• No results found

Power System Protection

N/A
N/A
Protected

Academic year: 2021

Share "Power System Protection"

Copied!
37
0
0

Loading.... (view fulltext now)

Full text

(1)

Power System Protection

Dr. Lionel R. Orama Exclusa, PE Week 1

(2)

Jan 18/2006 Copyright L.R. Orama 2006 2

Philosophy of Protective Relaying

Readings-Mason Chapter 1 • Relay function

• What exactly is a relay? • CT’s and PT’s

• Abnormal conditions-faults

• Desirable relay characteristics • Zones of protection

(3)

Relay function

• Causes fast disconnection of equipment from power system during abnormal

conditions

– Minimizes damage

– Minimizes effects on the system operation – Maximizes power transfer

(4)

Copyright L.R. Orama 2006 4

Relay function

(5)

What exactly is a relay?

• Measuring device-receives a signal from the Power System (PS) & determines if the condition is abnormal

• Control device-for abnormal conditions, it signals Circuit Breakers (CB) to

disconnect equipment

– It kind of “relays” a signal from the PS to the CB – Relay & CB is a system protection team

(6)

Copyright L.R. Orama 2006 6

(7)
(8)

Copyright L.R. Orama 2006 8

(9)

Current Transformers (CT’s)

• Device that produces current proportional to current in the power system conductor

• Ideal CT has current of:

• Rated ICT is aprox. 5A, typically (called CT secondary current) CT SYS CT N I I =

(10)

Copyright L.R. Orama 2006 10

Current Transformers (CT’s)

400 20005 200 1000:5 120 600:5 80 400:5 40 200:5 20 100:5 10 50:5 Turns Current Common ratios

(11)

Potential Transformers (PT’s)

• Device that produces voltage proportional to voltage in the power system bus

• Ideal PT has voltage of:

• Rated VPT is aprox. 120V, typically (called PT secondary voltage) 1 2 N N V VPT = SYS

(12)

Jan 20/2006 Copyright L.R. Orama 2006 12

(13)

Simple Contacts Diagram

• Short hand notation for the trip circuit

• Control Relaying & Instrumentation

(14)

Copyright L.R. Orama 2006 14

Relay Contacts

• “a” Contact

– Open when relay that controls it is not picked up, or when CB that controls it is open

– Closed when relay that controls it is picked up, or when CB that controls it is closed

• “b” Contact

– Closed when relay that controls it is not picked up, or when CB that

controls it is open

– Open when relay that controls it is picked up, or when CB that controls it closed

(15)

Contacts

• A relay is said to be picked up when its:

– Its “a” contacts are closed or

(16)

Copyright L.R. Orama 2006 16

Faults (Short Circuits)

• Most common type of abnormal condition • Often Abnormally high currents flow IF>>IL • Flow of current in a path not intended for it • To interrupt IF, circuit must be opened

(17)

Faults (Short Circuits)

• Cause high current

– mechanical stress

• Cause high temperature arcs

– destroy equipment, cause fires

• Alter system voltage

• Cause system unbalance • Block the flow of power

• Cause generator overspeed

(18)

Copyright L.R. Orama 2006 18

Fault Current Interruption

(19)

Desirable Relay Characteristics

• Speed (time to make decision 1/60sec)

– Minimizes damage from current

– Maximizes power transfer and stability

• Security

– Relay should not cause CB to open during normal conditions

• Dependability (reliability)

– Relay should cause CB to open during abnormal operation

(20)

Copyright L.R. Orama 2006 20

Desirable Relay Characteristics

• Sensitivity

– Ability to detect all faults for the expected limiting system and fault conditions

• Selectivity

– Ability to discriminate between faults internal and external to its intended zone of protection

(21)

Primary & Backup Protection

• Relays, CB’s, CT’s & PT’s located at substations • Substation is a point of – Interconnection – Switching – Voltage transformation

(22)

Jan 23/2006 Copyright L.R. Orama 2006 22

Primary & Backup Protection

• Every equipment should be protected by at least two independent protection

systems

• Equipment

– Lines, busses, transformers, generators

• Protection system

(23)

