Polytechnic University of Catalonia
Master Thesis
Energy Engineering
Numerical simulation of a cooling
tower and its plume
Author:
Antonio Peris Alonso
Professors:
Marc Secanell Gallart
Morris R. Flynn
Contents
1 Abstract 3
2 Introduction 4
2.1 Cooling Towers . . . 4
2.1.1 Wet Cooling Towers . . . 4
2.1.2 Dry Cooling Towers . . . 6
2.1.3 Hybrid Cooling Towers . . . 6
2.2 Operating Principles . . . 8
2.2.1 Physical processes occurring inside a cooling tower . . . 8
2.2.2 Physical phenomena occurring in the plume . . . 9
2.3 Methods of Analysis of a Cooling Tower . . . 11
2.4 Literature Review and objectives . . . 11
3 Methodology 13 3.1 Plume Model (Single plume) . . . 13
3.2 Wet cooling tower models . . . 17
3.2.1 Merkel Method . . . 17
3.2.2 Klimanek Method . . . 19
3.3 CoolIT . . . 22
3.3.2 Coupling scheme . . . 23 3.3.3 Graphical user interface . . . 25
4 Results and Discussion 26
4.1 Comparative study between Merkel and Klimanek methods . . . 26 4.2 Parametric study of the fill height (hf ill) for plume abatement . . . 31
4.3 Parametric study of the L/G ratio for plume abatement . . . . 36
5 Conclusions 50
6 References 52
7 Annex 55
7.1 Single plume class (SinglePlume) . . . . 55 7.2 Governing equations class (GovernEq) . . . . 70 7.3 Air and vapour properties class (AirVapour) . . . . 73
1
Abstract
Cooling tower design has been an active area of research for over 40 years with the goal of reduceing the visibility of their effluent water vapor plumes. Plume visibility occurs when water vapour leaving the tower is exposed to ambient, cold air, resulting in condensation. In order to minimize plume visibility, the research field of cooling towers has been diverse. On the one hand, research has been conducted on designing cooling towers improving their plume abatement (from wet and dry to hybrid cooling towers). On the other hand, other lines of research focused on the evaluation of a predefined cooling tower over a variety of operating conditions to determine its optimal plume abatement. The main objective of this project is to analyze the effect of the ambient and cooling tower operating conditions on plume visibility.
A numerical model based on wet cooling towers has been coupled with a numerical plume model that considers the possibility of condensation.The wet cooling tower model proposed by Klimanek and Merkel methods have been used to study the tower. In the case of the plume, a theoretical steady-state plume model that is adapted from the work of Wu and Koh (1978) and Ali Moradi and M. R. Flynn et al. is considered [1] that assumes a uniform, rather than a coaxial plume, and takes into account the event of condensation.
The coupling between models, cooling tower and plume, has been carried out using an open source simulation package especially developed for the analysis and design of cooling towers: CoolIT. As CoolIT already had a wet cooling tower model implemented with Klimanek and Merkel methods, the main task of this thesis was to implement and couple the plume model to the existing tower models in CoolIT using the Python programming language and object-oriented programming structure. Then, some cases are simulated to illustrate the effect of plume visibility while comparing both methods and varying certain operating conditions.
2
Introduction
2.1
Cooling Towers
Cooling towers emerged as a means of dissipating large quantities of waste heat using water and air as heat transfer media. Although cooling towers can be classified in several ways, such as by relative direction of air movement (counter flow or cross flow) and the type of water distribution system, the greatest distinction is between wet, dry and wet-dry hybrid towers [2][3]. In particular, the analysis in the thesis is focused on a wet cooling tower. However, the other two type of towers are presented as well since they also can be used to size any section by estimating when the plume is not visible (the work in this thesis can be reproduced in any of the other types of tower). Moreover, it will help to characterize and understand the so-called plume abatement; term used to describe visible plume prevention.
2.1.1 Wet Cooling Towers
Wet cooling towers work on the principle of evaporative cooling. Water contacts un-saturated air causing some of the water to evaporate and, as a consequence, the process water temperature decreases (Figure 1) [2]. At the same time, there is an increase in the wet bulb temperature of the air passing through the cooling tower [3]. In order to enhance air-water interfacial area and increase evaporation, wet cooling towers typically contain a wetted medium called “fill”. The unsaturated air enters the tower forced by a fan and faces the warm water coming from the nozzles above the fill. Due to water contact and evapora-tion, the counterflowing air gains temperature and humidity. Finally, after collecting possible small water droplets in the drift eliminator, the damp air leaves the cooling tower forming a plume.
Figure 1: Wet Cooling Tower Scheme (source: FANS a.s. website)
Wet cooling towers consume large quantities of water due to evaporation, drift and draining losses and a visible plume may form at the fan stack depending on operating conditions and design. This plume is often considered undesirable because it could dangerously obstruct the view and/or form undesirable icing over cold surfaces [5]. In order to avoid having a visible plume (plume abatement), a number of innovative cooling tower systems have been, and are still being, developed.
This thesis will be focus on the analysis of a wet cooling tower and its plume. Within this type of cooling towers, the counter-flow mechanical draft configuration has been chosen for the study. The counter-flow configuration has been found the most appropriate as it is generally more efficient, cheaper and more compacted than cross-flow cooling towers. Moreover, the mechanical draft has been chosen over the natural draft since it makes possible the mass flux of air variation which is needed for the plume abatement analysis of the wet cooling tower.
2.1.2 Dry Cooling Towers
In dry cooling tower, heat is transferred through air-cooled heat exchangers that separate the working fluid from the cooling air. As there is no direct contact between the working fluid and the ambient air, no water is lost to evaporation in the system [4]. However, dry cooling towers require large surface areas and have relatively high energy consumption, even with higher water temperatures, compared to wet cooling towers [5][6].
In the case of a direct dry cooling tower (Figure 2), turbine exhaust steam is condensed directly through an air-cooled condenser (ACC). The turbine steam flows directly from the tubes of the ACC to a heat exchanger where it is condenses by means of heat transfer with the flowing air [4].
