Super Solution
Super Solution
Low voltage
circuit breakers
Susol L
V
cir
cuit br
eakers
Overview
Electrical characteristics
Trip units
Accessories
Technical information
Characteristics curves
Overall dimensions
4
10
11
12
19
20
22
Contents
Contents
■
Design for technical strong point: The Susol MCCB
SuSol Series MCCB is available forworld best breaking capacity up to
150kA, and MS is seal structure for hidden electricity Arc.
SuSol product represents simultaneously simple and complicated
design for using cut diamond motive to emphasis on the hardness of
industrial product.
And we applied the identity of product image by designing same concept
MCCB and MS which is installed to cubicle.
SuSol Series acquire the competitive power through getting the picking
up GD product and wining IF Design Award.
Super
Performance
Super
Breaking capacity
Super
Optimum coordination
Super
Extensive applications
TE series
New member of Susol MCCBs
New borning of 160AF
The fifth frame TE100, TE160
Small, but Big benifit
More compact and less cost
TE100
In : 16~100A (fixed )
Icu : 37kA(S), 50kA(N), Ics=Icu
3 and 4 pole
76(W) x 130(H) x 82mm(D)
TE160
In : 100~160A (fixed or thermally adjustable)
Icu : 37kA(S), 50kA(N), Ics=Icu
3 and 4 pole
TE100/160
In 16~160A
Icu : 37kA(S), 50kA(N)
Ics=Icu
76(W) x 130(H) x 82mm(D)
Susol TD, TS, TE circuit breakers are rated from 16 to
800 amperes and are available in four frame sizes.
MCCB
TS800N TS800H TS800L 150kA TS630N TS630H TS630L TS400N TS400H TS400L TS250N TS250H TS250L TS160N TD160N TS160H TD160H TS160L TD160L 100kA 85kA 65kA 50kA 37kA 100A 160A 250A 400A 630A 800ABreaking capacity Icu at 380 / 415V (kA)
Rated current, In (A)
50kA
37kA
85kA
100kA
65kA
150kA
TS100N TD100N TE160STE100S TE160N TE100N TS100H TD100H TS100L TD100LIn 700, 800A
Icu: 65kA(N), 100kA(H), 150kA(L)
Ics=Icu
210(W) x 320(H) x 135mm(D)
TS800
TS400/630
TS100/160/250
In 300~630A
Icu: 65kA(N), 85kA(H), 150kA(L)
Ics=Icu
140(W) x 260(H) x 110mm(D)
In 40~250A
Icu: 50kA(N), 85kA(H), 150kA(L)
Ics=Icu
105(W) x 160(H) x 86mm(D)
Super Performance
28 models in 5 frames
TD100/160
In 16~160A
Icu : 50kA(N), 85kA(H), 150kA(L)
Ics=Icu
MCCB
Flexibility through modularity
Susol series offer various and compatible accessories which are providing
simple installation and easy upgrading of the circuit breaker. Harmonization
of the accessories allows stock reduction and greater service flexibility.
