Data Centre Cabling

20 August 2015 Stefan Naude RCDD The SIEMON Company

(2)

Agenda

1. Data Centre Standards

2. The Need for Speed

3. Copper in the Data Centre 4. Fibre in the Data Centre

5. Top of Rack vs EOR topology 6. Other Design Considerations 7. Future Technology

(3)
(4)

Data Centre Standards

ISO 24764

IT Generic Cabling Systems Part 1: General requirements for Data

Centers

ISO/IEC 11801

Information technology – Generic cabling for customer premises

ISO/IEC 14763-1

Information technology – Implementation and operation of customer premises cabling – Part 1:

Administration

ISO/IEC 14763-2

Information technology – Implementation and operation of customer cabling – Part 2: Planning and

Installation

ISO/IEC 14763-3

Information technology – Implementation and operation of customer cabling – Part 3: Testing of

Optical Fibre

ISO/IEC 14763-2

Information technology – Implementation and operation of customer cabling – Part 4: Testing of balanced copper cabling in the horizontal subsystem

(5)

Data Centre Standards

ANSI/TIA 568-C.0

Generic Telecommunications Cabling for Customer Premises

ANSI/TIA 569-C

Telecommunications Pathways and Spaces

ANSI/TIA 606-B

Administration Standard Telecommunications Infrastructure

ANSI/TIA 607-B

Generic Telecommunications Bonding & Grounding for Customer Premises

ANSI/TIA 568-C.1

Commercial Building Telecommunications Cabling

ANSI/TIA 568-C.2

Balanced Twisted-Pair Telecommunications Cabling &

Components

ANSI/TIA 568-C.4

Broadband Coaxial Cabling & Components

ANSI/TIA 862-A Building Automation Systems Cabling ANSI/TIA 570-C Residential Telecommunications Infrastructure Standard ANSI/TIA 75B-A

Customer Owned Outside Plant Telecommunications Infrastructure

ANSI/TIA 942-A

Telecommunications Infrastructure Standard for Data Centres

ANSI/TIA 1005-A

Telecommunications Infrastructure Standard for Industrial Premises

ANSI/TIA 568-C.3

Optical Fibre Cabling Components

(6)

Data Centre Standards

BICSI 002-2011 – Data Centre Design and best practices

o Addresses telecommunication , information technology , electrical ,mechanical and

architectural issues for the design and installation of Data Centre’s

o Guidance on coordination between design and construction disciplines

(7)

Agenda

1. Data Centre Standards

2. The Need for Speed

3. Copper in the Data Centre 4. Fibre in the Data Centre

5. Top of Rack vs EOR topology 6. Other Design Considerations 7. Future Technology

(8)

The Need for Speed

(9)

The Need for Speed

o Server Virtualization o New Applications

o IoT (Estimated 50 Billion object by 2020) o TV/Video on demand

o Wireless Devices

o “Big Brother” society o Cloud Computing

(10)

The Need for Speed

255Tbs speeds achieved via spatial multiplexing 5.1Tbs per carrier and 50 carriers down the 7

(11)

Agenda

1. Data Centre Standards 2. The Need for Speed

3. Copper in the Data Centre

4. Fibre in the Data Centre

5. Top of Rack vs EOR topology 6. Other Design Considerations 7. Future Technology

(12)

Copper in the Data Centre

Why a minimum of CAT6A in the Data Centre? o 1G vs 10G around 15 to 20% cost difference o Standards advise Category 6A

o Biggest concern at high frequency is ANEXT o Difficult to test ANEXT and time consuming

(13)

Copper in the Data Centre

• Alien Near End Cross Talk happens at high frequency transmission when you

can ̎hear ̎ the signal

transmitted on a cable, on another cable in the bundle • Its not NEXT which happens

(14)

Copper in the Data Centre

Problem ANEXT Solution

(15)

Copper in the Data Centre

Why 10G on copper ?

o Energy Efficient Ethernet

o Wake on LAN

o Short Reach Mode

o Auto negotiate between speed

o 10G more efficient then 1G (less watt per port)

(16)

Agenda

1. Data Centre Standards 2. The Need for Speed

3. Copper in the Data Centre

4. Fibre in the Data Centre

5. Top of Rack vs EOR topology 6. Other Design Considerations 7. Future Technology

(17)

Fibre in the Data Centre

o With 10G to the server (Access)

o 40G and 100G is already used in Data Centres o Higher Data rates required on the uplinks

(18)

Fibre in the Data Centre

o OM3 to 100m o OM4 to 150m o Spare 4 fibre's can be used to create another port TX TX TX TX TX TX TX TX RX RX RX RX RX RX RX RX 10G 10G 10G 10G 10G 10G 10G 10G 40G MTP

(19)

Fibre in the Data Centre

o OM3 to 70m o OM4 to 100m o Approved by IEEE March 2015 TX TX TX TX TX TX TX TX RX RX RX RX RX RX RX RX 25G 25G 25G 25G 25G 25G 25G 25G 100G MTP

