General Line Protection
General Line Protection
General Line Protection
General Line Protection
1.
1. Distance relays
Distance relays -
- basics
basics
2.
2. Operating
Operating characteristics
characteristics
3.
3. Effect
Effect of
of parallel
parallel line
line
4.
4. Phase
Phase selection
selection
5.
5. Power
Power swing
swing blocking
blocking
6.
6. Communication
Communication scheme
scheme
7.
7. Switch
Switch on
on to
to fault
fault
8.
8. Weak
Weak end
end infeed
infeed
9.
9. Supervision
Supervision fuse
fuse failure
failure
10. System supervision.
10. System supervision.
11. Fault locator
11. Fault locator
12. Stub protection
12. Stub protection
13. Earth fault protection
13. Earth fault protection
14.
14. Auto
Auto reclosing
reclosing systems
systems
List of Topics
General Line Protection
General Line Protection
General Line Protection
General Line Protection
1-Distance relay basics
General Line Protection
General Line Protection
General Line Protection
General Line Protection
1-Distance relay basics
General Line Protection
General Line Protection
General Line Protection
General Line Protection
Objective of relay
Objective of relay
protection
protection
•
•
Protect persons and equipment in the surrounding of the
Protect persons and equipment in the surrounding of the
power system
power system
•
•
Protect apparatus in the power system
Protect apparatus in the power system
•
•
Separate faulty parts from the rest of the power system to
Separate faulty parts from the rest of the power system to
facilitate the operation of the healthy part of the system
General Line Protection
General Line Protection
Electrical faults in the power system
• Transmission lines
85%
• Busbar
12%
• Transformer/ Generator
3%
General Line Protection
General Line Protection
Fault statistics
• Single phase to earth
80%
• Two phases to earth
10%
• Phase to phase faults
5%
• Three phase faults
5%
The probability of line faults caused by
General Line Protection
General Line Protection
Fault types
• Transient faults
– are common on transmission lines, approximately 80-85% – lightnings are the most common reason
– can also be caused by birds, falling trees,Forest growth, swinging lines, High velocity winds etc.
– will disappear after a short dead interval
• Persistent faults
– can be caused by a broken conductor fallen down – can be a tree falling on a line
General Line Protection
General Line Protection
Fault types on double circuit lines
• Simultaneous and Interline faults
– On parallel line applications a problem can occur with simultaneous faults.
– A full scheme relay is superior when the protection is measuring two different fault types at the same time.
L1
L3
L3
L1
L2
L2
~~
Z< L2-N L1-NGeneral Line Protection
General Line Protection
Fault resistance
• multi-phase faults
consist only of arc resistance
• earth faults
consist of arc and tower footing resistance
L1
L3
L3
L1
L2
L2
Footing resistanceR
arc=
28707 x L
1.4I
Warrington´s formulaL= length of arc in meters I= the actual fault current in A
General Line Protection
General Line Protection
Fault types
• Mid-span faults
– the fault resistance is out of control
– can be caused by growing trees, bushfire or objects
touching a conductor
– this type of high resistive faults can not be detected by
impedance protection
General Line Protection
General Line Protection
MAIN REQUIREMENTS ON LINE PROTECTION ARE:
• SPEED
• SENSITIVITY
• SELECTIVITY
• DEPENDABILITY
• SECURITY
• RELIABILITY
• MTBF
General Line Protection
General Line Protection
Measuring principles
• Overcurrent protection
• Over current & under voltage
combination
• Differential protection
• Phase comparison
• Directional- wave protection
• Distance protection
General Line Protection
General Line Protection
The principle of distance protection
Z<
Z
K
=U
k
/ I
k
U
k
=0
U
k
Z
k
I
k
A B metallic faultGeneral Line Protection
General Line Protection
The principle of distance protection
• Power lines have impedances of size 0,3- 0,4 ohm/ km and normal
angles of 80 - 85 degrees in a 50Hz systems.
• The line impedance must be converted to secondary values with the
formula:
A Z< B Z<Z
L=R+jX
Z
sec=
VT
secVT
primCT
secCT
primZ
prim x xGeneral Line Protection
General Line Protection
The principle of distance protection
t
l
A Z< B Z< Z< C Z<t
t1 t2 t3l
t1 t2 t3 f1 f2 f3General Line Protection
General Line Protection
Measuring loop for earth faults
• The distance protection relays are always set
based on the phase impedance to the fault
Z
sR
L
X
LThe measured Impedance is a function of
positive and zero sequence impedance
R
NX
NIL1
UL1
General Line Protection
General Line Protection
Measuring loop for two- phase faults
• The distance protection relays are always set
based on the phase impedance to the fault
Z
sR
L
X
LUL1-L2
IL1
IL2
The measured impedance is equal to the
positive sequence impedance up to the fault
location
General Line Protection
General Line Protection
Measuring loop for three- phase faults
• The distance protection relays are always set
based on the phase impedance to the fault
The measured impedance is equal to the
positive sequence impedance up to the fault
location
Z
sR
LX
LUL1
IL1
IL2
IL3
UL2
UL3
General Line Protection
General Line Protection
The earth fault measurement
U= I
1Z
1+I
0Z
0+I
2Z
2Z
1=Z
2U= Z
1( I
1+I
2+I
0) +I
0Z
0-I
0Z
1I= I
1+I
2+I
0U=I Z
1+I
0( Z
0- Z
1)
3I
0=I
NU=IZ
1+I
N(
Z
0- Z
13
)
U=I Z
1+
I
N3
( Z
0- Z
1)
General Line Protection
General Line Protection
The earth fault measurement
• The current used is thus the phase current plus the residual
current times a factor K
N= (Z
0-Z
1) / 3Z
1, the zero sequence
compensation factor.
