Output Equations – Main Dimensions - KVA output for single and three phase transformers – Window space factor – Overall dimensions – Operating characteristics – Regulation – No load current – Temperature rise in Transformers – Design of Tank -Methods of cooling of Transformers.
3 3
INTRODUCTION:
A transformer is essentially a static electromagnetic device consisting of two or more windings which link with a common magnetic field.
The primary is connected to an alternating voltage source, an alternating flux is produced whose amplitude depends on the primary voltage and the no. of turns.
A transformer is not an energy conversion device, but a device that transforms electrical energy from one or more primary a.c circuits to one or more secondary a.c circuits with changed values of voltage and current.
The transformer is extremely important as a component in many different types of electric circuits, from small-signal electronic circuits to high voltage power transmission systems.
IMPORTANT FUNCTIONS OF A TRANSFORMER
:
Changing voltage and current level in an
electric system.
Matching source and load impedances for
maximum power transfer in electronic and
control circuitry.
5 5
PARTS OF A TRANSFORMER
7 7
CLASSIFICATION:
Based on construction,
i. Core type and ii. Shell type
Based on application,
i. Distribution and
ii. Power transformers.
CORE TYPE:
The magnetic core is built of laminations to form a rectangular frame.
The windings are arranged concentrically with each other around the legs or limbs.
9 9
The top and bottom horizontal portion of the core are
called yoke.
The yokes connect the 2 limbs and have a
cross-sectional area >or =to that of limbs.
Each limb carries one half of primary and secondary.
The 2 windings are closely coupled together to reduce
the leakage reactance.
The low voltage winding is wound near the core and the
h.v winding is wound away from the core in order to
reduce the amount of insulating materials required.
SHELL TYPE
:
The windings arte put around the central limb & the
flux path is completed through the 2 side limbs.
Central limb carries total mutual flux.
Side limbs form a part of a parallel magnetic circuit
& carry half the total flux.
The cross-sectional area of the central limb is twice
that of each side limbs
.
11 11
DISTRIBUTION TRANSFORMER:
These are transformers upto 200kVA(or 500kVA)
are used to step down distribution voltage to a
standard service voltage.
They are kept in operation all the 24 hours a day
whether carrying any load or not.
The load varies from time to time & it will be on no
load most of the time.
Distribution transformers are designed with less
iron loss and have a maximum efficiency at a load
much lesser than the full load.
It should have good regulation to maintain the
variation of supply voltage within limits. So it is
designed with small value of leakage reactance.
POWER TRANSFORMER:
Used in sub-stations and generating stations & have
ratings above 200kVA.
13 13
A substation has number of transformers working
in parallel.
During heavy loads all the transformers are put in
operation & during light loads some of them are
disconnected.
So power transformers should be designed to have
a maximum efficiency at or near full load.
Designed to have a greater leakage reactance to
limit fault current.
COMPARISON OF CORE TYPE AND SHELL TYPE:
CORE TYPE SHELL TYPE
1. Easy in design and construction.
2. Has low mechanical strength due to non-bracing of windings. 3. Reduction of leakage
reactance is not easily possible.
4. The assembly can be easily dismantled for repair work.
1. Comparatively complex. 2. High mechanical
strength .
3. Reduction of leakage reactance is not highly possible.
4. The assembly cannot be easily dismantled for repair work.
15 15 5. Better heat dissipation from
windings.
6. Has longer mean length of core and shorter mean
length of coil turn, hence best suited for EHV
requirements.
5. Heat is not easily
dissipated from windings, since it is surrounded by core.
6. It is not suitable for EHV requirements.
LOW VOLTAGE WINDING HIGH VOLTAGE WINDING
H
H L L H H L L H H L L H
CORE CORE
17 17
CROSS SECTION OF SINGLE PHASE TRANSFORMER
Ww
Hw
Ww W
w
Hw
CROSS SECTION OF CORE TYPE SINGLE PHASE
TRANSFORMER
CROSS SECTION OF SHELL TYPE SINGLE PHASE
TRANSFORMER WINDOW AREA WINDOW AREA WINDOW AREA CORE CORE
OUTPUT EQUATION OF SINGLE-PHASE TRANSFORMERS
The equation which relates the rated kVA output of
a transformer to the area of core and window is
called output equation.
In transformers the output kVA depends on flux
density & ampere turns.
The flux density is related to the core area and the
ampere-turns is related to the window area.
