GENERATOR PROTECTION
GENERATOR PROTECTION
By
By
Subhash Thakur
Subhash Thakur
PE-Elect
PE-Elect
[email protected]
[email protected]
Gen Stator Thermal Protection
Gen Stator Thermal Protection
Field Thermal Protection
Field Thermal Protection
Gen stator fault Protection
Gen stator fault Protection
Gen rotor field Protection
Gen rotor field Protection
Gen abnormal operating conditions
Gen abnormal operating conditions
System backup Protection
System backup Protection
Power transformer Protection
Power transformer Protection
Generator Protection
Generator Protection
Generator Protection
Generator Protection
Stator Thermal protection
Stator Thermal protection
Thermal protection for the generator stator core and windings Thermal protection for the generator stator core and windings
Generator overloadGenerator overload
Winding Temperature Winding Temperature Over currentOver current
Failure of cooling systemsFailure of cooling systems
RTDs ThermocoupleRTDs Thermocouple
Flow and pressure sensorFlow and pressure sensor
Localized hot spots caused by core lamination Localized hot spots caused by core lamination
insulation failures or by localized or rapidly developing insulation failures or by localized or rapidly developing winding failures
winding failures
Generator Protection
Generator Protection
Generator Protection
Generator Protection
Generator Field Thermal protection
Generator Field Thermal protection
Thermal Protection
Thermal Protection
Direct rotor Body temperature measurement Direct rotor Body temperature measurement not possible
not possible
Core Monitor may detect overheatingCore Monitor may detect overheating
Protection for field over excitation
Protection for field over excitation
IDMT/ Definite Time IDMT/ Definite Time Excitation limitersExcitation limiters
Generator Protection
Generator Protection
Generator Protection Requirement
Generator Protection Requirement
Generator faults are considered to be serious since they Generator faults are considered to be serious since they may cause severe and costly damage to insulation,
may cause severe and costly damage to insulation,
windings, and the core may also produce severe
windings, and the core may also produce severe
mechanical torsional shock to shafts and couplings.
mechanical torsional shock to shafts and couplings.
Fault current may continue to flow for many seconds even Fault current may continue to flow for many seconds even after the generator is tripped, because of trapped flux
after the generator is tripped, because of trapped flux
within the machine, thereby increasing the amount of fault
within the machine, thereby increasing the amount of fault
damage.
damage.
As a consequence, for faults in or near the generator that As a consequence, for faults in or near the generator that produce high magnitudes of short-circuit currents, some
produce high magnitudes of short-circuit currents, some
form of high-speed protection is normally used to trip and
form of high-speed protection is normally used to trip and
shut down the machine as quickly as possible in order to
shut down the machine as quickly as possible in order to
minimize damage.
Stator fault Protection
Stator fault Protection
High Speed Differential protection
High Speed Differential protection
– Will detect Phase to Phase Faults, Double phase Will detect Phase to Phase Faults, Double phase faults involving earth
faults involving earth
– Single phase to Earth will not be detected due to Single phase to Earth will not be detected due to limited earth fault current available.
limited earth fault current available.
Two types of high-speed differential relays
Two types of high-speed differential relays
are commonly used for stator phase fault
are commonly used for stator phase fault
detection:
detection:
– High-impedance differentialHigh-impedance differential
– Biased differentialBiased differential
High Impedance Differential Relay
High Impedance Differential Relay
Use two sets of identical dedicated CTs.
Use two sets of identical dedicated CTs.
PS class CT with stringent parameters to be used
PS class CT with stringent parameters to be used
This scheme has higher sensitivity than the
This scheme has higher sensitivity than the
percentage differential relay.
percentage differential relay.
Through fault stability achieved by using
Through fault stability achieved by using
stabilising resistors in the relay circuit
stabilising resistors in the relay circuit
.
.
High Impedance Differential Relay
High Impedance Differential Relay
Stabilizing resistor calculation :
Stabilizing resistor calculation :
Vs = If (Rct+2Rl)
Vs = If (Rct+2Rl)
If - Maximum through fault current in the
If - Maximum through fault current in the
system
system
(converted to sec side)
(converted to sec side)
Rct- Secondary resistance of the CT
Rct- Secondary resistance of the CT
Rl – lead resistance of the sec connection
Rl – lead resistance of the sec connection
(typ 8.73 ohms per km for 2.5 sq mm cu
(typ 8.73 ohms per km for 2.5 sq mm cu
cable)
cable)
Rs = Vs/Is – (VA/Is*Is)
Rs = Vs/Is – (VA/Is*Is)
Typical setting 5- 10% of rated current.
