Siemens AG
Automation and Drives
Industrial Communication
Postfach 48 48
90327 NÜRNBERG
Cat
alog
IK PI · 2007
Industrial Communication
for Automation and Drives
industrial
COMMUNICATION
Cat
alog
IK PI · 2007
Industrial Communication for A
ut
omation and Driv
es
Subject t
o c
hange without prior no
tice | Dispo 26000 | K G 0906 35.0 S 1236 EN / 621608 | Print ed in German y | © Siemens A G 2006
The information provided in this catalog contains descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice.
s
Supersedes:
Catalog IK PI · 2005 and
Catalog IK PI News July · 2005
The products contained in this
catalog are also contained in
the electronic Catalog CA 01
Order No.:
E86060-K4001-A110-C4-7600 (CD-ROM)
E86060-K4001-A510-C4-7600 (DVD)
Please contact your local
Siemens branch office.
© Siemens AG 2006
Industrial
Communication
for Automation
and Drives
Catalog IK PI · 2007
1
PROFINET / Industrial Ethernet
according to IEEE 802.3
2
Industrial Mobile Communication
3
PROFIBUS
according to IEC 61158/EN 50170
4
SIMATIC ET 200 distributed I/Os
5
AS-Interface
according to EN 50 295/IEC 62 026-2
6
SINAUT Telecontrol
7
Network transitions
8
ECOFAST System
9
Appendix
10
The products andsystems described in this catalog are manu-factured/distributed under application of a certified quality mana-gement system in accordance with DIN EN ISO 9001 (Certified Registration No. can be found in the appendix). The certificate is re-cognized by all IQNet countries.
Welcome
More than 60,000 people aiming for the same goal:
increasing your competitiveness. That's Siemens
Automation and Drives.
We offer you a comprehensive portfolio for sustained
success in your sector, whether you're talking
automa-tion engineering, drives or electrical installaautoma-tion
sys-tems. Totally Integrated Automation (TIA) and Totally
Integrated Power (TIP) form the core of our offering.
TIA and TIP are the basis of our integrated range of
products and systems for the manufacturing and process
industries as well as building automation. This portfolio
is rounded off by innovative services over the entire life
cycle of your plants.
Learn for yourself the potential our products and
systems offer. And discover how you can permanently
increase your productivity with us.
Your regional Siemens contact can provide more
infor-mation. He or she will be glad to help.
AS-Interface PROFIBUS Industrial Ethernet PROFINET
ERP
Enterprise
Resource
Planning
MES
Manufacturing
Execution
Systems
Ethernet Ethernet Material Management Equipment Management Production Order Management Production Operations Recording SIMATIC NET Industrial Communication Safety IntegratedControl
SINAUT TelecontrolSystem SIMATICSoftwareSIMATIC Sensors
PC-based Automation
SIMATIC Controllers/ Automation System
Totally Integrated Automation
With Totally Integrated Automation (TIA), Siemens is the only
manufacturer to offer an integrated range of products and
sys-tems for automation in all sectors – from incoming goods to
out-going goods, from the field level through the production control
level to connection with the corporate management level.
On the basis of TIA, we implement solutions that are perfectly
tailored to your specific requirements and are characterized by a
unique level of integration. This integration not only ensures
significant reductions in interface costs but also guarantees the
highest level of transparency across all levels.
Plant Information Management Detailed Production Scheduling
SIMATIC IT Framework
Production Modeler Product Specification Management System Laboratory Information Management System Field Instru-mentation/ Analytics SIMATIC PCS 7Process Control System SIMATIC HMIHuman Machine Interface Drive Systems/ SINAMICS PROFIBUS PA SENTRON Circuit Breakers SIMATIC Distributed I / O SIMOTION Motion Control System SINUMERIK Computer Numeric Control SIMOCODE pro Motor Manage-ment System HART SIWAREX Weighing Technology SINAMICS SIMODRIVE SINAMICS SIRIUS Soft Starter
the first planning steps, through operation, right up to
modern-ization. Consistent integration in the further development of
our products and systems guarantees a high degree of
invest-ment security here.
Totally Integrated Automation makes a crucial contribution
towards optimizing everything that happens in the plant and
thus creates the conditions for a significant increase in
produc-tivity.
PROCESS FIELD BUS U I cos o P W £ 110 kV U I cos o P W
Planning
and configuration
Products and systems
Communication
Process/production
automation
Load manage-mentHMI Graphs Prognoses
Totally Integrated Power
Totally Integrated Power (TIP) brings together all the components
of electrical energy distribution into an integrated whole. Thus TIP
provides the answer to growing market demands in the planning,
construction and use of utility buildings and industrial buildings.
On the basis of TIP, we offer integrated solutions for energy
distri-bution, from medium voltage to the power outlet. Totally
Inte-grated Power is based here on integration in planning and
config-uring as well as on perfectly matched products and systems.
Substation Distribution Maintenance task
Hall 1 Air conditioning system checkup Distribution 3 Replacing circuit
breaker contacts Infeed II Replacing meters
CODES V=VACATION H=HOLIDAY S=SICK
REGULARHOLIDAYOTHER OVER THE HOURS TIME & ONE-HALFSICKVACATION
TOTAL HOURS DATE IN OUT IN OUT OVERTIME
SUNMONTUEWEDTHURFRISATSUNTOTAL TOTAL HOURS DATE IN OUT IN OUT OVERTIME
SUNMONTUEWEDTHURFRISATSUNTOTAL TOTAL HOURS DATE IN OUT IN OUT OVERTIME
SUNMONTUEWEDTHURFRISATSUNTOTAL DATE:
EMPLOYEE COST CENTER PAY PERIOD BEGINNING PAY PERIOD ENDING
central ON OFF local ON OFF tripped instabus EIB Message/ error manage-ment Selective protection
Main-tenance Protocols Powerquality Cost center
Building
automation
distribution systems to industrial automation and
building automation. This enables the
implemen-tation of significant savings potential.
Introduction
Your requirements
Do you want to launch new products quickly? And do you want
to respond quickly and flexibly to market requirements and
reduce conversion times and thus reduce the "time-to-market"?
Do you want to produce efficiently and economically? And do
you want to utilize the capacity of your plant/machine optimally
and minimize possible downtimes?
All the machines in your plant should then work optimally
together. Rely on open, integrated communication for your
automation needs throughout your company and beyond.
Avoid island solutions in automation and in information
technology through:
A seamless flow of information from the sensor/actuator
level up to the company management level
Availability of information in any place
Fast data exchange between plant sections
Simple, consistent configuration and efficient diagnostics
Integrated security functions which prevent unauthorized
accesses
Fail-safe communication and standard communication over
the same cable
Our offer
Communication networks are of central importance in
automation solutions. SIMATIC NET Networking for Industry
stands for a versatile portfolio of modular blocks designed
for industry which contribute to solving your communication
tasks efficiently.