19 19 The induced emf in a transformer, E= 4.44fΦmT volt
Emf per turn, Et = E/T
= 4.44fΦm volts
The window in a single-phase transformer contains one primary and one secondary winding.
Window space factor Kw is the ratio of conductor area in window to the total area.
Kw = Ac / Aw
The current density is the same for both the windings.
So current density, δ= I
p/ a
p= I
s/ a
s Area of cross section of primary conductor, a
p= I
p/ δ
and
Area of cross section of primary conductor, a
s= I
s/ δ
Ampere turns, AT= T
pI
p= T
sI
sA
w= total window area ;
K
w= window space factor = A
c/ A
wA
c= conductor area
= K
wA
w21 21
The total copper area in the window:
A
c= Copper area of primary winding+ Copper area of
secondary winding
= (no. of primary turns × area of cross section of primary
conductor)+ (no. of secondary turns × area of cross
section of secondary conductor)
A
c= T
pa
p+ T
sa
s= T
pI
p/δ+ T
sI
s/δ (since a
p= I
p/ δ & a
s= I
s/ δ)
= ( T
pI
p+ T
sI
s)/δ
= 1/ δ (AT+AT)
= 2AT/ δ
On equating equation (1) & (2), we get KwAw = 2AT/ δ
Ampere turns, AT = KwAw δ/2
KVA OUTPUT OF SINGLE PHASE TRANSFORMER:
Rating in kVA ,Q = Vp Ip x 10 -3 (1Φ) = Ep Ip x 10 -3
= Ep ( Tp Ip )/ Tp x 10 -3 = Et AT x 10 -3
On substituting the value of Et & AT,
Q = 4.44 f Φm (Kw Aw δ ) /2 x 10 -3 where Φm = Bm Ai
23 23
OUTPUT EQUATION OF THREE-PHASE TRANSFORMERS
The induced emf in a transformer, E= 4.44fΦmT volt Voltage per turn, Et = E/T
= 4.44fΦm volt
In case of a three-phase transformer, each window contains two primary and two secondary windings.
The total copper area in the window:
Ac = 2Tpap + 2Tsas = ( TpIp+ Ts Is)2/δ = 4AT/ δ
since ap = Ip/ δ and as = Is / δ
since AT= TpIp = TsIs ( neglecting magnetizing current) Aw = total window area ;
Kw = window space factor = Ac / Aw Ac = conductor area = Kw Aw
= 4AT/ δ ampere turns, AT = KwAw δ/4
KVA OUTPUT OF THREE PHASE TRANSFORMER: Rating in kVA ,Q = 3 x Vp Ip x 10 -3 = 3 x Ep Ip x 10 -3 = 3 x Ep ( Tp Ip )/ Tp x 10 -3 = 3 x Et AT x 10 -3 Q= 3 x 4.44 f Φm (Kw Aw δ ) /4 x 10 -3 where Φm = Bm Ai = 3.33 f Bm Ai Kw Aw δ x 10 -3 Using the output equation it can also be shown that
E t = K √ kVA where K =√ 4.44 f r x 10 -3
r = Φm / AT
r is a constant for transformer of a given type ,service and
method of connection, since Φm determines the core section and AT fixes the total copper area.
25
Value of K
• ( 1.0 to 1.2) for single phase shell type
• 1.3 for three-phase shell type (power)
• (0.75 to 0.85) for single phase core type
• (0.6 to 0.7) for three phase core type (power)
Output Equations – Main Dimensions - KVA output for
single and three phase transformers – Window space
factor – Overall dimensions – Operating characteristics – Regulation – No load current – Temperature rise in Transformers – Design of Tank -Methods of cooling of Transformers.
27
WINDOW SPACE FACTOR
Defined as the ratio of copper area in the window of the total window area.
It depends upon the relative amounts of insulation and copper provided, which in turn depends upon the voltage rating and output of transformer.
Empirical formula:
For below 50kVA Kw=8/(30+kV) For 50kVA to 200kVA Kw=10/(30+kV) For 1000kVA Kw=12/(30+kV)
Where Kv is the voltage of high voltage winding in kv
MAIN DIMENSIONS
(i) Design of core.
(ii) Design of yoke.
29 29
DESIGN OF CORES
The core section of the core type transformer may be
rectangular, square or stepped.
Shell type transformers use cores with rectangular cross section.
In core type transformers with rectangular core the ratio of depth to width of the core is 1.4 to 2.
In shell type transformers with rectangular core the width of the central limb is 2 to 3 times the depth of the core.
When circular coils are required for high voltage transformers
,square and stepped cores are used .
