Page 1 of 6
This document provides additional assistance with wiring your Extron IP Link enabled product to your device. Different components may require a different wiring scheme than those listed below.
For complete operating instructions, refer to the user’s manual for the specific Extron IP Link enabled product or the controlled device manufacturer supplied documentation.
Minimum Software and Firmware Requirements:
IP Link Compiler
IP Link
Firmware GC Version
1.6.0 1.17 3.5.1
Version History:
Driver
Version Date Notes
8 9/24/2103 Extron Certified. Tested on QSE-CI-NWK-E. Updated driver to be compatible with GC 3.5.1
7 1/3/2012 Fixed delay issue when sending commands. 6 12/4/2012 Added model. Quantum System.
5 9/7/2011 Extron Certified. Added models QSNE-2DAL-D and QSN-4S16-S. Tested on both models.
4 5/27/2011 Extron Certified. Added model QSN-2ECO-S. Tested on QSN-2ECO-S. 3 10/1/2010
Extron Certified. Tested on QSE-CI-NWK-E system with a Grafik Eye, two seeTouch QS panels, and a Sivoia QS shade. Added models Sivoia QS and seeTouch QS. Added Button, Button Mode, Device select and Shade Position. 2 8/2/2010 Modified the driver to accept serial numbers
1 2/18/2010 Initial version.
Device Specifications:
Device Type: Lighting Control Manufacturer: Lutron
Firmware Version: Grafik Eye QS - CODE:5.30, BOOT:4.1, HW:2.1 QSE-CI-NWK-E - CODE:7.15, BOOT:2.9, HW:1.0 Sivoia QS - CODE:0.100, BOOT:2.9, HW:8.6 seeTouch QS - CODE:2.50, BOOT:2.3, HW:1.1 QSN-2ECO-S- CODE:5.17, BOOT:0.3, HW:3.1 QSNE-2DAL-D - CODE:5.8, BOOT:5.1, HW:3.1 QSN-4S16-S - CODE:5.15, BOOT:1.5, HW:1.1
Model(s): Grafik Eye QS, QSE-CI-NWK-E, Sivoia QS, seeTouch QS, QSN-2ECO-S, QSNE-2DAL-D, QSN-4S16-S, Quantum System
Page 2 of 6 Control Commands & States:
Area Level7 0 to 100 in steps of 1
Area Level (Step) 7 Up Down Stop
Area Scene7 0-32
Area Select4 1-200
Button 1-100
Button Mode1 Execute
Stop
Daylight Automation7 Active Inactive
Device Select 1-3
Fade 1-592
1-10 Min
15 Min
20 Min
Select
Integration ID7 1-200
Master Level (Step)1 Up Down Stop
Output Level7 0 to 100 in steps of 1
Output Level (Step) 7 Up Down Stop
Preset Scene 1-16 Off
Serial Digit 1-8 0-9 A-F
Shade Group Level7 0 to 100 in steps of 1
Shade Group Level (Step) 7 Up Down Stop
Shade Group Preset7 1-30
Shade Position 0-100
Zone Select3 1-100
Level 0-100 in steps of 1
Driver Notes:
Zone Select includes Fade Time; default Fade Time is 1 second. The Configuration Notes on pg.3 explain how to set up the driver.
Page 3 of 6 1
This command has press/release functionality. The stop command is used for configuration purposes
only.
2
This value is in seconds.
3
Zones 25-100 are for the QSN-2ECO-S. QSN-2ECO-S. Zones 1-32 are for the QSNE-2DAL-D, and
zones 1-4 are for the
QSN-4S16-S.4
When using the QSN-2ECO-S, select an area before sending the preset scene command. Only areas 1-32
will work on the QSNE-2DAL-D and 1-4 on the
QSN-4S16-S.7
Will only work with Quantum System.
Status Available:
Connection Status Connected Disconnected
Area Scene 0-32
Daylight Automation Active Inactive
Shade Group Preset 1-30
Output Level 0 to 100 in steps of 1
Preset Scene 1-16 Off
Level 0-100
Shade Position 0-100
Page 4 of 6 Configuration Notes:
1.
Use the Device Select command to select the type of device being controlled according to the
following table:
Device Select
Device
1
Grafik Eye QS
2 QS
Shade
3 seeTouch
QS
4 QSN-2ECO-S
5
QSN-4S16-S6
QSNE-2DAL-D2.
Next use Serial Digit 1-8 in the driver to match the serial digit on the device that you are trying to
control. This will have to be configured for every device in the system. For example, if the serial
number on a Grafik Eye is
00AC123D, then you will configure the Serial Digits in the driver as the following:Serial Digit 1 will be 0
Serial Digit 2 will be 0
Serial Digit 3 will be A
Serial Digit 4 will be C
Serial Digit 5 will be 1
Serial Digit 6 will be 2
Serial Digit 7 will be 3
Serial Digit 8 will be D
Note: If you are going to control/monitor another device, such as a QS Shade, then you also need
to configure the Serial Digits to match that device before controlling it and use the correct Device
Select in the driver.
3.
In addition to the first two steps, to control a seeTouch QS keypad or the front panel of a Grafik
Eye QS, you must select the button in the driver that corresponds with the buttons on the device.
See Appendix A in integration protocol or contact manufacturer to see what button number in the
driver corresponds to what button on the device.
4.
Light intensity levels on a Grafik Eye QS or
QSN-2ECO-S, QSNE-2DAL-D, or QSN-4S16-Scan be
changed by using the Level command in the driver. In order to change Level command, you must
select Zone Select and Fade commands. Level Status will only show level of currently selected
zone.
Page 5 of 6 Configuration Notes for Quantum System:
1.
Use the Device Select command to select the type of device being controlled according to the
following table:
Device Select
Device
7
Quantum System2.
Next use Integration ID 1-200 in the driver to match the device that you are trying to control. This
will have to be configured for every device in the system.
Page 6 of 6 Ethernet Driver Configuration Description:
Please refer to user manual for settings and changes to the network communication parameters such as: User Name, Passwords.
Notes for the Device: Network communication:
When configuring the Ethernet driver, be sure device settings match that of the GC configuration. Multi-connection can only work with 2 devices; the second user name is nwk2.
Port Type: Ethernet
Logon Credentials Supported:
Yes
Default User Name: nwk
Default Password:
N/A
Default Port: 23
Multi-Connection Capable:
Yes