• The factor K
Nis a transmission line constant and Z
0/ Z
1is
presumed to be identical throughout the whole line length.
• (1+K
N) Z
1gives the total loop impedance for the earth fault
loop for single end infeed.
General Line Protection
General Line Protection
Double end infeed
I1
I1
I2
U
FR
FU
F= R
F( I1 + I2 )
R
F( I1 + I2 )
R
F1=
U1
U2
I
LoadGeneral Line Protection
General Line Protection
Measuring error at high resistive earth fault on a
line with double end infeed
X
ZL
Rf Load export Rf Load import
General Line Protection
General Line Protection
Remote faults
– Due to current contribution If2 and If3 in substation B, the
distance protection in station A will measure a higher
impedance than the "true" impedance to the fault.
– The relay will thus underreach and this means in practice it
can be diffcult to get a remote back-up.
Um= If1
xZL+ (If1+If2+If3)
xZF
Z< If1 If2 If3 If=If1+If2+If3 ZL ZF A B UmGeneral Line Protection
General Line Protection
Directional measurement
• When a fault occurs close to the relay location the
voltage can drop to a value where the directional
measurement can not be performed.
– Modern distance protection relays will instead use the
healthy voltage e.g. for L1- fault the voltage UL2-L3,
shifted 90 degrees compared to UL1. This cross
polarisation is used in different proportions between
healthy and faulty phases in different products.
– At three- phase fault close to the station all phase
voltages are low and cross polarisation is not of any use.
Instead a memory voltage is used to secure correct
General Line Protection
General Line Protection
Design of distance protection
• Switched scheme
– consists of a start relay to select (switch) the measuring
loop to the single measuring relay
• Full scheme
– has a measuring element for each measuring loop and
for each zone
~
~
Z<L2-N L1-N
General Line Protection
General Line Protection
General Line Protection
General Line Protection
SHOULD COVER AS MUCH AS POSSIBLE OF PROTECTED CIRCUIT AND OF ADDITIONAL RESISTANCE.
• IN CASE OF Ph TO GROUND FAULT FOLLOWED BY RECLOSURE TO TRIPPING IN UNFAULTED PHASES.
• FAST OPERATION
• DIRECTIONAL DISCRIMINATION.
General Line Protection
General Line Protection
EXTENSION UPWARDS AND TO THE RIGHT SHOULD ENCLOSE AS MUCH OF LINE IMPEDANCE AND ADDITIONAL RESISTANCE WITHOUT OVERREACH.
• REACH IN RESISTIVE DIRECTION SHOULD BE LARGE ENOUGH TO COVER LARGE RESISTANCE AND TO GET GOOD DYNAMIC
PERFORMANCE BUT LIMITED TO AVOID UNWANTED TRIPPING IN CASE OF POWER SWINGS , OVERREACH IN ADDITIONAL RESISTANCE IS SEEN WITH LARGE CAPACITIVE REACTANCE , SHORT TIME OVERLOADING.
General Line Protection
General Line Protection
EXTENSION UPWARDS IS DECIDED BY IMPEDANCE OF PROTECTED LINE AND SETTING OF I ZONE OF ADJACENT LINES.
• IN MOST CASES R-AXIS REACH OF ZONE - II SAME AS ZONE -I
IS SATISFACTORY. IF ADDITIONAL RESISTANCES ARE EXPECTED WHICH ZONE - I IS NOT ABLE TO COVER THEN DIFFERENT SETTING FOR ZONE - II IS ADVANTAGEOUS.
General Line Protection
General Line Protection
THIS IS THE WIDEST OF ZONES IN WHICH TRIPPING CAN OCCUR AFTER LONGEST TIME DELAY.
• IS REQUIRED TO GIVE REMOTE BACKUP THOUGH IN
MANY CASES IT IS IMPOSSIBLE TO GET COMPEREHENSIVE REMOTE BACK UP.
General Line Protection
General Line Protection
DISTANCE PROTECTION ON SHORT LINES.
jX
R F
XF
R
• Low measured reactance
• Ratio between fault resistance
and resistance is high.
• Distance protection with
mho characteristic can not
see an average fault resistance.
General Line Protection
General Line Protection
DISTANCE PROTECTION ON SHORT LINES
jX
R F
XF R
• Low measured reactance
• Ratio between fault
resistance and reactance is
high.
• Distance protection with
mho characteristic can not
see average fault resistance.
• Cross polarization has no
General Line Protection
General Line Protection
jX
R F XF
R
DISTANCE PROTECTION ON SHORT LINES
• Quadrilateral characteristic
improves sensitivity for
higher R
F/X
Fratio.