Figure 2: Dry Cooling Tower Scheme (source: FANS a.s. website)
2.1.3 Hybrid Cooling Towers
Hybrid cooling towers use both dry and wet cooling to eject waste heat to the atmosphere [7]. As with other cooling tower types, its operation depends on the heat load, the air flow rate and the ambient air conditions [6]. Hybrid cooling towers can be applied to a wide range
of configurations, as presented by Streng [8]. One of the most effective cooling processes overall is the Parallel Path Wet/Dry (PPWD) tower [5][8]. In this method, as shown in Figure 3, the air is drawn by an induced draft fan in a parallel path through the dry and the wet sections. The warm water is firstly circulated through the dry section, where a finned heat exchanger decreases its temperature; then, the water enters the wet section and is sprayed over the fill which enhances its evaporation and finishes cooling it down. The air leaving the dry sections is heated without adding moisture, becoming hot and having low humidity. On the other hand, the air leaving the wet sections is typically considered to be 100% saturated. Both streams are mixed in a plenum, so the resultant air discharged from the fan leaves at a reduced relative humidity, relative to the air leaving the fill, which can prevent condensed droplets from forming, thereby avoiding a visible plume.
2.2
Operating Principles
2.2.1 Physical processes occurring inside a cooling tower
As mentioned previously, cooling towers operate based on latent and sensible heat transfer. In order to illustrate these phenomena and all the process states, a psychrometric analysis of the air passing through a cooling tower is shown in Figure 4 [9].
Figure 4: Psychrometric analysis of the air inside the cooling tower [9]
Air enters at the ambient condition Point A, absorbs heat and mass (moisture) from the water, and exits at Point B usually at saturated conditions. For very small loads, the discharged air may be subsaturated. The air heated (Vector AB in Figure 4) can be separated into component AC, which represents the sensible portion of the heat absorbed by the air as the water is cooled, and component CB, which represents the latent portion (evaporation). If the entering air condition is changed to Point D at the same wet-bulb temperature but at a higher dry-bulb temperature, the total heat transfer remains constant, but the sensible and latent components change significantly. DE represents sensible cooling of air, while EB represents latent heating as water evaporates. Thus, for the same water-cooling load, the
depending upon the ambient air conditions.
Therefore, thermal performance of a cooling tower depends principally on the entering air wet-bulb temperature. The entering air dry-bulb temperature and relative humidity, taken independently, have a lesser influence on thermal performance of mechanical-draft cooling towers, but do affect the rate of water evaporation in the cooling tower [9].
2.2.2 Physical phenomena occurring in the plume
As previously mentioned, warm air discharged from a cooling tower is typically either saturated or close to saturation. Under certain operating conditions, the ambient air sur-rounding the tower cannot absorb all of the moisture in the tower exhaust discharge, and the excess condenses resulting in a visible plume. Assuming a process of adiabatic mixing in the atmosphere, this plume visibility can be determined by drawing a straight line on a psychrometrical chart (Figure 5). The line goes from the entering air condition to its ex-haust condition. Thus, when this line crosses the saturation curve, a visible plume is formed. Moreover, its intensity becomes stronger as the area to the left of the saturation curve grows. This fact together with the degree of mechanical and convective mixing with the ambient air determines the persistence of the visible plume.
Figure 5: Psychrometric analysis of the plume [10]
In order to illustrate the plume state, the operating lines of a common wet cooling tower have been compared with those of a hybrid cooling tower including plume abatement (Figure 5) [10]. As it can be appreciated, the oversaturated area, which leads to fog formation (visible plume), is smaller in wet/dry operation compared with wet operation. This is due to the dry section in the hybrid tower where the introduced outside air is heated at a constant specific humidity. Thus, after this air is mixed with the moist air coming from the wet section, the exhaust air is produced with less moisture content, therefore, a lower operating line.
For environmental and safety reasons, the potential for fogging and its effect on tower sur-roundings has to be considered, specially in large windowed areas or traffic arteries, airports [10]. Often, while selecting cooling tower sites, the most practical solution is to predict where visible plumes should form, accordingly to the ambient and operating conditions [10]. These operating lines and, consequently, the prediction of the visible plume can be ob-tained analytically considering momentum, energy, and moisture (absolute humidity) trans-port equations.
2.3
Methods of Analysis of a Cooling Tower
Although the evaporative cooling phenomenon is a quite ancient knowledge, it is only relatively recently (within the last century) that it has been modeled and studied scientifically [11]. Regarding cooling towers, Merkel [12] was the first to develop a theory for the thermal evaluation of cooling towers in 1925. Unfortunately, this work was largely neglected until 1941 when the paper was translated into English. Then, in 1989 Jaber and Webb [13] developed the equations necessary to apply the e-NTU method directly to counter flow or cross flow cooling towers. Two years later, Poppe and R¨ogener presented a more rigorous model called Poppe method [14] and, finally, Klimanek and Bialicki developed an alternative method in 2009 [15].
Despite that the resolution process takes into account several input operating parameters related to its different areas (the geometry, the fan, the drift eliminator, the spray zone, fill and rain zone), the equations presented in each methodology are the main governing equations considering a counter flow configuration of a wet cooling tower. Thus, in all methodologies the input states of water and air are known: mass flow rate, temperature and pressure (and relative humidity in case of the air). Consistently, the common goal is to obtain the final states - outputs - of air and water. Therefore, the differences between methods are how the outputs are obtained, illustrated in the governing equations. Further down, the Merkel and Klimanek methods, which are used in the thesis to model the tower, are presented. Merker represents the most common used method, while Klimanek represents the one with the least number of assumptions.
