Operation and Maintenance Manual
Operation and Maintenance Manual
3500/33 16-Channel Relay Module
3500/33 16-Channel Relay Module
Part Number 162291-01 Part Number 162291-01
Rev. B Rev. B (02/08)(02/08)
3500/33 16 Channel Relay Module Operation and Maintenance Manual 3500/33 16 Channel Relay Module Operation and Maintenance Manual
Copyright 2002. Bently Nevada LLC.
Copyright 2002. Bently Nevada LLC.
All rights reserved.
All rights reserved.
The information contained in this document is subject to change without notice. The information contained in this document is subject to change without notice.
The following are trademarks of General Electric Company in the United States and other The following are trademarks of General Electric Company in the United States and other countries:
countries: Bently Nevada Bently Nevada
The following are trademarks of the legal entities cited: The following are trademarks of the legal entities cited: Velostat is a trademark of 3M Company.
Velostat is a trademark of 3M Company.
Contact Information
Contact Information
The following contact information is provided for those times when you cannot contact The following contact information is provided for those times when you cannot contact your local representative:
your local representative: Mailing
Mailing Address Address 1631 1631 Bently Bently Parkway Parkway SouthSouth Minden,
Minden, Nevada Nevada USA USA 8942389423 USA USA Telephone 1.775.782.3611 Telephone 1.775.782.3611 1.800.227.5514 1.800.227.5514 Fax 1.775.215.2873 Fax 1.775.215.2873 Internet
3500/33 16 Channel Relay Module Operation and Maintenance Manual 3500/33 16 Channel Relay Module Operation and Maintenance Manual
Copyright 2002. Bently Nevada LLC.
Copyright 2002. Bently Nevada LLC.
All rights reserved.
All rights reserved.
The information contained in this document is subject to change without notice. The information contained in this document is subject to change without notice.
The following are trademarks of General Electric Company in the United States and other The following are trademarks of General Electric Company in the United States and other countries:
countries: Bently Nevada Bently Nevada
The following are trademarks of the legal entities cited: The following are trademarks of the legal entities cited: Velostat is a trademark of 3M Company.
Velostat is a trademark of 3M Company.
Contact Information
Contact Information
The following contact information is provided for those times when you cannot contact The following contact information is provided for those times when you cannot contact your local representative:
your local representative: Mailing
Mailing Address Address 1631 1631 Bently Bently Parkway Parkway SouthSouth Minden,
Minden, Nevada Nevada USA USA 8942389423 USA USA Telephone 1.775.782.3611 Telephone 1.775.782.3611 1.800.227.5514 1.800.227.5514 Fax 1.775.215.2873 Fax 1.775.215.2873 Internet
Internet www.ge-energy.com/bentlywww.ge-energy.com/bently
Additional Information
Additional Information
Notice:
Notice:
This manual does not contain all the information required
This manual does not contain all the information required to operate and maintainto operate and maintain the product.
the product. Refer to the foRefer to the following manuals for other llowing manuals for other required information.required information.
3500 Monitoring System Rack Installation and Maintenance Manual
3500 Monitoring System Rack Installation and Maintenance Manual (Part
(Part
Number 129766-01)
Number 129766-01)
•
• General description of a standard system.General description of a standard system. •
• Instructions for installing and removing the module from a 3500 rack.Instructions for installing and removing the module from a 3500 rack. •
• Drawings for all cables used in the 3500 Monitoring System.Drawings for all cables used in the 3500 Monitoring System.
3500 Monitoring System Rack Configuration and Utilities
3500 Monitoring System Rack Configuration and Utilities Guide (Part
Guide (Part
Number 129777-01)
Number 129777-01)
•
• Guidelines for using the 3500 Rack Configuration software for setting theGuidelines for using the 3500 Rack Configuration software for setting the
operating parameters of the module. operating parameters of the module.
•
• Guidelines for using the 3500 test utilities to verify that the input and outputGuidelines for using the 3500 test utilities to verify that the input and output
terminals on the module are operating properly. terminals on the module are operating properly.
3500 Monitoring System Computer Hardware and Software Manual
3500 Monitoring System Computer Hardware and Software Manual (Part
(Part
Number 128158-01)
Number 128158-01)
•
• Instructions for connecting the rack to 3500 host computer.Instructions for connecting the rack to 3500 host computer. •
• Procedures for verifying communication.Procedures for verifying communication. •
• Procedures for installing software.Procedures for installing software. •
• Guidelines for using Data Acquisition / DDE Server and Operator Display Software.Guidelines for using Data Acquisition / DDE Server and Operator Display Software. •
• Procedures and diagrams for setting up network and remote communications.Procedures and diagrams for setting up network and remote communications.
3500 Field Wiring Diagram Package (Part Number 130432-01)
3500 Field Wiring Diagram Package (Part Number 130432-01)
•
• Diagrams that show how to hook up a particular transducer.Diagrams that show how to hook up a particular transducer. •
3500/33 16 Channel Relay Module Operation and Maintenance Manual 3500/33 16 Channel Relay Module Operation and Maintenance Manual
Product Disposal Statement Product Disposal Statement
Customers and third parties, who are not member states of the European Union, who are Customers and third parties, who are not member states of the European Union, who are in control of the product at the end of its life or at the end of its use, are solely
in control of the product at the end of its life or at the end of its use, are solely responsible for the proper disposal of the product. No person, firm, corporation, responsible for the proper disposal of the product. No person, firm, corporation,
association or agency that is in control of product shall dispose of it in a manner that is association or agency that is in control of product shall dispose of it in a manner that is in violation of any appli
in violation of any applicable federal, state, local cable federal, state, local or international law. or international law. Bently Nevada LLCBently Nevada LLC is not responsible for the disposal of the product at the end of its life or at the end of its is not responsible for the disposal of the product at the end of its life or at the end of its use.
use.
iv iv
Contents
Contents
1.
1.
Receiving
Receiving and
and Handling
Handling Instructions
Instructions ...
...
...