Typical setting 5- 10% of rated current.
Biased Type Diff Relay
Biased Type Diff Relay
Less stringent CT parameters. CTs can be shared with other Less stringent CT parameters. CTs can be shared with other
protections. protections.
Through fault stability achieved through biasing.Through fault stability achieved through biasing.
CT mismatch (typ of the order of 1:5 ) can be accommodated.CT mismatch (typ of the order of 1:5 ) can be accommodated. More suitable for numerical integrated protection systems as the More suitable for numerical integrated protection systems as the
CTs can be shared for many functions. CTs can be shared for many functions.
Modern numerical relays have flexible settings for Modern numerical relays have flexible settings for Id, b (point of slope change) and the slopes. Id, b (point of slope change) and the slopes.
Biased Differential protection
Biased Differential protection
Current based systemCurrent based system
– For generators with split neutrals with all six terminals For generators with split neutrals with all six terminals brought out on neutral side.
brought out on neutral side.
– Delayed low-set o/c relay which senses the current in Delayed low-set o/c relay which senses the current in the connection between the neutrals of the stator
the connection between the neutrals of the stator
windings
windings
Voltage based system
Voltage based system
– Relay compares the neutral NGT sec voltage and Relay compares the neutral NGT sec voltage and Genertaor terminal open delta voltage.
Genertaor terminal open delta voltage.
– Balance during external E/F or normal conditionBalance during external E/F or normal condition
– During inter turn fault open delta voltage will be During inter turn fault open delta voltage will be
developed and NGT sec voltage will be zero, resulting in
developed and NGT sec voltage will be zero, resulting in
a differential voltage which makes the relay operate.
a differential voltage which makes the relay operate.
Typical setting
Typical setting
Definite time type relays: minimum setting with 1 sec delay.
Definite time type relays: minimum setting with 1 sec delay.
INTERTURN PROTECTION
Inter turn protection
Inter turn protection
Split Phase Protection
V o l t g a Voltage Based
Generator Grounding Practices
Generator Grounding Practices
It is common practice to ground all types of
It is common practice to ground all types of
generators through some form of external
generators through some form of external
impedance
impedance
limit the mechanical stresses and fault damage limit the mechanical stresses and fault damage in the machine,
in the machine,
to limit transient voltages during faults, and to limit transient voltages during faults, and to provide a means for detecting ground faults to provide a means for detecting ground faults
within the machine.
within the machine.
Typical Grounding practices
Typical Grounding practices
UngroundedUngrounded
Solid GroundingSolid Grounding
High-impedance groundingHigh-impedance grounding Low-resistance groundingLow-resistance grounding Reactance groundingReactance grounding
Generator Grounding Practices
Generator Grounding Practices
Ungrounded
Ungrounded
–
Phase to ground fault current limited
Phase to ground fault current limited
–
Generators are not often operated ungrounded
Generators are not often operated ungrounded
as it may produce high transient over-voltages
as it may produce high transient over-voltages
during faults and makes the fault location
during faults and makes the fault location
difficult to determine.
difficult to determine.
Solid Grounding
Solid Grounding
–
Solid grounding of a generator neutral is not
Solid grounding of a generator neutral is not
generally used since this practice may result in
generally used since this practice may result in
high mechanical stresses and excessive fault
high mechanical stresses and excessive fault
damage in the machine.
Generator Grounding Practices
Generator Grounding Practices
High Impedance GroundingHigh Impedance Grounding – High resistance groundingHigh resistance grounding
The high-resistance grounding method utilizes a resistor The high-resistance grounding method utilizes a resistor
connected across the secondary of the distribution transformer connected across the secondary of the distribution transformer to limit the maximum ground fault current.
to limit the maximum ground fault current.
For a single-phase-to-ground fault at the machine terminals, the For a single-phase-to-ground fault at the machine terminals, the primary fault current will be limited to a value in the range of primary fault current will be limited to a value in the range of about 3 A to 25 A.
about 3 A to 25 A.