• It still has some limitations.
-The value of set R
F/ X
Fratio is
is limited by 5
- Remote infeed increases the
apparent value of fault resistance.
- Requirements on current
instrument transformers are
stringent.
General Line Protection
General Line Protection
DISTANCE PROTECTION ON SHORT LINES.
jX
R R F
XF
•
Teleprotection schemes improve
the total system behavior.
•
Overreaching permissive schemes
increase the sensitivity.
•
Weak infeed logic for very high
fault resistance.
•
Requirements on CT’s are
decreased.
•
Independent underreaching
zone 1 is sometimes an
additional advantage.
General Line Protection
General Line Protection
jX
R
DISTANCE PROTECTION ON LONG LINES
• Load impedance limits the
reach in resistive direction.
• High value of R
F/ X
Fratio is
General Line Protection
General Line Protection
DISTANCE PROTECTION ON LONG LINES
R
• Load impedance limits the reach in resistive direction.
• High relay of R F/ XFratio is generally not necessary
• Circular (mho) characteristic - has no strictly defined reach
in resistive direction.
- needs limitation in resistive direction (blinder)
• Influences of heavy load current at phase to earth faults.
General Line Protection
General Line Protection
• AT THE ORIGIN DIRECTIONAL DISCRIMINATION REQUIRED BY LINE PASSING THROUGH 2nd QUADRANT , 4th QUADRANT
AND ORIGIN.
• THE DIRECTIONAL MEASUREMENT IS BASED ON THE USE OF + VE SEQUENCE VOLTAGE FOR THE RESPECTIVE FAULT LOOP. •VOLTAGE USED FOR R PH ELEMENT IS
0.8 U1R + 0.2 U 1RM
WHERE U1RM IS MEMORY VOLTAGE (+VE SEQUENCE)
THIS WILL ENSURE CORRECT DIRECTIONAL DISCREMINATION. EXTENSION IN 2nd AND 4th LIMITED TO AVOID OPERATION OF
UNFAULTED PHASE AN ALSO DURING SWINGS YET GIVE GOOD DYNAMIC PERFORMANCE.
General Line Protection
General Line Protection
LOAD CURRENT INFLUENCES THE IMPEDANCE MEASUREMENT.
L i n e i m p e d a n c e
General Line Protection
General Line Protection
Characteristic with out load compensation The same fault position Equal fault resistance LOAD CURRENT INFLUENCES THE IMPEDANCE MEASUREMENT.
L i n e i m p e d a n c e
General Line Protection
General Line Protection
∼
ILOAD∼
EA EB A B R F IFA I FB ZL EXPORTING END OVERREACHING IMPORTING END OVERREACHING ZM = ZL + R F(
1 + IFB I FA)
Note : Currents and voltages are phasorsGeneral Line Protection
General Line Protection
Characteristic with out load compensation The same fault position Equal fault resistance LOAD CURRENT INFLUENCES THE IMPEDANCE MEASUREMENT.
Load compensated characteristic
L i n e I m
p d e a n c e
General Line Protection
General Line Protection
IT IS NOT WHAT MANY HOPE IT IS
•RCALC is an interactive PC based program,
which helps the users in determination of
optimum settings of distance protection.
•Its operation is based on real algorithms
used in the distance protection.
•It includes measuring characteristics for :
-RAZOA and RAZFE
-REZ 1
and REL 100
-distance protection in REL 5XX
R C
A L
General Line Protection
General Line Protection
IT IS NOT WHAT MANY HOPE IT IS
•It presents the operation areas of distance
protection zones in impedance ( R- X ) plane
• Simulates two machine system :
-single line.
-double circuit line with zero
sequence mutual coupling.
-remaining network (line)
between two busbars.
-load conditions
-changing fault resistance.
R C
A L
General Line Protection
General Line Protection
General Line Protection
General Line Protection
Zero- sequence mutual coupling on parallel lines
ZA< overreaching ZB< underreaching
Z
L
~
Z
OM
Z
L
~
ZA< ZB<~
~
General Line Protection
General Line Protection
Zero- sequence mutual coupling on parallel lines
• In double circuit lines and parallel lines the zero sequence coupling
will result in measuring errors, specially at ground faults.
• The mutual impedance will either cause an extension or reduction of
the set reach on the relay.
• Maximum overreaching will occur when the parallel line is out of
service and grounded at both ends.
• The overreaching caused by the grounded parallel line can be
avoided at the setting of the relay, by the K
Nfactor.