... 1
1
1.11.1 ReceivReceiving ing InspecInspection...tion... 11 1.2
1.2 HandliHandling ng and and StorinStoring g ConsidConsiderationerationss... 11
2.
2.
General
General Information
Information ...
...
...
...
... 3
3
2.12.1 The The 16-Chan16-Channel Relay nel Relay ModuleModule ... 33 2.2
2.2 Statuses...Statuses... 77 2.2.1
2.2.1 Module Module StatusStatuseses ... 77 2.2.2
2.2.2 Channel Channel StatusStatus ... 88 2.3
2.3 LED LED DescrDescriptions...iptions... 99
3.
3.
Configuration
Configuration Information
Information ...
...
...
... 11
11
3.13.1 Hardware Hardware ConsideConsiderationsrations ...11...11 3.2
3.2 EnteriEntering ng Alarm Alarm Drive Drive Logic...Logic...11...11 3.2.1
3.2.1 Relay Relay Module Module ConfiguConfiguration ration ConsideConsiderationsrations ...12...12 3.2.2
3.2.2 Relay Relay Module Module ConfiguConfiguration ration Options...Options...12...12 3.3
3.3 Software Software SwitcSwitcheshes ...14...14 3.3.1
3.3.1 ConfiguConfiguration ration ModeMode ...15...15 3.3.2
3.3.2 Bypass...Bypass...15...15
4.
4.
Output Module
Output Module Description
Description...
...
...
... 17
17
4.14.1 16-Chan16-Channel nel Relay Relay Output Output Module.Module...17...17 4.2
4.2 Wiring Wiring Euro Euro Style Style ConnectorConnectorss ...19...19
5.
5.
Maintenance
Maintenance ...
...
...
...
... 21
21
5.15.1 VerifyVerifying a ing a 3500 Rack 3500 Rack - - Relay ModuleRelay Module ...21...21 5.1.1
5.1.1 ChoosinChoosing g a a MainteMaintenance nance Interval...Interval...21....21 5.1.2
5.1.2 RequirRequired ed Test Test EquipmEquipment...ent...22...22 5.1.3
5.1.3 TypicTypical al VerifiVerification cation test test setupsetup ...22...22 5.1.4
5.1.4 Using Using the the Rack Rack ConfiguConfiguration ration Software...Software...23....23 5.1.5
5.1.5 Standard Standard Relay Relay ChannelChannelss ...24...24 5.1.6
5.1.6 If If a a Channel Fails Channel Fails a a VerifiVerification Test...cation Test...26...26 5.2
5.2 16-Chan16-Channel nel Relay Firmware Relay Firmware Upgrade ProcedureUpgrade Procedure ...26...26
6.
3500/33 16 Channel Relay Module Operation and Maintenance Manual
6.1 Self-test...28
6.2 LED Fault Conditions...29
6.3 System Event List Messages ...30
6.4 Alarm Event List Messages ...41
7.
Ordering Information...42
7.1 16-Channel Relay Module ...42
7.2 Spares...42
8.
Specifications...43
8.1 Relays ...43 8.2 Environmental Limits...44 8.3 Mechanical...44 8.4 Electromagnetic Compatibility...44 8.5 Approvals ...45 8.6 Physical...46 8.6.1 Main Module...46 8.6.2 Output Module...468.7 Rack Space Requirements ...46
Section 1 - Receiving and Handling Instructions
1. Receiving and Handling Instructions
1.1 Receiving Inspection
Visually inspect the module for obvious shipping damage. If shipping damage is apparent, file a claim with the carrier and submit a copy to Bently Nevada LLC.
1.2 Handling and Storing Considerations
Circuit boards contain devices that are susceptible to damage when exposed to electrostatic charges. Damage caused by obvious mishandling of the board will void the warranty. To avoid damage, observe the following precautions in the order given.
Application Advisory
Machinery protection will be lost when this module is removed from the rack.
• Do not discharge static electricity onto the circuit board. Avoid tools or
procedures that would subject the circuit board to static damage. Some possible causes include ungrounded soldering irons, nonconductive plastics, and similar materials.
• Personnel must be grounded with a suitable grounding strap (such as 3M
Velostat® No. 2060) before handling or maintaining a printed circuit board.
• Transport and store circuit boards in electrically conductive bags or foil. • Use extra caution during dry weather. Relative humidity less than 30%
tends to multiply the accumulation of static charges on any surface.
• When performed properly, you may install this module into or remove it
from the rack while power is applied to the rack. Refer to the Rack Installation and Maintenance Manual (part number 129766-01) for the proper procedure.
Section 2 - General Information
2. General Information
You can use the 16-Channel Relay Module for most monitoring applications. The module uses a single relay to drive the output for each channel. See Section 2.1 for additional information on the 16-Channel Relay Module.
4 5 6 7 1 2 3 NE NDE RELAY MODE NDE NE 1. Relay module
2. I/O module (front view) 3. I/O module (left side view)
4. LEDs indicating the module status.
5. LEDs indicating the status of the Relay Channels.
6. Terminals for connecting relay contacts to external devices. 7. Switches that control how the relay contacts work.
Figure 2-1: Views of 16-Channel Relay Module
2.1 The 16-Channel Relay Module
The 3500/33 16-Channel Relay Module is a full-height module that provides 16 relay outputs. You can place any number of these relay modules in any of the slots to the right of the Rack Interface Module (RIM).
You can use AND and OR voting to fully program each relay output. The Alarm Drive Logic for each relay channel can use alarming inputs (Alert, Danger, Not OK, and individual channel parameters) from any monitor channel in the rack. You program this Alarm Drive Logic using the Rack Configuration Software.
3500/33 16 Channel Relay Module Operation and Maintenance Manual The three common configuration types of Alarm Drive Logic are:
1) Bussed relays. Bussed relays use an Alarm Drive Logic that ORs the Alerts or Dangers for all channels in the rack to drive a single relay. 2) Individual relays. Individual relays use Alarm Drive Logic that ORs the
Alerts or Dangers for channel pairs (channel 1 and channel 2 or channel 3 and channel 4) in a monitor to drive a single relay.