– Ground fault neutralizer groundingGround fault neutralizer grounding
The ground fault neutralizer grounding method utilizes a The ground fault neutralizer grounding method utilizes a
secondary tunable reactor to limit the maximum ground fault secondary tunable reactor to limit the maximum ground fault current.
current.
Low –resistance groundingLow –resistance grounding
In this method, a resistor is connected directly between the In this method, a resistor is connected directly between the
generator neutral and ground. generator neutral and ground.
For a single-phase-to-ground fault at its terminals the primary For a single-phase-to-ground fault at its terminals the primary
fault current will be limited to a value in the range of about 200 fault current will be limited to a value in the range of about 200 A up to 150% of rated full-load current.
A up to 150% of rated full-load current.
Stator Earth Fault Protection
Stator Earth Fault Protection
E/F current is typically limited to
E/F current is typically limited to
5-10A
to
5-10A
to
minimizes
minimizes
the
the
damage to laminations.
damage to laminations.
First earth fault is less critical
First earth fault is less critical
but needs clearance as
but needs clearance as
IIt may develop into a ph to ph fault .t may develop into a ph to ph fault . Second fault will result in very high Second fault will result in very high
current. current.
Two types of coverage:
Two types of coverage:
100 % winding100 % winding 95 % winding95 % winding
Any fault involving earth results shift of
Any fault involving earth results shift of
Neutral voltage.
Neutral voltage.
This shift can be detected by measuring the
This shift can be detected by measuring the
Voltage across Grounding Resistor Or from the
Voltage across Grounding Resistor Or from the
generator terminal Open Delta voltage.
generator terminal Open Delta voltage.
Typical coverage
Typical coverage
95% Of Stator Winding.
95% Of Stator Winding.
Typical Setting:
Typical Setting:
–
5% with 1 Sec TD
5% with 1 Sec TD
95 % Stator Earth Fault
100 % Stator E/F Protection
100 % Stator E/F Protection
•
Third Harmonic Principle
Third Harmonic Principle
•
Relay responds to the reduction of the 3
Relay responds to the reduction of the 3
rdrdHarmonic Component
Harmonic Component
•
For a Stator Phase-to-ground fault at or
For a Stator Phase-to-ground fault at or
near the Generator Neutral, there will be
near the Generator Neutral, there will be
an increase in third Harmonic Voltage at
an increase in third Harmonic Voltage at
The Generator Terminals, which Will Cause
The Generator Terminals, which Will Cause
Relay Operation.
Relay Operation.
100% SEF based on third harmonics
100% SEF based on third harmonics
measurements
100% SEF based on third harmonics
100% SEF based on third harmonics
measurements
measurements
Disadvantages
Disadvantages
Due to design variations, certain generating
Due to design variations, certain generating
units may not produce sufficient third
units may not produce sufficient third
harmonic voltages.
harmonic voltages.
This method does not protect the machine
This method does not protect the machine
during stand still conditions.
100% stator earth fault protection
100% stator earth fault protection
(Low freq. injection principle)
(Low freq. injection principle)
20 Hz RE max. 200 V I 20 Hz RE max. 200 V I
Detects the ground faults
Detects the ground faults
by injecting a low frequency
by injecting a low frequency
signal (say 20 hz) at the
signal (say 20 hz) at the
neutral earthing transformer
neutral earthing transformer
and monitor the earth
and monitor the earth
current in the winding.
current in the winding.
SEF USING INJECTION PRINCIPLE
SEF USING INJECTION PRINCIPLE
TYPICAL CONNECTION
TYPICAL CONNECTION
Typical settings for 500 MW unit
Typical settings for 500 MW unit
Trip : 1 KOhm / 1 sec Trip : 1 KOhm / 1 sec Alarm : 10 Kohm /10 sec Alarm : 10 Kohm /10 sec
DC or AC Blocking RL Bandpass (8Ω at 20 Hz) 20-Hz-Generator (appr. 25 V) U I Relay a b a b 400A 5A Low ohmic Earthing transformer Neutral transformer
Rotor Earth Fault Protection
Rotor Earth Fault Protection
Effects
Effects
First rotor E/F does not cause immediate damageFirst rotor E/F does not cause immediate damage Second E/F results in short circuit of rotor winding.Second E/F results in short circuit of rotor winding. Causes magnetic unbalance/mechanical forcesCauses magnetic unbalance/mechanical forces
Measure
Low frequency injection method
– Modern rotor earth fault protection relay operates on
the principle of low frequency injection into the field winding via capacitors.