In the different automation areas
Across the whole workflow
Across the whole plant life cycle
For all sectors
SIMATIC NET offers solutions which utilize the advantages of
Ethernet and integrate fieldbus systems. Outstanding examples
are:
The exploitation of the field level for Industrial Ethernet
The consistency from the field level up to the company
management level
The pushing ahead of mobile communication
The integration of IT technologies
Worldwide trends
A distributed plant configuration reduces the overhead for
installation, maintenance and diagnostics. A distributed plant
configuration reduces the overhead for installation,
mainten-ance and diagnostics. Such configurations involve the use of
intelligent devices at the local level which are interfaced to one
another over networks. Openness and flexibility are important
in linking different systems and carrying out expansions. The
standards for bus systems are defined and standardized in
international committees.
Industrial Ethernet (IEEE 802.3, IEEE 802.3u and IEEE 802.11 WLAN) the international standard network standard for all levels
Industrial Ethernet
PROFIBUS (IEC 61158/EN 50170) the international standard for the field is the world-wide market leader for fieldbusses
PROFIBUS
PROFINET the open Industrial Ethernet standard for automation
AS-Interface (IEC 62026-2/EN 50295) connects sensors and actuators using a two-wire cable which is an economic alternative to cable harnesses.
KNX/EIB (EN 50090, ANSI EIA 776) is the universal bus system for the entire house and building technology. KNX was developed by the Konnex Association based on EIB (European Installation Bus).
AS-Interface
With Totally Integrated Automation, Siemens is the only supplier
of a consistent range of products and systems for automation
in all sectors from incoming goods storage via the production
process up to dispatching products, from the field level via the
production control level up to the integration of the company
management level.
The advantages of Totally Integrated Automation already pay
off at the design and engineering level, but also during assembly
and startup as well as during operation and maintenance.
Automation solutions can be created with little outlay. New
freedoms make it easier to respond more quickly and flexibly
to new market requirements.
Plants can be easily expanded or converted without having to
interrupt current operations.
Thanks to the fact that Industrial Ethernet has been venturing
more and more into automation all the way down to the field
level, two ingredients of Totally Integrated Automation are
achieving ever greater significance: PROFINET and SCALANCE.
PROFINET ... increases the productivity of your plant
For your strategic decisions you require a seamless,
company-wide information flow - from the first manufacturing step via
the operational level up to the company management level.
To achieve this, you must rely on efficiency and consistency at
the very beginning when you design your plant.
PROFINET, the open, innovative Industrial Ethernet standard,
fulfills all the demands of industrial automation and enables
integrated, company-wide communication.
PROFINET also supports the direct connection of distributed
field devices to Industrial Ethernet and the solution of Motion
Control applications in isochrone mode. PROFINET also enables
distributed automation with the aid of component technology
which allows vertical integration and fail-safe applications.
PROFINET also supports controller-to-controller communication.
SCALANCE ... for the security, flexibility and performance
of your industrial communication networks
Totally Integrated Automation by Siemens shows with a number
of successful applications around the world to what extent
consistent solutions with shared tools and standardized
mechanisms can be created today. Closely connected to this
is the selective further development of industrial communication
with SIMATIC NET. A revolutionary milestone of this
develop-ment is SCALANCE, the new generation of components for the
installation of uniform networks:
Industrial Communication
by Totally Integrated Automation
Conducted electrically or optically or wireless via Industrial
Wireless LAN (IWLAN).
In industrial environments and similar.
SCALANCE is available in three different versions:
The security modules of SCALANCE S are the core of this
pioneering safety concept for automation engineering from
Siemens that protects networks and data.
Based on Industrial Wireless LAN, SCALANCE W supports
integrated communication as far as areas that until now
have been difficult or even impossible to access.
The Industrial Ethernet switches (active network components)
of SCALANCE X ensure future-oriented networks; and the
perfect switch is always available for every task.
An overall solution comprises a
a bus system
passive network components, e.g. cables
active network components, e.g. switches
interfaces for connecting the programmable controllers to
the bus systems
integrated interfaces
separate communications processors
gateways, e.g. a link
software for configuring the networks
tools for maintenance and diagnostics
SIMATIC NET offers all the components required for an integrated
overall solution, and supports the following bus systems:
Enterprise Resource Planning (ERP) (e.g. PC) Control (e.g. S7-300)
Bus system
AS-Interface PROFIBUS DP Industrial Ethernet PROFINET Drives (e.g. SINAMICS) Simple field devices (e.g. digital I/O modules) Sensors/actuators Intelligent field devices (e.g.ET200S) Motion Control (e.g. SIMOTION) Level Failsafe communication not suitable Suitable W ell suit ed
Industrial Ethernet
(IEEE 802.3 and 802.3u)
The international standard for
local area networking. With a
market share of 90%
world-wide it is now the number one
with respect to local area
net-works. Industrial Ethernet can
be used to construct
high-performance communication
networks that span great
distances.
PROFINET
The international standard
uses Industrial Ethernet and
enables real-time
communica-tion all the way down to the
field level while also including
the enterprise level.
Despite full use of existing IT
standards, PROFINET enables
isochronous motion control
applications, efficient
cross-vendor engineering and a
high level of machine and
plant availability on the
Indus-trial Ethernet. PROFINET
sup-ports distributed automation
(including
controller-to-controller communication)
and makes fail-safe
applicati-ons possible.
PROFIBUS
(IEC 61158/EN 50170)
The international standard for
the field level is the world
market leader among field
bu-ses. It is the only field bus
which permits
communica-tion for manufacturing as well
as process-oriented
appli-cations.
Bus systems for Industry
Industrial Ethernet
PROFIBUS
PROFIBUS PA
Telecontrol and substation control PC Controller Notebook PC/PG Monitoring and control system Field device forintrinsically safe area Monitoring and control system Teleservice Controller Coupler Link Motor manager Drives Field devices Machine Vision Numeric Control Numeric Control
KNX
AS-Interface
ControllerSecurity PC/PG
Motion Control Systems Telecontrol and substation control Motion Control Systems Controller Link Actuator
Power supply unit Sensors
Field devices Machine Vision Access Point Client Module Field device Drives Controller Controller Link Link Access Point Notebook IWLAN RCoax Cable Link Link
PROFINET
Industrial Ethernet
AS-Interface
(IEC 62026/EN 50295)
Combines sensors and
actua-tors using a two-wire line as
price-effective alternative to
a wiring harness.
The basis for building services
automation is the global
KNX/EIB (EN 50090,
ANSEI EIA 776) standard.
Network interfaces are
imple-mented via controllers or
links. Configuration and
diag-nostics can be carried out
from any location in the plant.
S7-200
Industrial Ethernet
Industrial Ethernet offers a
powerful area and cell
network in accordance
with standard IEEE 802.3
(ETHERNET), IEEE 802.3u and
802.11 a/b/g/h (Wireless LAN)
for industry.
Ethernet is the basic technology of the Internet for worldwide
networking. The different possibilities of the Intranet, Extranet
and Internet, which are already available in office
environ-ments today, can, using Industrial Ethernet, also be utilized for
manufacturing and process automation.
The Ethernet technology which has been used successfully for
many years for switching, full duplex and autosensing allows
the user to adapt the necessary network performance to
re-quirements. The user can select the data rate as needed since
the consistent compatibility permits step-by-step introduction
of the new technology.