3) Independent relays. Independent relays use Alarm Drive Logic that cause each alarm level (Alert and Danger) from a channel to drive a separate relay channel.
The following examples show the drive logic for these three types of logic .
S = Monitor Slot A1 = Alert/Alarm 1
C = Channel A2 = Danger/Alarm 2
Example 1: Bussed Relays (Alert and Danger)
##A1 = Any Active Alert ##A2 = Any Active Danger
((S02C##A1) OR (S03C##A1) OR ... OR (S15C##A1)) Trip Relay Channel 1 ((S02C##A2) OR (S03C##A2) OR … OR (S15C##A2)) Trip Relay Channel 2
Figure 2-2: Bussed Relays Example
Section 2 - General Information Example 2: Individual Relays (Alert and Danger)
(S02C01A1) OR (S02C02A1) Trip Relay Channel 1 (Alert Relay) (S02C01A2) OR (S02C02A2) Trip Relay Channel 2 (Danger Relay) (S02C03A1) OR (S02C04A1) Trip Relay Channel 3 (Alert Relay) (S02C03A2) OR (S02C04A2) Trip Relay Channel 4 (Danger Relay)
3500/33 16 Channel Relay Module Operation and Maintenance Manual Example 3: Independent Relays (Alert and Danger)
(S02C01A1) Trip Relay Module in slot 2 Channel 1 (Alert Relay) (S02C02A1) Trip Relay Module in slot 2 Channel 2 (Alert Relay) (S02C03A1) Trip Relay Module in slot 2 Channel 3 (Alert Relay) (S02C04A1) Trip Relay Module in slot 2 Channel 4 (Alert Relay) (S02C01A2) Trip Relay Module in slot 2 Channel 5 (Danger Relay) (S02C02A2) Trip Relay Module in slot 2 Channel 6 (Danger Relay) (S02C03A2) Trip Relay Module in slot 2 Channel 7 (Danger Relay) (S02C04A2) Trip Relay Module in slot 2 Channel 8 (Danger Relay)
Independent relays require one 16-Channel Relay Modules for each monitor module.
Figure 2-4: Independent Relays Example
Section 2 - General Information
2.2 Statuses
The 16-Channel Relay Module will return both module and channel statuses. This section describes the available statuses and where you can find them.
2.2.1 Module Statuses
OK
This indicates if the 16-Channel Relay Module is functioning correctly. The module returns a Not OK status under any of the following conditions:
• Hardware Failure in the module • Node Voltage Failure
• Configuration Failure • Slot ID Failure
If the Module OK status goes Not OK, then the module will drive the system OK Relay on the Rack Interface I/O Module to a Not OK state.
Configuration Fault
This indicates if the 16-Channel Relay Module configuration is invalid. Bypass
This indicates if some condition has caused the system to bypass any channel in the 16-Channel Relay Module. Any of the following conditions can cause the system to bypass the Relay Module:
• A channel has never been configured • The Relay Module is in configuration mode • A Fatal error was found during self-test • Rack Alarm Inhibit has occurred
• A channel has an invalid configuration • Any active channel is bypassed
Alarm 1 Active
This indicates that one or more channels of the 16-Channel Relay Module is in alarm.
3500/33 16 Channel Relay Module Operation and Maintenance Manual Table 2-1: Location of Module Statuses
Statuses Comm. Gateway Module Rack Configuration Software Operator Display Software 3500/94 VGA Display Module OK X X X
Module Configuration Fault X Module Bypass X
Module Alert/Alarm 1 Active X X X
2.2.2 Channel Status
OK
This indicates that the associated channel of the 16-Channel Relay Module has detected no fault. If the Channel OK status goes not OK, then the module will drive the system OK Relay on the Rack Interface I/O Module to a Not OK state.
Bypass
This indicates if some condition has caused the system to bypass the
associated 16-Channel Relay Module channel. Any of the following conditions can cause the system to bypass the channel:
• The channel has never been configured • The Relay Module is in configuration mode • A Fatal error was found during self-test • Rack Alarm Inhibit has occurred
• The channel has an invalid configuration
• The channel is bypassed using a software switch
Channel Off
This indicates if the associated 16-Channel Relay Module channel has been turned off (not Active). You may turn off the Relay channels (inactivated) using the Rack Configuration Software.
Alarm 1 Active
This indicates if the associated 16-Channel Relay Module channel is in alarm.
Table 2-2 shows where the you can find the channel statuses.
Section 2 - General Information Table 2-2: Location of Channel Statuses
Statuses Comm. Gateway Module Rack Configuration Software Operator Display Software 3500/94 VGA Display Channel OK X X X X Channel Bypass X X X X Channel Off X X X
Channel Alert/Alarm 1 Active X X X
2.3 LED Descriptions
The LEDs on the front panel of the 16-Channel Relay Module indicate the
operating status of the module as shown in Figure 2-5. Refer to Section 6.2 for all of the available LED conditions.
1. OK LED: Indicates that the 16-Channel Relay Module and the 16-Channel Relay Output Module are operating correctly.
2. TX/RX LED: Flashes at the rate that messages are received.
3. Channel Alarm LED: Indicates that an alarm condition has occurred with this relay. Figure 2-5: 3500/33 Front Panel LEDs
Section 3 - Configuration Information
3. Configuration Information
You configure 3500 relay modules through the 3500 Rack Configuration Software, by using the Relay Association screen to enter alarm drive logic for each relay channel and the Software Switches screen to set software switches. This section defines the options on these configuration screens. The Rack Configuration and Utilities Guide (part number 129777-01) shows how to operate those screens.
3.1 Hardware Considerations
The slots in the 3500 rack are numbered from 0 to 15, counting from left to right. The power supplies go into slot 0 and the RIM goes into slot 1. Slots 2 through 15 are called “monitoring positions”. You can install the 3500/33 module into any of the monitoring positions. However, if you will use the 3500/20 Rack Interface Module and Data Manager I/O to interface to DDIX, TDIX or TDXnet, refer to the 3500/20 manual for slot restrictions that this may place on your configuration.