� � � � �
�
� � � � � � � ��
Circuit breaker
�
Insulation barrier
�
Terminal cover(short, long)
�
Connection terminals
�
Direct rotary handle
�
Extended rotary handle
�
Electrical auxiliaries
�
Mechanicla interlock device
Electrical characteristics
10
TE100
TE160
Frame size [AF] Rated current In [A] No. of poles
Rated operational AC [V] voltage, Ue DC [V] Rated impulse withstand voltage, Ui [V] Rated ultimate short-circuit breaking capacity, Icu
AC 50/60Hz 220/240V [kA] 380/415V [kA] 440/460V [kA] 480/500V [kA] 600/690V [kA] DC 250V [kA] DC(2poles in series) 500V [kA] Rated service breaking capacity, Ics [%Icu] Rated ultimate short-circuit making capacity, Icm
AC 50/60Hz 220/240V [kA] 380/415V [kA] 440/460V [kA] 480/500V [kA] 600/690V [kA] Category of utilization Isolation behavior Trip unit(release) Thermal magnetic
●fixed-thermal, fixed-magnetic FTU
●adjustable-thermal, fixed-magnetic FMU
●adjustable-thermal, adjustable-magnetic ATU
●magnetic only MTU Electronic
●LSI ETS
●LSI ETM Option Earth-fault protection, lg
Zone selective interlocking, 'ZSI Ammeter
Communication
Earth-leakage protection module Connection Fixed front-connection
rear-connection Plug-in front-connection rear-connection
Mechanical Life [operations] Electrical life @ 415V AC [operations] Basic dimensions, WxHxD 3-pole [mm] (front connection) 4-pole [mm] Weight 3-pole [kg] (front connection) 4-pole [kg] Reference standard 100 160 16~100 100,125,160 3,4 3,4 690 690 500 500 8 8 S N S N 50 85 50 85 37 50 37 50 25 37 25 37 18 25 18 25 6 8 6 8 37 50 37 50 37 50 37 50 100% 100% 100% 100% 105 187 105 187 77.7 105 77.7 105 52.5 77.7 52.5 77.7 36 52.5 36 52.5 9.2 13.6 9.2 13.6 A A ● ● ● ● ● ● - -- -- -- -- -- -- -- -- -● ● ● ● - -- -25000 25000 10000 10000 76x130x82 76x130x82 101x130x82 101x130x82 1.05 1.05 1.35 1.35 IEC60947-2 IEC60947-2
Trip units
Thermal magnetic trip units
Overview
Characteristics
FTU
�Fixed thermal
16A ... 160A rated currents
�Fixed magnetic
400A ... 1600A tripping currents
Fixed thermal, fixed magnetic trip units
Im=1600A
160A
TE160 FTU
Ir Im
FMU
�Adjustable thermal 16A ... 160A rated currents Adjustable : 0.8~1×In
�Fixed magnetic
400A ... 1600A tripping currents
Adjustable thermal, fixed magnetic trip units
160A
Im=1600A
TE160 FMU
Setting details
TE160 In Thermal setting Ir[A] Magnetic setting Im[A] Neutral protection
[A] 4P4T 4P3T 16 16 400 =Ir =Im 20 20 400 =Ir =Im 25 25 400 ±20% =Ir =Im 32 32 400 =Ir =Im 40 40 400 =Ir =Im
FTU 50 Ir = In 50 500 =Ir =Im
63 63 630 =Ir =Im
80 80 800
10xIn ±20% =Ir =Im 100 100 1000 =Ir =Im 125 125 1250 =Ir =Im 160 160 1600 =Ir =Im 16 12.8 16 400 =Ir =Im 20 16 20 400 =Ir =Im 25 20 25 400 ±20% =Ir =Im 32 25.6 32 400 =Ir =Im 40 32 40 400 =Ir =Im FMU 50 Ir = 0.8-1In 40 50 500 =Ir =Im 63 50.4 63 630 =Ir =Im 80 64 80 800
10xIn ±20% =Ir =Im 100 80 100 1000 =Ir =Im 125 100 125 1250 =Ir =Im 160 128 160 1600 =Ir =Im no protection no protection
Accessories
12
Auxiliary switch (AX)
Auxiliary switch is for applications requiring remote “ON”and “OFF”indication. Each switch contains two contacts having a common connection.
One is open and the other closed when the circuit breaker is open, and viceversa.
Alarm switch (AL)
Alarm switches offer provisions for immediate audio or visual indication of a tripped breaker due to overload, short circuit, shunt trip, or undervoltage release conditions.
They are particularly useful in automated plants where operators must be signaled about changes in the electrical distribution system. This switch features a closed contact when the circuit breaker is tripped automatically. In other words, this switch does not function when the breaker is operated manually.
Its contact is open when the circuit breaker is reset.
Combination switch (AX+AL)
It consists of one auxiliary switch (AX) and one alarm switch (AL) in a body to connect into the same position of
the breaker.
Contact
Rating
Auxiliary and Alarm switch
MCCB
AX
AL
ON OFF TRIP
Conventional thermal current, Ith Rated operational current, Ie
AC 50/60Hz DC 5A Voltage, Ue 125V 250V 500V 30V 125V 250V Current, Ie
Resistive load Inductive load
5 3 3 2 - -4 3 0.4 0.4 0.2 0.2
Accessories
Shunt trip, SHT
The shunt trip opens the mechanism in response to an externally applied voltage signal. The releases include coil clearing contacts that automatically clear the signal circuit when the mechanism has tripped.