Ethernet presently has a market share of over 90% with a
tendency to rise further, thus placing it in pole position in the
LAN landscape worldwide.
Ethernet offfers important advantages:
Fast start-up thanks to the simplest connection method.
High availability since existing networks can be extended
without any adverse effects
Almost unlimited communications performance because
scalable performance is available through switching
techno-logy if required.
Networking of different application areas such as the office
and production areas.
Company-wide communication thanks to linking up via WAN
(Wide Area Network) such as ISDN or Internet
Investment security through continuous compatible further
development.
Data storage for Industrial Wireless LAN (IWLAN)
"Rapid Roaming"
For very fast forwarding of mobile nodes between different
access points
Chronologically exact allocation of events throughout the
whole plant system through plant-wide clock control.
SIMATIC NET relies upon this well-proven technology. Siemens
has supplied well over two million connections worldwide for
rough and EMC polluted areas of industry.
Machine Vision MOBIC SIMATIC TDC S7-300 with SINAUT ST7 Industrial Ethernet Access Point SCALANCE W788-1PRO S7-300 S7-400 SIMATIC HMI with WinAC S7-200 with SINAUT MICRO ET 200
SIMATIC NET provides important supplements to Ethernet
technology for industrial environments:
Network components designed for use in rough industrial
environments
Fast assembly on site thanks to the FastConnect wiring
system with RJ45 technology
Fail-safe networks thanks to fast redundancy and redundant
power supplies
Continuous monitoring of network components through a
simple and effective signaling concept.
Future-oriented network components with the SCALANCE X
switch family, the members of which build on one another
Note-book MOBIC SIMOTION C/P/D SINUMERIK SINAMICS S 120
workstations to be connected. The maximum volume of useful
data per task is 64 KB. S7 communication offers simple, powerful
communication services and provides a network-independent
software interface.
S5-compatible communication (SEND/RECEIVE)
S5-compatible communication (SEND/RECEIVE) is used by
SIMATIC S7/C7 to communicate with existing systems, especially
with SIMATIC S5 partner, but also with PCs over PROFIBUS and
Industrial Ethernet.
FETCH and WRITE is also available over Industrial Ethernet to
ensure that software created for SIMATIC S5 can continue to
be used with SIMATIC S7 without any modifications.
Standard communication
This comprises standardized protocols for data communication,
e.g. FTP. Fail-safe communication is also possible via Industrial
Ethernet.
OPC
(OLE for Process Control)
is a standardized, open and manufacturer-independent interface
and allows OPC-capable Windows applications to interface to
S7 communication and S5-compatible communication (SEND/
RECEIVE) and PROFINET.
Information technology (IT) with e-mail
and Web technology
integrates SIMATIC, SIMOTION and SINUMERIK into the IT
through Industrial Ethernet. In the office environment, e-mail
and Web-browsers are widely used communication techniques.
Ethernet is used as the main communication route, in addition
to telephone cables and the Internet.
The socket interface for Industrial Ethernet
facilitates data communication with computers via TCP/IP.
Users can program the data exchange freely using this widely
used interface in the PC and UNIX world. SIMATIC S7 and
SIMATIC TDC use the SEND/RECEIVE blocks (S/R) to access TCP/IP.
PROFINET communication services
PROFINET IO for connecting distributed field devices to
Industrial Ethernet
PROFINET CBA for modern plant construction for the
implementation of distributed automation structures based
on pre-assembled components
The following communication functions/services are offered
by Industrial Ethernet:
PG/OP communication
This includes integrated communication functions, via which
the SIMATIC, SIMOTION and SINUMERIK automation systems
can carry out data communication with any HMI device (TD/OP)
and SIMATIC PG (STEP 7).
PG/OP communication is supported by all networks.
S7 communication
S7 communication is the integral communication function
(system function block) for the S7-400 or loadable function
blocks for the S7-300 which have been optimized in the context
PC with WinCC flexible or SINAUT MICRO SC PC Field PG M SIMATIC WinAC Access Point SCALANCE W788-1RR Client Module SCALANCE W747-1RR SINAMICS S120 ET 200 SCALANCE X202-2P IRT ET 200S with IM 151-3 PN FO SIMOTION D/P SCALANCE S SINUMERIK
PROFINET
The open standard for automation
The increasing importance of
vertical integration shows the
important role played by
industrial communication
throughout modern
automa-tion engineering.
PROFINET, the open and cross
vendor standard based on Industrial Ethernet, enables direct,
transparent access from the corporate management level to
the field level. To make this possible, PROFINET relies on
established IT standards and fully supports TCP/IP.
Make use of synergies and protect investments:
Problem-free integration of existing systems
Do you want to continue utilizing and expanding existing
systems and plant sections which communicate over PROFIBUS
and other fieldbuses in future? No problem! With PROFINET,
integration of the installed basis is easy and can be done
without a lot of overhead. PROFINET thus ensures a high level
of investment protection for existing systems and you can rely
on an innovative standard now and in the future.
The optimum basis for PROFINET: Industrial Ethernet
Ethernet has established itself as standard in the office world.
Thanks to its excellent market acceptance, Ethernet was chosen
for continuous further development, for example as regards
transmission rates. In order to make it possible to utilize Ethernet
for hard industrial demands, we have been offering Industrial
Ethernet, a standard-based network, for more than 15 years.
PROFINET utllizes this basis to link devices from the field level
to the management level, thereby combining industrial
capa-bilities with the continuity and transparency of inter-company
communication.
PROFINET: New possibilities for Industrial Ethernet
As a component of IEC 61158, PROFINET is based on the
international Ethernet standard (IEEE 802.3) and builds
systematically on Fast Ethernet with 100 Mbit/s and switching
technology. PROFINET is particularly distinguished by the
following: Shared use of real-time and TCP-based
communi-cation over the same cable as well as scalable real-time
communication for programmable controllers, distributed I/O
and motion control. PROFINET therefore ensures short response
times and continuity from the field level to the management
level.
Process
Real-time
communication
Distributed
field devices
Motion
control
Distributed
intelligence
Network
installation
IT standards
& security
Safety
Integrated
PROFINET
Safety Integrated
PROFINET also fulfills all required prerequisites as regards
complete safety for humans, machines and the environment.
The use of PROFIsafe enables a network for standard and
fail-safe communication on one and the same cable.
IT standards & security
PROFINET provides all functions for optimum configuration
and diagnostics. All relevant data can be accessed from
anywhere in the world over the Internet. PROFINET also fulfills
increased demands on data and network security.
Simple network installation
PROFINET relies systematically on 100 Mbit/s switching
technology and supports linear and ring network topologies
as well as the star topology customary with Ethernet. This
minimizes cabling overhead and ensures the highest possible
availability. Wireless communication opens the door to new
industrial applications.
Distributed intelligence
PROFINET offers new options for the implementation of
distributed automation structures: Systematic modularization
and simple machine-to-machine communication with
plant-wide engineering - thanks to Component Based Automation
Motion control
PROFINET makes it possible to implement very fast, isochronous
drive control for high-performance motion control applications
without a lot of overhead while at the same time using TCP/IP
communication.