3.2 Entering Alarm Drive Logic
Use the Relay Association screen to define the alarm logic that will determine which alarms will cause the channels in the relay to drive the output.
3500/33 16 Channel Relay Module Operation and Maintenance Manual
3.2.1 Relay Module Configuration Considerations
• Add monitor modules to the rack configuration before configuring the Relay
Module.
• Activate only the Relay Module channels that will be used.
• Note that only monitor modules may be used in the alarm drive logic.
• Plan ahead to determine if you will configure any channels as channel pairs
(DPDT).
• Determine whether your application will need True AND or Normal AND voting
logic.
• Consider using the Copy function if you configure several channels with
similar logic or conditions.
• Note that prior to downloading, the configuration software will determine if
the number of instructions exceeds the limit of your relay module. The software limits the 16-Channel Relay module to 100 logical operations per channel for each of the 16 channels.
• Note that prior to exiting the Relay Association screen, the configuration
software will determine if there are errors in any channel alarm drive logic. The cursor will be placed at the location of the syntax error.
3.2.2 Relay Module Configuration Options
Available Monitors
This field shows the monitors in the rack. Rack Type
This specifies the type of RIM installed in the rack (Standard or TMR). Config ID
This is a unique 6-character identifier that the software enters when downloading a configuration to the 3500 rack.
Relay Slot
This indicates the location in the 3500 rack of the relay module you are configuring.
Active
This check box applies to the selected channel in the Channel Association group. The relay channel drives the output only when this box is enabled (⌧) and the alarm drive logic for the channel is TRUE.
Section 3 - Configuration Information Latching Relays
When you select this option, the corresponding relay alarm channel will hold the alarm state until it receives a rack reset or the relay is reconfigured. Relay Channel Pair (DPDT)
Selecting this option will group the current channel with its channel pair, thus allowing both channels to have identical configurations and alarm logic. Standard Relay Channel Association
This is a group for you to select the channel, or channel pair, you wish to configure and activate.
Relay NE/NDE Switch Status
This indicates the the relay hardware switch settings on the Relay Output Module. This status is available only after you have uploaded the relay. Available Monitor Channels/Alarms
When you select a monitor, this area shows all the alarms that are available for the relay module.
Alarm Drive Logic
This is the area in which you build the alarm drive logic using the available monitor alarms.
AND Voting Setup
3500/33 16 Channel Relay Module Operation and Maintenance Manual Normal AND Voting (Default)
With you select this option, if an alarming parameter is Not OK or bypassed (due to either user selection or monitor failure), then the software will remove the parameter from the relay logic. Please note that the software will not remove a “Not-OK” alarming parameter (a parameter intended to alarm on a Not-OK condition) from the alarm logic equation.
True AND Voting
True AND logic causes alarming parameters that are Not OK or bypassed to remain in the relay logic. True AND logic will not drive an alarm if an alarming parameter being ANDed is
• Not OK (parameters are not intended to alarm on a Not-OK
condition), or
• in bypass.
Application Advisory
Take care when selecting the AND voting to be used. You should consider the configuration settings for the channel you
intend to use as an alarm parameter. Not OK Channel Defeat (single channel measurements), Not OK Channel Pair Defeat
(paired channel measurements), Timed OK Channel Defeat and Latching vs. Non-Latching Not OK modes all affect the
circumstances that cause a channel to be "Not OK" or bypassed.
Note in particular that the following channel types have special scenarios that you must consider:
Thrust Position: Monitor reports an Alarm (not a "Not OK" condition) to the relay module for a transducer not OK.
Overspeed, Zero-Speed, Rotor Speed:
These channel types have optional "OK Voltage Checks" that will determine if the monitor will or will not report a Not OK status to the relay module due to a transducer voltage error.
Eccentricity: "Direct Channel Above 600 RPM" affects bypass and Not OK status.
3.3 Software Switches
Software switches for relay modules let you temporarily bypass or inhibit the relay module and channel functions. Set these switches on the Software Switches screen under the Utilities Option on the main screen of the Rack
Section 3 - Configuration Information Configuration Software. Switch settings take affect only after you press the Set button.
3.3.1 Configuration Mode
This module software switch allows you to configure the 16-Channel Relay Module (see Figure 3-3).
Module Switch Number Switch Name
1 Configuration Mode
Figure 3-3: Module Software Switches Screen
To configure a relay module, enable (⌧) this switch and set the key switch on the front of the RIM to the PROGRAM position. When downloading a configuration from the Rack Configuration Software, this switch will automatically be enabled and disabled by the Rack Configuration Software. If the connection to the rack is lost during the configuration process, use this switch to remove the module from Configuration Mode.
The module switch number is used in the Communication Gateway Module.
3.3.2 Bypass
When enabled (⌧), the channel will be turned off and not allow alarming (see Figure 3-4).
Channel Switch Number Switch Name
3500/33 16 Channel Relay Module Operation and Maintenance Manual
Figure 3-4: Channel Software Switches Screen
The channel switch number is used in the Communication Gateway Module.
Section 4 - Output Module Description
4. Output Module Description
This section describes the output module that is associated with the 16-Channel Relay Module. This section also describes how to use the connectors on the Relay Output Module and describes where to install each Output module.
4.1 16-Channel Relay Output Module
The 16-Channel Relay Output Module contains 16 sets of relay contacts (1 set for each channel). You can set up the module so that each channel (in groups of 4 channels) is Normally Energized or Normally De-energized. You must install the 16-Channel Relay Output Module behind the 16-Channel Relay Module (in a Rack Mount or a Panel Mount rack) or above the 16-Channel Relay Module (in a
Bulkhead rack). NE NDE RELAY MODE NDE NE 3 4 1 2
1. I/O module (front view) 2. I/O module (left side view)
3. Terminals for connecting to the single-pole, double-throw (SPDT) relays.
4. DIP switches for configuring the relays for Normally Energized (NE) or Normally De-Energized (NDE) operation. The numbers refer to relay channel groups. For example, CH1-4 corresponds to relay channels 1 through 4.