(20)
(21)

Fibre in the Data Centre

Benefits of MTP fibre

o MTP fibre 10G day 1(MTP to LC cassettes) o Once equipment is ready – upgrade to

40G/100G

o Plug and Play o Pre tested

(22)

Fibre in the Data Centre

Design Considerations for fibre in the DC o Link budgets

o Upgrade path o Fibre Polarity o High Density

(23)

Fibre in the Data Centre

Link Budgets Application Distance (Meters) Max Channel Loss/Connector Loss Fiber Attenuation (3.0dB/km) 10 GbE OM3 @850 nm 300 2.6 dB/NA 0.9 dB 40/100 GbE OM3 @ 850 nm 100 1.9 dB/1.5 dB 0.3 dB 10 GbE OM4 @850 nm 400 2.9 dB/NA 1.2 dB 40/100 GbE OM4 @ 850 nm 150 1.5 dB/1.0 dB 0.4 dB

(24)

Fibre in the Data Centre

(25)
(26)

Fibre in the Data Centre

(27)

Fibre in the Data Centre

Link Budgets Fibre loss @

1. Length Attenuation – physical fibre 2. LC to LC interface (Front of cassette)

3. MTP to MTP interface( Back of cassette) **Consider Low Loss products**

(28)

Fibre in the Data Centre

(29)

Fibre in the Data Centre

(30)

Fibre in the Data Centre

(31)

Fibre in the Data Centre

(32)

Fibre in the Data Centre

High Density

o Space in a DC comes at premium

o Environments with high volume of fibre

oSAN switches oLAN Switches

oCross Connects in a centralized patching zone

o 144 Cores in 1U is high density

(33)

Agenda

1. Data Centre Standards 2. The Need for Speed

3. Copper in the Data Centre 4. Fibre in the Data Centre

5. Top of Rack vs EOR topology

6. Other Design Considerations 7. Future Technology

(34)
(35)
(36)
(37)
(38)

Agenda

1. Data Centre Standards 2. The Need for Speed

3. Copper in the Data Centre 4. Fibre in the Data Centre

5. Top of Rack vs EOR topology

6. Other Design Considerations

(39)

Other Design Considerations

Data Centre is a complex collection of many aspects including:

o Facility and Facility layout

Cooling , power (UPS, ATS, Generator, Mains etc.) Flooring , Lights

o Network – Switching , redundancy , maintenance ,

SLA’s

o Servers – Physical , Applications

o Security – Physical and Network

(40)

Other Design Considerations

We are only looking at physical infrastructure

o Routing - above or below or both? ( Fill ratios, bending) o Coordination with other services (Lights , power)

o Type of Network topology (EOR , MOR , CPZ?) o Cable Management (In rack and other)

o Level of Redundancy

o Physical Layout of racks in the room ( cold isle/hot?) o Switch Harnessing

(41)

Other Design Considerations

(42)

Other Design Considerations

(43)

Other Design Considerations

(44)

Other Design Considerations

(45)

Other Design Considerations

(46)

Agenda

1. Data Centre Standards 2. The Need for Speed

3. Copper in the Data Centre 4. Fibre in the Data Centre

5. Top of Rack vs EOR topology 6. Other Design Considerations

(47)

Future Technology

Category 8 Copper for 25GBaseT/40GBaseT

o 30m link

o 1250 MHz for 25G and 2000MHz for 40G

o 2 Connector link

o Shielded- RJ45 (Class I)

o Fully Shielded – TERA (Class II)

o 2w per port

(48)

Future Technology

o Demand only one way - UP

o DCIM – more complex monitoring for efficiency

o IoT - Cisco research shows that today’s global data traffic per month is 24 times that in

2013; it will be 95 times that by 2018, reaching 15.9 exabytes per month by 2018

o Storage – flash/solid state

References

Related documents

Information technology – Generic cabling for customer premises TIA 568C: Commercial Building Telecommunication Cabling Standard EN 50173-1: Information technology Generic

Siemon offers the broadest range of copper and fiber high speed interconnect assemblies, category cabling and cable management solutions. For more information on Siemon

As mentioned in 2.3.1, the minimum performance class requirement defined by the data center cabling standard for copper cabling systems is Class E A which is backward compatible

3.1.3 Enhancement of the exchange of information between the EU Member States and Commission services on the one hand and third countries authorities on the other

Systemic treatments, including methotrexate (MTX) and cyclosporin (CyA), are associated with potential hepatotoxicity, due to either direct liver damage or immunosuppression or

Conductors are twisted in pairs, separated by an integrated pair divider, surrounded by a patent-pending matrix tape and protected by a LSZH flame-retardant PVC jacket.. Ideal

• The connecting hardware used for balanced cabling shall be installed to provide minimal signal impairment by preserving wire pair twists and conductor separation as closely

telecommunications cabling infrastructure  Provides requirements for the data center. telecommunications