

Figure 2-2. World oil prices during the past 10 years.

If natural gas is the power generation fuel, it also has

an international market value to an increasing extent.

Natural gas demand is growing worldwide, driven by rapidly growing energy requirements in China, India and other developing nations, continued growth in

industrialized countries and declining domestic reserves

in the u.s. The natural gas market is becoming a

competitive, market-driven sector with a trend toward

liquefaction and export. These trends mean that the market price for natural gas will trend upward as it becomesan increasingly tradable commodity as liquefied natural gas (LNG) in international markets.

5

30 25

V

V

20

~

/ '

/'

~ ~ 15

0.

/ '

/ '

~ 10 ~ , / ::>

/ '

. / 5 . / /

1/

0 ~ ~ l),~ '!>~ Il?

':P

r§> '\~

*

c§>.sP ....

~ ~ ¢~

.:P

,&

US$ per barrel ofoil

Figure2-3. Oil prices in US$ per MMBtu.

US$ per barrel of US$ per million Btu

oil equivalent (BOE) (MMBtu)

0 0 10 1.72 20 3.45 30 5.17 40 6.90 50 8.62 60 10.34 70 12.07 80 13.79 90 15.52 100 17.24 110 18.97 120 20.69 130 22.41 140 24.14 150 25.86

Table 2-2. Conversion of fuel prices in US$ per barrel oil equivalent (BGE) to US$ per MMBtu.

Long-term infrastructure choices made by Middle Eastern governments should be made based on the recognition that, although power generation fuel can be "priced" internally at a low level, the value of that energy will be significantly higher. In other words, there will be an

increasing "opportunity cost" associated with using

available naturalgasfor power generation insteadof using it for higher value uses or exporting it as LNG.

Natural gas or LNG pricesare frequently tied to oil prices. Figure 2-4 shows the projected impact of changes in oil prices on the price of delivered LNG, based on extrapo-lation from analysis of historical price data.'

Asillustrated in Figure 2-2, oil pricesjumped substantially

between early2007 and mid-2008.Asthis report goes to

print, world oil priceshave pulled back from the highs set in July 2008. However, in the mid-term (2010-2015), the

(22)

DISTRICT COOLING BEST PRACTICE GUIDE

e2008Infema(ional DiWictEnergy A550cialion. Alln'ght>re5efVed.

price floor is likely to exceed US$140/barrel. Based on Figure2-4, delivered LNG prices can be expected to seek a mid-term levelof US$9/MMBtu to US$18JMMBtu,with an average value of US$13.50/MMBtu.

Excluding the costs of liquefaction, transportation and regasification, the estimated average "opportunity cost" of natural gas in the mid-term is US$9/MMBtu, equivalent to about US$50/barrel of oil equivalent (BOE). In other words, this is the lost revenue if gas in hand is burned instead of sold into the LNG market and is an appropriate basis for long-term valuation of fuel used in Middle Eastern power plants.

In discussion of fuel prices, prices are

referred to

in

terms of dollars per BOE, or the cost of the energy in one barrel of oil. Conversion of fuel prices between U.S. dollars per BOE, U.S. dollars per MMBtu and BOE per MMBtu is summarized in Table 2-2 shown earlier.

$30

~

:; $25 :;

"

- -High ~ Co $20

..

...

-Average

~

,

" ,

0 $15

,

• • • Low

" ,

.§.

",'

" ,

...

o

.

.

z

$10

,

.

-'

...

"

~ $5

...

~

0;

c

$0 $80 $100 $120 $140 $160 $180 $200

Oilprice(US$ perbarrel)

Figure 2-4. Projected impact of oil priceon price of delivered liquefied natural gas.

Total costs of electricity

Governments cannot make good decisions about

allocating capital and natural resources unless all of the long-run marginal costs of generating and delivering power are considered, including amortized capital and the market value of fuels in the context of long-term world energy prices.