3500/33 16 Channel Relay Module Operation and Maintenance Manual 1 2 3 1. Screwdriver 2. Module cover 3. DIP Switch
Figure 4-2: Configuring the Normally Energized and Normally De-Energized Relays
CAUTION
The output module can carry high voltages while installed in the rack with power applied to
the rack. High voltages can shock or burn service personnel and damage the output module during the relay configuration process.
Remove power from the rack and remove the output module from rack before attempting to
configure the relays.
NOTE
Relay contacts are marked NC (Normally Closed), NO (Normally Open), and ARM (Armature). NC and NO define the state
of the relay contacts with no power applied to the relay coil (de-energized,
non-alarm state).
Section 4 - Output Module Description
1
2
3
1. No Power/ No Alarm (shelf state) 2. With Power/ No Alarm
3. With Power/ In Alarm
Figure 4-3: Normally Energized (NE) Relay States
2
3 1
1. No Power/ No Alarm (shelf state) 2. With Power/ No Alarm
3. With Power/ In Alarm
Figure 4-4: Normally De-Energized (NDE) Relay States
4.2 Wiring Euro Style Connectors
To remove a terminal block from its base, loosen the screws attaching the
terminal block to the base, grip the block firmly and pull, as shown in Figure 4-5. Do not pull the block out by its wires because this could loosen or damage the wires or connector.
3500/33 16 Channel Relay Module Operation and Maintenance Manual
Figure 4-5: Removing Terminal Block From a Typical 3500 Output Module
DANGER
High voltage may be present on the relay contacts or relay wiring. High voltage can result in shock, burns, or death. Use
proper isolation techniques and remove all power when working with the relays.
Refer to the 3500 Field Wiring Diagram Package for the recommended wiring. Do not remove more than 6 mm (0.25 in) of insulation from the wires.
Figure 4-6: Connnecting Wire to Relay Terminal Block
Section 5 - Maintenance
5. Maintenance
You cannot repair the boards and components inside of 3500 modules in the field. 3500 rack maintenance consists of testing module channels to verify that they are operating correctly. You should replace modules that are not operating correctly with a spare.
When performed properly, you may install the main module into or remove the modoule from the rack while power is applied to the rack. You should install or remove the relay output module only after removing the power to the rack. Refer to theRack Installation and Maintenance Manual (part number 129766-01) for the proper procedure.
This section shows how to verify the operation of the 3500/33 16-Channel Relay Module.
5.1 Verifying a 3500 Rack - Relay Module
The 3500 Monitoring System is a high precision instrument that requires no
calibration. You must, however, verify the functions of Relay Module channels at regular intervals. At each maintenance interval, we recommend that you use the procedures in this section to verify the operation of all active channels in the Relay Module.
Section Number
Topic Page
Number
5.1.1 Choosing a Maintenance Interval 21
5.1.2 Required Test Equipment 22
5.1.3 Typical Verification Test Setup 22
5.1.4 Using the Rack Configuration Software 23
5.1.5 Standard Relay Channels 24
5.1.1 Choosing a Maintenance Interval
Use the following approach to choose a maintenance interval:
• Start with an interval of one year and then shorten the interval if either of
the following conditions apply:
3500/33 16 Channel Relay Module Operation and Maintenance Manual
- The 3500 rack is operating in a harsh environment, such as in extreme temperature, high humidity, or in a corrosive atmosphere.
• At each interval, use the results of the previous verifications and ISO
Procedure 10012-1 1992(E) to adjust the interval.
5.1.2 Required Test Equipment
The test equipment you will need to simulate the inputs for the relay channel will depend on the type of monitor providing inputs to the Relay Alarm Drive Logic. You can identify this equipment under “Required Test Equipment” in the
Maintenance section of the specific monitor manual.
5.1.3 Typical Verification test setup
The following figure shows the typical test setup for verifying a Relay Module. The test equipment is used to simulate the transducer signal to selected monitors and the laptop computer is used to observe the output from the rack.
1. 3500 Rack 2. Test Equipment
3. RS-232 communications 4. Laptop Computer
Figure 5-1: Typical Test Setup
You can connect transducers to a 3500 rack in a number of ways. Depending on the wiring option for the I/O module of your monitor, connect the test equipment to the Monitor Module and Relay Module using one of the following methods:
Section 5 - Maintenance
1. Connect test equipment here. 2. Inputs
3. Monitor I/O Module (Internal Termination)
4. External Termination Block (Euro Style Connectors) 5. External Termination Block (Terminal Strip Connectors)
Figure 5-2: Test Setup Wiring Methods
1. Outputs
Figure 5-3: 16-Channel Relay Output Module
5.1.4 Using the Rack Configuration Software
3500/33 16 Channel Relay Module Operation and Maintenance Manual
parameters in the rack. To perform the test procedures in this section you must be familiar with the following features of the Rack Configuration Software to
• upload and save configuration files • display the Verification screen
TheRack Configuration and Test Utilities Guide (part number 129777-01) explains how to perform these operations.
NOTE
Save the original rack configuration before doing any maintenance or
troubleshooting procedures.
The Verification screen displays relay channel output from a 3500 rack as shown in Figure 5-4. Information such as Alarm Drive Logic, Channel Alarm State and Channel OK State are used to verify relay channels.
Figure 5-4: 3500 Rack Configuration Software Verification Screen
5.1.5 Standard Relay Channels
Verify relay channels by forcing alarms from the monitors that provide inputs for the Relay Alarm Drive Logic. When the logic is true, the Channel Alarm State will change to Alarm on the Verification screen and the alarm relay and front panel LED for that channel will change state. Verify only those channels that are active and configured.
To verify that a 16-Channel Relay channel is working correctly.
Section 5 - Maintenance 1. Run the Rack Configuration Software on the test computer.
