POWER SYSTEM
POWER SYSTEM
PROTECTION
PROTECTION
Fundamentals of
Fundamentals of
Protection Practice
Protection Practice
Why power system need the
Why power system need the
protection system?
protection system?
Severe disruption to normal routine of modern
Severe disruption to normal routine of modern
society is likely if power outages are frequent or
society is likely if power outages are frequent or
prolonged.
prolonged.
Many items of equipment are very expensive,
Many items of equipment are very expensive,
and the complete power system represent a very
and the complete power system represent a very
large capital investment.
large capital investment.
Fault may represent a risk to life and/or property.
Fault may represent a risk to life and/or property.
Why power system need the
Why power system need the
protection system?
protection system?
5 Other 3 Control equipment 10 Instrument transformer 12 Transformer 15 Busbar 10 Underground Cable 45 Overhead line % of faults % of faults Type of equipment Type of equipmentWhy power system need the
Why power system need the
protection system?
protection system?
2 Other 5 Series Fault 10 Three Phase ShortCircuit
5 Two Phase Short Circuit
18 Two Phase to Earth
60 One Phase to Earth
% of fault
% of fault
Type of faults
Type of faults
What can the protection system do?
What can the protection system do?
Increase emphasis on reliability and
Increase emphasis on reliability and
security of supply.
security of supply.
Prevent the diverse items of equipment
Prevent the diverse items of equipment
from the severe damage by detect and
from the severe damage by detect and
disconnect elements of the power system.
More fundamental
More fundamental
However, is the power system should operate
However, is the power system should operate
in a safe manner at all times. No matter how well
in a safe manner at all times. No matter how well
designed, faults will always occur on a power
designed, faults will always occur on a power
system.
system.
The provision of adequate protection is
The provision of adequate protection is
therefore on integral part of power system
therefore on integral part of power system
design.
design.
As requirements of reliability and economic are
As requirements of reliability and economic are
largely opposed, power system design is
largely opposed, power system design is
inevitable a compromise
inevitable a compromise
Protection System
Protection System
Protection system is a complete arrangement ofProtection system is a complete arrangement of
protection equipment and other devices required to
protection equipment and other devices required to
achieve a specified function based on a protection
achieve a specified function based on a protection
principal.
principal.
Protection equipment is a collection of protection device
Protection equipment is a collection of protection device
( relay, fuse, etc.) excluded are device such as CT
( relay, fuse, etc.) excluded are device such as CT’’s, s, CB
CB’’s, contactor, etc.s, contactor, etc.
Protection scheme is a collection of protection
Protection scheme is a collection of protection
equipment providing a defined function and including all
equipment providing a defined function and including all
equipment required to make the scheme work (i.e.
equipment required to make the scheme work (i.e.
relays, CT
Protective Relay
Protective Relay
Relay maybe classified according to the
Relay maybe classified according to the
technology used. technology used. electromechanical electromechanical static static digital digital numerical numerical
The different type have somewhat different
The different type have somewhat different
capabilities due to limitations of technology
capabilities due to limitations of technology
used.
used.
Type of protective relay
Type of protective relay
a relay that responds to single quantity
a relay that responds to single quantity
a relay that responds to several quantities
a relay that responds to several quantities
a single relay containing several elements, each responding
a single relay containing several elements, each responding
independently to a different quantity
independently to a different quantity
I > I >
ANSI / IEC Relay Symbols
ANSI / IEC Relay Symbols
59N 59N Neutral point Neutral point displacement relay displacement relay 32 32 Directional Directional overpower relay overpower relay 59 59 Overvoltage Overvoltagerelayrelay
27 27 Undervoltage Undervoltage relay relay 55 55
Power factor relay Power factor relay
26 26 Overtemperature Overtemperature relay relay 51V 51V Voltage Voltage restrained/controlled restrained/controlled overcurrent overcurrentrelayrelay
21 21 Distance relay Distance relay 51N 51N
Definite time earth Definite time earth
fault
fault overcurrentovercurrent relay relay
14 14
Underspeed Underspeedrelayrelay
51G 51G
Inverse time earth Inverse time earth
fault
fault overcurrentovercurrent relay relay
12 12
Overspeed Overspeedrelayrelay
IEC 60617 IEC 60617 ANSI ANSI Description Description IEC60617 IEC60617 ANSI ANSI Description Description ω > ω < Z< θ > U< P> U I> cosϕ > U> Ursd>
O I
ANSI / IEC Relay Symbols
ANSI / IEC Relay Symbols
87 87 Differential relay Differential relay 81O 81O Overfrequency Overfrequencyrelayrelay
51 51
Inverse time Inverse time overcurrent overcurrentrelayrelay
81U 81U Underfrequency Underfrequency relay relay 50 50 Instantaneous Instantaneous overcurrent overcurrentrelay relay
79 79
Autoreclose Autorecloserelayrelay
49 49 Thermal relay Thermal relay 78 78
Phase angle relay Phase angle relay
47 47 Negative sequence Negative sequence voltage relay voltage relay 67N 67N Directional earth Directional earth fault relay fault relay 46 46 Negative sequence Negative sequence relay relay 67 67 Directional Directional overcurrent overcurrentrelayrelay
37 37 Undercurrent relay Undercurrent relay 64 64 Earth Earth--fault relayfault relay
37 37
Underpower Underpowerrelayrelay
IEC 60617 IEC 60617 ANSI ANSI Description Description IEC 60617 IEC 60617 ANSI ANSI Description Description P< I< I2< U2< I>> I > I > I > I > ϕ< f< f> Id>
Zones of Protection
Zones of Protection
To limit the extent of power system that is
To limit the extent of power system that is
disconnected when a fault occur.