Circular coils are preferred because of their superior mechanical characteristics.
CROSS-SECTION OF TRANSFORMER CORES RECTANGULAR CORE SQUARE CORE STEPPED CORE
31 31
SQUARE CORE:
Let d= diameter of the
circumscribing circle.
Also d=diagonal of the square
a= side of the square
Diameter of the circumscribing circle,
d = √a
2+a
2= √2a
2= √2a
Side of the square, a= d/√2
Gross area of the square, A
gi= area of the square=a
2=
(d/√2)
2= 0.5d
2Let stacking factor, Sf=0.9
a
a
a
Net core area, Ai=Stacking factor× Gross core area
= 0.9 × 0.5d
2=
0.45 d
2 Gross core area is the area including the insulation
area.
Net core area is the area of iron alone excluding
insulation area.
Area of circumscribing circle = Π /4d
2The ratio, Net core area/ Area of
circumscribing circle
33 33
The ratio, Gross core area/ Area of
circumscribing circle
= 0.5d
2/(Π /4d
2) = 0.64
Core area factor is the ratio of net core area and
square of the circumscribing circle.
Core area factor= Net core area/square of the
circumscribing circle
= Ai/d
2= 0.45d
2/d
2TWO STEPPED CORE (or) CRUCIFORM CORE:
In stepped core the dimensions of the steps should be
chosen, such as to occupy maximum area within a
circle.
The dimensions of the 2 step to give maximum area
for the core in the given area of the circle are
determined below:
Let, a= length of the rectangle.
b= breath of the rectangle.
d= diameter of the circumscribing circle.
Also
d=diagonal of the rectangle.
θ=Angle between the diagonal & the
length of the rectangle.
35 35 b d θ b a a b d θ b a b a-b/2 a-b/2 b b d θ
CROSS SECTION OF TWO STEPPED CORE
The maximum core area for a given d is obtained
when θ is maximum.
Cosθ= a/d; so a=dcosθ
(1)
sin θ= b/d; so b=dsin θ
(2)
The 2 stepped core can be divided into 3 rectangles.
The area of three rectangles give the gross core area.
Gross core area, A
gi= ab+[(a-b)/2]b+[(a-b)/2]b
= ab+ab-b
237 37
Substitute for a and b in equation (3),
A
gi= 2(dcosθ)(dsinθ)-(dsinθ)
2= 2d
2cosθsinθ-d
2sin
2θ
= d
2(2cosθsinθ-sin
2θ)
= d
2(sin2θ -sin
2θ)
= d
2sin2θ -d
2sin
2θ
(4)
To get maximum value of θ, differentiate A
giw.r.t θ ,
and equate to zero,
i.e.,d/dθ A
gi= 0
On differentiating equation (4) w.r.t θ we get,
d/dθ A
gi= d
2cos2θ×2- d
22cosθsinθ
So d
2cos2θ×2- d
22cosθsinθ =0
d
22cosθsinθ = d
2cos2θ×2
d
2sin2θ = d
2cos2θ×2
sin2θ/cos2θ =2
tan2θ= 2; 2θ=tan
-12
θ= 1/2 tan
-12 = 31.72°
When θ= 31.72°, the dimensions of the core will give
the maximum area for the core for a specified d.
a=d cosθ ; b=d sin θ
= d cos31.72; = d sin31.72
= 0.85d; = 0.53d
39 39
Substitute the values of a &b in equation (3) we get,
Gross core area, A
gi= 2ab-b
2= 0.618d
2Let stacking factor, Sf=0.9
Net core area, Ai=Stacking factor× Gross core
area
= 0.9 × 0.618d
2= 0.56d
2The ratio, Net core area/ Area of
circumscribing circle
= 0.56d
2/(Π /4d
2)= 0.71
The ratio, Gross core area/ Area of
circumscribing circle
= 0.618d
2/(Π /4d
2) = 0.79
Core area factor= Net core area/square of the
circumscribing circle
= Ai/d
2= 0.56d
2/d
241 41
CHOICE FLUX DENSITY and CURRENT DENSITY ( Bmand δ )
Bm determines the core area.
Higher Bm → smaller area → smaller Lmt → saving in the cost of iron and copper.
But higher Bm increases the iron loss and temp rise. For Distribution transformer Bm = 1.1 to 1.35 Wb/m2. For Power transformer Bm = 1.25 to 1.45 Wb/m2.
The area of conductors for the primary and secondary windings determined after choosing a suitable value for δ which depends on the method of cooling.