2. ChooseVerification from the Utilities menu. A screen prompting for the slot and channel number of the relay to be tested will appear.
3. Choose the proper Slot number and Channel number and then click on the Verify button. The Verification screen will appear.
4. Verify that the Channel OK State status on the Relay Verification screen readsOK.
5. Use the Relay Verification screen to determine what inputs must be simulated.
6. Simulate the required Alarm Drive Logic inputs to cause the relay to change states.
For example, for a 3500 Rack with the following configuration:
Slot Number Module Type
1 Rack Interface Module
2 3500/42 – 4 Channel Monitor
3 3500/42 – 4 Channel Monitor
4 3500/42 - 4 Channel Monitor
5 3500/33 - 16-Channel Relay
and a relay channel with the following Alarm Drive Logic: ( S02C01A1 * S03C01A1 ) + S04C01A2
send test signals to the monitors in the rack to cause Slot 2 Channel 1 AND Slot 3 Channel 1 to be in Alert OR cause Slot 4 Channel 1 to be in Danger. 7. Verify that the Channel Alarm State status on the Relay Verification screen
changes to Alarm. Verify that the relay contacts change state and the front panel LED illuminates.
8. If the Relay channel does not respond correctly, check the inputs to ensure they meet the Alarm Drive Logic requirements. If the module still does not meet specifications, go to Section 5.1.6 (If a Channel Fails a Verification Test).
9. Select the next channel to be tested by using the Channel drop down list on the Verification screen. Repeat steps 4 through 8 to test the next relay channel.
3500/33 16 Channel Relay Module Operation and Maintenance Manual
5.1.6 If a Channel Fails a Verification Test
When handling or replacing circuit boards always be sure to adequately protect against damage from Electrostatic Discharge (ESD). Always wear a proper wrist strap and work on a grounded, conductive work surface.
1. Use the Rack Configuration Software to save the configuration for the module.
2. Replace the module with a spare. Refer to the installation section in the 3500 Monitoring System Rack Installation and Maintenance Manual (part number 129766-01).
3. Return the faulty module to Bently Nevada LLC for repair.
4. Use the Rack Configuration Software to download the configuration for the spare module.
5. Verify the operation of the spare.
5.2 16-Channel Relay Firmware Upgrade Procedure
Occasionally you may need to upgrade the original firmware that ships with the 3500/33 16-Channel Relay Module. The following instructions describe how to upgrade the existing firmware using the 3500 Configuration software. You must use the 3500 Rack Configuration Software to reconfigure the module after
upgrading its firmware.
Application Advisory
During the following procedure you must not not interrupt power to the rack
or remove the monitor that you are upgrading from the rack. Either of thse
events may cause the monitor to become inoperable.
1. Start the 3500 Configuration software and connect to the rack.
2. Upload and save the current configuration of the monitor, the upgrade process will erase any configuration in the monitor.
3. Under the Utilities menu option select Upgrade Firmware.
Section 5 - Maintenance
4. Select the module you wish to update and click on the OK button.
5. The software will request you to download the file. Select the file and click on the Open button.
6. The software will now download the file.
7. After the download completes, reload the configuration to the monitor. If the process fails (simultaneous flashing alarm LEDs), depending on the failure mode, the module may revert to its old code. See Section 6.2, “LED Fault Conditions” for an explanation of the failure mode. Under no
circumstances should you remove the module until it the download process finishes.
3500/33 16 Channel Relay Module Operation and Maintenance Manual
6. Troubleshooting
This section describes how to use the module self-test, the LEDs, and System Event List to troubleshoot a problem with the 16-Channel Relay Module or the Output module.
6.1 Self-test
To perform a self-test:
1. Connect a computer running the Rack Configuration Software to the 3500 rack (if needed).
2. SelectUtilities from the main screen of the Rack Configuration Software. 3. SelectSystem Events/Module Self-test from the Utilities menu.
4. Press theModule Self-test button on the System Events screen.
Application Advisory
Machinery protection will be lost while the module performs its self-test.
5. Select the slot that contains the relay module and press the OK button. The relay module will perform a full self-test and the software will display the System Events screen. Note that the list will not contain the results of the self-test.
6. Wait 30 seconds for the module to run a full self-test.
7. Press theLatest Events button. The software will update the System Events screen to include results of the self-test.
8. Verify if the relay module passed self-test. If the module failed the self test, refer to Section 6.3.
Section 6 - Troubleshooting
6.2 LED Fault Conditions
The following table shows how to use the LEDs to diagnose and correct problems with the 16-Channel Relay Module.
Table 6-1: OK and TX/RX LED Fault Condition Diagnostics
OK LED TX/RX Condition Solution
1 Hz 1 Hz Relay Module is not configured. Reconfigure the Relay Module.
5 Hz applicableNot
Relay Module or the Relay Output Module has detected an internal fault and are not OK.
Check the System Event List.
ON Flashing Relay Module and the Relay OutputModule are operating correctly. No action is required.
OFF Not
applicable
Relay Module is not operating
correctly. Replace the Relay Module.
Not applicable
Not flashing
Relay Module is not
communicating correctly or the Relay Module is not associated with any monitors in the rack that are communicating.
Check the System Event List or configure the alarm logic of at least one active relay channel.
Table 6-2: Alarm LED Fault Condition Diagnostics
Alarm LED Condition Solution
ON Channel is in Alarm. No action is required.
OFF Channel is not in Alarm. No action is required.
All LEDs Flashing (5 flashes in 3 seconds)
Failed firmware download due
to a recoverable error. Re-attempt firmware download.
All LEDs Flashing at (5 flashes in 5 seconds)
Failed firmware download due to a non-recoverable error.
Replace the relay module with a spare. Return the relay module to a Bently Nevada service center for repair.
3500/33 16 Channel Relay Module Operation and Maintenance Manual
6.3 System Event List Messages
This section describes the System Event List Messages that are entered by the 16-Channel Relay Module. Table 6-3 is an example of a System Event List Message.