General Line Protection
General Line Protection
EFFECT OF MUTUAL COUPLING ON DISTANCE
RELAYS
∼
∆
∆
∼
PARALLEL LINE EARTH CURRENT = IEP= 3IOP
INDUCED VOLTAGE IN THE FAULT LOOP = IEP • ZOM
/
3DISTANCE RELAY PH- EARTH UNIT MEASURES
Z = VPH- E
/ (
I PH + K OIE)
WHERE K O = ZOL- ZL/
3ZL = ZL •IPH+ (
ZOL- ZL)
IE/
3ZL+
IEP •ZOM/
3ZL IPH + K O IE = ZL[
1 + K OM •IEP/
IPH + K O IE]
WHERE K OM = ZOM/
3ZL ZOM ERRORGeneral Line Protection
General Line Protection
EFFECT OF MUTUAL COUPLING ON DISTANCE RELAYS
- THE ERROR ISα
MUTUAL COUPLING FACTOR ZOM / 3ZL .- ERROR INCREASES WITH IEP IN RELATION TO THE RELAY CURRENT IPH + KO IE
- THE RELAY UNDER REACHES WHEN IEP IS IN PHASE WITH IPH AND IE
- THE RELAY OVER REACHES WHEN IEP , IPH AND IE HAVE OPPOSITE SIGNS.
General Line Protection
General Line Protection
EFFECT OF MUTUAL COUPLING ON DISTANCE RELAYS
∆
∆
∼
∼
∆
Z = - ZL
K
OM• Z
OM/ Z
OL1 + K
O•
= - 0.23 Z
LGeneral Line Protection
General Line Protection
EFFECT OF MUTUAL COUPLING ON DISTANCE RELAYS.
∆
Z =
∼
∆
D
K
OM1 + K
O• Z
L= 0.38 Z
LK
O =Z
OL -Z
L3 Z
L= 0.864
K
OM =Z
OM/ 3Z
L =0.716
R 1+ j X1= 0.0289 + j 0.307Ω
/
KM R O+ j X0= 0.276 + j 1.0715Ω
/
KM R MO1+ j XMO= 0.228 + j 0.622Ω
/
KM∴
ZL = 0.308Ω
/
KM ZOL =1.106Ω
/
KM ZOM =0.662Ω
/
KMGeneral Line Protection
General Line Protection
SETTING OF DISTANCE ZONE FOR PARALLEL LINES.
•
SETTING OF ZONE 1.
SETTING OBJECTIVE IS TO AVOID OVERREACH BEYOND THE REMOTE END IN CASE SHOWN BELOW. ALSO SETTING SHOULD COVER AS
MUCH OF THE LINE AS POSSIBLE ( MIN 50 % + SAFETY MARGIN )
∼
D
PH- E 1 +(
ZOL - ZL 3ZL-
K OM • ZOM ZOL)
1 + K OZ = X Z
L•
∴
SET
K
O=
[
ZOL - ZL 3ZL-
K OM ZOM ZOL]
General Line Protection
General Line Protection
WITH THE ABOVE FOR OTHER CASES VIZ PARALLEL LINES
SWITCHED OFF AND NOT EARTHED & BOTH LINES IN SERVICE THE REACH WILL REDUCE AS GIVEN BELOW.
-
PARALLEL LINE SWITCHED OFF AND NOT EARTHED - 69%
- BOTH LINES IN SERVICE
- 60%
General Line Protection
General Line Protection
SETTING OF DISTANCE ZONES FOR PARALLEL LINES
• SETTING OF ZONE 2
SETTING OBJECTIVE IS RELAY MUST SAFELY COVER 100 % OF THE LINE WITH SAFTEY MARGIN OF 20 % FOR THE MOST
UNFAVOURABLE CONDITION.
∼
PH - EZ = Z
L 1 +(ZOL - ZL )/
3ZL+ K OM 1 + K O[
]
∴
SET K 0=
ZOL - ZL 3 ZL + K OM AND REACH TO 120 %General Line Protection
General Line Protection
FOR OTHER CASES VIZ PARALLEL LINE SWITCHED OFF AND EARTHED AT BOTH LINE ENDS IT MUST BE ENSURED THAT THIS DOES NOT OVERLAP WITH THE ZONE 2 OF THE
FOLLOWING LINE.
Z
Z
Z
L0. 44
THIS MEANS IN THE CASE OF 2nd ZONE SET TO 120 % OF ZL
WOULD HAVE A REACH OF 173 % OF ZL.
IN NORMAL PRACTICE THIS PROVIDES NO PROBLEMS AS OVERRECH IN TO FOLLOWING LINE IS REDUCED BY
General Line Protection
General Line Protection
THE INFLUENCE OF ZERO SEQUENCE MUTUAL COUPLING CAN BE COMPENSATED IN NUMERICAL RELAYS IN TWO DIFFERENT WAYS
ALT 1
-BY USING POSSIBILITY OF DIFFERENT VALUES OF EARTH RETURN COMPENSATING FACTOR K FOR DIFFERENT ZONES WITHIN THE SAME GROUP OF SETTING PARAMETERS.
ALT 2
-BY USING DIFFERENT GROUPS OF SETTING PARAMETERS FOR DIFFERENT OPERATING CONDITIONS OF PROTECTED DOUBLE CIRCUIT LINE.
General Line Protection
General Line Protection
ALTERNATIVE 1
K
N1=
[
ZOL-
ZL 3ZL-
K OM ZOM ZOL]
=
[
ZOL-
ZL 3ZL+
K OM]
=
[
ZOL-
ZL 3ZL]
K
N2K
N3 WHERE K OM = ZOM/
3ZLGeneral Line Protection
General Line Protection
ALTERNATIVE 2
=[
ZO L - ZL 3 ZL - K O M ZO M ZO L]
CASE 1 - PARALLEL LINE SWITCHED OFF WITH BOTH ENDS
EARTHED.