2.4
Literature Review and objectives
Tyagi et al. [16] presented a case study of the prediction and control of plume in wet cooling towers from a huge commercial building in Hong Kong. The building contained a central air conditioning system comprising six water-cooled chillers and 10 cooling towers. The study took the weather data available for a particular year, 1989, in Hong Kong: ambient
temperatures of 15ºC with 95% of relative humidity for winter and ambient temperatures of 25ºC with 95% of relative humidity for spring. The main conclusion regarding plume abate-ment was that, for this particular case, a proper operation of wet cooling towers, increasing the number and air speed of towers, can reduce and/or control the potential of visible plume. Xu et al. [17] studied the plume potential and a plume abatement system in a large commer-cial office building in Hong Kong. The evaluation consisted on a dynamic simulation using, as in the previous case, a representative meteorological data of Hong Kong. The study stated that the yearly dynamic simulation is crucial to predict the plume potential and determine the parameters for designing the plume abatement system. Alternative control strategies, such as set-point control logics of the supply cooling water temperature and fan modulation, have significant impacts on the visible plume frequency and, therefore, should be included in the design of a plume abatement system.
There are other studies focused on heating the exhausted air to achieve plume abatement. Wang et al. [18] presented the application and utility of solar collectors heating system to control the visible plume and Tyagi et al. [19] compared a similar system based on solar collectors with a heat pump system to control visible plume economically. However, these other ways of plume abatement are more focused on adding new systems and, thus, differ from the main objective in this project: analyze the effect of the ambient and cooling tower operating conditions on plume visibility.
This thesis follows the idea of varying the operating conditions for plume abatement [16] [17], increasing the mass flux of air, but with distinctions and novelties. This study is not based on the ambient conditions of a specific location, it takes into account different values of temperature and relative humidity, hence, a wide range of ambient conditions. The object of study is a single wet cooling tower and its plume. The visible plume is measured in terms of height rather than persistence, time. Although Merkel and Klimanek methods [12] [15] have been used in different cooling tower studies, they haven’t been coupled with a plume model to study plume abatement. Therefore, this project through object oriented programming in Python will try to extend the mechanisms to predict and control (or avoid) visible plume.
3
Methodology
3.1
Plume Model (Single plume)
The solution of the plume is based on a theoretical steady-state model that takes into account the event of condensation. In particular, the model applied is adapted from the work of Wu and Koh (1978) [20] who made predictions of the behaviour of a plume discharged to a wet or dry atmosphere by integrating turbulent plume theory with psychrometrics. The unknowns in the plume model are practically the same as Wu and Koh’s model: plume’s temperature, moisture (vapor and liquid phases), humidity, pressure, and density of the plume as well as the visible plume length in case of condensation. Moreover, both approaches follow the same assumptions in order to develop the model:
I. Since turbulent transport is significantly larger than molecular transport, the model’s output is considered independent of the Reynolds number.
II. The cross-sectional profiles of the plume vertical velocity, temperature, density, vapor and liquid phase moistures are considered constant. This is because plume properties are assumed to exhibit “top-hat” profile (Figure 6); i.e., a given property, such as the plume vapor phase moisture, is constant inside the plume and zero outside.
III. The variation of the plume density is small, i.e., no more than 10%. IV. The fluid pressure is hydrostatic throughout the flow field [23].
V. The plumes are axisymmetric and propagate vertically upwards (Figure 6).
VI. Due to the relatively low height used in that type of simulations (elevations of more than 100 m aren’t worrisome for fog formation), the ambient temperature has been assumed independent of the elevation as well as to lack liquid phase moisture and to be uniform in density and humidity.
VII. Since the temperature and concentration profiles have the same shape and the flow is turbulent, the Lewis number, Le, is equal to 1 (Kloppers and Kr¨oger [24]). The Lewis number is formulated as the ratio of thermal diffusivity to mass diffusivity.
Figure 6: Axisymmetric top-hat plume scheme (image based on Shuo Li, Ali Moradi, Brad Vickers and M.R. Flynn work [1])
From the above assumptions, and using Boussinesq approximation to relate temperature and density, a set of differential governing equations is obtained [1],
dQ dz = E (Volume) (1) dM dz = g Ta · DF · Q M − g · W · Q M (Momentum) (2) d dz DF − Lv Cpa · W ! = 0 (Energy) (3) d dz(H + W ) = 0 (Moisture) (4)
DF = Z
A
(Tp − Ta) · Up·dA (5)
Where Q is the plume volume flux, M is the momentum flux, DF is the deficiency flux’s temperature, H is the specific humidity deficiency flux, W is the specific liquid moisture deficiency flux and Cpa, Lv, U and A are, respectively, the air’s specific heat capacity, the
latent heat due to condensation, vertical velocity, and cross-sectional area. Moreover, E is the volume rate of entrainment of ambient fluid, expressed as [23],
E = S · α · Up, (6)
where S is the plume circumference, and α is the entrainment coefficient whose value is approximately 0.1 for axisymmetric plumes and 0.2 for line-source plumes. Moreover, as the energy and moisture with respect to z are constant- they are independent of the height- they won’t be integrated. Instead, another variable has been added that has been found dependent on z: pressure. This is due to the fact that the pressure within the plume is imposed by the external (hydrostatic) ambient [23]. Thus, considering the virtual temperature relation and the relation between densities (Equations (10) and (11)), the the final governing equations are: dQ dz = 2 · α · √ π · M (Volume) (7) dM dz = g0· Q2 M (Momentum) (8) dp dz = −g · p Ra· Tv,a (Pressure) (9)
Where Tv and g0 are formulated by Emmanuel [25] as, Tv = T · (1 + 0.608 · q − σ), (10) g0 = g ·ρa− ρ ρ0 = g · ρa− ρ ρa = g · 1 − p Ra·Tv,p p Ra·Tv,a = g · 1 − Tv,a Tv,p ! , (11)
where q is the specific humidity and σ is the specific liquid moisture, which is higher than 0 when condensation occurs (RHp ≥ 100 %) and, otherwise (RHp < 100 %), equal to 0. For
a prescribed source, the exit of the cooling tower, and at a certain ambient conditions, this governing equations equations are integrated up to some prescribed vertical distance above the cooling tower. The boundary conditions of the model are set at source level (z = 0). These boundary conditions are
Q(z = 0) = U0· A0 (12)
M(z = 0) = U02 · A0 (13)
P(z = 0) = Pamb. (14)
In addition, the input variables are the source velocity U0 in m/s, source relative humidity RH0, source temperature T0 in Kelvin, source area A0 in m2, ambient relative humidity RHa, ambient temperature Ta in Kelvin, ambient pressure Pa in Pascals, the interval steps
3.2
Wet cooling tower models
3.2.1 Merkel Method
The Merkel method relies on several critical assumptions:
I. The Lewis factor, Lef, relating heat and mass transfer is equal to 1. In other words,
thermal and mass diffusivity are exactly the same.
