BNI EIP-502-105-Z015

IP67 Modules

4 IO Link/In-/Outputs,12 In-/Outputs

User’s Guide

(2)

Content

1 Notes 3

1.1. About this guide 3

1.2. Structure of the guide 3

1.3. Typographical Conventions 3 Enumerations 3 Actions 3 Syntax 3 Cross-references 3 1.4. Symbols 3 1.5. Abbreviations 3 2 Safety 4 2.1. Intended use 4

2.2. General safety notes 4

2.3. Meaning of the warnings 4

3 Getting Started 5 3.1. Modul overview 5 3.2. Mechanical connection 6 3.3. Electrical connection 6 Power Supply 6 Grounding 6 Ethernet IP Interface 6 I/O-Port 7 IO Link-Port 7 4 Technical data 8 4.1. Dimensions 8 4.2. Mechanical data 8 4.3. Operating conditions 8 4.4. Electrical data 8 4.5. Ethernet 9 4.6. Function indicators 9 Modul status 9 Port 9 5 Integration 10 5.1. Data Configuration 10 5.2. Config Data 10 Module Configuration 10

IO Link Port Configuration 10

6 Process Data 11

6.1. Process Data Inputs 11

Standard Input Data 11

IO Link Input Data 11

6.2. Process Data Outputs 12

Standard Output Data 12

IO Link Output Data 12

7 Display 13

7.1. General 13

7.2. Adress Defaults 13

(3)

www.balluff.com 2 7.7. Main Menue 14 7.8. IP Setup 15 7.9. IP Config 15 7.10. Module information 16 7.11. General Informations 16 8 Webserver 17 8.1. General 17 8.2. Home 17 8.3. Diagnostic Process 17 8.4. Device Properties 17 8.5. Diagnostic Module 17 8.6. Configurations 17 9 Appendix 18 9.1. Included material 18 9.2. Ordercode 18 9.3. Order Information 18

(4)

1 Notes

1.1. About this guide The BNI EIP-… serves as a decentralized IO Link, input and output module for connecting

to an EtherNet/IP™ network.

1.2. Structure of the guide

The guide is organized so that the chapters build on one another. Chapter 2: Basic safety information.

Chapter 3: The main steps for installing the device. Chapter 4: Technical data for the device

Chapter 5: Integration Chapter 6: Process data Chapter 7: Display Chapter 8: Webserver Chapter 9:Appendix

1.3. Typographical Conventions

The following typographical conventions are used in this Guide.

Enumerations Enumerations are shown in list form with bullet points.

• Entry 1, • Entry 2.

Actions Action instructions are indicated by a preceding triangle. The result of an action is indicated

by an arrow.

 Action instruction 1.  Action result.  Action instruction 2.

Procedures can also be shown as numbers in brackets. (1) Step no. 1

(2) Step no. 2

Syntax Numbers:

Decimal numbers are shown without additional indicators (e.g. 123),

Hexadecimal numbers are shown with the additional indicator hex (e.g. 00hex) or with the prefix “0x” (e.g. 0x00)

Cross-references Cross references indicate where additional information on the topic can be found (see

chapter 4 ”Technical Data”).

1.4. Symbols Note tip

This symbol indicates general notes.

Note

This symbol indicates a security notice which most be observed.

1.5. Abbreviations BNI Balluff Network Interface

I Standard input port EIP EtherNet/IP™

EMC Electromagnetic Compatibility FE Function ground

(5)

www.balluff.com 4

2 Safety

2.1. Intended use This guide describes The BNI EIP-… serves as a decentralized IO Link, input and output

module for connecting to an EtherNet/IP™ network.

2.2. General safety notes

Installation and startup are to be performed only by trained specialists. Any damage resulting from unauthorized manipulation or improper use voids the manufacturer’s guarantee and warranty.

The device is in accordance with EMC Class A. Such equipment may generate RF noise. The operator must take precautionary measures accordingly.

The device must be powered only using an approved power supply (see chapter 4 “Technical data”). Only approved cable may be used.

Operating and testing

The operator is responsible for observing local prevailing safety regulations.

When defects and non-clearable faults in the device occur, take it out of service and secure against unauthorized use.

Approved use in ensured only when the housing is fully installed.

2.3. Meaning of the

warnings Note! The pictogram used with word ”Caution“ warns of a possible hazardous situation

affecting the health of persons or equipment damage. Ignoring these warnings can result in injury or equipment damage.