K
N1K N2 , K N3 IDENTICAL TO ALT 1
CASE 2 - DOUBLE CIRCUIT PARALLEL LINE IN OPERATION.
=
[
ZOL-
ZL 3ZL+
K OM]
K N2 , K N3 IDENTICAL TO ALT 1K
N1General Line Protection
General Line Protection
General Line Protection
General Line Protection
AN INDEPENDENT PHASE SELECTION FUNCTION OPERATES
AS A COMPLEMENT TO THE IMPEDANCE MEASURIING ELEMENT SO AS TO SECURE CORRECT PHASE SELECTION IN CASE
OF SINGLE PH TO EARTH FAULTS ON HEAVILY LOADED LONG TRANSMISSION LINES AND ALSO MULTI CIRCUIT.
IT IS NOT NECESSARY TO SET THESE TO COVER ALL
ZONES. IT IS ENOUGH IF IT COVERS FIRST OVERREACHING ZONE ( ZONE 2 ) MEASURING ELEMENT FOR DIFFERENT FAULT LOOPS BUT FOR PHASE INDICATIONS.
General Line Protection
General Line Protection
PHASE SELECTION
• I PH FAULTS.
Characteristic of phase selector for single-phase faults.
jX XNPh RNPh R RN2 2 . ( 1 + Kn )
U
RI
R<
R
N4+ j x
N4Us
Is
R
N4+ j x
N4<
U
TI
TR
N4+ j x
N4<
ALSO
3I
o> 0.1 I
n&
3I
o>
0.2 I
pHMAXGeneral Line Protection
General Line Protection
PHASE SELECTION
• 2 PH FAULTS.jX R XPh RPh 2. X2 2.R2 70•
α
∂
U
R -U
TI
R<
R
4+
j X
4R
4+ j x
4R
4+ j x
4U
s -U
R<
I
SU
T -U
RI
T<
ALSO
General Line Protection
General Line Protection
Characteristic of phase selectors at three phase faults.
jX
R
100• RPh 2/√
3 2.X2 2. R2 XPh .2/α
δ
jX’ R’PHASE SELECTION
• 3 PH FAULTS. THIS IS SIMILAR TO PH - PH FAULTS WITH FOLLOWING DEVIATIONS. - ROTATED ANTICLOCKWISE BY 30 DEGREES. - REACH 2/√
3 TIMES THAT OF FOR PH - PH FAULTS.General Line Protection
General Line Protection
General Line Protection
General Line Protection
Power Swing Blocking (PSB) function
• A power swing can be started by sudden load change due to
a fault somewhere in the network.
• Close to the centre of the power swing, low voltage and thus
low impedance will occur.
• A distance protection relay must then be blocked during the
power swing.
• This can be done by mesuring the transit time of the
impedance locus passing two dedicated impedance zones.
• Normally the time used is 35-40 ms.
General Line Protection
General Line Protection
POWER SWING BLOCKING FUCTION
•WHEN POWER SWING DETECTION UNIT OPERATES ANY IMPEDENCE ZONE CAN BE SELECTED TO BE BLOCKED OR NOT AS REQUIRED.
•OPERATION OF POWER SWING DETECTION UNIT IS INHIBITED WHEN ZERO SEQUENCE CURRENT IS DETECTED. THIS FEATURE IS
INCLUDED TO ENSURE TRIPPING OF HIGH RESISTANCE EARTH FAULTS WHERE FAULTS WHERE FAULT RESISTANCE CAN DECREASE SLOWELY. •THE RESIDUAL CURRENT INHIBIT CONDITION ENSURE PSD
WILL NOT BLOCK DUE TO UNBALANCED LOAD OR
RESIDUAL CURRENT EXPERIENCED WITH UNTRANSPOSED TRANSMISSION LINES.
General Line Protection
General Line Protection
Power Swing Blocking function
∆
t∆
t = 40 ms
X
R
General Line Protection
General Line Protection
EFFECT OF VOLTAGE COLLAPSE ON DISTANCE RELAYS.
• APPARENT IMPENDANCE PRESENTED TO A DISTANCE RELAY
AS THE LOAD VOLTAGE VARIES DEPENDS ON VOLTAGE CHARACTERISTIC OF THE LOAD. • FOR A MOTOR P = 0.35 ( 0.75 + O.25 V )2
X
R
V = 0.8PU• •V = 1.1 PUGeneral Line Protection
General Line Protection
• SIMPOW IS A COMPUTER PROGRAMME DEVELOPED BY ABB POWER SYSTEM AB
• FOLLOWING STUDIES CAN BE DONE BY SIMPOW
- STEADY STATE (POWER FLOW , FAULT CURRENT , HARMONICS). - ELECTRO MECHANICAL TRANSIENTS ( LONG TERM DYNAMICS ,
SHORT TERM DYNAMICS , MACHINE TRANSIENTS).
- ELECTRO MAGNETIC TRANSIENTS (SATURATION AND RESONANCE SWITCHING TRANSIENTS , LIGHTNING TRANSIENTS).