– Corresponding current or resistance during E/F is sensed
Typical setting for a 500 mw Generator
Alarm 25 k ohm time = 10 sec Trip 5 k ohm time = 1 sec
Rotor E/F Using Low frequency injection method
Rotor E/F Using Low frequency injection method
Negative sequence protection
Negative sequence protection
Causes of negative squence currentCauses of negative squence current
– one pole open in lineone pole open in line – Unbalanced loadsUnbalanced loads
– Unbalanced system faultsUnbalanced system faults
Induces double frequency rotor current in the rotor surface Induces double frequency rotor current in the rotor surface
thereby leading to high and dangerous temperatures in a short thereby leading to high and dangerous temperatures in a short
span of time. span of time.
Negative sequence protection relays shall be set to the NPS Negative sequence protection relays shall be set to the NPS
withstand capability of the machine which is given by withstand capability of the machine which is given by
k =
k = ii2222x t x t
Typical for 500 mw Typical for 500 mw
Permissible neg seq current = 5 – 8 % of stator currentPermissible neg seq current = 5 – 8 % of stator current permissive i
permissive i2222x t = 5 – 10x t = 5 – 10
settings adopted for ntpc settings adopted for ntpc
ii2 =2 = = 7.5 % = 7.5 % i
Negative sequence protection
Loss of field protection
Loss of field protection
Loss of field protection
Acts as an induction generatorActs as an induction generator
Induced eddy currents in the field winding, rotor body, Induced eddy currents in the field winding, rotor body,
wedges and retaining rings
wedges and retaining rings
MW flow in to the system/ MVAR flows in to the machine.MW flow in to the system/ MVAR flows in to the machine. The apparent imp moves in to the forth quadrant of x-y The apparent imp moves in to the forth quadrant of x-y
plane
plane
Method of detection:Method of detection:
Impedance measurement with Under VoltageImpedance measurement with Under Voltage
Some relays are set in the admittance plane matching Some relays are set in the admittance plane matching
with the capability curve of the machine.
Trip characteristics of loss of field protection
Trip characteristics of loss of field
Trip characteristics of loss of field
protection
protection
Trip characteristics of loss of field protection
Generator Capability Curve
Generator Capability Curve
Out of step protection
Out of step protection
Machine runs out of synchronism with the networkMachine runs out of synchronism with the network Cyclic variation of rotor angle Cyclic variation of rotor angle
Current increases.Current increases.
Results in the winding stressResults in the winding stress
It may also damage the auxiliaries of the affected unit It may also damage the auxiliaries of the affected unit Method of detection
Method of detection
– Variations in impedance measured at Gen TerminalVariations in impedance measured at Gen Terminal
– Distinguish between the recoverable swing and the Distinguish between the recoverable swing and the irrecoverable swing
irrecoverable swing
– blinders and a supervisory mho element, blinders and a supervisory mho element,
– Trips the machine when imp is inside the mho and Trips the machine when imp is inside the mho and cross the blinders with the specified time.
cross the blinders with the specified time.
– Minimum impedance (multiple zone) + counting no Minimum impedance (multiple zone) + counting no of swings
Out of step protection settings
Typical Over Fluxing Withstand
Typical Over Fluxing Withstand
Capability
Accidental back energisation
Accidental back energisation
CauseCause
– Flash over of the generator breakerFlash over of the generator breaker
– Incorrect closing of the generator breakerIncorrect closing of the generator breaker EffectsEffects
– Cause operation as an induction motorCause operation as an induction motor
– Damage machine and turbineDamage machine and turbine
– The rapid heating iron paths near the rotor surface The rapid heating iron paths near the rotor surface due to stator induced current.
due to stator induced current.
Over current + CB auxiliary contactsOver current + CB auxiliary contacts
– checks for the current when the gen breaker checks for the current when the gen breaker contacts are open
contacts are open
– set below the rated current(90%)set below the rated current(90%)
– o/c and u/v measurementso/c and u/v measurements
Accidental Back Energisation
Low forward and reverse power
Low forward and reverse power
inter lock
inter lock
To allow entrapped steam in the turbine to
To allow entrapped steam in the turbine to
be utilized to avoid damage of the turbine
be utilized to avoid damage of the turbine
blade.
blade.
