UTES Experiences from Sweden

Göran Hellström

Lund University, Sweden NeoEnergy Sweden Ltd

(2)

Closed Loop - Sweden

400,000 Ground-Source Heat Pumps (GSHP) installed

Ground source supplies 15 % of national heating demand 30-35 % of all single-family houses has a heat pump

(3)

UNDERGROUND THERMAL

ENERGY STORAGE

(4)

Underground Thermal Energy Storage

ATES – Aquifer Thermal Energy Storage Sweden: ca 40 systems

BTES – Borehole Thermal Energy Storage

Sweden: ca 50 systems larger than 5000 m drilling

CTES – Cavern Thermal Energy Storage

Sweden: 3 systems

(5)

ATES/Open loop - Arlanda Airport

World’s largest open loop system –savings 3-4 Gwh electricity, 10-15 Gwh heat Payback time 6-7 years

(6)

6

ATES/Open loop - Arlanda Airport

(7)

BTES - Project Lulevärme, Luleå

• Summer: Storage of waste heat from steel plant

• Stored heat: ca 2000 MWh (maximum temp 82 °C)

• Winter: University building heated with/without heat pump

• Extracted heat: 1000-1200 MWh

• In operation 1983-1989

Seasonal storage of waste heat

(8)

BTES - Luleå

Borehole heat store: 120 boreholes depth 65 m

(9)

Connection pipes and manifold

BTES - Luleå

(10)

Measured temperature in center of store

BTES - Luleå

(11)

Measured and simulated energy balance 1983-1988

-1500 -1000 -500 0 500 1000 1500 2000 2500 3000 3500 4000 4500

Energy (MWh)

Simulated heat injection Measured heat injection Simulated heat extraction Measured heat extraction

1983-84 1984-85 1985-86 1986-87 1987-88

BTES - Luleå

(12)

Estimated ground temperature after charging

Simulation results in good agreement with measurements

BTES - Luleå

(13)

BTES - Project Emmaboda

• Summer: Storage of waste heat from foundry

• Stored heat: ca 3600 MWh

• Winter: Factory building heated

• Extracted heat: 2000 MWh

• In operation 2010-

Seasonal storage of waste heat

(14)

BTES - Emmaboda

Borehole heat store: 141 boreholes depth 148,5 m

(15)

BTES Emmaboda

System layout

(16)

BTES Emmaboda

Borehole heat exchanger

Open coaxial pipe of polypropylene

(17)

BTES Emmaboda

Borehole heat exchanger

(18)

BTES Emmaboda

Connecting pipes

(19)

BTES Emmaboda

Connecting pipes

3000 m DN40 polypropylene pipes 14 manifolds

Foam glass insulation

(20)

BTES Emmaboda

Boreholes

Measurements of borehole deviation

(21)

BTES Emmaboda

Operation strategy

Heat carrier fluid temperature

(22)

BTES Emmaboda

First operating experience

Charged energy: 900 MWh (2010), 3000 MWh (2011)

(23)

CTES

Lyckebo

Volume of cavern: 104,300 m3

• Storage capacity: 5,5 GWh

• Store temperature 60-90 ºC

• Used for seasonal storage

• Cost: 17,5 MSEK (1982)

(24)

CTES

Lyckebo

System design

(25)

CTES

Lyckebo

Solar

collector field

(26)

CTES

Lyckebo

Rock cavern

schematic

(27)

CTES

Lyckebo

Rock cavern during

construction

(28)

CTES

Avesta

Temperature field

(29)

CLOSED LOOP

BOREHOLE HEAT EXCHANGERS

(30)

Astronomy Department, Lund

BTES heating and free cooling combined with district heating Office space 4.900 m2

(31)

Energy load

(32)

Energy supply

(33)

Energy balance

Key factors Normal year (adjusted)

Seasonal performance factor - heat pump (incl. circulation) 4,5

Seasonal performance factor - free cooling 47

Heating and cooling demand 126 kWh/m2,yr

Bought energy 28 kWh/m2,yr

Seasonal performance factor

– ground source (heat pump + free cooling) 5,7

Seasonal performance factor

– total (ground source + district heating) 4,4

Energy balance Normal year (adjusted)