- ANALYSIS (FREQUENCY SCANNING , EIGEN VALUES AND VECTORS, MODEL ANALYSIS).
General Line Protection
General Line Protection
General Line Protection
General Line Protection
General Line Protection
General Line Protection
COMMUNICATION EQUIPMENT
COMMUNICATION EQUIPMENT
∼
∼
×
×
×
×
×
×
×
×
×
×
×
×
∼
∼
A A BBIN THE ABSENCE OF COMMUNICATION LINK
IN THE ABSENCE OF COMMUNICATION LINK
-THE OPERATION ZONE OF END ZONE FAULT IS LONGER.
-THE OPERATION ZONE OF END ZONE FAULT IS LONGER.
-AUTO RECLOSING IS NOT POSSIBLE.
General Line Protection
General Line Protection
General Line Protection
General Line Protection
Communication equipment
Communication equipment
•• Powe
Power li
r line ca
ne carrier
rrier (PLC
(PLC) eq
) equipme
uipment is
nt is base
based on
d on a cap
a capaciti
acitive
ve
connection of signals with frequency in the range 50- 500 kHz
connection of signals with frequency in the range 50- 500 kHz on the
on the
power line.
power line.
•• Radio
Radio link
link is a
is a good a
good and rel
nd reliable
iable commu
communicat
nication e
ion equime
quiment, bu
nt, but is
t is
rarely used due to the high cost.
rarely used due to the high cost.
•• Opti
Optical fi
cal fibres h
bres have th
ave the adva
e advantage
ntage to be i
to be insen
nsensitiv
sitive to no
e to noise an
ise and can
d can
transmit a huge amount of information.
General Line Protection
General Line Protection
General Line Protection
General Line Protection
RELAY SETTING AND THE WAY SIGNALS ARE USED IS GIVEN RELAY SETTING AND THE WAY SIGNALS ARE USED IS GIVEN BELOW.
BELOW.
FIRST ZONE REACH FIRST ZONE REACH
• UNDER REACHING (0.8 TO 0.9 Z AB ) • UNDER REACHING (0.8 TO 0.9 Z AB ) • OVER
• OVER REACHING REACHING ( ( 1.2 Z 1.2 Z AB)AB) USE OF RECIVED SIGNAL
USE OF RECIVED SIGNAL
• OPERATION OF CB IF LOCAL RELAY HAS PICKED UP • OPERATION OF CB IF LOCAL RELAY HAS PICKED UP •
• AS INFORMATIAS INFORMATION REGARDINON REGARDING DIRECTION G DIRECTION OF FAULTOF FAULT -
- FOR FOR COMPARISON COMPARISON WITH WITH LOCAL LOCAL ENDEND -
- TO TO EXTEND EXTEND ZONE ZONE I I REACHREACH -
- TO TO BLOCK BLOCK RELAY RELAY OPERATIONOPERATION
COMMUNICATION EQUIPMENT
General Line Protection
General Line Protection
Permissive communication schemes
– Communication signal carrier send (CS) is sent to remote end
when the fault is detected in forward direction. Tripping is achieved
when the commmunication signal carrier receive (CR) is received
and the local relay has detected a forward fault.
– In a permissive underreaching scheme the communication signal is
sent from a zone that underreaches the remote end.
– In a permissive overreaching scheme the communication signal is
sent from a zone that overreaches the remote end.
A
Z< Z< B
Carrier send CS = Z< forward, under or overreach Trip = ZM1 + ZM2 (t2 + CR) + ZM3 x t3
General Line Protection
General Line Protection
General Line Protection
General Line Protection
PERMISSIVE OVERREACHING SCHEMES
PERMISSIVE OVERREACHING SCHEMES ARE ARE ADOPTED FOR ADOPTED FOR SHORTSHORT LINES
LINES (
( ALSO ALSO CALLED CALLED DIRECTIONAL DIRECTIONAL COMPARISON COMPARISON SCHEMES)SCHEMES) ADVANTAGES
ADVANTAGES AREARE •
• BETTER PERFORMANCBETTER PERFORMANCE FOR HIGH E FOR HIGH RESISTANCE FAULTS.RESISTANCE FAULTS. •
• SUPERIOR TO PILOT SUPERIOR TO PILOT WIRE AS WIRE AS DIGITAL DECISIONS AREDIGITAL DECISIONS ARE EXCHANGED
EXCHANGED AND AND NOT NOT ANALOGUEANALOGUE • SUPERIOR
• SUPERIOR TO PHASE TO PHASE COMPARISON WHICH REQUIRESCOMPARISON WHICH REQUIRES FAITHFUL
FAITHFUL TRANSMISSION TRANSMISSION OF OF PHASE PHASE INFORMATION.INFORMATION.
PERMISSIVE COMMUNICATION SCHEMES
General Line Protection
General Line Protection
General Line Protection
General Line Protection
Blocking communication schemes
Blocking communication schemes
–
– Communication
Communication signal (CS) i
signal (CS) is sent to rem
s sent to remote end when
ote end when the
the
fault is detected in the
fault is detected in the reverse direction. Tripping is achieved
reverse direction. Tripping is achieved
when this blocking signal is not received within a time T0
when this blocking signal is not received within a time T0
(20-40 ms) and the local relay has detected a fault in the forward
40 ms) and the local relay has detected a fault in the forward
direction.
direction.