disconnected when a fault occur.
G
Zone 1 Zone 2 Zone 3 Zone 4
Zone 4 Zone 6
G
G
Zones of Protection
Zones of Protection
Ideally the zones of protection should overlap. So that no part
Ideally the zones of protection should overlap. So that no part
of the power system is left un protected.
of the power system is left un protected.
The point of connection of the protection with the power
The point of connection of the protection with the power
system usually defines the zone and corresponds to the
system usually defines the zone and corresponds to the
location of CT
location of CT’’s.s.
Zones of Protection
Zones of Protection
Unit protection will result in the boundary being a clearly
Unit protection will result in the boundary being a clearly
define close loop.
define close loop.
Zone maybe un restricted, the extent or reach will depend on
Zone maybe un restricted, the extent or reach will depend on
measurement of the system quantities.
measurement of the system quantities.
G
Principal of Protection
Principal of Protection
ReliabilityReliability
Operate under all required condition, and refrain from Operate under all required condition, and refrain from
operating when so required.
operating when so required.
Incorrect operation can be attributed to one of
Incorrect operation can be attributed to one of
Incorrect design / settingIncorrect design / setting
Design: Due consideration must be given to the nature,
Design: Due consideration must be given to the nature,
frequency and duration of fault, all relevant parameters of
frequency and duration of fault, all relevant parameters of
the power system and type of protection equipment used.
the power system and type of protection equipment used.
Setting: The setting are chosen for protection relays and
Setting: The setting are chosen for protection relays and
system which take in to account the primary system, fault,
system which take in to account the primary system, fault,
load levels etc. The characteristic of power system
load levels etc. The characteristic of power system
changes with time change in load etc. Therefore, setting
changes with time change in load etc. Therefore, setting
value of relay may need to be checked at suitable intervals
value of relay may need to be checked at suitable intervals
to ensure that are still appropriate.
to ensure that are still appropriate.
Principal of Protection
Principal of Protection
Incorrect installation / testingIncorrect installation / testing
Installation: The complexity of interconnections of
Installation: The complexity of interconnections of
many systems and their relationship to the remainder
many systems and their relationship to the remainder
of the installation may make checking difficult.
of the installation may make checking difficult.
Deterioration in serviceDeterioration in service
The time between operations of protection relays
The time between operations of protection relays
maybe years rather than days. During this period
maybe years rather than days. During this period
defects may have developed unnoticed until revealed
defects may have developed unnoticed until revealed
by the failure of the protection to respond to a power
by the failure of the protection to respond to a power
system fault. For this reason, relays should be
system fault. For this reason, relays should be
regularly tested in order to check for correct
regularly tested in order to check for correct
functioning.
Principal of Protection
Principal of Protection
SelectivitySelectivity
To trip only those circuit breakers whose operation is To trip only those circuit breakers whose operation is
required to isolate the fault. The property of selectivity
required to isolate the fault. The property of selectivity
tripping is also called
tripping is also called ‘‘discriminationdiscrimination’’and is achieved and is achieved by two general methods.
by two general methods.
Time Grading
Time Grading
Protection systems in successive zones are arranged to Protection systems in successive zones are arranged to
operate in times that are graded through the sequence of
operate in times that are graded through the sequence of
equipments so that upon the occurrence of a fault although a
equipments so that upon the occurrence of a fault although a
number of protection equipments respond, only those relevant
number of protection equipments respond, only those relevant
to the faulty zone complete the tripping function. The others
to the faulty zone complete the tripping function. The others
make incomplete operations and then reset.
make incomplete operations and then reset.