Distributed field devices
Distributed field devices can be directly interfaced to Industrial
Ethernet via PROFINET. This enables fast data interchange
between I/O and controller and provides for significantly better
diagnostic options.
Real-time communication
PROFINET fulfills all real-time demands relevant to automation,
including isochronous mode. PROFINET is therefore also suitable
for particularly sophisticated, complex applications, for example
those involving motion control.
Process
PROFINET was conceived as a comprehensive standard for all
automation tasks. Special requirements for use in industrial
plants and the interfacing of process instrumentation devices
and analyzers are currently being worked on with an eye toward
standardization.
while differentiating between three basic communication
characteristics:
Non-real-time such as TCP/IP and UDP/IP communication
Real-time (RT) and
Isochronous real-time (IRT)
TCP/IP and UDP/IP communication
Non-time-critical data transmission with TCP/IP and UDP/IP is
the technical basis for communication for instance for
assigning parameters and configuration. In the IT landscape,
TCP/IP is a defacto standard.
The solution for all demands:
Industrial Mobile Communication
IMC stands for the industrial mobile communication products
of SIMATIC NET that utilize wireless communication. This is
based on worldwide standards, such as IEEE 802.11, GSM,
GPRS or, in the future, UMTS.
Also possible is fail-safe wireless
communi-cation over IWLAN.
IWLAN/ PB Link PN IO PROFIBUS Access Point SCALANCE W788-1RR Client Module SCALANCE W747-1RR Access Point SCALANCE W788-1RR ET 200S S7-300 with PROFINET-CPU or CP 343-1 ET 200pro SINAMICS PC with SINEMA E planning software ET 200S S7-300 with CP 343-1 Lean with integrated 2-port switch PROFINET IWLAN RCoax Cable
The key to future market success lies in the ability to provide
information and access to information at any time and in any
location.
With mobile systems interconnected via fast wireless radio
networks (Wireless LAN), processes can be designed for greater
efficiency. The main advantage of wireless solutions is easy
and flexible access to mobile stations. Industrial Mobile
Communication (IMC) plays an important role in this:
Increased competitiveness since greater mobility achieves
higher flexibility
Maintenance work is simplified, service costs and downtimes
are reduced and personnel is used optimally
Spare parts lists and manuals are available regardless of the
location
Work orders can be received and acknowledged online
Integrated radio network for voice and data beyond corporate
boundaries
The system solution is tested and well-proven because the
network components, communications processors and
software are perfectly matched to each other
Remote diagnosis for different production machines from a
central service location reduces service costs
Difficult to reach installations can be accessed easily; there
is no need for complex wiring
Fast commissioning of new plant sections due to reduced
overhead for the installation of the communications network
with the aid of the SINEMA E planning, simulation and
configuration software.
No wear on rotating and moving devices or equipment
Cost-effective connection to devices which are remote,
difficult to access or in hostile environments.
SCALANCE W wireless communication
The products of SCALANCE W offer the unique combination of
reliability, ruggedness and security.
With Industrial Wireless LAN (IWLAN), an extension to the
IEEE 802.11 standard is made available that addresses the
requirements of industrial customers in particular with regard
to a deterministic response and redundancy. For the first time
customers are getting a single radio network both for data
critical to the process (e.g. alarm signaling) as well as for
uncritical communication (e.g. for service and diagnostics).
IWLAN components SCALANCE W and PROFINET, the Industrial
Ethernet standard, provide a mobile solution for new
applications all the way down to the field level.
and waterproof construction (IP65) of the metallic enclosures,
fulfilling SIMATIC's well-known high demands on mechanical
stability.
To protect against unauthorized access, the products provide
modern standard mechanisms for user identification
(authen-tication) and encryption of data, but can also be easily integrated
into existing security policies.
The "Rapid Roaming" function is available for very fast forwarding
of mobile nodes between two different access points.
AS-Interface
ET 200S
PROFIBUS
PROFIBUS DP/PA is used to
link field devices such as
distributed I/O stations or
drives with programmable
controllers such as
SIMATIC S7, SIMOTION
or PCs.
PROFIBUS, standardized to IEC 61158, is a powerful open and
robust field system with short response times. PROFIBUS is
available in different designs for different applications.
PROFIBUS DP
(distributed I/O)
is used to connect distributed field devices, e.g. SIMATIC
ET 200 or drives with very fast response times. PROFIBUS DP
is used when actuators/sensors are distributed throughout the
machine or plant (e.g. field level).
Openness all the way
Thanks to the openness of PROFIBUS DP it is, of course, also
possible to connect standardized components of other
manufacturers. The IEC 61158/EN 50170 standard ensures
that your investments are secure for the future.
Member companies worldwide offer a wide range of products
with PROFIBUS DP interface for the field level. Siemens has a
complete product portfolio of standard and fail-safe controllers,
network components, communications software and field
devices.
And for manufacturers of field devices, we offer everything
that has to do with the PROFIBUS DP, such as ASICs, training,
certification and much, much more.
PROFIsafe
Permits standard and fail-safe communication over one and
the same bus cable. PROFIsafe is an open solution for fail-safe
PROFIBUS DP SIMATIC C7 SIMOREG SIMATIC S7 ET 200M ET 200L Field PG M Notebook RFID systems SIMATIC RF MICRO-MASTER SIMOVERT MASTER-DRIVES SIMOCODE PRO SIMOTION C/P/D SIMODRIVE ET 200pro ET 200M with F I/O S7-300F with standard and F I/O
SINAMICS SINUMERIK DP/AS-Interface Link 20E ET 200eco DP/AS-i LINK Advanced
Isochronous mode
CPU, drives, I/O and user program are synchronized to the
PROFIBUS clock. The "isochronous mode" function is supported
by the CPUs of the SIMATIC S7-400, SIMOTION/SINUMERIK
and servo drives. The PROFIdrive profile is used for drive
control
PROFIBUS PA
(Process automation)
expands PROFIBUS DP with safe data and power transmission
(e.g. measuring transmitters in the food industry) in
accordance with international standard IEC 61158-2 (same
protocol, different design).
DP/EIB Link Mobile Panel
KNX
(EN 50090, ANSI EIA 776) is the worldwide standardized building installation system and the basis for building automation.
Vision Sensor VS 120 VS 130 DP/PA coupler/link SITRANS F US SITRANS P Customer specific sulutions with ASICs PROFIBUS PA RS 485iS coupler
Intrinsically safe area SIMATIC TDC DP/DP coupler ET 200iSP Power Rail Booster DP slave Customer specific sulutions with ASICs SIPART PS2 PROFIBUS FMS SIMATIC HMI S7-400 S7-300 non-Siemens
devices SIMATIC C7 Field PG M SIMATIC C7
PROFIBUS DP
* PDM is a parameterization tool for intelligent field devices
*
PROFIBUS FMS
(fieldbus message specification)
for the data communication of programmable controllers
provided by different manufacturers. In this way, general control
and measuring tasks can also be solved accurately in a
distributed fashion in addition to motion control tasks.