The shunt release can be installed in the right accessory compartment of the MCCBs.
- Range of operational voltage AC : 0.7~1.1Vn, DC : 0.8~1.1Vn - Frequency(Only AC) : 45Hz ~ 65 Hz
Rating
Voltage
Max.opening time
Tightening torque of terminal screw AC/DC 12V AC/DC 24V AC/DC 48V AC/DC 60V AC/DC 100~130V AC/DC 200~250V AC 380~450V AC 440~500V AC (VA) 0.35 0.64 1.09 1.2 0.73 1.21 1.67 1.68 Power consumption DC (W) 0.36 0.65 1.1 1.22 0.75 1.35 -50ms (max.) 8.2 kgf∙cm mA 30 27 23 20 5.8 5.4 3.8 3.5 Control voltage, Ue
Accessories
14
The undervoltage release automatically opens a circuit breaker when voltage drops to a value ranging between 20% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be re-closed again until the voltage returns to 85% of line voltage.
Continuously energized, the undervoltage release must be operating before the circuit breaker can be closed. The undervoltage release can be easily installed in the right accessory compartment of the MCCBs.
- Range of tripping voltage: 0.2 ~ 0.7Vn
- MCCB making is possible voltage: 0.85Vn (Exceed) - Frequency (Only AC): 45Hz ~ 65Hz
Rating
Maximum possibilities
Undervoltage release, UVT
Voltage
Max.opening time
Tightening torque of terminal screw Operating voltage range AC/DC 24V AC/DC 48V AC/DC 100~110V AC/DC 200~220V AC 380~440V AC 440~480V Trip Reset/Closing AC (VA) 0.64 1.09 0.73 1.21 1.67 1.68 Power consumption DC (W) 0.65 1.1 0.75 1.35 -50ms (max.) 8.2 kgf∙cm 20~70% Vn ≥0.85Vn mA 27 23 5.8 5.4 3.8 3.5 Control voltage, Ue Left-hand seat AX 1 AL 1 AX 1 Right-hand seat AL 1 SHT/UVT 1 TE160 3/4P Position Type
Accessories
Rotary handles
The rotary handle operating mechanism is available in either the direct version or in the extended version on the compartment door.
It is always fitted with a compartment door lock and on a request it can be supplied with a key lock in the open position.
Direct rotary handles
MCCB Rotary handle TE160 DH1E
Extended rotary handles
MCCB Rotary handle TE160 EH1E
Degree of protections
Type Degree of protection IP DH1E The acess probe of 1.0mm diameter IP40
shall not penetrate
EH1E Totally protected against ingress of IP55 dust and water jets from any direction
Accessories
16
Terminals
Front connection
Extended terminal
- As an optional part of circuit breaker - Can increase the pitch of the terminals
Flat terminals
MCCB Pole Type Feature
TE100 3P ET13E
TE160 4P ET14E
Rear connection
Rear connection terminals are used to adapt Susol TE circuit breakers to switchboards or other application that require rear connection.
These can be connected directly to circuit breakers without any modification.
MCCB Pole Type Feature
TE100 3P RTF13
Accessories
Insulation
Insulation by barrier
These allow the insulation characteristics between the phases at the connections to be increased.
They are mounted from the front, even with the circuit-breaker already installed, inserting them into the corresponding slots.
They are incompatible with both the insulating terminal covers.
It is possible to mount the phase separating partitions between two circuit-breakers side by side.
Insulation by terminal cover
Insulation terminal cover
The terminal covers are applied to the circuit-breaker to prevent accidental contact with live parts and thereby guarantee protection against direct contacts.
Two types by length are available:
Short type covers, ITS
�IP40 degree of protection
�For fixed circuit-breakers with rear terminals and for moving parts of plug-in Long type covers, ITL
�IP40 degree of protection
�For fixed circuit-breakers with front, front extended, front for cables terminals.