To protect the machine from motoring action
To protect the machine from motoring action
Trip under class B after a short time delay in
Trip under class B after a short time delay in
case the turbine is already tripped ( typ set at
case the turbine is already tripped ( typ set at
2 sec)
2 sec)
Trip under class A, after a
Trip under class A, after a
long time delay
long time delay
if
if
turbine is not tripped (typically set at 10 -30
turbine is not tripped (typically set at 10 -30
sec)
sec)
O/V & U/F protection
O/V & U/F protection
Typical settings of a 3 stage o/v relay is as follows
Typical settings of a 3 stage o/v relay is as follows – Alarm 110 % 2 sec Alarm 110 % 2 sec
– Trip 120 % 1 secTrip 120 % 1 sec
– 140 % instantaneous140 % instantaneous
Abnormal Frequency protection
Abnormal Frequency protection
Typical setting:
Typical setting:
U/FU/F O/FO/F Alarm - 48.5hz 5 sec 51 hz 1 sec
Alarm - 48.5hz 5 sec 51 hz 1 sec
Trip - 47.4 hz 2 sec
For uncleared system faultFor uncleared system fault
The backup protection is time delayed to The backup protection is time delayed to coordinate with the zone 3 setting of lines
coordinate with the zone 3 setting of lines
Detected byDetected by
– over current over current
– impedanceimpedance
– Impedance type preferred as the line is Impedance type preferred as the line is provided with distance relays
provided with distance relays
Setting should be made to cover the GT imp and Setting should be made to cover the GT imp and the longest line impedance.
the longest line impedance.
Setting should take care of the infeed from other Setting should take care of the infeed from other generators connected to the same bus also.
generators connected to the same bus also.
Time setting 1.5 –2 secTime setting 1.5 –2 sec
Over view of type of fault Vs protection
Over view of type of fault Vs protection
FAULT/
FAULT/
ABNML
ABNML
EFFECT
EFFECT PROTECTIONPROTECTION
Thermal over Thermal over loading
loading Over heating of stator wdg / Over heating of stator wdg / insulation failure
insulation failure Thermo couples/ Thermo couples/
Over current relays Over current relays External fault
External fault Unbalanced loading stressUnbalanced loading stress Over load/negative phase Over load/negative phase sequence relay, Backup sequence relay, Backup Impedance/ Earth Fault Impedance/ Earth Fault Stator faults
Stator faults
Winding burn out Winding burn out
Shorting of of core lamination Shorting of of core lamination
Differential protection Differential protection
100% E/F prot/95% E/F 100% E/F prot/95% E/F
Inter turn protection Inter turn protection Rotor fault
Rotor fault Damage to shaft/bearingDamage to shaft/bearing Two stage rotor E/F protectionTwo stage rotor E/F protection Motoring
Motoring Damage to turbine bladesDamage to turbine blades LFPR/Rev power Inter lockLFPR/Rev power Inter lock O/V,O/F,U.F
O/V,O/F,U.F Insulation failure,Heating of Insulation failure,Heating of core failure of blades
core failure of blades O/V relay Volt/Hz relay O/V relay Volt/Hz relay
U/F relay U/F relay Loss of field
Loss of field Induction gen operationInduction gen operation Absorb MVAR from
Absorb MVAR from
system/damage to rotor wdg system/damage to rotor wdg
Loss of field Loss of field
COMMONLY USED GEN/GEN TRFR RELAYS
COMMONLY USED GEN/GEN TRFR RELAYS
PROTECTION
PROTECTIONALSTOM/AREVAALSTOM/AREVA ABBABB SIEMENSSIEMENS REMARKREMARK HIGH IMP HIGH IMP DIFF DIFF CAG 34 CAG 34 MICOM P343 MICOM P343 RADHA RADHA REG 216
REG 216 7UM SERIES7UM SERIES
In case of duplicated diff,
In case of duplicated diff,
one low imp & one high
one low imp & one high
imp preferred
imp preferred
For trfr biased relay
For trfr biased relay
preferred preferred BIASED DIFF BIASED DIFFMBCHMBCH MICOM MICOM P 633 P 633 RADSB RADSB RET 316 RET 316 7 UT 7 UT POWER POWER RELAYS RELAYS RXPE