A A BB Z< Z< Z<Z<Carrier send CS = Z< reverse zone
Carrier send CS = Z< reverse zone
Trip = ZM1 + ZM2 (t2 + CR x T0) + ZM3 x t3
General Line Protection
General Line Protection
General Line Protection
General Line Protection
BLOCKING COMMUNICATION SCHEMES
BLOCKING COMMUNICATION SCHEMES
BLOCKING SCHEMES ARE USED WHEN COMMUNICATION SIGNALS BLOCKING SCHEMES ARE USED WHEN COMMUNICATION SIGNALS SHALL NOT BE TRANSMITTED OVER FAULTY LINE FOR RELIABILITY SHALL NOT BE TRANSMITTED OVER FAULTY LINE FOR RELIABILITY REASONS
REASONS
Ex : BOOSTING OF SIGNAL NOT PERMITTED. Ex : BOOSTING OF SIGNAL NOT PERMITTED.
General Line Protection
General Line Protection
General Line Protection
General Line Protection
Current reversal logic
~
~
~~
A:1 B:1 A:2 B:2 A:1 B:1 A:2 B:2Permissive overreaching schemes
can trip healthy line without C.R.L
1 Fault occurs on line 1
Fault detection by protection A:1 B:1 and A:2 2 Relay B:1 trips CB and sends carrier to A:1 Relay A:2 sees fault in forward direction and sends carrier to B:2
3 Fault cleared at B:1, current direction changed on line 2
4 Carrier from A:2 and forward looking measuring element in relay A:2 does not reset before relay B:2 detects the fault in forward direction and
trips, also relay A:1 will trip when receiving carrier from B:1
C.R.L allows slowly resetting
General Line Protection
General Line Protection
General Line Protection
General Line Protection
Switch On To Fault (SOTF)
• When energizing a power line onto a forgotten earthing no
measuring voltage will be available and the directional measuring
can thus not operate correctly.
– A special SOTF function is thus provided. Different principles
can be used, from one phase current to undirectional
impedance measuring.
Z<
U=0 V
SOTF conditon can either be
taken from the manual closing
signal activating the (BC) input
or it can be detected internaly by
a logic.
General Line Protection
General Line Protection
General Line Protection
General Line Protection
Weak end infeed
Weak end infeed is a condition which can occur on a transmission
line, either when the circuit breaker is open, so there is no current
infeed from that line end, or when the current infeed is low due to
weak generation behind the protection.
CS = ZM2
TRIP = ZM1 + ZM2(CR + t2)
CS (echo)=CR x low voltage x no start forward or reverse
l
t1 t2 t3 Z< Z< CS CS (echo) CR CRGeneral Line Protection
General Line Protection
WEAK END INFEED
• IN PERMISSIVE OVER REACH SCHEMES BOTH CBS MAY FAIL TO TRIP INSTANEOUSLY DUE TO NO CARRIER SEND SIGNAL AND NO RELAY OPERATION IN WEAK END.
• IN PERMISSIVE UNDERREACH SCHEMES FAST FAULT CLEARENCE OF WHOLE LINE SECTION WILL NOT BE THERE BECAUSE NO
SIGNALS WILL BE SENT FROM THE WEAK END.
• IN BLOCKING SCHEME OR PERMISSIVE UNDERREACH SCHEME THE LOW INFEED END WILL FAIL TO TRIP INSTANTANEOUSLY.
General Line Protection
General Line Protection
WEAK END INFEED.
THE LOGIC DESCRIBED FOR PERMISSIVE OVERREACH SCHEME CAN BE USED IN TWO MODES.
-ECHO FOR COMMUNICATION SIGNAL ONLY.
-ECHO OF COMMUNICATION SIGNAL AND TRIP OF LOCAL CB.
IN CASE OF PERMISSIVE UNDERREACH SCHEME THE LAST 10-20 % TOWARDS WEAK END WILL BE CLEARED IN ZONE II TIME .
IF THIS IS NOT ACCEPTABLE OVERREACH SCHEME SHOULD BE USED. IN BLOCKING SCHEME WEAK END CB CANNOT BE TRIPPED .
IN SUCH CASE DIRECT TRIPPING FROM ZONE I AND ACCLERATED ZONE MUST BE USED.
General Line Protection
General Line Protection
General Line Protection
General Line Protection
THIS FUCTION IS BASED ON CONDITION
3UO> 20 % OF Un/
√
3 AND 3IO < 20 % OF InIT CAN BE SELECTED TO BLOCK PROTECTION AND GIVE ALARM OR JUST TO GIVE ALARM.
FUSE FAIL SUPERVISION IS BLOCKED FOR 200ms FOLLOWING LINE ENERGISATION IN ORDER NOT TO OPERATE FOR UNEQUAL POLE CLOSING AND ALSO DURING AUTORECLOSING.
MCB CAN ALSO BE USED.
