• No results found

Copy of Distance_setting

N/A
N/A
Protected

Academic year: 2021

Share "Copy of Distance_setting"

Copied!
8
0
0

Loading.... (view fulltext now)

Full text

(1)

Single Line Diagram: System Data: Local End: Remote End: Voltage: 132.00 kV Circuit Length: 0.45 km Max. Loading 25.50 MW PF 0.90

Base Impedance: 174.24 Ω =((KV)^2)/MVA Max Loading: 123.93 A

Max. Fault Current 56.94 pu

Min.Fault Current 70.00 % of Max. fault current

Impedances: All values are total values in % on 100MVA base

R1 X1 R0 X0

9.31E-04 2.22E-03 2.33E-03 9.31E-03

Z1 Mag 0.00240363 pu

R0m X0m Z1 Angle 67.2114 Deg

0 0 Z0 Mag 0.0096 pu

Z0 Angle 75.9609 Deg

Max. Fault current 9920.79 A Min. fault current 6944.553 A

Max.Fault MVA 13.0954428 MVA Min.Fault MVA 9.16680996 MVA

Positive Phase Sequence Zero Phase Sequence

Mutual Zero Phase Sequence

Total Line Imepdence (Z1) 0.02 In ohms Zero Seq. Impedence (Z0) 0.09 In ohms Bina 400 KV 52 89 89 Gwalior400 KV 52 Bina 400 KV 52 89 89 Gwalior400 KV 52

(2)

Page: 2

CT Ratio: 150/1

Ratio Used: 150 /1

VT Prim Voltage: 132 (kV) Phase to Phase voltage VT Sec Voltage: 110 (V) Phase to Phase voltage

VT Ratio: 1200 :1

Relay Rating: 1.0 Amp(s)

Element Used:

Ranges available Min - All Zones Reach - Max Step Size

0.02 500.00 0.01 values shown in secondary ohms

30 90 1 values shown in Degrees

Setting Criteria:

Distance protection shall be set as follows: Zone 1

i) Reach at the line angle of 80% of the protected line (ii) Time delay - 0 seconds

Zone 2

i) Reach at the line angle of 120% of the protected line ii) Time delay of 0.5 seconds.

Zone 3

i) Reach at the line angle of 170% of the protected line ii) Time delay of 1.0 seconds.

The Main Protection is a distance protection scheme using a D60 UR relay. The D30 consists of five phase and ground distance zones of protection (either mho or quadrilateral characteristics). In addition to the Main protection, the D30 also provides Powerswing Blocking, Directional Earth fault protection, Overvoltage protection, Fault Recording and VT supervision.

DISTANCE

Min - Relay Char Ang - Max

Local End Remote End

FP1 UR Relay - D60 End A CT FP2 End B CT F1 F5 F1 F5

(3)

Page: 3

ZONE 1: Phase Settings:

The relay characteristic angle should be set to match the characteristic angle of the protected line: +ve sequence RCA = 67 Degrees Setting = PHASE DISTANCE Z1 RCA zero sequence RCA = 67 Degrees Setting = GROUND DISTANCE Z1 RCA

Direction of Zone = Forward Setting = PHASE DISTANCE Z1 Direction Shape of zone = Mho Setting = PHASE DISTANCE Z1 Shape

Required zone 1 reach = 0.0188 Ω sec = 0.8 * Z

Time Delay on zone 1 = 0.000 seconds Setting = PHASE DISTANCE Z1 Delay

The Phase Distance Z1 Comp Limit setting can be used to shape the operating characteristic of the zone: Comp Limit = 90 Degrees Setting = PHASE DISTANCE Z1 Comp Limit

The directional supervising function RCA and Comp Limit should be to the same as the distance element settings: 67 Degrees Setting = PHASE DISTANCE Z1 DIR RCA 90 Degrees Setting = PHASE DISTANCE Z1 DIR Comp Limit