AS-Interface
Sensors, valves, actuators,
drives different components
operate on the field level.
All these actuators/sensors
must be connected to a
programmable controller.
This is implemented with the
help of distributed I/O devices; so to speak as intelligent outposts
on site.
AS-Interface connects the components of the field level by
means of a twisted pair cable as a low-cost alternative to a
cable harness.
AS-Interface is used where individual actuators/sensors are
distributed spatially over the machine (e.g. in a bottling plant).
AS-Interface is the open international standard IEC 62026-2/
EN 50295, and is supported worldwide by 280 member
companies of the AS International Association, including the
leading manufacturer of actuators and sensors. The system
has been used successfully in the field since 1994, and is with
10 million installed nodes the uncontested market leader
among bit-oriented bus systems.
AS-Interface is a single-master system. There are
communica-tions processors (CPs) for SIMATIC and for SIMOTION and Links
which, as master, control field communication.
With AS-Interface Specification V2.1 resp. V3.0, it is possible
to connect as many as 62 slaves. AS-Interface Specification
V3.0 enables the connection of up to 1,000 digital inputs/
outputs (Profile S-7.A.A: 8DI/8DO as A/B slave). New profiles
open the door to the use of expanded addressing, even for
analog slaves. "Fast Analog Profiles" speed up analog value
transfer. Thanks to integrated analog-value processing in the
masters, the access to analog values is just as simple as the
access to digital values.
The connection of SIMATIC S7 controllers, WinAC or other
systems to AS-Interface is implemented via IE/AS-iLINK PN IO,
DP/AS-i LINK Advanced or via the DP/AS-Interface Link 20E.
DP/AS-i-LINK Advanced and DP/AS-interface Link 20E in IP20
are available for direct interfacing of the AS-Interface to
PROFIBUS DP. This allows the AS-Interface to be used as subnet
for PROFIBUS DP.
IE/AS-i LINK PN IO enables direct interfacing of the AS-Interface
to Industrial Ethernet and thus direct embedding in the
PROFINET environment.
In this way, you can make savings
AS-Interface replaces complex cable harnesses and connects
binary actuators and sensors such as proximity switches, valves
or indicator lights with a programmable controller, e.g. SIMATIC.
In practice, this means: Installation runs smoothly because
data and power are transported together on one cable.
Thanks to the specially developed flat cable (in yellow) and to
insulation displacement, the AS-Interface slaves can be
con-nected at any point.
This concept ensures extreme flexibility while saving a significant
amount of time and money. Special knowledge about
installation and commissioning is not required. In addition, the
ease of laying the cable and the clear structure of the cable as
well as the special version of the cable not only significantly
reduce the fault risk, but also the overhead for service and
maintenance.
AS-Interface distributor (without AS-Interface chip) AS-Interface-Netzteil I/O module digital/analog (without AS-Inter-face chip) Repeater LOGO! Operator control panel
Safe slave with EMERGENCY STOP
Compact starter IP 65
AS-Interface power supply
AS-Interface master * PROFIBUS DP
Safety monitor Signal evaluation 24 V DC power supply
AS-i Extension Plug (for segment length up to 200 m) Max. AS-iI cable length
per segment:
100 m without Extension Plug 200 m with Extension Plug
Max. AS-iI cable length per segment:
100 m without Extension Plug 200 m with Extension Plug
connected to an AS-I line.
SIMATIC C7 DP/AS-Interface Link 20E
S7-300 S7-200 SIMOTION C AS-Interface distributor PROFINET Industrial Ethernet AS-Interface master * S7-300 with PROFINET-CPU S7-200 SIMATIC C7 IE/AS-i LINK PN IO AS-Interface DP/AS-i LINK Advanced
Telecontrol and remote maintenance
SINAUT Telecontrol
SINAUT, the telecontrol system based on SIMATIC S7, consists
of two independent systems:
SINAUT ST7
Versatile telecontrol system based on SIMATIC S7-300,
SIMATIC S7-400 and WinCC for fully-automatic monitoring
and control of process terminals which exchange data with
one or more control centers or with each other via a WAN
or over Ethernet (TCP/IP).
SINAUT MICRO
Telecontrol system for monitoring and controlling distributed
plants using wireless communication (GPRS) on the basis of
SIMATIC S7-200 and WinCC flexible or WinCC. As a result of
its bidirectional communications capability, SINAUT MICRO
can handle simple telecontrol tasks.
An OPC server is available for both systems which permits
connection to a non-Siemens control center system (OPC client).
SINAUT ST7
SINAUT ST7 facilitates an integrated communications concept
(TIA) and complete integration into the SIMATIC environment.
The modular design and the support of a huge variety of
network forms and operating modes including Ethernet permit
the design of flexible network structures that can also contain
redundant links.
By using all forms of transmission media (e.g. dedicated line,
wireless, dial-up networks, SMS, FAX), the networks can be
optimally adapted to the respective local conditions.
First-time configuration of even highly complex networks and
their expansion can be carried out easily and cost-effectively
thanks to the software packages provided and STEP 7.
The control center
The following can be used as central control centers:
SIMATIC S7-300 or S7-400 controllers.
SINAUT ST7cc, the PC control system (simple or redundant),
is based on WinCC. It is a supervisory control system specially
matched to the event-controlled and time-stamped data
transmission of the SINAUT system.
SINAUT ST7sc for connecting control centers of other
manufacturers over OPC. The SINAUT telecontrol technology
can also be connected to control center systems of other
manufacturers via the data access interface. ST7sc features
extensive buffer mechanisms which prevent data from being
lost even if the OPC client fails.
SINAUT WANs
Dedicated lines (copper and fiber-optic cables)
Private radio networks (optionally with time slice procedure)
Analog telephone network
Digital ISDN network
SINAUT over Ethernet
SINAUT communication over Ethernet or TCP/IP-based networks
is possible between the stations and the control point as well
as between stations. Prerequisites are fixed IP addresses as well
as connections that are similar to dedicated lines.
Change-driven data transmission
The SINAUT software in the stations ensures that process data
is transmitted between the individual CPUs and with the control
center in the event of changes.
Local data storage
A special characteristic of the TIM transmission module used
for the SINAUT ST7 system is the local storage of the data
messages (incl. time stamp) if the communication path is
disturbed, a partner is lost or for cost optimization when dialing
networks.
Date and time are always up-to-date
A DCF77 radio clock can be used to supply the CPUs and the
control center, e.g. ST7cc, with the date and time across the
network. The systems therefore always have the exact time;
including daylight savings time switchover. The GPS (Global
Positioning System) can also be used as the time source instead
of DCF77.
SINAUT remote programming and remote diagnostics
All diagnostics and programming functions provided by SIMATIC
and SINAUT for station automation and WAN communication
can be used via the SINAUT networks without interrupting
process data transmission.
MPI DCF 77 GPS MPI SINAUT ST7cc SINAUTST7sc Central controller SINAUT Ethernet TCP/IP Industrial Ethernet WAN WAN TIM 4 TIM 4
SINAUT MICRO is the cost-effective extension to the monitoring
and control of simple telecontrol tasks. It consists of a
GSM-GPRS modem, OPC and connection management software
optimized for GPRS and an S7-200 program block package.