Primary Protection

• Primary

– To do it, zones are drawn on the system’s one-line diagram

– Zones are defined by CT location and include equipment & CB’s that isolate equipment

(24)

Copyright L.R. Orama 2006 24

Primary Protection

• Primary protective zones

– CB’s located in connection to each PS equipment

– Zones configured so the fault within the zone causes all CB’s in the zone to open – CB’s open simultaneously &

instantaneously (no intentional delay) – If primary zone is

successful, minimum effect on the system (power

(25)

Primary Protection

• Primary protective zones – Zones defined by the CT’s located in the bushings of the CB’s – Zones overlap to avoid uncovered areas and CB

(26)

Copyright L.R. Orama 2006 26

Primary & Backup Protection

Causes of Relay Failure • CT’s and circuits

• PT’s and circuits • Loss of DC supply

– Short circuit – Open circuit

– Failure of auxiliary switches

(27)

Primary & Backup Protection

Causes of CB failure • Loss of DC supply • Open trip coil

• Short circuit trip coil • Mechanical failure

(28)

Copyright L.R. Orama 2006 28

Backup Protection

• Provided in case of:

– Primary relay failure – Circuit breaker failure

• Ideally primary & backup must be independent

– Relay, CB’s, CT’s, PT’s

– However, duplicity of CB’s is not practical & causes other problems

• Backup is slower than primary

• Opens more CB’s than necessary to clear a fault • Provides primary protection when primary

(29)

Backup Protection

Types of backup protection • Remote backup

– Clears fault one substation away from where the failure has occured

• Local backup

– Clears fault in the same substation where the fault has occured

(30)

Copyright L.R. Orama 2006 30

Remote Backup

• CB’s P and O opens • CB M stay closed

• Then B, C and I has to open • Load is lost in this case

(31)

Remote Backup

• Trips more system than necessary to clear the fault

• Long backup times from 50-60 cycles (0.8-1.0 sec)

• Difficult to set remote relays • Initially, more economical

(32)

Copyright L.R. Orama 2006 32

Local Backup

• Primary relay op. & energizes timer • If CB relays

remain picked up & timer times out

– Opens all CB’s on the bus (trips all CB’s)

(33)

Local Backup

• J opens • H closed

(34)

Copyright L.R. Orama 2006 34

Local Backup

• P and O open • M closed • G and I opens • L trips locally • I tripped by communicated signal (Transfer Trip) • A special kind of backup keeps Z closed

(35)

Local Backup

When a CB does not work

• Trips least amount of system in clearing a fault

• Fastest backup times are 9-20 cycles (0.15-0.33 sec)

• Simple relay settings

(36)

Copyright L.R. Orama 2006 36

Remote vs. Local Backup

• Remote

(37)

Remote vs. Local Backup

• Remote

References

Related documents

q) Validation Service on Mobile Device enforces result format r) Validation Service passes result (or error) to Client Application. s) Loop to M

Upon successful detection of the video properties - whether the video mono or stereo and/or whether the video is a simple quadrangular video, 180-degree video, or 360-degree video,

Programda Kvapil' in149 bir yazısı, iyi bir yönetmenin (ama oyunda yönetmenlik Reinhardt'a150 öykünmekten öteye geçmiyordu) kötü bir yapıtı güç­ lü bir dramatik

6 For example, the Council asked the ALJ to consider evidence in the record, a December 3, 2009 email from the enrollee, indicating that the enrollee had received new,

The following policy recommendations are based on the results of the research carried out in Romania, Russia and Ukraine but would also have broad relevance to

Проведено моніторинг надходжень податку на прибуток підприємств до Зведеного бюджету України і оцінювання фіскальної ефективності та регулюючого потенціалу податку

HF Side scan and camera surveys of Haig Fras with surfacing between each mission section to monitor the health of the main logger and camera logger... Cruise

A CSI Workshop shall be held, prior to contract time beginning, for the Contractor and Department to discuss potential CSI Proposals.. The purpose of the workshop is to discuss