Heat from heat pump 475 MWh

Cold from ground source (free cooling) 155 MWh

Electricity to heat pump compressor 104 MWh

District heating (hot water + peak load) 40 MWh

Electricity to circulationspumps (ground and condensor side) 7 MWh

(34)

Project Boreholes Bore depth (m) Total (m)

Brf. Ljuskärrsberget, Stockholm Saltsjöbaden 156 230 35880

Kemicentrum (IKDC), Lund 153 230 35190

Lustgården, Stockholm 144 230 33120

Vällingby Centrum, Stockholm 133 200 26600 Brf. Igelbodaplatån, Stockholm Saltsjöbaden 120 200 24000

Kv. Bergen, Stockholm Husby 98 215 21070

ITT Flygt, Emmaboda 140 150 21000

Kv. Galgvreten, Enköping 86 220 18920

Copperhill Mountain Lodge, Åre 92 200 18400

Centrala Gribbylund, Täby 87 210 18270

Thulehem, Lund 86 200 17200

IKEA, Uppsala 100 168 16800

NIBE, Markaryd 110 150 16500

Centralsjukhuset, Karlstad 80 200 16000

Backavallen, Katrineholm 91 172 15652

IKEA, Karlstad 100 120 12000

Musikhögskolan, Örebro 60 200 12000

Sjukhuset, Kristinehamn 55 210 11550

Vattenfalls Huvudkontor, Solna 53 200 10600

IKEA, Helsingborg Väla 67 150 10050

Stenungsbaden Yacht Club, Stenungsund 50 200 10000

Näsby Parks Slott, Stockholm 48 180 8640 Projekt Lulevärme, Luleå 120 65 7800

Large Swedish BTES

(35)

Hybrid GSHP

Ground source

Exhaust air source

Outdoor air source

Water source (lake, river)

Solar source

Waste heat

(36)

COOLING

HP

HEATING

• Hot water

• Space heating

• Increasing HP evaporator temperature

• Recharging of ground loop

Glazed solar

collectors

GSHP/Solar hybrid

(37)

Seasonal storage of solar heat

Examples: Neckarsulm, Germany, and Anneberg, Sweden

High-temperature seasonal energy storage

(38)

Sea Water

Hybrid system - Boreholes with summer recharge from lake Boreholes

Water intake

Water outlet

(39)

Common ground source

RESIDENTIAL OFFICE

Combining ground-source for buildings with different load

Community clusters

(40)

Area : 180,000 m2

Energy store : 90 boreholes, depth 200 m + 70 borehole, depth 260 m

Hotel

University

Offices Flats

Combining ground-source for buildings with different load

Avantor-Nydalen, Oslo, Norway

(41)

Chemistry Department, Lund

Chemistry IKDC

Architecture

Energy balance by combining buildings with different load profiles

Energy store 153 boreholes

(42)

Heating load

Chemistry IKDC

Heating load

Total heat demand 8,5 MW Heat pump capacity 1,8 MW - From ground loop 1,2 MW

(43)

Cooling load

Chemistry IKDC

Architecture

Cooling load

Total cooling demand 3,0 MW

(44)

Common ground source

ICE RINK Cooled sep-may

OFFICE Heated sep-may

Katrineholm Sport Centre

Community clusters

Outdoor ICE RINK Cooled when air

below 0 C

GYMNASIUM Heated sep-may

Outdoor SOCCER Heated when air

above 0 C SWIMMING POOL

Heated all year

(45)

At present two office/service buildings and six stores are using borehole storage (BTES) or aquifer storage (ATES) for combined heating and cooling

Distribution Centre, Torsvik, installed 1999 (BTES + horizontal GSHP)

• IKEA Meeting Point in Helsingborg, installed 2003 (BTES)

• IKEA Store in Karlstad, installed 2007 (BTES)