(6)

3 Getting Started

3.1. Modul overview

Figure 0.1 – Overview BNI EIP-502-100-Z016

1 Mounting hole 2 EtherNet/IP™ port 2 3 Display

4 Status LED: Communication / Module 5 Port 5 (Standard I/O)

6 Pin/Port LED : Signal status 7 Port 6 (Standard I/O) 8 Port 7 (IO Link, Standard I/O) 9 Port 8 (IO Link, Standard I/O)

10 Port 4 (IO Link, Standard I/O) 11 Port 3 (IO Link, Standard I/O) 12 Port 2 (Standard I/O) 13 Port 1 (Standard I/O) 14 Power Supply Port 15 Label 16 EtherNet/IP™ port 1 17 Grounding connection 1 5 2 3 11 10 12 13 14 17 7 9 6 8 16 15 4

(7)

www.balluff.com 6

3 Getting Started

3.2. Mechanical connection

The module is attached using 2 M6 screws and 2 washers. Isolation pad as accessory available

3.3. Electrical connection

Power Supply Pin Function Description

1 +24 V Output Power

2 +24 V Input Power

3 0 V Input Power Common GND

4 0 V Output Power Common GND

Note

Provide sensor/bus power and actuator power from separate power sources if possible.

Total current <9A. The total current of all modules may not exceed 9A even when daisy chaining the actuator supply.

Grounding

Note!

The FE connection from the housing to the machine must be low-impedance and kept as short as possible.

Ethernet IP Interface M12, D-coded, female Pin Function 1 Tx+ 2 Rx+ 3 Tx- 4 Rx-

(8)

3 Getting Started

I/O-Port M12, A-coded, female

Pin Function 1 +24V, 200mA 2 Input / Output 3 GND 4 Input / Output 5 FE Note!

For the digital sensor inputs follow the input guideline per EN61131-2, type 2.

Note!

Each output serves a maximum current of 1,6 amperes. Total current of the module has to be lower than 9 amperes.

Note!

Unused I/O port socket must be fitted with cover caps to ensure IP67 protection rating.

IO Link-Port M12, A-coded, female

Pin Function

1 +24V, 1,6 A 2 Input / Output

3 GND

4 IO Link / Input / Output 5 n.c.

(9)

www.balluff.com 8

4 Technical data

4.1. Dimensions

4.2. Mechanical data Housing material Die case zinc, matt nickel plated

Enclosure rating per IEC 60529 IP 67 (only when plugged-in and threaded-in)

Supply voltage 7/8” 4-pin male

Input ports / Output ports M12, A-coded (8 x female) Dimensions (W x H x D in mm) 68 x 224 x 30.9

Mounting type 2-hole screw mount

Ground strap attachment M4

Weight Approx. 670 gr. 4.3. Operating conditions Operating temperature Ta Storage temperature -5 °C ... 70 °C -25 C ... 70 °C EMC - EN 61000-4-2/3/4/5/6 - EN 55011

- Severity level 2B/3A/4B/2B/3A - Gr.1, CL. B

Shock/vibration EN 60068-2-6, EN 60068-2-27 EN 60068-2-29, EN 60068-2-64

4.4. Electrical data Supply voltage 18...30.2 V DC, per EN 61131-2

Ripple <1%

(10)

4 Technical data

4.5. Ethernet Ethernet IP port 1 x 10Base-/100Base-Tx

Connection for Ethernet IP port M12, D-coded

Cable types per IEEE 802.3 Shielded twisted pair min. STP CAT 5/ STP CAT 5e Data transmission rate 10/100 Mbit/s

Max. cable length 100 m

Flow control Half Duplex/Full Duplex (IEEE 802.33x-Pause)

4.6. Function indicators

Modul status LED Anzeige Funktion

green Output power OK

UA

red Low Output power (< 18V)

green Input power OK

US

red Low Input power (<18V)

green flashing Wrong or no configuration on module

green Modul operating

red flashing Fixed busclock is not possible Mod

red-green flashing Initial sequence

off Module got no IP address

green flashing Module got IP, but no connection could be established

green Connection established

red flashing Connection timeout Net

red-green flashing Initial sequence

off Bus clock: 10 Mbit/s

100

yellow Bus clock: 100 Mbit/s

LNK green Data transfer

Port Each Port has two two-colour LEDs to indidcate the I/O-States.

Anzeige Funktion Bemerkung

off I/O-State State of the Input or Output Pin is 0 yellow I/O-State State of the Input or Output Pin is 1

single LED: Short-circuit on dedicated Pin (only if this pin is used as an output)

I/ O P o rt red Short-circuit

both LEDs: Short-circuit between Pin 1 and 3 or

Short-circuit on both output pins green IO Link IO Link communication running

Green flashing

IO Link No IO Link communication

red Short-circuit single LED: Short-circuit on Pin 4

both LEDs: Short-circuit between Pin 1 and 3

IO -L in k P o rt

red IO Link IO Link Device has wrong configuration

Status –LEDs: Modul status

Port/Pin LEDs:

(11)

www.balluff.com 10

5 Integration

5.1. Data

Configuration

Please enter the following values to your Control System. They describe the datasizes for input, output and config data.