II. The air exiting the tower is saturated with water vapor and it is characterized only by its enthalpy.
III. The reduction of water flow rate by evaporation is neglected in the energy balance (dmw = 0).
By applying these assumptions, the mass and energy balances for the control volume in Figures 7(a) and 7(b), result in [21]:
dima dz = hd· af i· Af r ma ·(imasw− ima), (15) dTw dz = ma mw · 1 cpw ·dima dz , (16) where:
• Tw is the water temperature in K.
• af i is the surface area of the fill per unit volume of fill in m−1.
• Af r is the cross-sectional packing area in m2.
• hd is the mass transfer coefficient in m/s.
• ima is the enthalpy of the air-water vapor mixture per unit mass of dry-air in kJ/kg.
• ma is the mass flow rate of air in kg/s.
• mw is the mass flow rate of water in kg/s.
• cpw is the specific heat at constant pressure of water in kJ/kg · K.
Equations (15) and (16) describe, respectively, the change in the enthalpy of the air-water vapor mixture and the change in water temperature as the air travel distance changes. Both can be combined to yield upon integration the Merkel equation,
M eM = hd· af i· Af r · Lf i mw = hd· af i· Lf i Gw =Z Twi Two cpw·dTw imasw− ima , (17) where:
• MeM is the transfer coefficient or Merkel number according to the Merkel’s approach.
• Lf i is the fill height in m.
• Gw is the mass velocity of the water in kg/s · m2.
Merkel’s Equation (17) assumes that the air leaving the fill is saturated with water vapor, therefore, it is not possible to calculate the true state of the air leaving the fill. Even so, this assumption allows the calculation of the air temperature leaving the fill.
3.2.2 Klimanek Method
Klimanek and Bialecki [15] developed a method to describe the heat and mass transfer in the fill by considering it as a porous medium without the simplifying assumptions commonly used in Merkel’s method. By not making these assumptions, Klimanek (as Poppe) method can calculate the amount of water evaporated (which is not possible with Merkel). Moreover, the equations are formulated with respect to the spatial distribution of all the flow parameters which is not the case in the standard methods such as Merkel, e-NTU and Poppe. Therefore, this model is able to predict the flow parameters along the height such as temperature of air and water, mass flow rate of water and humidity ratio. The formulation of the method consists on four non-linear differential equations that take into account whether the exhaust air is either unsaturated (including the case for saturation) or supersaturated [15].
The governing equations for the unsaturated air of humidity ratio, air enthalpy and temper-atures of air and water are:
dmw dA = β · af · Az·(ωws − ω) (18) dω dz = β · af · Az ·(ωsw− ω) ma (19) dTa dz = β · af · Az ·[Lef ·(Tw− Ta) · (capa+ ω · capv) + (cwpv· Tw− capv· Ta) · (ωs− ω)] ma·(capa+ capv· ω) (20) dTw dz
=
β·af·Az·[Lef·(Tw−Ta)·(capa+ω·cpva )+(r0+cwpv·Tw−cww·Tw)·(ωs−ω)]
mw·cw
where af is the transfer area per unit volume of the fill (area density in m−1), Az is the
cross sectional area of the fill in m2, β is the average mass transfer co-efficient in m/s and the difference between humidity ratios, (ωw
s − ω), represents the driving force of the mass
convection process [15]. Moreover, cw
w is the average specific heats at constant pressure of
water in kJ/kg ·K evaluated at water w temperature. Analogously, a is used to indicate that the variable is evaluated at bulk air temperature. Moreover, the air humid enthalpy and the Lewis factor are expressed using Boˇsnjakovic relationships [22] (as in Poppe’s formulation),
ha= capa· Ta+ ω · (r0+ capv· Ta), (22) Lef = 0.8662/3· ωw s + 0.622 ω+ 0.622 −1 · lnωsw+ 0.622 ω+ 0.622 −1 . (23)
where ha represents the enthalpy of the humid air per unit mass of dry air (in kJ/kg) and capa
and ca
pv in kJ/kg · K are the specific heats and the average specific heats at constant pressure
of dry air, respectively. Moreover, r0 stands for the latent heat of evaporation evaluated at Tw = 0 °C (expressed in kJ/kg) and ωsw is the humidity ratio of the saturated air at the
air-water interface in kg/kg.