Figure 2-5 shows the long-run marginal costsfor electricity in the Middle East under a range of fuel cost assumptions. "Long-run marginal costs" are the total costsof providing an additional kilowatt-hour of energy output over and above any energy currently being produced, and they include all capital and operating costs. Thesecalculations reflect the total costs of building and operating highly efficient new combined-cycle power plants and power

transmission and distribution infrastructure, based on the

capital and operating costs discussed above. A capacity

$20 $2S $3a $40 $5a $6Cl $70 $all $90 $100 Power plant fuel(US$ per barrel 01equivalent)

Figure 2-5. Long-run marginalcosts of delivered electricity from new combined-cycle plant at a rangeof fuel prices.

factor of 60% was assumed. Capital costs were amortized assuminga weighted average cost of capitalof 8.7% over a 20-year term, based on 70/30 debt/equity ratio, 6.0% debt interest rate and 15.0% return on equity.

Power utility recognition of district cooling benefits

Governments throughout the Middle East are grappling with the challenge of meeting rapidly growing power demands. While district cooling is viewed as beneficial in this regard, there is generally no recognition of its benefits in the structure and levels of power tariffs. Most power rates continue to be subsidized and generally do not

incorporate incentives to reduce peak power demand.

Power utilities in North America, Europe and other

regions often encourage peak power demand reduction through the rate structure or with special incentives.

Examples of this include the following:

.A

portion of the cost of service, particularly for large

users, may be paid in a demand charge (or capacity charge).

• Rates during the high-load summer season are often set above the rates for other parts of the year. • Rates during high-load times of day are higher

than low-load periods (time-of-day rates). • Utilities sometimes provide a capital incentive to

install technologies such as thermal energy storage, which is tied to the number of kilowatts of peak demand reduced.

(23)

DISTRICTCOOLING BESTPRACTICE GUIDE

C2008InremaUonal DismcrEnergyA55fxiab'on. Allnghl5re~.

Use of demand charges, seasonal and time-of-day rates anddemand reduction incentives betterreflects the actual cost of service and gives appropriate "price signals" to users, leading to optimaluse of capital andfuel resources. In a competitive electricity market, costs of power production can varysignificantly from day to night, and thisisreflected in market-based powerrates. For example, prices from the New England Hourly Electricity Price Index are shown as bars in Figure 2-6, measured against the scale on the right (in US$/kWh). Not surprisingly, the highest prices occurin the period of highest demand (as indicated by the curved shaded area).

~ 2.00 ~

s

1.75

8-i

1.50 & c 1.25

~

c 0 1.00

;;.

E ~ 0.75 8 0 0.50 B g 'a

..

,

0.25 c ~

Figure2-7. Annual electric energy consumption savings with districtcooling.

The bottom line is thatthere are sound economic reasons to structure power rates to better reflect actual costs, and that doing so will increase the value of district cooling generally andTES in particular.

Air-cooled buildll\{i systems District cooling (electric) District cooling (electricwilh TESI District cooling (100%gas-fired) District cooling (50% gas-fired with TES)

""

$0.70

...

saee ~.~

...

~

~ $0.40:t

,

..

,

~.~

,

..

'01'

~o $D.l0 0 $D.oo ,,~

..

~

/'

...

il"' "

..

~;f'

Figure 2-6. Example of time-of-day power rates compared with power demand, per New England Hourly Electricity Price Index.

2.3 Environmental Benefits

District cooling can help the environmentby increasing energy efficiency and reducing environmental emissions, including air pollution, the greenhouse gas carbon dioxide (C02) and ozone-destroying refrigerants.

2.3.1 Energy efficiency

Figure 2-7summarizes representative annual electric energy efficiencies of several majortypes of district cooling systems and compares them with a representative annual efficiency of conventional air-cooled systems. District cooling reduces annual electricity consumption in newdevelopment by45% to 86% depending on the type of technology used. Note that although gas-driven district cooling drastically reduces electricity consumption, these systems require the consumption of natural gas at the plant.