RXPE PPXPPX 7 UM SERIES7 UM SERIES Directional power relays Directional power relays LOSS OF
LOSS OF
FIELD
FIELD YCGFYCGF RAGPC(DIR O/C+U/V)RAGPC(DIR O/C+U/V) 7UM SERIES7UM SERIES ImpedanceadmittanceImpedanceadmittance / /
100% E/F 100% E/F PVMMPVMM MICOM P343 MICOM P343 PG871 PG871 GIX GIX REG 216 REG 216 7UE22 7UE22 7UM SERIES 7UM SERIES
Low frequency injection
Low frequency injection
type
type preferred over 3 rd preferred over 3 rd harmonic principle
harmonic principle
95% E/F
95% E/F VDGVDG 7UM SERIES7UM SERIES Open delta of gen sec VTOpen delta of gen sec VT BACK UP
BACK UP
IMP
PROTECTIO
PROTECTIO
N
N ALSTOM
ALSTOM ABBABB SIEMENSSIEMENS RemarksRemarks OVER OVER FLUXING FLUXING GTTM GTTM RATUBRATUB RALK RALK 7RW 7RW IDMTIDMT POLE POLE SLIPPING SLIPPING ZTO+YTGM1 ZTO+YTGM1 5 5 RXZF+RXPE
RXZF+RXPE 7UM 5167UM 516 IMPEDANCEIMPEDANCE IMP+ DIR O/C
IMP+ DIR O/C
IMP+NO OF POWER IMP+NO OF POWER SWINGS SWINGS ACC. BACK ACC. BACK ENERG ENERG CTIG
CTIG RAGUARAGUA 7UM SERIES7UM SERIES O/C +CB AUX CONTACTO/C +CB AUX CONTACT
CURRENT CURRENT ELEMENT+U/V ELEMENT+U/V INTER INTER TURN TURN VDG VDG MICOM MICOM REG
REG 7UM SERIES7UM SERIES comp of open delta 0n comp of open delta 0n gen term+ngt sec
gen term+ngt sec
voltage voltage NEG PH NEG PH SEQ SEQ CTN
CTN RARIBRARIB 7UM SERIES7UM SERIES MEASUREMENT OF I2MEASUREMENT OF I2 REF
REF CAG/FAGCAG/FAG RADHDRADHD 7UM SERIES7UM SERIES HIGH IMP PREFFEREDHIGH IMP PREFFERED ROTOR E/F ROTOR E/F VDGVDG MICOM MICOM SERIES SERIES REG SERIES
REG SERIES 7UR 227UR 22
7 UM SERIES
Type of fault
Type of fault ProtectionProtection ChannelChannel RecommendatioRecommendatio n n Short circuit Short circuit 87 G187 G1 87G2 87G2 87 GT 87 GT 1 1 2 2 1 OR 2 1 OR 2
Stator Earth Fault
Stator Earth Fault 64G164G1 64G2 64G2 1 1 2 2 Inter turn Inter turn 95G95G 1 OR 21 OR 2 unbalance unbalance 46G46G 1 OR 21 OR 2 Over load
Over load 51G51G AlarmAlarm Loss of excitation Loss of excitation 40G140G1 40G2 40G2 1 1 2 2 Out of step Out of step 98G98G 1 OR 21 OR 2 >100 MW>100 MW Motoring Motoring 32 G1/2 / 37 G1/G232 G1/2 / 37 G1/G2 1 / 21 / 2 O/V,O/F O/V,O/F U/F U/F 59/99 59/99 81G1/81G1 81G1/81G1 1 /2 1 /2 1/2 1/2 System back up
System back up 21G21G 1 & 21 & 2 Accidental energisation
Accidental energisation 50GDM50GDM 1 &21 &2 Rotor E/F
Generator Transformer Protection
Generator Transformer Protection
DifferentialDifferential
– biased differential biased differential
20 % bias setting (to cover tap range and
20 % bias setting (to cover tap range and
ct mismatch if any)
ct mismatch if any)
time: instantaneous
time: instantaneous
Back up earth fault
Back up earth fault
Definite time or IDMT relay
Definite time or IDMT relay
30 % with 2 sec time delay
30 % with 2 sec time delay
To be coordinated with distance prot zone 3
To be coordinated with distance prot zone 3
UT PROTECTION
UT PROTECTION
Differential
Differential
Biased differential used
Biased differential used
biased setting 20%
biased setting 20%
Back up over current
Back up over current
2-3 times the full load current
2-3 times the full load current
Delay of 1 sec to take care of any large motor
Delay of 1 sec to take care of any large motor
starting case
starting case
Restricted E/F
Restricted E/F
High impedance
High impedance
Set to 5%-10% in high impedance earthing
Set to 5%-10% in high impedance earthing
Backup E/F
Backup E/F
Other Protections
Other Protections
Overall Differential Protection (87GT)
Overall Differential Protection (87GT)
- Covers generator, GT & UT
- Covers generator, GT & UT
GT overhang differential Protection
GT overhang differential Protection
(87HV)
(87HV)
- Protects GT HV wdg & overhang
- Protects GT HV wdg & overhang
portion between GT bushing
portion between GT bushing
and switchyard.