In the second case - supersaturated air - the governing equations are: dmw dA = β · af · Az·(ωsw− ω a s) (24) dω dz = β · af · Az·(ωws − ωsa) ma (25)
dTa dz = −β · af · Az ma ·hLef· capa·(Tw− Ta) − ωws ·(r0+ cwpvTw) + ca w ·(Lef ·(Tw− Ta) · (ω − ωas) + Ta·(ωws − ω a s)) + ωa s ·(r0+ capv·Lef ·(Ta− Tw)) + cwpv· Tw i · " capa+ caw· ω+ dω a s dTa ·(r0+ capv· Ta− caw· Ta) + ωsa·(c a pv− c a w) #−1 (26) dTw dz
=
β·af·Az·[(r0+cwpv·Tw−cww·Tw)·(ωsw−ωsa)+Lef·(Tw−Ta)·(capa+cwa·(ω−ωas)+capv·ωsa)]
mw·cww (27)
where, this time, using again Boˇsnjakovic relationships [22], the Lewis factor follows the previous expression, Equation (23) (using ωa
s though), and the air humid enthalpy has a
different formulation:
has= capa· Ta+ ωas ·(r0+ capv· Ta) + (ω − ωas)cawTa (28)
This governing equations are integrated considering some boundary conditions which are set at the bottom of the rain zone (z = 0) and on the top of the spray zone (z = H) of the cooling tower. These boundary conditions are:
mw(z = H) = mwi (29)
ωa(z = 0) = ωai (30)
Ta(z = 0) = Tai (31)
Tw(z = H) = Twi (32)
where mwi is the mass flow rate of inlet water, ωai is the inlet humidity ratio, Tai is the
3.3
CoolIT
For cooling tower modelling, an open source simulation framework developed for its design and analysis has been used, namely CoolIT. CoolIT uses additional libraries than those supplied by Python, such as SciPy for scientific math functions. In order to use CoolIT, a CONDA environment with numerous pre-installed scientific Python packages are used to prevent any conflicts with other local packages already installed.
3.3.1 Numerical implementation
CoolIT uses object oriented programming and contains a wide number of classes that interact with one another to create the program. The goal of implementing the plume code in CoolIT implies creating an object oriented scheme for that code. So, taking into account the different functions used to obtain the solution, the single plume code has been divided into three classes: SinglePlume, PlumeGovernEq and AirVapour (located in the Annex as Listings 1, 2 and 3).
The SinglePlume object receives the input parameters of the plume model and solves it. The member functions associate to the class are: solve gov eq(), solve var(), plot rh(), plot rd(),
plot hr(), plot psychrometric() and find condensation(). These are described below. The
member function solve gov eq() solves the governing equations (Equations (7), (8) and (9)) with the odeint Python function and returns an array of values referring to volume, momen-tum and pressure at certain heights set in the input variables. Member function solve var(), using the results from the previous method, calculates and returns an array of all the physical parameters that characterize the plume (relative humidity, water content, temperature, etc.). The other member functions are focused on either plotting the results (plot rh(), plot td(),
plot hr() and plot psychrometric()), printing the interval of heights where there is
conden-sation, and, if condensation does not take place, the value and height where the maximum relative humidity is achieved (find condensation()).
The PlumeGovernEq class contains the equations that SinglePlume solves. The member function govern eq() contains the differential form of the governing equations already pre-sented (Equations (7), (8) and (9)) taking into account condensation phenomena. This class also includes the member function condensation() which is used by the govern eq() from this class as well as solve var() from SinglePlume class. It contains the function that fsolve, also from scipy Python package, solves to calculate the water content in the plume.
Finally, the AirVapour class contains the physical properties of air/vapour that both classes,
SinglePlume and PlumeGovernEq use for the resolution of the plume. These properties
are divided into attributes, like the ideal gas constant or the masses of air and vapor, and methods, for calculating the vapour saturation pressure, latent and specific heats, etc.
Figure 8: Object oriented programming scheme for single plume resolution
3.3.2 Coupling scheme
The addition of the plume model to CoolIT implies also a connection of this model to the existing wet cooling tower model. This coupling scheme, Figure 9, consists on solving first the cooling tower model, and then the plume model since the plume model uses some of the
wet cooling tower outputs as inputs.
Figure 9: Coupling scheme
Thus, for a given tower architecture and operating conditions, the cooling tower model in CoolIT, either Merkel or Klimanek, is solved to obtain, among others, the tower outlets of air temperature, velocity and relative humidity. These three values and the ambient conditions, previously set by the wet cooling tower model, together with the interval steps, plume height and entrainment coefficient are used to solve the plume model. The results of the plume are displayed together with the wet cooling tower results file. In addition, the output file displayed after the wet cooling tower simulation, also contains the resultant interval of heights where condensation occurs. Finally, a unit test has been created to assess the validity of the code. In this test, the plume results obtained from CoolIT (SinglePlume class) are compared to the ones obtained from the source plume code devolped in Matlab by Ali Moradi [1].
3.3.3 Graphical user interface
CoolIT can be set up and executed via a graphical user interface that displays the input parameters used to define the method (either Klimanek or Merkel), the tower geometry, and the fan, drift eliminator, spay, rain and fill zones, and the fluxes of air (inlet) and water (inlet and outlet). Besides that, it is also possible to perform parametric studies for the different variables involved during the process as well as to save and import predefined models of cooling tower. Once the simulation is run, the output variables obtained from both studies (cooling tower and plume solutions) are exported to a text file in an output directory and the plots from the plume study are displayed. The commented interface looks as Figure 10:
Figure 10: CoolIT graphical user interface
The purpose of this project is to develop a plume model and a GUI tab, called Plume, that contains the input parameters that are specific to the model. Thus, as Figure 10 shows, the plume height, over which it has been computed the plume solution, has been chosen as the parameter to vary and an image illustrating it has been included. Other input parameters contained in the other tabs can be taken from the cooling tower solution as mentioned in the
4
Results and Discussion
At this point, after the integration of the model into CoolIT, three different types of simulations have been carried out. Firstly, the effect of using a detailed cooling tower model, Klimanek and Merkel, on plume visibility has been assessed. Through this comparison, one of the methods will be chosen to carry out the next simulations. Secondly, the effect of a design parameter, the fill height, on plume visibility has been studied. Finally, the last study has been focused on evaluate an operational parameter, the L/G ratio, to mitigate plume visibility. Thus, the fan power consumption will be taken into account as well as the compliance with reasonable operational conditions.