Type Applied MCCB Set quantity 3P 4P B13C TE100, TE160
2pcs 4pcs
Type Terminal cover
Frame type pole Long type Short type TE100, TE160
3P ITL13E ITS13E 4P ITL14E ITS14E Short type covers
Accessories
18
Mechanical interlocking device
The mechanical interlock (MIT) can be applied on the front of two breakers mounted side by side, in either the 3-pole or 4-pole version and prevents simultaneous closing of the two breakers.
Fixing is carried out directly on the cover of the breakers.
The front interlocking plate allows installation of a padlock in order to fix the position. (possibility of locking in the O-O position as well)
This mechanical interlocking device is very useful and simple for consisting of manual source-changeover system.
Interlock
Note) Terminal covers do not use with the interlock.
Mechanical Interlock (Padlocks are not supplied)
Left MCCB: ON/OFF is possible Right MCCB: Off lock
Operation
Left MCCB: Off lock
Right MCCB: ON/OFF is possible
Interlock handle
Interlock bar
Both MCCBs are of locked
MCCB
Frame type pole Interlock TE100, TE160
3P MIT13E 4P MIT14E
Technical information
Power dissipation / Resistance
Susol TE series MCCB with thermal-magnetic trip units
AF TE100 TE160
Rationg (A) 16 20 25 32 40 50 63 80 100 125 160 R (MΪ ) 8.5 8.5 6.4 2.6 2.5 1.8 1.4 1.2 0.8 0.6 0.5 Fixed MCCB Watt single pole 2.2 3.4 4.0 2.7 4.0 4.5 5.6 7.7 8.0 9.4 12.8 Watt three pole 6.5 10.2 12.0 8.0 12.0 13.5 16.7 23.0 24.0 28.1 38.4
Characteristics curves
20
Thermal-Magnetic trip units
TE100
FTU
FMU
16~100A
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TE160
FTU
FMU
100~160A
Overall dimensions
22
TE100/TE160
110 25 M4 OR ∅5 110 47 83 47 83 25 78 103 CL CL CL CL CL CL CL CLPanel drilling
Front panel cutting
[mm] 21.5 70 82 89.5 L L W T 130 110 81 45 25 25 50 25 101 50 76 CL CL
Wire size Min 2.5mm
2 Max. 70mm2 L(mm) 17.5 W(mm) ≤13.5 T(mm) ≤6 Torque ≤8Nm
Overall dimensions
Direct rotary handle
DH1E for TE100/TE160
114.9 11 0 101.5 77.5 68.2 t 1.2~3.2 121 92.1
OFF
4-∅5Overall dimensions
24
Extended rotary handle
EH1E for TE100/TE160
min 165 t 1.2~3.2 max 589(shaft 459mm) 47 47
OFF
2-∅6 ∅53Overall dimensions
Mechanical interlocking device
MIT13E, MIT14E
82 47 83 70 E C D E C ∅4~∅6 30mmOverall dimensions
26
Terminal cover
ITS13E, ITS14E
ITL13E, ITL14E
69.5 150 24.5 76 101 76 69.5 64.5 230 101Overall dimensions
Rear connection
RTF13, RTF14
135 18 8 70 130 8N�m (82kgf�cm) 8N�m (82kgf�cm) 150 13.8 25 8 42.5 92.5 25 25 ∅7Overall dimensions
28
Extended terminal
ET13E, ET14E
190 170 25 76 130 81 5 21.5 70 82 45 50 16 50 5Max 16Ma x 8N�m (82kgf�cm) 8N�m (82kgf�cm)Memo
�
�
HEAD OFFICE
LS Tower 1026-6, Hogye-dong, Dongan-gu,
Anyang-si, Gyeonggi-do 431-848, Korea
Tel. (82-2)2034-4887, 4873, 4918, 4148
Fax. (82-2)2034-4648 http://www.lsis.biz
�
�
Cheong-Ju Plant
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,
Cheong Ju, 361-720, Korea
Tel. (82-43)261-6001 Fax. (82-43)261-6410
Specifications in this catalog are subject to change without notice due to continuous products development and improvement.
20090901 / STAFF
ⓒ2009.9 LS Industrial Systems Co.,Ltd. All rights reserved.