Min Fault at 132 = 13.1 MVA = 763.624

Zone 1 Reach = 0.0188 Fault at limit of zone 1 = 763.643

= 57 A

= 0.382 pu

Choose setting in range: 0 < Supervision < 0.382

Choose = 0.050 pu Setting = PHASE DISTANCE Z1 Supervision Ground Settings:

Direction of Zone = Forward Setting = GROUND DISTANCE Z1 Direction Shape of zone = Quad Setting = GROUND DISTANCE Z1 Shape Z0/Z1 Magnitude = 3.99 Setting = GROUND DISTANCE Z1 Z0/Z1 Mag

Z0/Z1 Angle = 9 Degrees Setting = GROUND DISTANCE Z1 Z0/Z1 Ang Ground distance reach = 0.02 Ω sec Setting = GROUND DISTANCE Z1 Reach

Comp Limit = 90 Degrees Setting = GROUND DISTANCE Z1 Comp Limit Directional RCA = 67 Degrees Setting = GROUND DISTANCE Z1 DIR RCA Directional RCA Comp Limit = 90 Degrees Setting = GROUND DISTANCE Z1 DIR Comp Limit

0.01 Ω sec Setting = GROUND DISTANCE Z1 Quad Right Bld 67 Degrees Setting = GROUND DISTANCE Z1 Quad Right Bld RCA 0.01 Ω sec Setting = GROUND DISTANCE Z1 Quad Left Bld

67 Degrees Setting = GROUND DISTANCE Z1 Quad Left Bld RCA 0.050 pu Setting = GROUND DISTANCE Z1 Supervision Time Delay on zone 1 = 0.000 seconds Setting = GROUND DISTANCE Z1 Delay Note: Z0/Z1 Magnitude and Angle are used for zero sequence compensation of the ground fault element

The supervision function provides current supervision of the distance elements to avoid maloperation under fuse fail conditions. It is set above load if possible, but below 95% of the current for a fault at the limit of Zone 1.

If the Fuse Fail function is arranged to block the distance function, then the setting shall be at minimum.

Blinder = Reach *( Tan(RCA) -1/Sq.rt(3))/Tan(RCA

(4)

ZONE 2: Page: 4

Phase Settings:

The relay characteristic angle should be set to match the characteristic angle of the protected line: +ve sequence RCA = 67 Degrees Setting = PHASE DISTANCE Z2 RCA zero sequence RCA = 67 Degrees Setting = GROUND DISTANCE Z2 RCA

Direction of Zone = Forward Setting = PHASE DISTANCE Z2 Direction Shape of zone = Mho Setting = PHASE DISTANCE Z2 Shape

Required zone 2 reach = 0.0283 Ω sec = 1.2 * Z

Time Delay on zone 2 = 0.500 seconds Setting = PHASE DISTANCE Z2 Delay

The Phase Distance Z2 Comp Limit setting can be used to shape the operating characteristic of the zone: Comp Limit = 90 Degrees Setting = PHASE DISTANCE Z2 Comp Limit

The directional supervising function RCA and Comp Limit should be to the same as the distance element settings: 67 Degrees Setting = PHASE DISTANCE Z2 DIR RCA 90 Degrees Setting = PHASE DISTANCE Z2 DIR Comp Limit

Min Fault 13.1 MVA = 0.399

Zone 1 Reach = 3.7052 Fault at limit of zone 1 = 4.104

= 3517 A

= 3.517 pu

Choose setting in range: 0 < Supervision < 3.517

Choose = 0.050 pu Setting = PHASE DISTANCE Z2 Supervision Ground Settings:

Direction of Zone = Forward Setting = GROUND DISTANCE Z2 Direction Shape of zone = Quad Setting = GROUND DISTANCE Z2 Shape Z0/Z1 Magnitude = 3.99 Setting = GROUND DISTANCE Z2 Z0/Z2 Mag

Z0/Z1 Angle = 9 Degrees Setting = GROUND DISTANCE Z2 Z0/Z2 Ang Ground distance reach = 0.03 Ω sec Setting = GROUND DISTANCE Z2 Reach

