Power System Protection
Dr. Lionel R. Orama Exclusa, PE Week 1
Jan 18/2006 Copyright L.R. Orama 2006 2
Philosophy of Protective Relaying
Readings-Mason Chapter 1 • Relay function
• What exactly is a relay? • CT’s and PT’s
• Abnormal conditions-faults
• Desirable relay characteristics • Zones of protection
Relay function
• Causes fast disconnection of equipment from power system during abnormal
conditions
– Minimizes damage
– Minimizes effects on the system operation – Maximizes power transfer
Copyright L.R. Orama 2006 4
Relay function
What exactly is a relay?
• Measuring device-receives a signal from the Power System (PS) & determines if the condition is abnormal
• Control device-for abnormal conditions, it signals Circuit Breakers (CB) to
disconnect equipment
– It kind of “relays” a signal from the PS to the CB – Relay & CB is a system protection team
Copyright L.R. Orama 2006 6
Copyright L.R. Orama 2006 8
Current Transformers (CT’s)
• Device that produces current proportional to current in the power system conductor
• Ideal CT has current of:
• Rated ICT is aprox. 5A, typically (called CT secondary current) CT SYS CT N I I =
Copyright L.R. Orama 2006 10
Current Transformers (CT’s)
400 20005 200 1000:5 120 600:5 80 400:5 40 200:5 20 100:5 10 50:5 Turns Current Common ratiosPotential Transformers (PT’s)
• Device that produces voltage proportional to voltage in the power system bus
• Ideal PT has voltage of:
• Rated VPT is aprox. 120V, typically (called PT secondary voltage) 1 2 N N V VPT = SYS
Jan 20/2006 Copyright L.R. Orama 2006 12
Simple Contacts Diagram
• Short hand notation for the trip circuit
• Control Relaying & Instrumentation
Copyright L.R. Orama 2006 14
Relay Contacts
• “a” Contact
– Open when relay that controls it is not picked up, or when CB that controls it is open
– Closed when relay that controls it is picked up, or when CB that controls it is closed
• “b” Contact
– Closed when relay that controls it is not picked up, or when CB that
controls it is open
– Open when relay that controls it is picked up, or when CB that controls it closed
Contacts
• A relay is said to be picked up when its:
– Its “a” contacts are closed or
Copyright L.R. Orama 2006 16
Faults (Short Circuits)
• Most common type of abnormal condition • Often Abnormally high currents flow IF>>IL • Flow of current in a path not intended for it • To interrupt IF, circuit must be opened
Faults (Short Circuits)
• Cause high current
– mechanical stress
• Cause high temperature arcs
– destroy equipment, cause fires
• Alter system voltage
• Cause system unbalance • Block the flow of power
• Cause generator overspeed
Copyright L.R. Orama 2006 18
Fault Current Interruption
Desirable Relay Characteristics
• Speed (time to make decision 1/60sec)
– Minimizes damage from current
– Maximizes power transfer and stability
• Security
– Relay should not cause CB to open during normal conditions
• Dependability (reliability)
– Relay should cause CB to open during abnormal operation
Copyright L.R. Orama 2006 20
Desirable Relay Characteristics
• Sensitivity
– Ability to detect all faults for the expected limiting system and fault conditions
• Selectivity
– Ability to discriminate between faults internal and external to its intended zone of protection
Primary & Backup Protection
• Relays, CB’s, CT’s & PT’s located at substations • Substation is a point of – Interconnection – Switching – Voltage transformationJan 23/2006 Copyright L.R. Orama 2006 22
Primary & Backup Protection
• Every equipment should be protected by at least two independent protection
systems
• Equipment
– Lines, busses, transformers, generators
• Protection system
Primary Protection
• Primary
– To do it, zones are drawn on the system’s one-line diagram
– Zones are defined by CT location and include equipment & CB’s that isolate equipment
Copyright L.R. Orama 2006 24
Primary Protection
• Primary protective zones
– CB’s located in connection to each PS equipment
– Zones configured so the fault within the zone causes all CB’s in the zone to open – CB’s open simultaneously &
instantaneously (no intentional delay) – If primary zone is
successful, minimum effect on the system (power
Primary Protection
• Primary protective zones – Zones defined by the CT’s located in the bushings of the CB’s – Zones overlap to avoid uncovered areas and CBCopyright L.R. Orama 2006 26
Primary & Backup Protection
Causes of Relay Failure • CT’s and circuits
• PT’s and circuits • Loss of DC supply
– Short circuit – Open circuit
– Failure of auxiliary switches
Primary & Backup Protection
Causes of CB failure • Loss of DC supply • Open trip coil
• Short circuit trip coil • Mechanical failure
Copyright L.R. Orama 2006 28
Backup Protection
• Provided in case of:
– Primary relay failure – Circuit breaker failure
• Ideally primary & backup must be independent
– Relay, CB’s, CT’s, PT’s
– However, duplicity of CB’s is not practical & causes other problems
• Backup is slower than primary
• Opens more CB’s than necessary to clear a fault • Provides primary protection when primary
Backup Protection
Types of backup protection • Remote backup
– Clears fault one substation away from where the failure has occured
• Local backup
– Clears fault in the same substation where the fault has occured
Copyright L.R. Orama 2006 30
Remote Backup
• CB’s P and O opens • CB M stay closed
• Then B, C and I has to open • Load is lost in this case
Remote Backup
• Trips more system than necessary to clear the fault
• Long backup times from 50-60 cycles (0.8-1.0 sec)
• Difficult to set remote relays • Initially, more economical
Copyright L.R. Orama 2006 32
Local Backup
• Primary relay op. & energizes timer • If CB relays
remain picked up & timer times out
– Opens all CB’s on the bus (trips all CB’s)
Local Backup
• J opens • H closed
Copyright L.R. Orama 2006 34
Local Backup
• P and O open • M closed • G and I opens • L trips locally • I tripped by communicated signal (Transfer Trip) • A special kind of backup keeps Z closedLocal Backup
When a CB does not work
• Trips least amount of system in clearing a fault
• Fastest backup times are 9-20 cycles (0.15-0.33 sec)
• Simple relay settings
Copyright L.R. Orama 2006 36
Remote vs. Local Backup
• Remote
Remote vs. Local Backup
• Remote