With this package, as many as 256 SIMATIC S7-200 stations
can communicate easily and securely over GPRS mobile radio
with the control center and with each other. They are constantly
online.
SINAUT MICRO is perfect wherever small amounts of data are
to be transferred over wireless connections. The system is
configured using STEP 7 Micro/WIN.
Maintenance personnel can also access the secured control
center and query or set current values from the S7-200 stations
from home per Internet browser. SMS or fax fault messages
sent directly by S7-200 remote stations and received over
mobile radio telephone can be analyzed in the control center,
making it possible to respond more quickly.
The routing functionality of OPC server SINAUT MICRO SC also
enables bidirectional communication between S7-200 stations
interfaced via the SINAUT MD720-3 modem.
Under WinCC, OPC server SINAUT MICRO can be combined
with SINAUT ST7cc to create a cost-optimized central fault
annunciation and telecontrol system which can grow according
to need.
The MPI interface on SIMATIC S7/C7, SIMATIC TDC,
SIMOTION/SINUMERIK automation systems and OPs is
lengthened over the telephone network. This requires nothing
more than a TS adapter and a modem. The TeleService
engineering tool establishes a connection with the machine
or plant. The familiar functionality of STEP 7, Drive ES, SIMOTION
SCOUT and the diagnostic tools are available throughout.
This teleservice is handled as if a maintenance man were
actually sitting at the machine or in the plant. An additional
PC/PG is not required.
Central control center GSM/GPRS provider S7-200 station with modem SINAUT MD720-3 S7-200 station with modem SINAUT MD720-3 S7-200 station with modem SINAUT MD720-3 Internete.g. WinCC flexible, Win CC SINAUT MICRO SC OPC server and connection manager
KONNEX (KNX)
for home and building system technology
Higher requirements with respect to flexibility and ease-of-use
of the electronics installations, combined with the desire to
minimize own costs, have resulted in the development of
building system technology. The bus technology used for this
purpose uses a common European concept.
KNX is the universal bus system for the complete range of
home and building system technology which was developed
by the Konnex Association from the
EIB (European installation bus)
EHS (European home systems)
and BatiBUS
based on the EIB. KNX products therefore ensure interoperability,
product quality and functionality in the same way as EIB.
All products are configured with a manufacturer-independent
software tool. The functionality of each existing EIB system
can be expanded with KNX.
As the most successful and most established system on the
market, EIB remains the central and unchanging system core
of the KNX standard. The expansion of the system platform
has cleared the way to offering and marketing efficient and
economic new installations for non-residential buildings,
residential constructions and modernizations.
PROFIBUS
PROFIBUS PA
PC/PG Monitoring and
control system Field device for
intrinsically safe area
Controller Coupler Link Motor manager Field devices Machine Vision Numeric Control KNX
KNX also includes radio and infrared transmission media in
addition to twisted pair cables and Powerline. This opens up
opportunities for retrofitting. Furthermore, it is also possible
to integrate additional systems such networks of electrical
appliances (home appliances etc.). In addition, services such
as remote maintenance, remote data acquisition of consumer
data and security services can be offered with KNX.
System arguments
Conventional electrical installations require a separate cable
for each function and each control system requires a separate
network.
In contrast to this, EIB permits all operational functions and
procedures to be controlled, monitored and signaled over a
shared cable. In this way, power can be supplied directly to the
consumers without extra cabling.
Apart from saving cables, this also has the following
advan-tages: Installation in a building is much less complicated and
can later be easily expanded and modified. If the systems are
later used for different purposes or spaces are divided differently,
the EIB can be adapted easily by simply reassigning
(reconfi-guring) the bus stations without having to lay new cables.
AS-Interface WinAC
Network transitions
PC with PN OPC server IE/PB Link PN IO (Proxy) PC with SIMATIC WinAC (Proxy) S7-400 S7-300 DP/EIB Link PC PG S7-300 with PROFINET-CPU S7-200 S7-400 PROFIBUS KNX/EIB S7-300 with PROFINET-CPU IWLAN/PB Link PN IO (Proxy) S7-300 IE/PB Link SCALANCE W-780 Access PointNetwork transitions from one bus system to another are
implemented using links, PLCs or PCs. In the case of PLCs or
PCs, this can take place via integrated interfaces and
communications processors (CPs). Links pass on the data
autonomously from one network to the other.
The following links are available:
IE/PB Link and IE/PB Link PN IO for the transition from Industrial
Ethernet to PROFIBUS (also for fail-safe communication)
IE/AS-i LINK PN IO for the transition from Industrial Ethernet
to AS-Interface
IWLAN/PB Link PB IO for the transition from IWLAN to
PROFIBUS
DP/AS-i LINK Advanced and DP/AS-Interface Link 20E for the
transition from PROFIBUS to AS-Interface
DP/EIB Link for the transition from PROFIBUS to KNX/EIB
In the case of PLCs such as e.g. SIMATIC S7-200, S7-300,
S7-400, SINUMERIK or SIMOTION C, data is exchanged between
the individual networks by means of communications processors
or integrated interfaces. The data is linked by means of a PLC,
and therefore passed on to the other network already
pre-processed.
PROFINET network transition with proxy functionality
PROFIBUS segments can be connected to Industrial Ethernet
via PROFINET proxies. This connection can be implemented
using a solution with the SIMATIC WinAC PN optional package,
SIMATIC S7-300/400-CPUs with DP and PN interface, IE/PB Link
or via the IE/PB Link PN IO. For a wireless network transition,
a SCALANCE W-700 access point with the IWLAN/PB Link
PN IO can be used. This allows all PROFIBUS standard slaves to
be used unchanged for PROFINET.
PROFINET Industrial Ethernet SINUMERIK SIMATIC C7 IE/AS-i LINK PN IO AS-Interface master *
SIMATIC C7 DP/AS-Interface Link 20E
S7-300 S7-200
SIMOTION C
DP/AS-i LINK Advanced
* Only one master can be optimally connected to an AS-I line.
Data for practical applications
Criteria
Line Tree Star
Topology
electrical up to 5 km
optical up to 150 km
world-wide with TCP/IP
wireless with wireless LAN
Data rate
9.6 Kbit/s 12 Mbit/s
adjustable
31.25 Kbit/s
1)10/100 Mbit/s
1 Gbit/s (not for PROFINET)
62
Number of nodes
max.