4.1
Comparative study between Merkel and Klimanek methods
The aim of this study is to analyze the impact of plume using Merkel method vs. Klimanek method. Merkel assumes saturated outlet conditions and, as a result, it is expect to provide inaccurate tower outlet conditions in some cases. In turn, it will affect plume visibility condition. To study the ambient conditions where Merkel fails, ambient relative humidity and temperature were varied. The model input parameters of the cooling tower are shown in Table 1. On the other hand, the ambient conditions are modified as shown in Table 2, where each ambient temperature forms a test case with the different ambient relative humidities. The simulations are performed with Klimanek and Merkel methods for the purpose of comparing their visible plume heights results. 63 test cases were performed and used to study the differences between methods in terms of plume behaviour and plume visibility.
Table 1: Model input parameters of the cooling tower (Base case)
Method Merkel/Klimanek hrainzone (m) 3
Geometry Rectangular L/G(= mw/ma) 1
Width (m) 12 Pa (Pa) 101250
Type of fill OF21-ma Twi (K) 310
Table 2: Ambient conditions, relative humidity and temperature, from which the test cases are built
Tai (K) 306 301 296 291 286 282 279 274 269
RHa (%) 5 20 35 50 65 80 95
Regarding the visible plume height, it has been calculated through the difference between the heights where the visible plume appears and disappears, no matter if it starts at the source or later. The results are illustrated in Figures 11 and 12, using Merkel and Klimanek respectively.
Figure 12: Visible plume height as a function of the ambient conditions (Klimanek)
Both figures show that at the highest ambient temperatures there is an invisible plume. In contrast, at the lowest temperatures, the longest visible plumes are obtained. Regarding the ambient relative humidity, as it progressively increases, visible plume height also increases. However, it seems that this increase only becomes significant as the ambient temperature decreases. If the figures are taken into account separately, the results from Merkel show higher values of plume visibility than from Klimanek. This difference can be better appreciated in the contour plot that illustrates the difference in visible plume height between Merkel and Klimanek (Figure 13).
Figure 13: Difference in visible plume height considering Merkel minus Klimanek methods.
The comparison shows that the biggest differences between methods is located at low ambi-ent temperature. The highest difference is at minimum ambiambi-ent temperature and maximum relative humidity. These differences can be explained through the disparities between output values of the cooling tower solution, which are used for solving the plume, i. e., T0 and RH0. Merkel assumes 100% for RH0, while Klimanek calculates RH0. Thus, Merkel can’t predict either subsaturated or supersaturated cases. Even though Figure 15 shows subsaturation at the higher ambient temperatures and it is expected a high difference between methods, in reality this differences are nearly 0. This can be due to the high source temperatures (shown in Figure 14) that promotes plume abatement to a large extend. Regarding the negative and positive differences, following the same reasoning, could be due to, firstly, higher source tem-peratures in Klimanek and, then, largely higher source temtem-peratures in Merkel. This abrupt increase of temperature at low ambient temperatures and the wrong and recurrent allocation of 100% relative humidity show Merkel method inaccuracy at supersaturated conditions as well as subsaturated conditions. Therefore, since Klimanek model is able to provide better predictions for the outlet air temperature and relative humidity, it is the method likely to
provide more accurate predictions for plume visibility.
Figure 14: Source temperature as a function of the ambient conditions (hf ill = 1.2 m)
4.2
Parametric study of the fill height (h
f ill) for plume abatement
As Klimanek has been argued to be the more accurate method, as it is valid for super-saturation and subsuper-saturation conditions, in this section all simulations have been carried out only using this model. These simulations take into account the same ambient conditions range; however, this time a specific operating parameter which has direct relation with plume visibility (and keeping all the other constant) has been varied: the fill height. Because the base case used to compare results against the Merkel solution only takes into account a fixed fill height (particularly, 1.2 m), it was decided to test two more cases: one with a height value above and another with the value below (see Table 3) in order to study the effect of the evaporation reduction/increase.
Table 3: Fill height test cases
hf ill (m) 0.6 1.2 1.8
Following the same procedure as in the comparison of methods, the plume visibility height has been obtained and illustrated for the three cases, shown in Figures 16, 17 and 18.
Figure 17: Visible plume height as a function of the ambient conditions (hf ill = 1.2 m)
The figures show that as the fill height is increased, higher values for visible plume height are obtained. Similarly, it is appreciated that the starting points where visible plume is obtained appear earlier, at higher ambient temperatures. This phenomena can be related with the physical meaning of reducing or increasing the fill height, i.e. decreasing/increasing outlet
RH0.
Reducing the fill height also reduces the amount of water evaporated. Therefore, less heat is exchanged and, consequently, the leaving air temperature, generally, decreases (shown in Figures 19 and 14). In the case of the relative humidity, this expands its range (shown in Figures 20 and 15): at the highest ambient temperatures, the relative humidity becomes lower (directly related to the reduction of evaporation) and, at the lowest temperatures becomes higher. This last case may be related to the leaving air temperature reduction because less heat is transferred. Both parameters, source temperature and relative humidity, at the highest ambient temperature can illustrate that the differences in the Figures 16 and 17 are not that big since these tower outlets aren’t favourable for plume abatement.
Figure 20: Source relative humidity as a function of the ambient conditions (hf ill = 0.6 m)
On the other hand, increasing the fill height increases the amount of water evaporated. Hence, more heat is exchanged and, consequently, the leaving air temperature, generally, increases (shown in Figures 14 and 21). In the case of the relative humidity, this shrinks its range (shown in Figures 20 and 15): at the highest ambient temperatures, the relative humidity becomes higher (directly related to the increase of evaporation) and, at the lowest temperatures becomes lower. This last case may be related to the leaving air temperature increase because more heat is transferred. However, as both parameters, source temperature and relative humidity, does not suffer a big change in magnitude the differences in visible plume height (shown in Figures 17 and 18) are less significant than in the previous fill height case.
Figure 21: Source temperature as a function of the ambient conditions (hf ill = 1.8 m)
4.3
Parametric study of the L/G ratio for plume abatement
The purpose of this set of simulations is to study how the plume visibility changes as the
L/G ratio is varied. The economical viability is also taken into account too as increasing G will abate the plume at the expense of increasing fan power consumption. The impact of
varying the L/G ratio on the fan consumption has been quantified while trying to keep an acceptable cooling range. Therefore, three cases are proposed in addition to a base L/G ratio shown in Table 4. In all of them, the mass flow rate of water, L, has been kept constant at the base case value, 1000 kg/s, while the air flow rate, G, has been varied.