Current density value depends on method of cooling and range is 1.1 to 2.2 A/mm2
TYPES OF WINDINGS
Cylindrical winding with circular conductors.
Crossover winding with circular or rectangular
conductors.
Continuous disc type winding with rectangular
conductors.
43 43
DESIGN OF WINDING
The design of winding involves the
determination of
no. of turns & area of cross section
of the conductor
used.
The
no. of turns
is estimated using
voltage rating &
e.m.f per turns.
The
area of cross section
is estimated using
rated
current & current density.
Usually the no. of turns of L.V winding is estimated
first using the given data & it is corrected to the
nearest integer.
Then the no. of turns of H.V winding are chosen to
satisfy the voltage rating of the transformer.
Number of turns in a low voltage winding,
T
LV= V
LV/ E
tor AT/I
LVwhere,
V
LV= rated voltage of low voltage winding.
I
LV= rated current of low voltage winding.
Number of turns in a high voltage winding,
T
HV= T
LV× V
HV/ V
LVwhere,
V
HV= rated voltage of high voltage winding.
Rated current in a winding =
45
DESIGN OF YOKE
• The purpose of the yoke is to connect the
legs
providing a least reluctance path
. In order to
limit the
iron loss in the yoke
, operating flux density is
reduced by increasing the yoke area.
• Generally yoke area is made 20% more than the leg
area.
• In case of rectangular yoke ,
depth of yoke = the depth of core.
• In square or stepped ,
DESIGN OF YOKE
• Area of yoke =depth of yoke x height of yoke
= D
yx H
yD
y= width of largest core stamping = a
H
y=(1.15 to 1.25) A
gifor transformers using grain
oriented steel
47 47
OVERALL DIMENSIONS OF A TRANSFORMER
The main dimensions of a transformer are:Height of the window (Hw) and Width of the window (Ww) Other important dimensions are:
Width of the largest stamping(a)
Diameter of the circumscribing circle(d) Distance between the core centres(D) Height of the yoke(Hy)
Depth of the yoke(Dy)
Overall height of transformer frame(H) Overall width of transformer frame(W)
OVERALL DIMENSIONS
a = width of the largest stamping ;
d = diameter of the circumscribing circle;
D = distance between centres of adjacent limbs;
W
w, H
w= width and height of the window ( length of the
window);
Hy = height of the yoke;
For
core type
: D = d + W
w; D
y=a,
W = D+a ;
H = H
w+ 2 H
yWidth over two limbs=D + outer diameter of h.v.windings Width over one limbs=outer diameter of h.v.windings
49 49 For three phase transformers :
D= d + Ww , Dy=a, H=Hw+2Hy ;
W=2D+a;
Width over 3 limbs=2D+outer diameter of h.v.winding Width over one limb = outer diameter of h.v.winding For Single phase shell type :
Dy = b ; Hy = a ;
W = 2Ww+4a ; H = H w+ 2a
Output Equations – Main Dimensions - KVA output for single and three phase transformers – Window space factor – Overall dimensions – Operating characteristics – Regulation – No load current – Temperature rise in Transformers – Design of Tank -Methods of cooling of Transformers.
51
OPERATING CHARACTERISTICS
Resistance of winding
Lmts,Lmtp = length of primary & secondary windings,m;
rp,rs= resistance of primary and secondary winding respectively,m
Total I2 R loss in windings
Total resistance (per phase) of transformer referred to primary side
Per unit resistance
p mtp s mts p p p s
T L
T L
r
andr
a
a
2 2 c p p s sP
I r
I r
2 2 2.
p c s p p s p s p p sT
P
I
R
r
and r
r
r
I
I
T
p p r pI R
V
Leakage reactance of winding
The estimation of leakage reactance is the primarily the
estimation of the distribution of leakage flux and the resulting
flux leakages of the primary and secondary windings
The distribution of leakage flux depends upon the geometrical configuration of the coils and the neighboring iron masses and
permeability of the latter
Leakage reactance of core type transformer Leakage reactance of sandwich coils
Leakage reactance of core type transformer
Per unit leakage reactance
2
3
p s mt x o t cb
b
L
AT
f
a
E
L
53
Note on Reactance:
• Useful flux:
It is the flux that links with both
primary and secondary windings and is responsible
in transferring the energy Electro-magnetically from
primary to secondary side. The path of the useful
flux is in the magnetic core.
• Leakage flux:
It is the flux that links only with the
primary or secondary winding and is responsible in
imparting inductance to the windings. The path of
the leakage flux depends on the geometrical
configuration of the coils and the neighboring iron
masses.