Table 6-3: Example of a System Event List Message Sequence Number Event Information Event Number Class Event Date
(DDMMYY) Event Time
Event
Specific Slot 0000000123 EEPROM Memory
Failure 13 1 02/01/90 12:24:31:99 5 Sequence Number: This is the number of the event in the System Event List (for
example 123).
Event Information: This provides the name of the event (for example EEPROM Memory Failure).
Event Number: This identifies the specific event that occurred.
Class: This indicates the severity of the event. The following classes are available:
Table 6-4: System Event List Classes
Class Value Classification
0 Severe/fatal event
1 Potential problem event
2 Typical logged event
3 Reserved
Event Date: This specifies the date that the event occurred. Event Time: This specifies the time that the event occurred.
Event Specific: Provides additional information for the events that use this field.
Slot: This identifies the module with which the event is
associated. If the module is a half-height module in the upper slot or a full-height module, this field will be 0 to 15. If the module is a half-height module in the lower slot then this field will be 0L to 15L. For example, this field would identify a half-height module in the lower position of slot 5 as 5L.
Section 6 - Troubleshooting The 16-Channel Relay module may place following System Event List Messages, which are listed in numerical order. Events marked with a star (*)will not drive relays on the 16-Channel Relay Output Module. If you are unable to solve any problems contact your nearest Bently Nevada LLC office.
Flash Memory Failure Event Number: 11
Event Classification: Potential Problem
Action: Replace the Relay Module as soon as possible. * Internal Network Failure
Event Number: 30
Event Classification: Severe/Fatal Event
Action: Replace the Relay Module immediately. Resync Internal Network
Event Number: 31
Event Classification: Severe/Fatal Event
Action: Replace the Relay Module immediately. Device Not Communicating
Event Number: 32
Event Classification: Potential Problem
Action: Determine whether one of the following components is faulty:
• the Relay Module • the rack backplane
Device Is Communicating Event Number: 33
Event Classification: Potential Problem
Action: Determine whether one of the following components is faulty:
• the Relay Module • the rack backplane
3500/33 16 Channel Relay Module Operation and Maintenance Manual Fail Relay Coil Sense
Event Number: 55
Event Classification: Potential Problem
Action: Verify that the Relay Output Module is installed. If installed, determine whether one of the following components is faulty:
• the Relay Module
• the Relay Output Module
Pass Relay Coil Sense Event Number: 56
Event Classification: Potential Problem
Action: Determine whether one of the following components is faulty:
• the Relay Module
• the Relay Output Module
I/O Module Mismatch Event Number: 62
Event Classification: Potential Problem
Action: Determine whether one of the following components is faulty:
• the Relay Module
• the Relay Output Module
I/O Module Compatible Event Number: 63
Event Classification: Potential Problem
Action: Determine whether one of the following components is faulty:
• the Relay Module
• the Relay Output Module
Fail I/O Jumper Check (Fail read I/O module ID)
Event Number: 64
Section 6 - Troubleshooting Event Classification: Potential Problem
Action: Determine whether one of the following components is faulty:
• the Relay Module
• the Relay Output Module
Pass I/O Jumper Check (Pass read I/O module ID)
Event Number: 65
Event Classification: Potential Problem
Action: Determine whether one of the following components is faulty:
• the Relay Module
• the Relay Output Module
Fail Main Board +5V-A (Fail Main Board +5V - upper Power Supply) Event Number: 100
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, Determine whether one of the following components is faulty:
• the Relay Module
• the Power Supply installed in the upper slot
Pass Main Board +5V-A (Pass Main Board +5V - upper Power Supply) Event Number: 101
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Module
• the Power Supply installed in the upper slot
Fail Main Board +5V-B (Fail Main Board +5V - lower Power Supply) Event Number: 102
3500/33 16 Channel Relay Module Operation and Maintenance Manual Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Module
• the Power Supply installed in the lower slot
Pass Main Board +5V-B (Pass Main Board +5V - lower Power Supply) Event Number: 103
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Module
• the Power Supply installed in the lower slot
* Fail Main Board +5V-AB (Fail Main Board +5V - upper and lower Power Supplies)
Event Number: 104
Event Classification: Severe / Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
Pass Main Board +5V-AB (Pass Man Board +5V - upper and lower Power Supplies)
Event Number: 105
Event Classification: Severe / Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
Section 6 - Troubleshooting
• the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
* Fail Main Board +3.3V (Fail Main Board +3.3V Supply) Event Number: 162
Event Classification: Severe / Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
Pass Main Board +3.3V (Pass Man Board +3.3V Supply)
Event Number: 163
Event Classification: Severe / Fatal Event
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
Device Configured Event Number: 300
Event Classification: Typical logged event Action: No action required.
* Configuration Failure Event Number: 301
3500/33 16 Channel Relay Module Operation and Maintenance Manual Action: Replace the Relay Module immediately.
Configuration Failure Event Number: 301
Event Classification: Potential Problem
Action: Download a new configuration to the Relay Module. If the problem still exists, replace the Relay Module as soon as possible.
* Module Entered Cfig Mode Event Number: 305
Event Classification: Typical logged event Action: No action required.
Software Switches Reset Event Number: 305
Event Classification: Potential Problem
Action: Download the software switches to the Relay Module. If the software switches are not correct. replace the Relay Module as soon as possible.
Fail I/O Board +5V-AB (Fail OUTPUT Board +14V Supply)
Event Number: 390
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay OUTPUT Module • the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
Pass I/O Board +5V-AB (Pass OUTPUT Board +14V Supply)
Event Number: 391
Event Classification: Potential Problem
Section 6 - Troubleshooting Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Output Module • the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
Fail I/O Board +14V-AB (Fail OUTPUT Board +14V Supply) Event Number: 396
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay OUTPUT Module • the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
Pass I/O Board +14V-AB (Pass OUTPUT Board +14V Supply)
Event Number: 397
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Output Module • the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
Fail I/O Module DIP Sw (Fail Output Module DIP switch) Event Number: 398
3500/33 16 Channel Relay Module Operation and Maintenance Manual Event Classification: Potential Problem
Action: Verify that the Relay Output Module is installed. If the Relay Output Module is installed, replace the Relay Output Module as soon as possible.