Typical Generator
protection
scheme
GCB SCHEME
NON GCB SCHEME
TRIP LOGIC OF GENERATOR PROTECTION
TRIP LOGIC OF GENERATOR PROTECTION
Two independent channels with independent CT/VT inputs/ DC Two independent channels with independent CT/VT inputs/ DC
supply/ Trip relays supply/ Trip relays
Class “A” Trip (Urgent Trips)Class “A” Trip (Urgent Trips)
– All electrical tripAll electrical trip
– Issues instantaneous Trip toIssues instantaneous Trip to
Turbine , Excitation, Generator EHV CBs,UT LV CBs Turbine , Excitation, Generator EHV CBs,UT LV CBs – In GCB Scheme Class A1 and A2In GCB Scheme Class A1 and A2
– Class A1 Issues instantaneous Trip toClass A1 Issues instantaneous Trip to
Turbine , Excitation, Generator EHV CBs,GCB, UT LV CBs Turbine , Excitation, Generator EHV CBs,GCB, UT LV CBs – Class A2 Issues instantaneous Trip toClass A2 Issues instantaneous Trip to
Turbine , Excitation, GCB Turbine , Excitation, GCB
Class-B Trip (Non-urgent Trips)Class-B Trip (Non-urgent Trips)
– Turbine Trips, GT and UT OTI/WTI tripsTurbine Trips, GT and UT OTI/WTI trips
– Issues delayed Trip to (After Low Forward Power timer)Issues delayed Trip to (After Low Forward Power timer)
In Non-GCB scheme-Excitation, Generator CBs,UT LV CBsIn Non-GCB scheme-Excitation, Generator CBs,UT LV CBs In GCB scheme, only GCB and field are tripped, UT remains In GCB scheme, only GCB and field are tripped, UT remains
charged through GT. charged through GT.
Class C TripClass C Trip
Trips HV CB only. Trips HV CB only.
CLASS
OF TRIP BREAKERS TO BE TRIPPED UNDER VARIOUS CLASSES OF TRIPPING
GCB SCHEME
(additional LV CB between Gen and GT)
NON GCB SCHEME
Class A A1: GCB,HVCB,UT LV CB,
FIELD, TURBINE
(All the system tripped) A2 : GCB, FIELD, TURBINE
(Generator circuit tripped & Auxiliaries charged from the grid through GT&UT)
HVCB,UT LV CB, FIELD, TURBINE
(All the system tripped)
Class B GCB,FIELD BREAKER
Initiated by Turbine trip & Low Forward /reverse power, to release the trapped steam.
Generator circuit breaker
tripped & Auxiliaries charged from the grid through GT&UT)
HVCB,UT LV CB, FIELD BREAKER.
Class C HVCB
(Generator under House load ) HVCB (Generator under House
CLASS OF TRIP SL NO PROTECTION FUNCTION NON GCB GCB Preferred grouping of protection 1. Generator Differential Protection, (87 G) (DUPLICATED IN CASE OF GCB SCHEME) A A2 2. Overall Di fferential Protection (87GT). A A1 87 G and 87 GT shall be on two different channels of protection. 3. Generator Transformer Differential protection (87 T) A A1 87 T shall be in a different channel than 87 GT
4. Over hang differential
protection(87 HV) A A1 87 HV shall be in a different channel than 87T
5. Stator Earth Fault Protection covering 100% of winding based on low frequency injection principle.(64G1).
A A2
6. Stator Standby Earth Fault Protection covering 95% of winding (64 G2) A A2 64 G1 and 64 G2 shall be on two different channels of protection.