Instance ID Data length

INPUT 100 200

OUTPUT 101 134

CONFIG 102 98

5.2. Config Data In the following tables you can see the mapping of the configuration data string. The default

values which are stated below describe a configuration with IO Link function on Pin 4 and standard input function (normally open) on Pin 2 of each IO Link port. The other Ports does not get configured by config data string, the function of standard I/O ports is set by process data (see 6.1 - Process Data Inputs)

Byte Slot Modul part Description

0…1 1 Module General configuration for the whole module (see 0 - Module Configuration)

2…25 2 IO-Link Port 1 Configuration for the IO-Link Port 1 (see 0 - IO Link Port Configuration) 26…49 3 IO-Link Port 2 Configuration for the IO-Link Port 2 (see 0 - IO Link Port Configuration) 50…73 4 IO-Link Port 3 Configuration for the IO-Link Port 3 (see 0 - IO Link Port Configuration) 74…97 5 IO-Link Port 4 Configuration for the IO-Link Port 4 (see 0 - IO Link Port Configuration)

Module Configuration Bit B y te 7 6 5 4 3 2 1 0 Description 0 P3 P2 0 0 1 P7 P6 0 0 Port function 0x00: Standard I/O 0x01: IO-Link IO Link Port Configuration (optional) Bit B y te 7 6 5 4 3 2 1 0 Description

2 Base Time Cycle Time

3 Validation type

Validation type

0 no validation

1 compatible (VID + DID) 2 identical (VID + DID + SerNum)

4 Vendor ID 1 5 Vendor ID 2 Vendor ID 6 Device ID 1 7 Device ID 2 8 Device ID 3 Device ID 9 Serial number 1 … … 24 Serial number 16 Serial number 25 Parameter server Parameter server 0x8X Enable 0xX1 Upload enable 0xX2 Download enable

(12)

6 Process Data

6.1. Process Data Inputs

There are 200 bytes of Input data. Have a look at the tables below to see the mapping of the process data inputs.

Byte Modul part Description

0…7 Standard I/O ports Process data inputs on standard Inputs 8…55 IO-Link Port 1 Process data inputs on IO Link Port 1 56…103 IO-Link Port 2 Process data inputs on IO Link Port 2 104…151 IO-Link Port 3 Process data inputs on IO Link Port 3 152…199 IO-Link Port 4 Process data inputs on IO Link Port 4

Standard Input Data Bit B y te 7 6 5 4 3 2 1 0 Description

0 I32 I34 I22 I24 I12 I14 I02 I04 1 I72 I74 I62 I64 I52 I54 I42 I44

Input data

I04  Input on port 0 pin 4 If a port is configured as an IO Link port, result is 0.

2 S3 S2 S1 S0 3 S7 S6 S5 S4

Short circuit status

Short circuit between Pin 1 and 3 on stated port

4 O22 O34 O22 O24 O12 O14 O02 O04 5 O72 O74 O62 O64 O52 O54 O42 O44

Overload status

O04  Overload on port 0 pin 4 Only if port is configured as output

6 0 0 0 0 0 0 PS PA

Power status

PS: Sensor power PA: actor power

7 0 0 0 0 0 0 0 0 Reserved

IO Link Input Data

Bit B y te 7 6 5 4 3 2 1 0 Description 8 … 39

IO Link Port 1 Input data

40 0 0 0 0 0 0 DC IOL

IO-Link status

IOL: Port in IO Link Mode DC: Device connected 0: reserved 41 0 0 0 0 0 0 0 VF IO-Link Error VF: Validation failed 0: reserved 42 Vendor ID 1 43 Vendor ID 2 Vendor ID 44 Device ID 1 45 Device ID 2 46 Device ID 3 Device ID 47 Error Code 48 Additional Code 49 Additional Code Event 1 50 Error Code 51 Additional Code 52 Additional Code Event 2 53 Error Code 54 Additional Code 55 Additional Code Event 3 … The data of the other IO Link ports has the same structure and follows here

(13)

www.balluff.com 12

6 Process Data

6.2. Process Data Outputs

There are 134 bytes of output data. Have a look at the tables below to see the mapping of the process data outputs.