Comp Limit = 90 Degrees Setting = GROUND DISTANCE Z2 Comp Limit Directional RCA = 67 Degrees Setting = GROUND DISTANCE Z2 DIR RCA Directional RCA Comp Limit = 90 Degrees Setting = GROUND DISTANCE Z2 DIR Comp Limit

0.01 Ω sec Setting = GROUND DISTANCE Z2 Quad Right Bld 67 Degrees Setting = GROUND DISTANCE Z2 Quad Right Bld RCA 0.01 Ω sec Setting = GROUND DISTANCE Z2 Quad Left Bld

67 Degrees Setting = GROUND DISTANCE Z2 Quad Left Bld RCA 0.050 pu Setting = GROUND DISTANCE Z2 Supervision Time Delay on zone 2 = 0.500 seconds Setting = GROUND DISTANCE Z2 Delay Note: Z0/Z1 Magnitude and Angle are used for zero sequence compensation of the ground fault element

The supervision function provides current supervision of the distance elements to avoid maloperation under fuse fail conditions. It is set above load if possible, but below 95% of the current for a fault at the limit of Zone 1.

(5)

ZONE 3: Page: 5

Phase Settings:

The relay characteristic angle should be set to match the characteristic angle of the protected line: +ve sequence RCA = 67 Degrees Setting = PHASE DISTANCE Z3 RCA zero sequence RCA = 67 Degrees Setting = GROUND DISTANCE Z3 RCA

Direction of Zone = Forward Setting = PHASE DISTANCE Z3 Direction Shape of zone = Mho Setting = PHASE DISTANCE Z3 Shape

Required zone 3 reach = 0.0400 Ω sec = 1.7 * Z

Time Delay on zone 3 = 1.000 seconds Setting = PHASE DISTANCE Z3 Delay

The Phase Distance Z3 Comp Limit setting can be used to shape the operating characteristic of the zone: Comp Limit = 90 Degrees Setting = PHASE DISTANCE Z3 Comp Limit

The directional supervising function RCA and Comp Limit should be to the same as the distance element settings: 67 Degrees Setting = PHASE DISTANCE Z3 DIR RCA 90 Degrees Setting = PHASE DISTANCE Z3 DIR Comp Limit The load blinder shall be set with the same RCA as above and the maximum allowable resistive reach:

Min Fault at 13.1 MVA = 0.399

Zone 1 Reach = 3.7052 Fault at limit of zone 1 = 4.104

= 3517 A

= 23.440 pu

Choose setting in range: 0 < Supervision < 23.44

Choose = 0.050 pu Setting = PHASE DISTANCE Z3 Supervision Ground Settings:

Direction of Zone = Forward Setting = GROUND DISTANCE Z3 Direction Shape of zone = Quad Setting = GROUND DISTANCE Z3 Shape Z0/Z1 Magnitude = 3.99 Setting = GROUND DISTANCE Z3 Z0/Z1 Mag

Z0/Z1 Angle = 9.0000 Degrees Setting = GROUND DISTANCE Z3 Z0/Z1 Ang Ground distance reach = 0.04 Ω sec Setting = GROUND DISTANCE Z3 Reach

Comp Limit = 90 Degrees Setting = GROUND DISTANCE Z3 Comp Limit Directional RCA = 67 Degrees Setting = GROUND DISTANCE Z3 DIR RCA Directional RCA Comp Limit = 90 Degrees Setting = GROUND DISTANCE Z3 DIR Comp Limit

0.02 Ω sec Setting = GROUND DISTANCE Z3 Quad Right Bld 67 Degrees Setting = GROUND DISTANCE Z3 Quad Right Bld RCA 0.00 Ω sec Setting = GROUND DISTANCE Z3 Quad Left Bld

67 Degrees Setting = GROUND DISTANCE Z3 Quad Left Bld RCA 0.050 pu Setting = GROUND DISTANCE Z3 Supervision Time Delay on zone 3 = 1.000 seconds Setting = GROUND DISTANCE Z3 Delay Note: Z0/Z1 Magnitude and Angle are used for zero sequence compensation of the ground fault element

The supervision function provides current supervision of the distance elements to avoid maloperation under fuse fail conditions. It is set above load if possible, but below 95% of the current for a fault at the limit of Zone 1.