7. Inter -turn Fault
Protection (95G1), A A2 8. Duplicated Loss of field
protection (40G1/2 ). A A2 40G1 shall be on two and 40G2 different channels of protection.
9. Back up Impedance
Protection, 3 pole (21G) A A1 10. Backup Earth Fault
Protection on Generator Transformer HV neutral (51NGT) A A1 21 G and 51 NGT be in different channels 11. Negative Sequence Current Protection, (46G) A A2
RELAY GROUPING
1. Duplicated Low-Forward Power / reverse power Interlock for steam turbine generator (37 /32G1 & 37/32 G2), each having two stages, a) short time delayed
interlocked with turbine trip
b) long time delayed independent of turbine trip. B A B A2 37/32 G1 and 37/32 G2 shall be in two different channels of protection
2. Two Stage Rotor Earth Fault Protection based on injection principle.(64F).
A A2 3. Definite Time Delayed
Over-Voltage Protection (59G) A A2 4. Generator Under Frequency Protection (81G) with df/dt elements. C C
5. i) Over Fluxing Protection (99 T) for Generator Transformer
ii) Over fluxing protection for Generator (99 G)( only incase of GCB scheme) A --- A1 A2
Over Flux function (99) shall be in a different channel than O/V and U/F functions
6. Accidental Back Energisation protection (50GDM) on two principles a) based on U/V and O/C
b) based on CB status and O/C
A A1 50 GDM based on the two principle shall be on two different channels.
7. Instantaneous and time delayed Over Current protection to be used on HV side of excitation transformer.
A A2
8. Generator Pole slipping
1. Unit Transformer Differential Protection, 3 pole (87UT)
A A1
2. Unit Transformer LV back-up earth fault protection . ( 51NUT).
A A1
3. Unit Transformer LV REF
(64 UT LV) A A1 4. Unit transformer back-up
over current protection (51UT). A A1 87 UT & 51 NUT can be in one channel and 64 UT LV & 51UT shall be in another channel.
5. Gen Transformer OTI/WTI
trip Turbine Trip Turbine Trip After trip turbine other breakers are tripped through class B 6. Gen Transformer Buchholtz, PRD /other mechanical Protections A A1 7. Unit Transformer
OTI/WTI trip CB Trip UT LV & signal for change over of unit board. UT LV CB Trip & signal for change over of unit board. 8. Unit Transformer Buchholtz, PRD /other mechanical Protections A A1 9. 64 GT (For GT LV wdg & UT HV wdg) A1 10. EHV CB/GCB LBB A A1 11. EHV BB PROTN A A1
SL.NO INITIATION ACTION 1 GT FIRE
PROTECTION
TRIP CLASS A AND DISCONNECT POWER SUPPLY TO GT MB
2 UT FIRE
PROTECTION TRIP CLASS A AND DISCONNECT POWER SUPPLY TO UT MB 3 GT TAP CHANGER
OPERATED & HVCB CLOSED
TRIP CLASS A
4 HV CB /FCB CLOSED START GT COOLER 5 GT COOLER SUPPLY
TOTAL FAILURE TRIP CLASS A AFTER TIME DELAY 6 AVR SERIOUS
TROUBLE TRIP CLASS A
Numerical integrated generator protection
Numerical integrated generator protection
systems
systems
Many functions in the same relayMany functions in the same relay Takes multiple CT/VT inputs.Takes multiple CT/VT inputs.
Minimum of 2 nos to be used.Minimum of 2 nos to be used.
All the prot functions are to be divided in to 2 groups .All the prot functions are to be divided in to 2 groups . Built in DR(fast scan)/SOE functionsBuilt in DR(fast scan)/SOE functions
Self supervisionSelf supervision CommunicableCommunicable
Has programmable logic gates which simplifies the auxiliary Has programmable logic gates which simplifies the auxiliary
circuits. circuits.
COMMON RELAYS ARE COMMON RELAYS ARE REG series OF ABB
REG series OF ABB 7UM SERIES OF SIEMENS7UM SERIES OF SIEMENS MICOM SERIES OF AREVA.