Byte Modul part Description

0…5 Standard I/O ports Process data outputs on standard Inputs 6…37 IO-Link Port 1 Process data outputs on IO Link Port 1 38…69 IO-Link Port 2 Process data outputs on IO Link Port 2 70…101 IO-Link Port 3 Process data outputs on IO Link Port 3 102…133 IO-Link Port 4 Process data outputs on IO Link Port 4

Standard Output Data Bit B y te 7 6 5 4 3 2 1 0 Description

0 O32 O34 O22 O24 O12 O14 O02 O04

1 O72 O74 O62 O64 O52 O54 O42 O44

Output data

O04  Output on port 0 pin 4 To use this function on a IO Link port the port must be configured as an output (see 0- Module Configuration)

2 R32 R34 R22 R24 R12 R14 R02 R04 3 R72 R74 R62 R64 R52 R54 R42 R44

Restart

Restart output here after a detected short-circuit

4 0 0 0 0 0 0 0 0 Reserved

5 0 0 0 0 0 DL GO RO

Display Control

DL: Display lock / PLC lock GO: Green LED on Display on RO: Red LED on Display on

IO Link Output Data Bit B y te 7 6 5 4 3 2 1 0 Description 6 … 37

IO Link Port 1 Output data

(14)

7 Display

7.1. General With the implemented display, the address is set directly on the BNI EIP… devices.

The following address types are implemented: • IP address

• Subnet mask • Gateway address.

Each address type consists of 4 octets.

Additional the display shows information about the hard- and firmwarerevision.

There is a lock function fort he display which can be activated out of the control system. If the lock is set editing isn’t possible anymore (see Bit layout, chapter 8 „Appendix“).

7.2. Adress Defaults IP Address: 169.254.1.1

Subnetmask: 255.255.255.0 Gatewayaddress: 0.0.0.0 7.3. Controls and visualization 1 Display 2 Arrow-Key 3 Octett-Cursor

4 Address type cursor 5 „Set“-Key 6 LED 7.4. Display information IP: IP address SN: Subnet address GW: Gateway address 3: fourth octet 2: third octet 1: second octet 0: first octet

S

SN IP

GW 3 2 1 0 1 2 3 4 5 6

2

3

1

0

Cursor for selecting address type

Cursor zur Auswahl der Adressausprägung

Cursor for selecting octet

IP

SN

IP

GW

(15)

www.balluff.com 14

7 Display

7.5. Design and Symbols

There are some symbols used in the following flow-charts to describe the display-functionality:

7.6. Startup

7.7. Main Menue

• Scolling in main meue with short-time keypress on set-key • Step in menue with short-time keypress on arrow-key

IP 192 . 168 . 015 . 005 VERSION H W : 1 . 0 S W : 1 . 0 Subnet 255 . 255 . 255 . 000 Gateway 000 . 000 . 000 . 000

hard- und firmware-revision

Current IP Current subnetmask e Current gatewayaddress BNI EIP-502- 105-Z015 Module name B A L L U F F BALLUFF actual state change-over

S condition: short-time keypress on set key

S condition: long-time keypress on setkey (min. 3 seconds)  condition: short-time keypress on arrow key

IP CONFIG Default-view 4. octet of IP address Menue: IP Config Menue: IP Setup

Menue: Module Information

007

… … S  S S  S  … IP SETUP MODULE INFO

(16)

7 Display

7.8. IP Setup

• Long-time keyoress on set key starts editing mode.

• Configuration of the favored value by short-time keypress on arrow-key

7.9. IP Config

• Long-time keyoress on set key starts editing mode.

• Configuration of the favored value by short-time keypress on arrow-key • Long-time keypress on arrow key uses fast program mode

• Shorttime keypress on set key saves entered value and scrolls to the next octet. The 4.octet is the start of editing

• The whole entered address gets saved by short keypress on set value when editing first octet. The entered value can immediately seen on the ip overview screen.

• Manual changes of ip, subnet or gateway results in automatic change to “static” in IP Setup.

Hinweis:

To work with the new configuration the module needs a power-down

STATIC DHCP X FACTORY STATIC X DHCP FACTORY  x STATIC DHCP FACTORY S   S S S editing mode X STATIC DHCP FACTORY IP editing mode IP 192.168. 015.005 Subnet 255.255. 255.000 Gateway 000.000. 000.000 IP Config     e d it in g m o d e P ro g ra m m ie rm o d u s

005

015

168

192

S S S S S e d it in g m o d e P ro g ra m m ie rm o d u s

000

255

255

255

S S S S S e d it in g m o d e P ro g ra m m ie rm o d u s

000

000

000

000

S S S S S

(17)

www.balluff.com 16

7 Display

7.10. Module

information

• By short-time keypress on arrow key you can scroll through module information menu.