125
125 DP/PA Links
1)31 field devices pro
1)DP/PA Link
over 1000
electrical up to 600 m:
- With extension plug
up to 200 m
- With repeater or
extender up to 300 m
- With repeater and
extension plug
up to 600 m
Size of Network
LA N
(Local Area Network)
WA N
(Wide Area Network)
electrical up to 9.6 km
optical up to 90 km
Ex: max 1.0 km
1)Non-Ex: 1.9 km
1)1)with PROFIBUS PA
Line Tree Ring Star
Line Tree Ring Star
Update times £ 5 ms
Bus system
AS-Interface
PROFIBUS DP
Industrial
2/180 System interfacing for SIMATIC and SINUMERIK 2/181 CP 243-1 2/184 CP 243-1 IT 2/187 CP 343-1 Lean 2/190 CP 343-1 2/194 CP 343-1 Advanced 2/198 CP 443-1 2/201 CP 443-1 Advanced
2/205 System interfacing for PG/PC 2/207 Performance data
2/208 Connection options to SIMATIC PCs 2/209 CP 1616
2/212 CP 1604 2/215 CP 1613 A2
2/219 S7-REDCONNECT
2/221 SOFTNET for Industrial Ethernet 2/223 SOFTNET PN IO
2/225 OPC-Server for Industrial Ethernet 2/229 PN CBA OPC server
2/232 SNMP OPC server 2/234 SOFTNET for LINUX/UNIX 2/236 SOFTBUS for LINUX/UNIX
2/238 System interfacing for SIMATIC HMI 2/246 Accessories
2/246 C-PLUG
Sec. 3 Power Supply PS791-1PRO 2/248 SICLOCK time synchronization 2/252 ET 200S distributed I/Os 2/252 IM 151-3 PN interface modules 2/255 IM 154-4 PN interface modules 2/257 Motion Control System SIMOTION 2/259 Communication Board CBE30 2/260 Communication Board MCI-PN 2/261 PROFINET technology components 2/261 Enhanced Real-Time Ethernet Controller
ERTEC
2/267 Development kits for ERTEC 2/272 Development packages 2/273 Image Processing System 2/273 SIMATIC VS120
2/277 SIMATIC VS130-2 2/282 Engineering Tools Sec. 4 STEP 7
2/282 SIMATIC iMap Sec. 3 SINEMA E Lean
2/285 SINAMICS S120 Drive System 2/287 Communication Board CBE20 Sec. 3 Industrial Mobile Communication Sec. 8 Network transitions
Industrial Ethernet
according to IEEE 802.3
2/2 Introduction 2/2 General information 2/4 Data communication 2/5 Communications overview 2/7 Configuration examples 2/9 Topologies2/18 Network selection criteria 2/20 PROFINET
2/20 Introduction
2/23 PROFINET-Products for Industrial Ethernet 2/25 Passive Network Components
2/25 Summary of network components 2/26 Overview of Twisted Pair 2/27 Industrial Ethernet FastConnect 2/29 IE FC RJ45 Plug 2/32 IE connecting cable M12-180/M12-180 / M12 Plug PRO 2/33 IE FC TP Cable 2 x 2 2/38 IE FC TP Cable 4 x 2 2/41 IE Hybrid Cable 2/43 Energy Cables 2/46 IE TP Cord 2/51 IE FC Outlet RJ45 2/56 IE FC RJ45 Modular Outlet 2/62 Industrial Twisted Pair –
Cables/connectors
2/65 Overview of fiber-optic cables 2/66 Glass fiber-optic cables 2/74 POF- and PCF fiber-optic cables 2/78 POF/PCF-LWL termination kit 2/80 Active Network Components 2/81 Industrial Ethernet Switches
2/81 Overview
2/83 SCALANCE X005 Entry Level
2/86 SCALANCE X-100 unmanaged
2/92 SCALANCE X-200 managed
2/100 SCALANCE X-200IRT managed 2/109 SCALANCE X-400 modular 2/119 Industrial Ethernet ELS 2/124 Industrial Ethernet OSM/ESM
2/131 Industrial Ethernet media converters 2/131 SCALANCE X-100
unmanaged media converter
2/141 Industrial Ethernet OMC TP11 and TP11-LD 2/144 Industrial Security
2/144 Overview
2/145 SCALANCE S
2/149 SOFTNET Security Client 2/151 CPUs for SIMATIC S7-300 2/151 CPU 315-2 PN/DP 2/156 CPU 317-2 PN/DP 2/161 CPU 319-3 PN/DP 2/166 CPU 315F-2 PN/DP 2/171 CPU 317F-2 PN/DP 2/176 SIMATIC WinAC
Introduction
General information
2
■
Overview• Area and cell network according to the international IEEE 802.3 (Ethernet) standard designed for the industrial environment right down to the field level
• Connection of automation components to each other and to PC and workstations as well as components for wireless com-munication for homogeneous and heterogeneous communi-cation
• PROFINET, the open standard for automation, is based on Industrial Ethernet and supports the connection of devices from the field level up to the management level
• Comprehensive open network solutions can be implemented
• High transmission rate of up to 1 gigabit/s
• Industrial Ethernet is the industry standard, well-proven world-wide with international acceptance
• Connection to wireless LAN (WLAN) and industrial wireless LAN (IWLAN) according to IEEE 802.11
• The basis for IT in automation, such as Web function, e-mail function and IWLAN connections
• A safety solution specially designed for industrial automation with the industrial security concept SCALANCE S
Industrial Ethernet in the communications landscape
■
BenefitsEthernet presently has a market share of over 90% with a rising trend, thus placing it in pole position in the LAN landscape worldwide. Ethernet offers important characteristics that can give you significant advantages for your application.
• Investment security through continuous compatible further development
• Fast start-up thanks to the simplest connection method • High availability thanks to redundant network topologies
• High flexibility since existing networks can be extended without any adverse effects
• Basis for system-wide networking (vertical integration) • Basis for PROFINET
• Almost unlimited communications performance because scalable performance is available through switching tech-nology if required
• Networking of different application areas such the office and production areas
• Company-wide communication due to interface options via WAN (Wide Area Network) and use of Internet services • With SCALANCE W, IWLAN (Industrial Wireless LAN) from Industrial Ethernet PROFIBUS PROFIBUS PA KNX PROFINET Industrial Ethernet G_IK10_XX_50187 AS-Interface PROFIBUS PROFIBUS PA KNX AS-Interface
Introduction
General information
2
■
Technical specifications■
Ordering data Order No.1) Language versions and manuals can be found for the various products at:
Additional information can be found in the Internet under:
http://www.siemens.com/automation/csi/net
■
More informationNote:
In many SIMATIC NET components with management function extensive parameterization and diagnostics functions are pro-vided over open protocols and interfaces (e.g. Web Server, network management).
These open interfaces provide access to those components, which can also be used for illicit activities.
When using the above-mentioned functions and these open interfaces and protocols (such as SNMP, HTTP and Telnet), suitable security measures must be implemented that block un-authorized access to the components or the network especially from the WAN/Internet.
For this reason, automation networks can be isolated from the remaining corporate network using appropriate routers (e.g. the well-proven firewall systems).
The SCALANCE S products can be used to implement these routers.