I/O Module Detect Fault (Pass Output Module DIP switch – there was a detected fault that is no longer present)
Event Number: 399
Event Classification: Potential Problem
Action: Verify that the Relay Output Module is installed. If the Relay Output Module is installed, replace the Relay Output Module as soon as possible.
Pass Module Self-test Event Number: 410
Event Classification: Typical Logged Event Action: No action required.
Enabled Ch Bypass (Enabled Channel Bypass) Event Number: 416
Event Classification: Typical logged event Event Specific: Ch x
Action: No action required.
Disabled Ch Bypass (Disabled Channel Bypass) Event Number: 417
Event Classification: Typical logged event Event Specific: Ch x
Action: No action required.
Invalid Alm Drive Logic (Invalid Alarm Drive Logic) Event Number: 451
Event Classification: Severe/Fatal Event
Section 6 - Troubleshooting Action: Download a new configuration to the Relay Module. If the problem
still exists, replace the Relay Module as soon as possible. Fail Slot Id Test
Event Number: 461
Event Classification: Severe/Fatal Event
Action: Verify that the Relay Module is fully inserted in the rack. If the Relay Module is installed correctly, determine whether one of the
following components is faulty:
• the Relay Module • the rack backplane
Pass Slot Id Test
Event Number: 462
Event Classification: Severe/Fatal Event
Action: Verify that the Relay Module is fully inserted in the rack. If the Relay Module is installed correctly, determine whether one of the
following components is faulty:
• the Relay Module • the rack backplane
Fail I/O Board +15V-A (Fail Output Board +15V - upper Power Supply) Event Number: 554
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Output Module • the Relay Module
• the Power Supply installed in the upper slot
Pass I/O Board +15V-A (Pass Output Board +15V - upper Power Supply) Event Number: 555
3500/33 16 Channel Relay Module Operation and Maintenance Manual
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Output Module • the Relay Module
• the Power Supply installed in the upper slot
Fail I/O Board +15V-B (Fail Output Board +15V - lower Power Supply) Event Number: 556
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay Output Module • the Relay Module
• the Power Supply installed in the lower slot
Pass I/O Board +15V-B (Pass OUTPUT Board +15V - lower Power Supply) Event Number: 557
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay OUTPUT Module • the Relay Module
• the Power Supply installed in the lower slot
Fail I/O Board +15V-AB (Fail OUTPUT Board +15V - upper and lower Power Supplies)
Event Number: 558
Event Classification: Potential Problem
Section 6 - Troubleshooting Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the following components is faulty:
• the Relay OUTPUT Module • the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
Pass I/O Board +15V-AB (Pass Output Board +15V - upper and lower Power Supplies)
Event Number: 559
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem. If the problem is not caused by noise determine whether one of the following components is faulty:
• the Relay Output Module • the Relay Module
• the Power Supply installed in the lower slot • the Power Supply installed in the upper slot
6.4 Alarm Event List Messages
The 16-Channel Relay Module may place the following messages in the Alarm Event List.
Table 6-5: Alarm Event List Messages and Their Causes
Alarm Event List Message When the message will occur
Entered Not OK Module went Not OK
Left Not OK Module returned to the OK state
Relay Activated Condition for driving the relay channel met
3500/33 16 Channel Relay Module Operation and Maintenance Manual
7. Ordering Information
This section contains the ordering information for the 3500/33 16-Channel Relay Module.
7.1 16-Channel Relay Module
Part number 3500/33- AXX - BXX A:Output Module
0 1 16-Channel Relay Output Module B: Agency Approval Option
0 0 None
0 1 CSA-NRTL/C
7.2 Spares
149968
16-Channel Relay Control Module 149992-01
16-Channel Relay Output Module 00580453
Connector Header, 16-position 162291-01
3500/33 Relay Module Manual 04425545
Grounding Wrist Strap (single use only)
Section 8 - Specifications
8. Specifications
This section contains the specifications for the 3500/33 16-Channel Relay Module.
8.1 Relays
Type
Single-pole, double-throw (SPDT) relays Environmental sealing Epoxy-sealed Arc suppressors 250 Vrms, installed as standard. Contact Ratings (resistive load)
Max switched power
DC: 160 W AC: 1500 VA Min switched current 100 mA @ 12 Vdc Max switched current 6 A Max switched voltage DC: 300 Vdc AC: 400 Vac Contact Life 100,000 @ 5 A, 24 Vdc or 250 Vac
3500/33 16 Channel Relay Module Operation and Maintenance Manual
Operation
Groups of four channels are switch selectable for Normally De-energized or Normally Energized.
8.2 Environmental Limits
Temperature -30 ºC to 65 ºC (-22 ºF to 150 ºF) operating -40 ºC to 85 ºC (-40 ºC to 185 ºC) storage Humidity 95% non-condensing8.3 Mechanical
Impact 10 g’s for 11 ms ShippingPer mil Std 81D – Category G Equipment Vibration Sinusoidal, 3 g at 5 to 100 Hz
8.4 Electromagnetic Compatibility
EN50081-2 Radiated Emissions EN 55011, Class A Conducted Emissions EN 55011, Class A 44Section 8 - Specifications EN50082-2 Electrostatic Discharge EN 61000-4-2, Criteria B Radiated Susceptibility ENV 50140, Criteria A Conducted Susceptibility ENV 50141, Criteria A Electrical Fast Transient EN 61000-4-4, Criteria B Surge Capability EN 61000-4-5, Criteria B Magnetic Field EN 61000-4-8, Criteria A Power Supply Dip
EN 61000-4-11, Criteria B Radio Telephone
ENV 50204, Criteria B Low Voltage Directives
Safety
Requirements
EN61010-01
8.5 Approvals
CSA-NRTL/C