• Informations are the product name, the module revisions and the MacID.

7.11. General

Informations

• Longtime keypress for „fast scrolling“ in editing mode

• 10 secondes without keypress results in leaving actual screen and entering the default screen mode (4th octet of ip address). Unsaved changes gets lost

• Differences between new configuration and the configuration the module is working with are shown by a unequal-symbol. In this case the time to default screen is only 5 seconds.

• In editing mode the screen flashes. In fast scroll mode the screen is flickering • If the module receives a single ping, the word “ping” is shown in the display screen

for a few seconds. Afterwards the screen is reset to the screen which had been shown before. By short-time key press on set key the ping-mode can be left preterm.

• If the module receives a double ping, the word “ping” is shown in the display. This screen can be left only by short-time key press on set key. The screen shown before ping gets viewed again.

• The Led function at the display leds can be defined user specific ba setting some bits in the process data inputs. (see Bitlayout, chapter 8 „Annex“)

• The function plc-lock can also be used by setting a bit in the process data inputs. (see Bitlayout, chapter 8 „Annex“)

Hinweis:

Editing mode can not be chosen in display if the plc lock bit in process data inputs is (see Bitlayout, chapter 8 „Annex“)

BNI EIP-502- 100-Z016 Version SW: x.x HW: x.x MAC-ID XX : XX : XX : XX : XX : XX    … 

(18)

8 Webserver

8.1. General The BNI EIP-502 module includes an internal webserver to get detailed information about

the current state. Also you can use it to configurate the module and the connected IO Link devices.

First make sure that a correct integration into your network has been done. To get a connection to the webserver enter the IP address of the module to your browser address bar. A welcome page with a list of all Balluff Ethernet Network-interfaces is shown. Please use Internet Explorer 7 or 8. Other Browsers might not function correctly at the current development state.

8.2. Home By click on “play”-button “Home” active.

You can get some information about the configuration and network-activity of the module. At the top of the window you can see the navigation bar which allows you to switch between the different webpages, just click on the corresponding text.

8.3. Diagnostic Process

On this page you can get some information about the module’s current process data by having a look at the leds.

If a IO Link Device is connected to on of the IO Link ports some device data is shown besides the modul. You can use this text or the port on the module as a link to “Device properties”.

8.4. Device Properties On this page you can get information about the IO Link device that is connected on the

selected port. Also it is possible to configure the device by using the read/write functions. The indices and subindices which can be written or read are defined by the connected device. So for this reason have a look at the IO Link device manual.

8.5. Diagnostic Module

On this page you can see the current module and network status like you can see it on the module itself.

8.6. Configurations The configuration page allows you to configure the module. You can change

network-parameters and also assign own module information texts like a module description. This can only be used by entering a username and a password:

Username: Balluff Password: BNIEIP

(19)

www.balluff.com 18

9 Appendix

9.1. Included material The BNI EIP consists of the following components:

• IO-Link block • 4 blind plugs M12 • Ground strap • Screw M4x6 • 20 labels

9.2. Ordercode BNI EIP-502-105-Z015

Balluff Network Interface Ethernet IP

Functions

502 = IP 67 IO Link Master-Modul Variants

105 = Display version, 2-port switch Mechanical version

Z015 = Die-cast zinc housing

Material: 1. Balluff housing version Uplink: 2 x M12x1 internal thread Power: 7/8“ external thread

Sensor Ports: 8 x M12x1 internal thread

9.3. Order Information Product ordering code Order code

(20)

www.balluff.com

E • E d it io n 1 1 0 3 • S u b je c t to m o d if ic a ti o n

References

Related documents

2.1 Intended use The BNI IOL-… is a decentralized sensor input module which is connected to a host IO-Link master over an IO-Link interface.. 2.2 General safety

The example in the following figure shows the terminal assignment of the communication module IO-Link Master CM 8xIO-Link (3- and 5-conductor connection of IO-Link devices). ①

Forest Service (USDA Forest Service 2007).. List of tree species documented from the current and previous studies at Rock Creek Research Natural Area, Laurel County, KY.

The mounting holes are used to screw the sensor module on the wall or onto a flush mounted box.. In case

Network Configurator Application software to setup and monitor tag data Link for CJ2 (Built-in EtherNet/IP) CPU Units and EtherNet/IP Units... NX-IO Configurator Application software

Supply voltage is provided via the IO-Link interface and the higher-level IO-Link master module..

The class implementations are removed to reduce the size of the document. The second division is for parser definitions. Macro definitions with all tokens and nonterminal declarations

digital I/O. The module thus makes it possible to integrate IO-Link devices into a digital infrastructure and utilize almost the full extended range of functions of the