Leakage reactance of sandwich coils
The idealized flux distribution in shell type transformers
Each of n coils is sandwiched between two coils of L.v.winding. Per unit reactance
6
p s o mt x tb
b
f
AT
L
a
n
E
w
55
Output Equations – Main Dimensions - KVA output for single and three phase transformers – Window space factor – Overall dimensions – Operating characteristics –
Regulation – No load current – Temperature rise in Transformers – Design of Tank -Methods of cooling of Transformers.
REGULATION
On no load the secondary terminal voltage Vp’=Vp. The drop in secondary terminal voltage from no load to full load can be calculated by using the phasor diagram.
At lagging power factor cos Φ,
Assuming that the angle θ between Vp and Vp’ is very small, we have
, 2 2
( cos sin ) ( cos sin )
p p p p p p p p p p V V I R
I X
I X
I R
sin
cos
' p p p p p pV
I
R
I
X
V
57
REGULATION
The p.u regulation, for full load rated output Q and full load current Ip is :
If the regulation is large and the phase shift between Vp and Vp’ is not justified. For this case:
p p p p p p p p V X I R I V V V
cos sin ,
rcos
psin
2)
sin
cos
(
2
1
sin
cos
r
p
p
rOutput Equations – Main Dimensions - KVA output for single and three phase transformers – Window space factor – Overall dimensions – Operating characteristics –
Regulation – No load current – Temperature rise in
Transformers – Design of Tank -Methods of cooling of Transformers.
59
ESTIMATION OF NO LOAD CURRENT OF TRANSFORMER
No load current of a transformer has 2 components:
Magnetizing component –depends on the mmf required
to establish the desired flux.
Loss component – depends on the iron losses.
NO LOAD CURRENT OF A SINGLE PHASE TRANSFORMER:
Total length of core=2lc Total length of yoke= 2ly
lc=Hw = height of the window ly=Ww= width of the window
mmf for core = mmf/metre for max. flux density in core × total length of core
= atc ×2lc= 2 atclc
mmf for yoke = mmf /metre for max. flux density yoke × total length of yoke
= aty ×2ly = 2 atyly
Total magnetizing mmf,AT0=mmf for core + mmf for yoke + mmf for joints
=2 atclc + 2 atyly + mmf for joints
Maximum value for magnetizing current = AT0 / Tp
If the magnetizing current is sinusoidal, rms value for magnetizing current,
NO LOAD CURRENT OF THREE PHASE TRANSFORMER:
Total length of core=3lc Total length of yoke= 2ly lc=Hw = height of the window ly=Ww= width of the window
mmf for core= mmf/metre for max.flux density in core × total length of core
= atc ×3lc= 3 atclc
mmf for yoke = mmf /metre for max. flux density in yoke × total length of yoke
= aty ×2ly = 2 atyly
Total magnetizing mmf,AT0=mmf for core + mmf for yoke + mmf for joints
Output Equations – Main Dimensions - KVA output for single and three phase transformers – Window space factor – Overall dimensions – Operating characteristics –
Regulation – No load current – Temperature rise in
Transformers – Design of Tank -Methods of cooling of Transformers.
65
DESIGN OF INSULATION
Basic consideration in design the insulation ELECTRICAL INSULATION: Depends on the operating voltage, eddy current loss in the conductors and tank walls.
MECHANICAL CONSIDERATIONS: depends on the capable to with stand mechanical Stresses during fault .
THERMAL CONSIDERATIONS: depends on Safe operating of temperature values and types of cooling employed
Insulation of transformers divided in to four types
Major , Minor , insulation relative to tank , insulation between phases
MAJOR INSULATION : Between windings and core (grounded).
MINOR INSULATION :Between turns, coils and layers.
TRANSFORMER OIL AS A COOLING MEDIUM
The specific heat dissipation due to convection of oil
λ
conv= 40.3 (θ /H)
¼W/m
2- °C ;
where,
θ = temp difference of the surface relative to the oil, °C H = height of the dissipating surface, m.
Average values 0 2 0 20 . . 0.5 1 80 100 / conv C and H to m to W m C
67
TEMPERATURE RISE IN PLAIN TANKED WALLS
The transformer core and winding is placed inside a container called tank
The tank will dissipate the heat by both radiation and convections
For temperature rise over 400C over the ambient temperature 200C,
The specific heat dissipation are follows,
Due to radiation 6.0 W/m2-°C and Due to convection 6.5 W/m2-°c
Thus a total of 12.5 W/m2- °C is taken.