If the Fuse Fail function is arranged to block the distance function, then the setting shall be at minimum.

Blinder = sqrt(3)*Reach *( Tan(RCA)

(6)

-Power Swing Blocking: Page: 6 The Power Swing Blocking function is required, therefore apply the following settings:

Is Power Swing Block Required: Yes

Enabled Setting = POWER SWING DETECT Function Quad

Two step 0.05 pu 0.04 Ω sec

0.04 Ω sec Setting = Quad Fwd Out 87 Degrees Setting = Fwd Rca 0.01 Ω sec Setting = Rev Reach 0.01 Ω sec Setting = Quad Rev Out 0.04 Ω sec Setting = Outer Rgt Bld 0.008 Ω sec Setting = Outer Lft Bld

0.03 Ω sec Setting = Inner Rgt Bld 0.006 Ω sec Setting = inner Lft Bld

0.1 sec Setting = Delay 1 Pickup 0.05 sec Setting = Delay 1 Reset

ON Setting = Block Mode

Switch On To Fault

Min Fault at 132 = 9.2 MVA Less infeed from 0.45

Z fault = 3272.817 % = (3 * Z1s) + (2 * Z1ohl) + (Z0ohl)

3Io fault = 207.5 = 3 * Io

Required current setting = 159.6 A prim

= 1.064 pu

= 1.064 pu Setting = Phase IOC Line Pickup

Undervoltage setting = 0.850 pu Setting = UV Pickup

LEO Pickup Delay = 0.000 s Setting = Line End Open Pickup Delay SOTF time = 0.200 s Setting = Line End Open Reset Delay

= 0.200 s Setting = OV Pickup Delay

High Speed AR Bypass = Enabled Setting = Autoreclose Coordination Bypass

Directional Earth Fault

Element Used:

Range available I Pickup Min I Pickup Max Step Size

0.000 30.000 0.001 values shown pu (of Relay Rating)

RCA -90 Deg 90 Deg 1 Deg

Required current setting = 437.386 A prim MVA/(Sqrt(3) X KV)

= 2.916 pu

RCA -15 Degrees

NEUTRAL EARTHFAULT DIR. OVERCURRENT Setting = Shape Setting = Mode Setting = Supv

Blinder = Reach *( Tan(RCA) -1/Sq.rt(3))/Tan(RCA)

(7)

VT Fuse Failure function: Page: 7

Function Enabled Setting = VT Fuse Failure Function

The associated time delay is set using TIMER 9

VT Fail Alarm Timer = 3 seconds Setting = TIMER 9 Pickup Delay

The VT fuse fail can be used to block the operation of the Main Protection:

Is VT Fuse Fail to block MP: Yes Normal setting is "Yes" Enabled (Block ON) Setting = LATCH 3 Function

Phase Overvoltage

Element Used Stage1 for Alarm

Enabled Enabled Enabled

FxE 1 FxE 2 FxE 3 Setting = Flexielement Function Vag RMS Vbg RMS Vcg RMS Setting = input

SIGNED SIGNED SIGNED Setting = Input Mode LEVEL LEVEL LEVEL Setting = Compartor Mode

OVER OVER OVER Setting =Direction Type

1.150 pu 1.150 pu 1.150 pu Setting = Pickup Level 3.00% 3.00% 3.00% Setting = Hystersis

Element Used: Stage 2 For Trip

Measured Quantity = Setting = PHASE U/V1 Mode Required Under volts setting = 1.200 pu Setting = PHASE U/V1 Pickup

Characteristic = Definite Time Setting = PHASE U/V1Curve Time Delay = 0.00 Setting = PHASE U/V1 Delay Minimum voltage = 0.300 Setting = PHASE U/V1

Phase to Ground

This is designed to detect the loss of either 1, 2 or all 3 phase voltages. To detect the loss of 1 or 2 phases, the relay looks for a significant level of -ve sequence voltage, to detect loss of 3 phases, the relay looks for +ve sequence current and insignificant +ve sequence voltage. The fuse fail alarm is inhibited for a fault condition.