Principal of Protection
Principal of Protection
Unit Systems
Unit Systems
The protection systems that respond only fault conditions The protection systems that respond only fault conditions
occurring with in a clearly defined zone, it does not
occurring with in a clearly defined zone, it does not
involve time grading, is relatively fast in operation. The
involve time grading, is relatively fast in operation. The
speed of response is substantially independent of fault
speed of response is substantially independent of fault
severity.
Principal of Protection
Principal of Protection
Stability
Stability
The ability of protection system to remain The ability of protection system to remain
unaffected by conditions external to the
unaffected by conditions external to the
protected zone, for example through load
protected zone, for example through load
current and external fault conditions.
current and external fault conditions.
Principal of Protection
Principal of Protection
SpeedSpeed
The function of protection systems is to isolate faults The function of protection systems is to isolate faults
on the power system as rapidly as possible.
on the power system as rapidly as possible.
The main objective is to safeguard continuity of supply by
The main objective is to safeguard continuity of supply by
removing each disturbance before it lead to widespread loss
removing each disturbance before it lead to widespread loss
of synchronism and consequent collapse of power system.
of synchronism and consequent collapse of power system.
As the loading on a power system increase the phase shift
As the loading on a power system increase the phase shift
between voltages and different
between voltages and different busbarsbusbarson the system also on the system also
increases, and therefore so does the probability that
increases, and therefore so does the probability that
synchronism will be lost when system is disturbed by a fault,
synchronism will be lost when system is disturbed by a fault,
protection must thus operate as quickly as possible.
Principal of Protection
Principal of Protection
However speed of operation must beHowever speed of operation must be
weighed against economy.
weighed against economy.
Distribution circuits which do not
Distribution circuits which do not
normally require a fast fault clearance, are
normally require a fast fault clearance, are
usually protected by time
usually protected by time--graded systems. graded systems. Generating plant and EHV systems
Generating plant and EHV systems
require protection gear of highest attainable
require protection gear of highest attainable
speed. speed.
Principal of Protection
Principal of Protection
Sensitivity
Sensitivity
This is a term frequently used when referring This is a term frequently used when referring
to the minimum operating level ( current,
to the minimum operating level ( current,
voltage, power etc.) of relays or complete
voltage, power etc.) of relays or complete
protection scheme.
Primary and Back
Primary and Back
-
-
Up Protection
Up Protection
The reliability of a power system has been
The reliability of a power system has been
discussed earlier, including the use of more than
discussed earlier, including the use of more than
primary ( or main ) protection system operating
primary ( or main ) protection system operating
in parallel.
in parallel.
In the event of failure or non
In the event of failure or non--availability of availability of
the primary protection some other means of
the primary protection some other means of
ensuring that the fault is isolated must be
ensuring that the fault is isolated must be
provided. These secondary systems are referred
provided. These secondary systems are referred
to as
to as ‘‘backback--up protectionup protection’’..
Back
Back
-
-
Up Protection
Up Protection
Local back
Local back
-
-
up protection
up protection
This is achieved by protection which detect an This is achieved by protection which detect an
un
un--cleared primary system fault at its own cleared primary system fault at its own location and which then trip its own circuit
location and which then trip its own circuit
breakers, e.g. time
Back
Back
-
-
Up Protection
Up Protection
R1 R2 A B D E C + + Local back
Local back--up protectionup protection
Back
Back
-
-
Up Protection
Up Protection
R1 R2 A B C D E + + -Local back
Back
Back
-
-
Up Protection
Up Protection
Remote back
Remote back
-
-
up protection
up protection
This is provided by protection that detects an This is provided by protection that detects an
un
un--cleared primary system fault at a remote cleared primary system fault at a remote location and then issue a local trip command
location and then issue a local trip command
e.g. the second or third zones of distance
e.g. the second or third zones of distance
relay.
relay.
Back
Back
-
-
Up Protection
Up Protection
F R1 R2 R3 1 2 3 Current Time R 1 R 2 R 3 fault T1 T2 T3
Back
Back
-
-
Up Protection
Up Protection
The extent and type of back
The extent and type of back--up protection up protection applied will naturally be related to the failure
applied will naturally be related to the failure
risks and relative economic importance of the
risks and relative economic importance of the
system.
system.
For distribution systems where fault clearance times For distribution systems where fault clearance times
are not critical, time delayed remote back
are not critical, time delayed remote back--up up protection maybe adequate.
protection maybe adequate.
For EHV systems, where system stability is at risk For EHV systems, where system stability is at risk
unless a fault is cleared quickly, multiple primary
unless a fault is cleared quickly, multiple primary
protection systems, operating in parallel and possibly
protection systems, operating in parallel and possibly
of different type ( e.g. distance and unit protection )
of different type ( e.g. distance and unit protection )
will be used to ensure fast and reliable tripping.