Table 4: L/G ratio test cases
L/G 2 1 1/2 1/4
Following this procedure, the visible plume height has been obtained for the four cases, Figures 23, 24, 25 and 26. This time, though, besides the contour plots, the visible plume height against the L/G ratio has been represented for four specific cases (Figure 27). This cases are build varying the parameters of ambient relative humidity and temperature inside the ranges of the contour plot (Table 5).
Table 5: Ambient conditions test cases
Case 1 Case 2 Case 3 Case 4
Ta (K) 296 296 274 274
Figure 23: Visible plume height as a function of the ambient conditions (L/G = 2)
Figure 25: Visible plume height as a function of the ambient conditions (L/G = 0.5)
Figure 27: Visible plume height as a function of the L/G ratio
The figures show that as the L/G ratio is decreased, the visible plume height decreases. However, the changes between L/G = 2 and L/G = 1 are smaller than in the rest of the cases. Similarly, the starting points where the visible plume appears, occur later, at colder temperatures. This behaviour of the plume can be explained through the parameters of relative humidity and temperature. Their variation is illustrated in the following contour plots and plots of the cases shown in Table 5.
Figure 28: Source temperature as a function of the ambient conditions (L/G = 2)
Figure 30: Source temperature as a function of the ambient conditions (L/G = 1)
Figure 32: Source temperature as a function of the ambient conditions (L/G = 0.5)
Figure 34: Source temperature as a function of the ambient conditions (L/G = 0.25)
Figure 36: Source temperature as a function of the L/G ratio
The increase in air mass flux leads to the effluent leave the tower colder (as shown in Figures 28, 30, 32 and 34). Figure 36 shows that the higher is the ambient relative humidity and temperature, the higher is the output temperature, specially at lower L/G ratios. In addition (as shown in Figures 29, 31, 33, 35 and 37), at hot ambient conditions, by reducing the L/G ratio, the exhaust air can achieve subsaturation and its source relative humidity can be cut down significantly. However, the opposite effect occurs at lower ambient temperatures: as the
L/Gratio is decreased, the source relative humidity increases. This effect is less appreciable
than in high ambient temperatures. Therefore, source relative humidity and temperature tendency matches with the visible plume tendency, Figure 27, previously mentioned.
Conversely, while increasing the L/G ratio and taking the base case as a reference, the values of source temperature and relative humidity does not suffer a big change. Regarding the temperatures (Figures 28, 30 and 36), although there is a clear decrease, it is smaller than in the previous cases when the L/G ratio was decreased. Regarding the relative humidities (Figures 29, 31 and 37), the difference between them is almost negligible. This behaviour of temperature and relative humidity explains the main reason why, while increasing the L/G ratio, the visible plume heights between the L/G = 1 and L/G = 2 cases do not suffer a significant increase as expected.
Moreover, this mass flow rate of air variation must be studied also in terms of the force that allows it, in other words, the fan power consumption. This fan power consumption, Pcf, is
obtained using,
Pcf =
∆PT · Va
ηf · ηc
, (33)
where Va is the volumetric flow rate of air, ∆PT is the total pressure drop between the inlet
and outlet of the cooling tower, and ηf and ηc are the fan and conversion efficiencies which
Fan power consumption is shown in Figure 38. Contour plots are not shown because fan power appears to be insensitive to the ambient conditions used. Figure 38 shows the impact of varying the L/G ratio on cooling tower consumption. Decreasing the L/G ratio increases power consumption exponentially: the case with highest L/G ratio computes power values of the order of kilowatts, while the one with the lowest L/G ratio shows values of the order of megawatts. This is due to the previous fan power formulation (Equation (33)) where the total pressure drop and the volumetric flow rate of air are directly related to the air velocity, i.e. L/G ratio. Therefore, plume abatement come with a heavy expense.
Figure 38: Fan power consumption as a function of the L/G ratio
Besides the results of visible plume height and fan power consumption, in order to choose the best scenario, it has to be also taken into account its viability through the cooling range keeping acceptable operating conditions (Figures 39, 40, 41, 42 and 43).
Figure 39: Cooling range as a function of the ambient conditions (L/G = 2)
Figure 41: Cooling range as a function of the ambient conditions (L/G = 0.5)
Figure 43: Cooling range as a function of the L/G ratio
The figures show that, as the L/G ratio decreases, the cooling range increases. In addition, in the Figure 43, the cases with the lowest ambient temperature have the widest cooling range with a low sensitivity to the ambient relative humidity. On the other hand, at the highest ambient temperatures, the cooling range is lower and more sensitive to the ambient relative humidity variation. Although the highest L/G case may seem to be the best a priori in terms of energy consumption and plume visibility (as there isn’t a big change compared to the base case), it is quickly discarded while seeing their cooling ranges (Figure 43). Taking a reasonable operating requirement of 20°C for the cooling range, it can be appreciated that this L/G = 2 case is unsuitable since none of the cases accomplish it. On the other hand, the base case with L/G = 1 only satisfies this criterion for the coldest ambient temperatures, while for the other two cases, with L/G ratio equal to 0.5 and 0.25, fulfills it partially and almost fully, respectively.
5
Conclusions
A numerical software has been developed to analyze the effects of cooling tower ambient and operating conditions on plume visibility. To do so, a theoretical steady-state plume model adapted from the work of Wu and Koh (1978) [20] and Ali Moradi and M. R. Flynn et al. [1] has been implemented into CoolIT, a Python-based, object-oriented code for solving cooling towers. Subsequently, this turbulent plume model was coupled to two wet cooling tower models, Merkel and Klimanek which represent the most common and advanced model in literature. As a final step of this merging, a new tab for the plume study has been added to the CoolIT user graphical interface. Finally, the implementation has been verified by comparing the plume results obtained from CoolIT with the ones obtained from the Matlab-based source plume code.