As the settings for the voltage/current pickups are inbuilt to the relay, the only selectable setting for this function is to enable or disable it.

Flexi element 1,2 & 3

(8)

UR Distance Quadrilateral Blinder at Load Angle Calculations Page: 8

Milliseconds Milliseconds Milliseconds Milliseconds

20 20 20 20

0.300 s 0.000 s 0.000 s 0.000 s 0.000 s 0.000 s 0.000 s 0.000 s

OFF OFF OFF OFF

Self-reset Self-reset Self-reset Self-reset Enabled Disabled Disabled Disabled





















)

).(

tan(

.

2

3

1

)

tan(

.

Re

.

3

:

And

3

1

)

tan(

.

3

)

).(

tan(

.

2

3

2

.

)

30

tan(

.

Re

3

1

)

tan(

)

).(

tan(

.

3

1

)

.(

)

tan(

.

)

tan(

:

therefore

,

and

meet,

lines

When

.

3

1

.

)

30

tan(

:

)

.(

)

tan(

.

)

tan(

:

BldStg

BldRCA

BldRCA

ach

BldStg

BldRCA

BldStg

BldRCA

X

X

ach

BldRCA

BldStg

BldRCA

X

X

BldStg

BldRCA

X

BldRCA

y

y

X

x

x

x

y

Load

BldStg

BldRCA

x

BldRCA

y

Blinder

Blinder Setting =BldStg X Load Angle= 30 Deg Blinder RCA = BldRCA RCA

Load Line = Blinder Line Reach

 





















)

).(

tan(

.

2

3

1

)

tan(

.

Re

.

3

:

And

3

1

)

tan(

.

3

)

).(

tan(

.

2

3

2

.

)

30

tan(

.

Re

3

1

)

tan(

)

).(

tan(

.

3

1

)

.(

)

tan(

.

)

tan(

:

therefore

,

and

meet,

lines

When

.

3

1

.

)

30

tan(

:

)

.(

)

tan(

.

)

tan(

:

BldStg

BldRCA

BldRCA

ach

BldStg

BldRCA

BldStg

BldRCA

X

X

ach

BldRCA

BldStg

BldRCA

X

X

BldStg

BldRCA

X

BldRCA

y

y

X

x

x

x

y

Load

BldStg

BldRCA

x

BldRCA

y

Blinder

Blinder Setting =BldStg X Load Angle= 30 Deg Blinder RCA = BldRCA RCA

Load Line = Blinder Line Reach

References

Related documents

In these few next pages I want to briefly summarise the main findings in relation to the research questions I posed in the introductory chapter, and also address what this thesis

For health plan companies with 10 percent or more of the total private health insurance market in Minnesota and HMOs with more than 3 percent of the market, the minimum loss ratio

The Economic History Review published by John Wiley &amp; Sons Economic History Review, 0, 0 (2020).. figure S20), which suggests that there was also a shift to a growth curve with

Additionally, it was found that antibiotic resistance is widespread among subsurface bacteria, a high pro- portion of isolates exhibited multiple antibiotic resis- tance

This diversity is illustrated by the backgrounds of the authors of this paper: each of us has been working to develop shared control solutions in different domains (automotive,

Other than the efficiency of its application processors and its collaboration with several branded vendors in 2011, Nvidia's application processor is mainly embraced by Windows

Copyright © 2008 Pearson Education, Inc., publishing as Pearson Benjamin Cummings Figure