• IKEA Store in Uppsala, installed 2008 (BTES)

• IKEA Store in Malmö, installed 2009 (ATES)

• IKEA Store in Väla, installed 2010 (BTES)

•IKEA Store in Uddevalla, under construction 2012 (BTES)

• IKEA Store in Borlänge, under contruction 2012 (BTES)

IKEA – Applications in Sweden

(46)

General for a 25 000 m2 store in Swedish climate

(European system design)

50-60 % of the heat load covered by the HP, represents 85-90 % of the annual heat demand

Peak load covered by electric boiler, bio fuel burner or DH

60 % of the cooling load covered by free cooling from the storage,

represents 70-80 % of the annual cold demand

Peak load covered by running the HP as a chiller. Dry cooler used for disposal of condenser heat

IKEA – Applications in Sweden

(47)

Facts:

36 boreholes, 140 m deep, single U-pipe

• Heat pump, 90 kW piston compressors

• System heat capacity, 270 kW

• System cooling capacity, 350 kW

• SPF (measured) 6,3

Pay-back time

Expected, 5,5 years (2003) Actual, 4,5 years (2007)

IKEA – Meeting point 5,000 m2, Helsingborg

(48)

Heat demand

Max load, 1200 kW

• Energy, 1200 MWh/year

Cold demand

Max load, 800 kW

• Energy, 500 MWh/year

BTES system installed 2007

100 boreholes, 120 m deep, spaced 4,5 m

 Drilled on excavated rock (granite)

 Water filled holes, with single U-pipe

 Construction time 10 weeks (2 rigs)

 High water yields caused problem

 Linked to a 620 kW heat pump/chiller Expectations

SPF heating, 3.8 (boiler included)

• SPF cooling, 7.3

• Payback time, 6 years

IKEA – Store 25,000 m2, Karlstad

(49)

BTES system installed 2008

100 boreholes,168m deep, spaced 5 m

 20 m casing through soil into granite

 Water filled holes, with double U-pipes

 Construction time 10 weeks (3 rigs)

 Highly fractured rock caused problem

 Linked to 2 x 660 kW heat pumps/chillers Heat demand

• Max load, 1 300 kW

• Energy, 2 200 MWh/year Cold demand

• Max load, 1 300 kW

• Energy, 1 500 MWh/year

Expectations

SPF heating, 4.3 (boiler included)

• SPF cooling, 6.5 (Americ. design)

• Payback time, 5.5 years

IKEA – Store 36,000 m2, Uppsala

(50)

ATES system installed 2009

 5 warm and 6 cold wells,

 90 m deep into a fractured limestone

 Average well capacity, approx. 10 l/s

 Construction time 6 weeks (1 rig)

 Linked to 2 x 410 kW heat pumps/chillers Heat demand

Max load, 1 300 kW

• Energy, 2 350 MWh/year

Cold demand

Max load, 1 300 kW

• Energy, 1 450 MWh/annually

Expectations

SPF heating, 4.3 (boiler included)

• SPF cooling, 45 (100 %)

• Payback time, 4.5 years

IKEA – Store 44,000 m2, Malmö

(51)

Karlstad’s Hospital, Sweden

Heating and cooling with combined groud and river source

(52)

Karlstad’s Hospital, Sweden

Energy demand (=bought energy) BEFORE (2000)

District heating 26,4 GWh/year

Electricity 23,6 GWh/year

Total 50,0 GWh/year

Step 1. Energy efficiency measures

- Changing windows, improving thermal insulation Step 2. Change of energy production

- Installation of ground-source heat pump/energy storage with free cooling during summer and preheating of outdoor air during winter AFTER (2011)

District heating 2,5 Gwh/year HVAC/GSHP electricity 22,2 GWh/year

Total 24,7 MWh/year

Savings 24,1 GWh heat (91 %) 1,4 Gwh electricity

Payback time 5 years

(53)