7

A substantial portion of energysavings results from the fact that almost all district cooling systems use water to cool the chiller condensers, an inherently more efficient process than air cooling. District cooling systems are increasingly being designed so that no water isrequired from the municipal water system. Instead, these systems employ a variety of technologies, such as

• using seawaterto cool the condensers directly(the water actually runs through the chillers),

• using seawater for cooling tower makeup, .conditioning water by reverse osmosis desalination

for use in cooling towers and

.using treated sewage effluent (TSE) for cooling tower makeup.

District cooling's superior energy efficiency results in reduced fuel consumption, with corresponding reductions in emissions of air pollution and C02 (the greenhouse gas that causes global warming).

2.3.2 Climate change

Most Middle East countries are parties to the United Nations Framework Convention on Climate Change. With growing international interest in strong action on climate change, and with generally high emissions per capita in the Middle East, climate change will become an increasingly important issue for the Middle East governments.

TheKyoto Protocol, an international agreement to control greenhouse gas emissions, isexpected to be replaced by a more aggressive treaty with broader participation. It is widelyexpected that future international agreements will lead to worldwide greenhouse gas emissions trading, po-tentially providing economic incentives for energy-effi-cient technologies such as districtcooling. The ultimate cost of allowances will depend on manyfactors, includ-ing the level of greenhouse gas reduction commitments

(24)

DISTRICT COOUNG BEST PRACTICE GUIDE

C2008lnremaUonal Distrid Energy A55ociab'OI1. Allright> re>erVed.

and the specific rules of the "cap-and-trade" programs.

A number of corporations are using "shadow prices"

(an assumption of C02 emissions cost for the purpose of comparing options) of at least US$g/metric ton.

Prices in the European Union emissions trading system,

still in the beginning stages of implementation, averaged US$25/metric ton of C02 equivalent in 2006, spiked to almost US$40 in early 2006, then tumbled to US$12 later in 2006. Some studies conclude that an emissions value of US$l OO/metric ton will be required to bring greenhouse gas emissions down to a safe level.2

2.3.3 Ozone depletion

Chlorofluorocarbon (CFC) refrigerants used in chillers destroy the stratospheric ozone layer.The ozone layer's

destruction is of serious international concern because

this layer protects the earth from harmful ultraviolet radiation which can cause human health and environ-mental damage, including increased incidence of skin

cancer, cataracts, immune system suppression, damage

to crops and other impacts. CFCs and some other

refrigerants also act as greenhouse gases.

International agreements phased out the production of CFCs as of January 1996 and have scheduled the phaseoutof hydrochlorofluorocarbon(HCFC) refrigerants. Hydrofluorocarbons (HFCs) and ammonia, which are also used as refrigerants, are not restricted by interna-tional protocols.

District cooling can be a key strategy for accomplishing

an economical and environmentally wise phaseout of

harmful refrigerants. Through their better staffing and operational practices for monitoring and control, district cooling systems are better able to control

emissions of whatever refrigerant is used.

1"A Formula for LNG Pricing," Gary Eng, December 2006. 2 "Stern Review on the Economics of Climate Change,"

References

Related documents

Online community: A group of people using social media tools and sites on the Internet OpenID: Is a single sign-on system that allows Internet users to log on to many different.

UC-Paid Life Insurance: Appointed 50% or more for a year or more and participating in a university retirement plan. UC-Paid Disability Insurance: Appointed 50% or more for a year

For the poorest farmers in eastern India, then, the benefits of groundwater irrigation have come through three routes: in large part, through purchased pump irrigation and, in a

to effect a transfer of any immovable property, or of any movable property other than debentures issued by, or shares in, a company, shall, if the

Four basic themes emerged from the analysis; social and cyber arrangements within the Dublin Chemsex scene; poly drug use and experiences of drug dependence; drug and sexual

The PROMs questionnaire used in the national programme, contains several elements; the EQ-5D measure, which forms the basis for all individual procedure

A very large kinetic isotope ef- fect accompanied by an unusually strong carbon isotope frac- tionation between biomass and inorganic carbon, was observed during aerobic

In addition to its internal political problems, Pakistan also faces the issue of al-Qaida and Taliban training camps positioned in its literal back yard, the Federally