For further information, see Section "Industrial Security". It is important to note the boundary conditions for use of the specified SIMATIC Net products (Order Nos. 6GK..., 6XV1) which you can view inthe Internet:
Additional information can be found in the Internet under:
http://www.siemens.com/simatic-net/ik-info
Standard Ethernet to IEEE 802.3u, IWLAN
to IEEE 802.11 Data transmission rate 10/100/1000 Mbit/s
Number of stations unlimited
Network size
• Switched network unlimited (above 150 km, take into account signal propagation time )
Transmission medium
• Electrical network Industrial Twisted Pair and Twisted Pair cable
• Optical network Fiber-optic cable (glass)
• Wireless network Surrounding space
Topology Line, tree, ring, star
Protocols Protocol-independent
Manual for TP and fiber-optic networks
Paper version
Network architecture, compo-nents, configurations, installation guidelines
• German 6GK1 970-1BA10-0AA0
• English 6GK1 970-1BA10-0AA1
SIMATIC NET manual collection 6GK1 975-1AA00-3AA0 Electronic manuals for
commu-nication systems, protocols, products
Introduction
Data communication
2
■
OverviewCommunication functions/services
Data communication serves to exchange data between pro-grammable controllers or between a propro-grammable controller (controller and field devices) and intelligent partners (PCs, computers, etc.)
The following communication functions are available for this purpose:
PROFINET
Based on Industrial Ethernet, PROFINET enables direct commu-nication of field devices with controllers as well as the solution of isochronous motion control applications.
PROFINET also supports distributed automation with the help of component engineering.
PG/OP communication
Integral communication functions that are used by the SIMATIC programmable controllers to perform data communication with HMI devices (e.g. TD/OP) and SIMATIC PGs (STEP 7, STEP 5). PG/OP communication is supported by MPI, PROFIBUS and Industrial Ethernet.
S7 communication
S7 communication is the integral communications function (SFB) that has been optimized within the SIMATIC S7/C7. It enables PCs and workstations to be connected. The maximum volume of useful data per task is 64 KB. S7 communication offers simple, powerful communication services and provides a network inde-pendent software interface for all networks.
Open Industrial Ethernet and S5-compatible communication
(SEND/RECEIVE)
The open IE S5-compatible communication (SEND/RECEIVE) is used by SIMATIC S7/C7 to communicate with existing systems, especially with SIMATIC S5 but also with PCs over PROFIBUS and Industrial Ethernet. FETCH and WRITE is also available over Industrial Ethernet to ensure that software created for SIMATIC S5 (automation systems, HMI systems) can continue to be used with SIMATIC S7 without any modifications.
Standard Communication
This comprises standardized protocols for data communication . • OPC
(OLE for Process Control) is a standardized, open and manu-facturer-independent interface and allows OPC-capable Windows applications to interface to S7 communication and S5-compatible communication (SEND/ RECEIVE). Internet communication can be implemented over the OPC XML DA interface.
• ISO, TCP/IP and UDP transport protocols
ISO, TCP/IP and UDP are available as the transport protocols. • Information technology (IT) with Email and Web technology
Integrates SIMATIC into the IT through Industrial Ethernet. In the office environment, Email and Web browsers are widely used communication techniques. Ethernet is used as the main communication route, in addition to telephone cables and the Internet. These communication media and paths are also available to SIMATIC as a result of the TCP/IP protocol. SMTP (Simple Mail Transfer Protocol) can also be used for Email, HTTP (Hyper Text Transfer Protocol) for access using Web browsers and FTP communication for program-controlled data exchange with computers that have different operating systems installed.
• FTP;
The file transfer protocol (FTP) permits simple, universal cou-pling, e.g. PLCs can be connected to different computers or embedded systems.
System connections
For many data terminals, communications processors (CPs) are available that already have the communications functions imple-mented as firmware and that therefore relieve the data terminal of communications tasks (e.g. flow control, blocking, etc.).
Introduction
Communications overview
2
■
OverviewCommunications overview for SIMATIC, SINUMERIK and SINAUT 1) ISO protocol only
2) IT functionality included in IT-CP 3) If CPU is the time-of-day master 4) without client function
*) PG/OP communication
Hardware Transportprotocol S7 communication PROFINET S5 comp.communic. Time of day
Put/Get Client Put/Get Server H communication Sender (Master) Receiver Forward with NTP
ISO TCP UDP Fetch/W
rite IO controller CBA SINAUT ST7 CP 343-1 Lean CP 343-1 CP 343-1 Advanced CP 443-1 CP 443-1 Advanced CP 1430 Basic CP 1430 Ext. CP 1430 TCP CP 243-1 CP 243-1 IT TIM 3 V-IE TIM 3 V-IE Advanced SIMA TIC S7-300/C7 SIMA TIC S7-400 SIMA TIC S5 PG/ OP* IT TF 2) FTP SIMA TIC S7-200 G_IK10_XX_10057
BSEND BRECV USEND URECV
1) SEND/RECEIVE 4) 4) 3) 3) 4) CP 343-1 CP 343-1 Advanced SINUMERIK 840D powerline 4) 4) suitable
Introduction
Communications overview
2
■
Overview (continued)Communications overview for PG/PC
4) S7-1613 S7-REDCONNECT SOFTNET-PG CP 1613 A2 DK-16xx PN IO G_IK10_XX_10058 SEND/RECV
Put/Get Client Put/Get Server BSEND BRECV USEND URECV Fetch/W
rite TCP UDP 4) Win 2003 Server Win XP Professional ISO CP 7515 SOFTNET-S7 Lean SOFTNET-PG SOFTNET-S7 Lean
Win 2000 Prof./ Server LINUX
SOFTNET-S7
OPC PG/OP 2) PROFINET IT IWLAN
6) 6) 6) CP 1616 CP 1604 PN CBA OPC-Server CBA IO controller 4) FTP SOFTNET-S7 SOFTNET PN IO SOFTNET-S7/ LINUX Software
1) Further information for more hardware can be found under www.siemens.com/simatic-net/ik-info 2) PG/OP communication
3) supported by TLI/DLPI drivers
4) The IT-, FTP- and UDP functionality results in association with the hardware/ the CPs and the Windows/Linux software of the PC 5) Software source of the card driver included; for Suse 9.3 6) via driver portability
If you have questions to LINUX- / UNIX projects please contact I&S, e-mail: [email protected]
Time of day Transport protocol Hardware SIMATIC PG/PC with integrated interface 1) Operating system
H communication Sender Receiver Forward
S7 communication S5 comp.communic.
suitable not suitable
suitable under certain premisses
IO device
Ethernet Cards 3)
Introduction
Configuration examples
2
■
OverviewS7 communication with TCP/IP for Industrial Ethernet
S5-compatible communication for Industrial Ethernet S7-300 with CP 343-1 Lean, CP 343-1 or CP 343-1 Advanced S7-400 with CP 443-1 or CP 443-1 Advanced S7-400 with CP 443-1 Advanced PC/PG with CP 1616 or CP 1613 A2 PC with CP 1613 A2 with S7-1613 or SOFTNET-S7 Cell phone Field PG with CP 7515 S7-200 with CP 243-1 or CP 243-1 IT G_IK10_XX_10009 Industrial Ethernet Industrial Ethernet G_IK10_XX_10010 S7-300 with CP 343-1 Lean, CP 343-1 or CP 343-1 Advanced S7-400 with CP 443-1 or CP 443-1 Advanced S5-115U to 155U with CP 1430 PC/PG CP 1613 A2 CP 7515 SOFTNET-S7 or S7-1613