53

CSK Hus 41 Kyl-energiproduktion Alt 0

Frikyla älv

VKA

VKA 0

250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 4500

0 350 701 1051 1402 1752 2102 2453 2803 3154 3504 3854 4205 4555 4906 5256 5606 5957 6307 6658 7008 7358 7709 8059 8410 8760 Timmar [h]

Effekter [kW]

VKA VKAFrikyla älv CSK Hus 41 Värme- energiproduktion Alt 0

Fjärrvärme

0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 4500

0 350 701 1051 1402 1752 2102 2453 2803 3154 3504 3854 4205 4555 4906 5256 5606 5957 6307 6658 7008 7358 7709 8059 8410 8760 Timmar [h]

Effekter [kW]

Fjärrvärme

Energy supply - before

Heat

Cold Free cooling /

river Cooling

machine District heating

(54)

Energy supply - after

Heat

Cold Free cooling /

river

Cooling machine District

heating

CSK Hus 41 Värme- energiproduktion Alt 9 - 80 berghål

KB-systemet som värmekälla Berg 1

Älv EL VPA Fjärrvärme

0 250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 4500

0 350 701 1051 1402 1752 2102 2453 2803 3154 3504 3854 4205 4555 4906 5256 5606 5957 6307 6658 7008 7358 7709 8059 8410 8760 Timmar [h]

Effekter [kW]

Fjärrvärme EL VPA Älv Berg 1 KB-systemet

District heating

Heat pump electricity River

River

Ground

Hc fluid

CSK Hus 41 Kyl-energiproduktion Alt 9 - 80 borrhål

KB-systemet VKA

Frikyla berg 1

VKA 0

250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000 3250 3500 3750 4000 4250 4500

0 350 701 1051 1402 1752 2102 2453 2803 3154 3504 3854 4205 4555 4906 5256 5606 5957 6307 6658 7008 7358 7709 8059 8410 8760 Timmar [h]

Effekter [kW]

VKA Frikyla berg 1 VKA KB-systemet

Hc fluid Free cooling / ground

Cooling machine River

(55)

Kristinehamn’s Hospital, Sweden

Energy demand (=bought energy)

BEFORE

District heating 2135 MWh/year HVAC electricity 605 MWh/year

Total 2740 MWh/year

Step 1. Energy efficiency measures

- Changing windows, improving thermal insulation Step 2. Change of energy production

- Installation of ground-source heat pump/energy storage with free cooling during summer and preheating of outdoor air during winter AFTER

District heating 155 MWh/year HVAC electricity 465 MWh/year

Total 620 MWh/year

Savings 2120 MWh (78 %) Payback time 5 years

(56)

Kristinehamn’s Hospital, Sweden

0 500 1000 1500 2000 2500 3000

Before After energy efficiency measures After installation of GSHP

Bought energy (MWh)

HVAC electricity District heating

Bought energy (MWh)

(57)

Installation costs

Drilling* 20-35 EUR per m

Complete system (borehole heat exchanger, installation, heat pump)

1500 EUR per kW heating capacity

*Depending on local geological conditions

(58)

Thank you!

References

Related documents

Her skal jeg se på hvordan det kan argumenteres for at stridende kan deles i rettmessige og urettmessige stridende, og at de ikke kan føre krig på samme premisser, og hvordan

Background: Probiotic bacteria is commonly used as a food supplement intended to benefit the host by improving intestinal bacterial balance. Probiotics have also been investigated

S existing cross sections for every point on the road center line (ie, the master string) for both the ground model and the design model. For example, if you have generated

Applications must be submitted electronically following the instructions described in the SF424 (R&R) Application Guide. Paper applications will not

• Good partnership working between drug services All the areas reported good partnership working between all providers of drug services and a strong shared vision about how

education and 1 year of professional records management experience •   Or, 1 year of professional records manager experience can be.. substituted for each year of college education

A lease-based resource provisioning model that can act as a scheduling back-end for OpenNebula, supporting other provisioning models other than the immediate

in hospital margin for elective surgery by changing operating room time allocations or.. increasing nursing staffing to permit completion of more cases: A