. . . . . tan . 12.5 i c t total loss Temperature rise
sp heat dissipation heat dissipation surface of the k P P Temperature rise S
Where,
St = heat dissipating surface area of the tank. λ = Specific heat dissipation
Pi = Iron loss; Pc = copper loss
Heat dissipating surface of the tank =Total area of vertical sides+ 1/2 area of top cover.
The area of bottom of the tank should be neglected as it has very little cooling effect.
Transformers rated for larger outputs must be provided with means to improve the conditions of heat dissipation. This achieved by providing cooling tubes and radiators.
69
Output Equations – Main Dimensions - KVA output for single and three phase transformers – Window space factor – Overall dimensions – Operating characteristics – Regulation – No load current – Temperature rise in
Transformers – Design of Tank -Methods of cooling of
DESIGN OF TANK WITH COOLING TUBES
For small transformers,plain walled tank is enough to dissipate the losses.
The transformers are provided with cooling tubes to increase the heat dissipating area.
Tubes mounted on vertical side of the tank
Other hand, the tube will improve the circulation of oil. This
improves the dissipation of loss by convection The improvement in
71
Let,
Dissipating surface of the tank = S
tDissipating surface of the tubes = xS
tLoss dissipated by the tank surface = (6+6.5) S
t=12.5 S
tLoss dissipated by the tubes = (135/100 x 6.5)× x S
tby convection
= 8.8 x S
tTotal loss dissipated by the walls and tubes
= (12.5 S
t+ 8.8 xS
t)
= (12.5 + 8.8 x) S
tActual total area of tank walls and tubes
= S
t+ x S
t= S
t(1+ x)
Loss dissipated per m
2of dissipating surface
=Total loss dissipated/ Total area
=(12.5 + 8.8x) S
t/ S
t(1+ x)
= (12.5 + 8.8x)/(1+x)
Temperature rise in transformer with cooling tubes
,
θ= Total loss/ Total Loss dissipated
Total loss, P
loss= Pi + P
cHence,
θ = ( P
i+ P
c)/ (12.5 + 8.8x) S
t12.5 + 8.8x = ( P
i+ P
c)/ θ S
t73
Total area of cooling tubes = x S
t= (1/8.8) [ {(Pi + Pc)/ θ} – 12.5 S
t] S
tThe total number of tubes = n
t= Total tube area / Area of each tube
= Total tube area /(π d
tl
t)
n
t= (1/8.8π d
tl
t) [ {(P
i+ P
c)/ θ} –12.5 S
t]
The arrangement of the tubes on tank side walls should be made uniformly with a spacing of usually 75 mm.
The standard diameter of the cooling tubes is 50 mm and the
The dimensions of the tank are decided by the
dimensions of the transformer and the clearance
required on all sides.
Let
C1= clearance between winding & tank along the width C2= clearance between winding & tank along the length
C3= clearance between the transformer frame & the tank at the bottom
C4= clearance between the transformer frame & the tank at the top.
75
DIMENSIONS OF TRANSFORMER TANK
HT LT WT DOC DOC H D D C3 C4 C2
With reference to the figure we get,
Width of the tank, WT= 2D+ Doc+2 C1(3-phase) = D+ Doc+2 C1(1-phase)
length of the tank , LT= Doc+2 C2
Height of the tank , HT= H+C3+C4
The clearance on the sides depends on voltage and power rating of the winding
Voltage KVA rating Clearance in mm
C1 C2 C3 c4
Up to 11KV <1000KVA 40 50 75 375 Up to 11KV 1000-5000KVA 70 90 100 400 11KV to 30KV <1000KVA 75 100 75 450 11KV to 30KV 1000-5000KVA 85 125 100 475
77
Output Equations – Main Dimensions - KVA output for single and three phase transformers – Window space factor – Overall dimensions – Operating characteristics – Regulation – No load current – Temperature rise in
Transformers – Design of Tank -Methods of cooling of
METHODS OF COOLING OF TRANSFORMERS
The losses developed in a transformer are
converted
into heat energy
& cause heating of corresponding
transformer parts.
The
heat dissipation in a transformer
occurs by
conduction, convection & radiation
.
The path of heat flow in a transformer are:
From the
internal most heated spots
of a given
part(core or winding) to their
outer surface
in
contact with the oil by conduction
.
From the outer surface of a transformer part to the
oil that
cools it by convection
.
79