The analysis of the plume behaviour has been divided into three studies. The first study compared the effects of the two wet cooling tower methods, Klimanek and Merkel, on plume behaviour predictions. It is concluded that Klimanek model is able to provide better predic-tions for the outlet air temperature and humidity and, therefore, it is likely to provide more accurate predictions for plume visibility. Then, a parametric study varying the fill height has been carried out. Although the fill height reduction leads to an improvement in plume abatement, it is not feasible as it also leads to a reduction of the cooling tower performance. Finally, a parametric study is carried by varying the L/G ratio. Although the increase of the mass flux of air leads to a great increase in the fan power consumption, it is favourable since improves the plume abatement as well as the process performance, the cooling range becomes wider.
Proper design and operation of a cooling tower must take into account performance and plume abatement. The variation of the operating conditions, specifically the L/G ratio, has proven to be a good mechanism for reducing plume visibility. It is observed that at low ambient temperatures and high ambient relative humidities, it is more likely to observe plume visibility. Hence, during these conditions, fan power consumption must be increased. A control system can be implemented to do so efficiently. The amount of energy spent to
increase the mass flux of air would depend on the legal regulations in plume abatement for location and level of hazard.
6
References
[1] SHUO LI, ALI MORADI, BRAD VICKERS AND M.R. FLYNN. “Cooling tower plume
abatement using a coaxial plume structure”. International Journal of Heat and Mass
Transfer. Edmonton, Canada, Volume 120, Pages 178-193, May 2018.
[2] SPX COOLING TECHNOLOGIES, INC. “Cooling Tower Fundamentals”- second
edi-tion, Kansas, USA, 2009.
[3] EPA CONTRACT No. 68-DO-0137. “Development Of Particulate Emission Factors For
Wet Cooling Towers”, Kansas, September 1991.
[4] K. HOOMAN, Z. GUAN, H. GURGENCI. “Advances in dry cooling for concentrating
solar thermal (CST) power plants”, Queensland, Australia.
[5] PAUL LINDAHL, KEN MORTENSEN AND SPX COOLING TECHNOLOGIES.
“Plume Abatement - The next generation”, Houston, Texas, February 2010.
[6] J.P. JENSEN, B. CONRAD, U. SCHUETZ, F.R. ULLRICH, A. WANNING. “Hybrid
dry coolers in cooling systems of high energy physics accelerators”, Lucerne, Switzerland,
2004.
[7] G.J. KOSTEN. “Wet, dry and hybrid system, a comparison of thermal performance”, St Petersburg, Florida, August/September, 1994.
[8] A. STRENG. “Combined wet/dry cooling towers of cell type construction”, Energy Eng. 124, 104 - 121, 1998.
[9] ASHRAE. “Systems and Equipment of Cooling Towers”, 2008.
[10] K. TAKATA, T. MICHIOKA AND R. KUROSE. “Prediction of a Visible Plume from a
Dry and Wet Combined Cooling Tower and Its Mechanism of Abatement”, Japan, 2016.
[11] MCKELVEY, K. K., AND BROOKE, M. “The Industrial Cooling Tower”, Elsevier, Amsterdam, 1959.
[13] JABER, H., AND WEBB, R. L. “Design of Cooling Towers by the Effectiveness - NTU
Method”, ASME J. Heat Transfer, 111, pp. 837 – 843, 1989.
[14] POPPE, M., AND R ¨OGENER, H. “Berechnung von R¨uckk¨uhlwerken”, VDI - W¨armeat-las, pp. Mi 1–Mi 15, 1991.
[15] A. KLIMANEK AND R.A. BIALECKI. “Solution of heat and mass transfer in
counter-flow wet-cooling tower”, International Communications in Heat and Mass Transfer, 36,
No. 6, pp. 547-553, 2009.
[16] TYAGI SK, WANG SW, MA ZJ. Prediction, potential and control of plume from wet
cooling tower of commercial buildings in Hong Kong: a case study. Int J Energy Res.
31:778–95, 2007.
[17] XU X, WANG S, ZHENJUN M. Evaluation of plume potential and plume abatement of
evaporative cooling towers in a subtropical region. Appl Therm Eng. 28:1471–84, 2008.
[18] WANG SW, TYAGI SK, SHARMA A, KAUSHIK SC. Application of solar collectors
to control the visible plume from wet cooling towers of a commercial building in Hong Kong: a case study. Appl Therm Eng. 27:1394–404, 2007.
[19] TYAGI SK, WANG SW, PARK SR, SHARMA A. Economic considerations and cost
comparisons between the heat pumps and solar collectors for the application of plume control from wet cooling towers of commercial buildings. Renew Sust Energy Rev.
12:2194–210, 2008.
[20] F.H. WU AND R.C. KOH. “Mathematical model for multiple cooling tower plumes”, volume 1, Environmental Protection Agency, Office of Research and Development, En-vironmental Research Laboratory, 1978.
[21] J.C. KLOPPERS AND D.G. KR ¨OGER. “Cooling Tower Performance Evaluation:
Merkel, Poppe, and e-NTU Methods of Analysis”, Journal of Engineering for Gas
Tur-bines and Power, ASME, Vol. 127 / 7, South Africa, 2005.
[23] MORTON, B. R., TAYLOR, G. I., AND TURNER, J. S. ”Turbulent gravitational
con-vection from maintained and instantaneous sources”. Proc. Roy. Soc. Lon. A, 234:1–32,
1956.
[24] J.C. KLOPPERS AND D.G. KR ¨OGER. “The Lewis factor and its influence on the
per-formance prediction of wet-cooling towers”, International Journal of Thermal Sciences,
44(9): 879–884, 2005.
[25] EMANUEL K.A. “Atmospheric Convection”, Oxford University Press, New York, 580 pp, 1994.