General Line Protection
General Line Protection
General Line Protection
General Line Protection
SYSTEM SUPERVISION
.
• OVER LOAD SUPERVISION GIVES ALARM IF CURRENT EXCEEDS FOR 10 SECS.
• UNSYMMETRICAL LOAD CONDITION CHECK GIVES ALARM WHEN ANY PH CURRENT IS LOWER THEN 80% OF LARGEST PH CURRENT. ALSO
LARGEST PH CURRENT MUST BE > 15% OF NOMINAL CURRENT.
• LOSS OF VOLTAGE SUPERVISION CAN TRIP OR GIVE ALARM WHEN ALL 3 PH VOLTAGES ARE LOW FOR MORE THEN 7 SECS.
SYSTEM SUPERVISION CONSISTS OF FEATURES TO GIVE ALARM FOR UNNATURAL CONDITIONS VIZ.
- OVERLOAD SUPERVISION - BROKEN CONDUCTER - LOSS OF VOLTAGE
General Line Protection
General Line Protection
General Line Protection
General Line Protection
FAULT LOCATOR
×
R FP
PU
A IFAD
AI
A×
pZ
LI
R
FU
A= I
A×
PZ
L+
I
FAD
A×
R
FP
2- p
×
k
1+ k
2- k
3×
R
F= 0
General Line Protection
General Line Protection
FAULT LOCATOR
∼
∼
∼
-+
L
F
A
B
I
AI
FI
BZ
AZ
BR
F pZ
L( I - p )Z
L pZ
L( 1- p ) Z
LZ
AZ
BFault Locator Measuring Principle
UA=IAX PZL+ IFAX R F DA
DA =
(I-P) ZL+ZB ZA+ZL+ZB
General Line Protection
General Line Protection
FAULT LOCATOR
For Double Circuit Lines.
U
A= I
A. pZ
L+
I
FAD
A.
R
F+ I
OP. Z
OMp
2-
p k
1+ k
2- k
3R
F=
0
D
A=
(1-p) ( Z
1A+ Z
1L+ Z
1B)
2 Z
1A+ Z
IL+ 2Z
1BWHERE
I
AZ
1LZ
1L+ Z
ADDK
1=
U
A+
Z
1B+ 1
K
2=
I
AZ
1LZ
1L+ Z
ADDU
AZ
1B(
+ 1
I
AZ
1LZ
1L+ Z
ADDK
2=
I
FA(
Z
1A +Z
1B+ 1
,
)
)
General Line Protection
General Line Protection
General Line Protection
General Line Protection
Stub protection function
It is not possible for the distance protection relay to measure
impedance when the line
disconnector is open. Not to risk incorrect operation the distance protection must be blocked and a Stub protection is released.
The Stub protection is a simple current relay. line disc open I STUB > & trip 25ms Bus A Bus B > Z +
General Line Protection
General Line Protection
General Line Protection
General Line Protection
Earth fault current in solidly grounded system
Reverse operation Forward operation Upol -3U0 3I0D 0.6 3I0Dx
3I
0>
3I0 X cos(65-φ
)=3I0Dφ
= the characteristic angle of zero sequence source impedanceGeneral Line Protection
General Line Protection
• HIGH FAULT RESISTANCE CAN BE DIFFICULT TO DETECT THROUGH DISTANCE RELAYS.
• THIS CAN BE OVERCOME BY E/F O/C PROTECTION EITHER NON DIRECTIONAL OR DIRECTIONAL.
• PROVIDED WITH SECOND HARMONIC CURRENT RESTRAINT WHICH BLOCKS OPERATION IF RESIDUAL CURRENT CONTAINS 20% OR MORE OF SECOND HARMONICS.
• POLARIZING VOLTAGE CAN HAVE HIGH AMOUNT OF HARMONICS WHEN OUTPUT VOLTAGE IS LOW PARTICULARLY WHEN CVTS ARE PROVIDED. THEREFORE RELAY MUST HAVE BAND PASS FILTER. BAND PASS FILTER PROVIDES SECURE OPERATION DOWN TO 1% OF NOMINAL VOLTAGE.
EARTH FAULT CURRENT IN SOLIDLY
GROUNDED SYSTEM.
General Line Protection
General Line Protection
General Line Protection
General Line Protection
1.0 GENERAL
1.0 GENERAL
• The auto-reclosing of power lines has become a generally accepted practice.
• Reports from different parts of the world show that in
certain networks in region subject to a high lightening intensity only about 5% of the faults are permanent.
• Auto reclosing therefore provides significant advantages.
• Outage times will be short compared to where station personnel have to re-energize the lines after a fault.
• In interconnected networks auto-reclosing helps in maintaining system stability
General Line Protection
General Line Protection
1.1 Recommendations for provisions of auto-reclosing 1.1 Recommendations for provisions of auto-reclosing
• Presently 1 phase high speed auto-reclosure (HSAR) at 400kV and 220kV level is widely practised including on lines emanating from Generating Stations and the same is recommended for adoption. • If 3-phase auto-reclosure is adopted in future the application of the
same on lines emanating from generating stations should be studied and decision taken on case to case basis.